V-Series Incandescent
Photometric Data
Luminaires
Enclosed and Gasketed
Luminaires V-Series
Lamp: 150W/A23 Clear
Total Bare Lamp Lumens: 2800
To determine number and placement of fixtures, see Lighting Selector
Guide pages 665 to 689.
Zonal Lumens
Without
Zone
Guard
0-10 29 19
10-20 67 60
20-30 109 60
30-40 127 113
40-50 175 168
50-60 218 117
60-70 246 250
70-80 228 232
80-90 223 65
90-100 209 218
100-110 210 218
110-120 210 216
120-130 194 72
130-140 164 165
140-150 87 58
150-160 3 8
Total 2499 2039
Coefficient of Utilization
Effective Floor Cavity Reflectance 20%
% Reflectance Room Cavity Ratio
Eff. Ceil. Wall 12345
80 30 .623 .504 .417 .349 .298
70 30 .577 .466 .386 .324 .275
50 30 .491 .397 .328 .274 .234
30 30 .411 .332 .274 .228 .194
10 30 .337 .269 .221 .183 .156
% Reflectance Room Cavity Ratio
Eff. Ceil. Wall 678910
80 30 .259 .227 .199 .176 .153
70 30 .240 .210 .186 .164 .143
50 30 .205 .178 .158 .140 .122
30 30 .170 .149 .131 .117 .101
10 30 .136 .121 .106 .094 .081
50 .659 .558 .479 .416 .361
10 .591 .458 .367 .298 .248
50 .609 .515 .442 .384 .336
10 .545 .426 .342 .278 .230
50 .515 .434 .372 .321 .282
10 .469 .364 .293 .238 .197
50 .429 .359 .307 .264 .232
10 .395 .307 .245 .198 .165
50 .350 .290 .246 .211 .185
10 .325 .251 .199 .160 .132
50 .325 .290 .261 .236 .211
10 .212 .183 .157 .136 .116
50 .299 .268 .241 .219 .194
10 .197 .170 .146 .127 .108
50 .252 .226 .203 .185 .165
10 .169 .145 .125 .109 .092
50 .208 .186 .169 .153 .137
10 .141 .121 .105 .091 .076
50 .167 .151 .135 .124 .110
10 .114 .098 .084 .073 .060
NOTE: All data provided is
With
for 150W incandescent
Guard
lamp. Use following
candela/lumen multipliers
for the other lamp sizes:
100W – 0.61
Example: Zonal lumens
for 150W lamp for 0-40°
with guard is 252.
1L
US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright©2006 Cooper Crouse-Hinds
705