Crouse Hinds NDA Corro Gard CorrosionResistant Incandescent Luminaires Photometric Data

NDA CorroɀGardTMCorrosion-
Photometric Data
Resistant Incandescent Luminaires
Lamp: 200W/PS-25
To determine number and placement of luminaires, see Lighting Selector Guide, pages 665 to
689. NOTE: All data provided is for incandescent with 200W/PS-25 lamp. See Multipliers for other
wattages and lamp types.
Luminaire With Globe Luminaire With Globe and Luminaire With Globe and
Coefficient of Utilization
Effective Floor Cavity Reflectance 20%
% Reflectance Room Cavity Ratio Eff. Ceil.Wall 12345
50 .762 .651 .565 .494 .433
80 30 .715 .585 .491 .416 .358
10 .673 .529 .433 .357 .300
50 .708 .605 .526 .461 .406
70 30 .667 .546 .460 .390 .335
10 .626 .496 .407 .336 .282
50 .608 .519 .452 .395 .292
50 30 .576 .473 .399 .339 .250
10 .547 .432 .356 .295 .248
50 .516 .439 .382 .335 .297
30 30 .492 .404 .342 .290 .250
10 .469 .372 .307 .254 .215
50 .433 .366 .319 .279 .247
10 30 .413 .339 .287 .244 .211
10 .396 .315 .259 .215 .181
0 0 .354 .277 .226 .184 .154
% Reflectance Room Cavity Ratio Eff. Ceil.Wall 678910
50 .389 .348 .312 .284 .253
80 30 .312 .273 .240 .214 .185
10 .258 .222 .190 .166 .141
50 .363 .324 .291 .266 .236
70 30 .293 .256 .226 .201 .175
10 .242 .208 .179 .157 .133
50 .312 .280 .252 .230 .205
50 30 .256 .223 .198 .177 .153
10 .213 .183 .158 .139 .117
50 .266 .238 .216 .197 .175
30 30 .220 .193 .170 .152 .131
10 .185 .158 .137 .121 .100
50 .223 .201 .180 .166 .147
10 30 .185 .163 .144 .129 .110
10 .156 .135 .116 .102 .084
0 0 .132 .112 .096 .084 .068
Dome Reflector 30° Angle Reflector
Coefficient of Utilization
Effective Floor Cavity Reflectance 20%
% Reflectance Room Cavity Ratio Eff. Ceil.Wall 12345
50 .809 .703 .615 .541 .481
80 30 .773 .647 .550 .470 .408
10 .742 .601 .499 .416 .354
50 .791 .688 .604 .531 .470
70 30 .758 .636 .542 .465 .403
10 .729 .595 .494 .413 .315
50 .756 .659 .580 .510 .455
50 30 .729 .617 .528 .453 .395
10 .706 .579 .485 .408 .349
50 .726 .634 .558 .492 .439
30 30 .705 .599 .514 .442 .385
10 .684 .566 .477 .402 .344
50 .699 .610 .539 .475 .424
10 30 .663 .580 .501 .431 .378
10 .580 .553 .468 .396 .340
0 0 .647 .536 .451 .378 .323
% Reflectance Room Cavity Ratio Eff. Ceil.Wall 678910
50 .431 .386 .347 .317 .277
80 30 .360 .317 .280 .250 .211
10 .309 .269 .231 .204 .169
50 .423 .380 .342 .312 .272
70 30 .356 .312 .277 .247 .211
10 .305 .265 .231 .204 .169
50 .408 .368 .331 .302 .265
50 30 .348 .305 .272 .243 .207
10 .303 .263 .229 .202 .167
50 .396 .355 .321 .294 .257
30 30 .342 .301 .266 .238 .203
10 .300 .260 .227 .201 .165
50 .383 .346 .311 .285 .250
10 30 .334 .295 .262 .235 .200
10 .297 .258 .225 .199 .163
0 0 .281 .243 .210 .184 .150
Total Lumens Eff. %
2595 80.6
Multipliers for Other Lamps
Photometric data was developed using a 200 watt/PS-25 inside frosted incandescent lamp (3,220 lumens). For other incandescent watts/lamp size, use the following conversion factors (multipliers):
Watts Lamp Size Lumens Factor
100 A-19 1750 .54 100 A-21 1690 .52
150 A-21 2880 .89 150 PS-25 2680 .83
200 A-23 4010 1.25
300 PS-25 6360 1.98
Example: Zonal lumens for 200W/PS-25 luminaire with globe and dome reflector for 30-40° is 389. Zonal lumens for 100W/A-21 luminaire with globe and dome reflector for 30-40° is 389 × .52 202.
CANDLES AT 25 FT. IN PLANE
A-A’ WITHOUT GUARD
DEGREES FRONT BACK
10 672 577 15 677 539 20 677 498 25 677 465 30 677 422 35 677 388 40 640 338 45 630 278 50 630 89 55 625 24 60 583 5 65 551 70 525 75 461 80 422 85 385 90 346
95 310 100 273 105 207 110 68 115 24 120 5 125 130
Lamp Conversion
0 630 5 646 619
US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright©2006 Cooper Crouse-Hinds
707