Level control
ENRM
Adjusting one or two levels (min./max.)
Monitoring filling (UP) or emptying (DOWN) selected
by a switch on the front panel.
Probes supplied with AC current.
Ω.
Time delay preventing wave effect adjustable from 0.1
to 5s.
Specifications
Type Characteristics Voltages Code
ENRM Monitoring filling UP
Monitoring emptying DOWN
General characteristics
Operating range 0.85 1.10 x U n Maximum power consumption 3 VA Adjustable sensitivity 250 1 M Measurement accuracy (at maximum sen sitivity) ± 30 % Electrode voltage (max) 24 V AC (50/60 Hz) Electrode current (maximum) 1 mA (50/60 Hz) Maximum cable capacity 10 nF Response time high level 300 ms Response time low level 500 ms Output relay (according to AC1 resistive load) 1 AgNi changeover relay 8 A AC max. Galvanic isolation via transformer (4 kV, 8 mm creepage distance) Class II VDE 0551 Isolation of contacts and electrodes from power suppl y 2.5 kV AC Operating temperature range (°C) -20 +50°C Storage temperature range (°C) -40 +70°C Weight (g) 150
24 V AC 84 870 211 48 V AC 84 870 212 120 V AC 84 870 213 230 V AC 84 870 214
Dimensions
ENRM
32
3,5
57
63
95
22,5
A1 15 Y1
78
18 16 A2
5
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
1
Connections
Adjusting two levels Monitoring filling "Up"
R S T
N
14
A1
S
11
11
12
Min
12 A2
C
14
Max
Monitoring emptying "Down"
R S T
N
S
A1
11
11
14
12 A2
C
14 12
Max
2
3
MP
Common
B
Off
C
On
D
Output
E
A1-A2 : power supply
Max.
Min.
2
Max.
1
4
MP
Common
B
Off
C
Output
D
1
3
A1-A2 : power supply
Products and specifications subject to change without notice.