Level control
➜ ENRM
■ Adjusting one or two levels (min./max.)
■ Monitoring filling (UP) or emptying (DOWN) selected
by a switch on the front panel.
■ Probes supplied with AC current.
■ Sensitivity adjustable on front panel from 250 Ω to 1 M
Ω.
■ Time delay preventing wave effect adjustable from 0.1
to 5s.
Specifications
Type Characteristics Voltages Code
ENRM Monitoring filling UP
Monitoring emptying DOWN
General characteristics
Operating range 0.85 ➞1.10 x U n
Maximum power consumption 3 VA
Adjustable sensitivity 250 Ω ➞1 MΩ
Measurement accuracy (at maximum sen sitivity) ± 30 %
Electrode voltage (max) 24 V AC (50/60 Hz)
Electrode current (maximum) 1 mA (50/60 Hz)
Maximum cable capacity 10 nF
Response time high level 300 ms
Response time low level 500 ms
Output relay (according to AC1 resistive load) 1 AgNi changeover relay 8 A AC max.
Galvanic isolation via transformer (4 kV, 8 mm creepage distance) Class II VDE 0551
Isolation of contacts and electrodes from power suppl y 2.5 kV AC
Operating temperature range (°C) -20 ➞+50°C
Storage temperature range (°C) -40 ➞+70°C
Weight (g) 150
24 V AC 84 870 211
48 V AC 84 870 212
120 V AC 84 870 213
230 V AC 84 870 214
Dimensions
ENRM
32
3,5
57
63
95
22,5
A1 15 Y1
78
18 16 A2
5
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
1

Connections
Adjusting two levels
Monitoring filling "Up"
R
S
T
N
14
A1
S
11
11
12
Min
12 A2
C
14
Max
Monitoring emptying "Down"
R
S
T
N
S
A1
11
11
14
12 A2
C
14 12
Max
2
3
MP
Common
B
Off
C
On
D
Output
E
A1-A2 : power supply
Max.
Min.
2
Max.
1
4
MP
Common
B
Off
C
Output
D
1
3
A1-A2 : power supply
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com