Crouse Hinds FVN Series Photometric Data

FVN Series Flourescent Luminaires
CI.I, Div. 2, Groups A,B,C,D CI.I, Zone 2 Group IIC CI.II, Div. 1, Groups F,G
Wet Locations NEMA 3,3R
CI.III & Simultaneous Presence
Options:
The following special options are available from the factory by adding suffix to luminaire Cat. No.
Description Suffix
ɀ Low temperature electromagnetic ballast, 40W rated 0°F (-18°C), 60W rated -20°F (-29°C) BY ɀ 45° angle brackets (field installed) AG ɀ Adjustable angle brackets (field installed) KH ɀ Angle bars for chain suspension (field installed) CX ɀ Individually fused balast (internal) FB ɀ Emergency lighting battery unit (Class I, Division 2 only). Also available for use with T5 lamps
Supplied with charging indicator light and instructions for use with a remote push-to-test station.
If push-to-test operator installed in the luminaire is required, consult factory.
S799†
Temperature Performance Data:
(Based on 40°C ambient)
Lamp Supply2-Lamp 3-Lamp 2-Lamp 3-Lamp 2-Lamp 3-Lamp Wire
32W T5 T5 T6 T6 T4 T4 60°C 40W T5 T5 T6 T6 T4 T4 60°C 54W T3C T6 T3C/T6 75°C 60W T4 T6 T4 90°C
Cl. I, Div. 2 & Zone 2 Class II Simultaneous Presence Supply
Photometric Data:
Luminaire with two 54W High Output T5 Linear Fluorescent Lamps FVN4254
FVN .ies photometric files for use with our Luxicon®Lighting Layout Software are available from the Resources area of our website.
US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright©2006 Cooper Crouse-Hinds
853
FVN Series Fluorescent Luminaires
Luminaire: FVN with 2-40W lamps (tempered lens)
Lamp: 2-40/T-12 Zonal Degrees: 0-30 0-40 0-60 0-90 Zonal Lumens: 1182 1971 3555 4284 Total Bare Lamp Lumens: 6300
To determine number and placement of luminaires, see Lighting Selector Guide, pages 665 to 689.
NOTE: All data provided is for 2-lamp 40W RS cool white luminaires with tempered glass. Use 1.37 multiplier for 2-lamp 60W luminaires with tempered glass. Use .92 multiplier for 2-lamp 32W luminaires with tempered glass.
Photometric Data
Luminaire: FVN with 3-40W lamps (tempered lens)
Lamp: 3-40/T-12 Zonal Degrees: 0-30 0-40 0-60 0-90 Zonal Lumens: 1695 2834 5099 6079 Total Bare Lamp Lumens: 9450
To determine number and placement of luminaires, see Lighting Selector Guide, pages 665 to 689.
NOTE: All data provided is for 2-lamp 40W RS cool white luminaires with tempered glass. Use 1.37 multiplier for 2-lamp 60W luminaires with tempered glass. Use .92 multiplier for 2-lamp 32W luminaires with tempered glass.
Coefficient of Utilization
Effective Floor Cavity Reflectance 20%
% Reflectance Room Cavity Ratio Eff. Ceil. Wall 12345
50 .721 .643 .575 .513 .461
80 30 .695 .603 .527 .459 .404
10 .673 .569 .489 .418 .362 50 .706 .631 .566 .505 .452
70 30 .683 .594 .520 .455 .399
10 .661 .564 .485 .415 .359 50 .677 .607 .547 .488 .439
50 30 .657 .577 .508 .444 .392
10 .641 .549 .476 .410 .357 50 .650 .586 .528 .473 .426
30 30 .636 .561 .496 .435 .384
10 .621 .538 .468 .405 .353 50 .627 .568 .512 .459 .414
10 30 .614 .544 .484 .426 .378
10 .602 .526 .460 .399 .349
0 0 .589 .512 .447 .385 .336
% Reflectance Room Cavity Ratio Eff. Ceil. Wall 678910
50 .416 .375 .338 .309 .269
80 30 .359 .319 .283 .254 .215
10 .319 .281 .244 .217 .180 50 .409 .370 .333 .305 .265
70 30 .356 .315 .281 .252 .215
10 .316 .278 .244 .217 .180 50 .397 .359 .324 .297 .259
50 30 .350 .309 .277 .249 .211
10 .314 .276 .242 .215 .179 50 .386 .348 .316 .289 .253
30 30 .344 .306 .272 .244 .208
10 .311 .273 .240 .214 .177 50 .376 .341 .308 .282 .247
10 30 .338 .301 .268 .242 .205
10 .308 .271 .239 .212 .175
0 0 .295 .258 .226 .200 .164
Coefficient of Utilization
Effective Floor Cavity Reflectance 20%
% Reflectance Room Cavity Ratio Eff. Ceil. Wall 12345
50 .682 .610 .546 .488 .439
80 30 .658 .572 .501 .438 .385
10 .637 .540 .466 .399 .346 50 .668 .599 .538 .480 .430
70 30 .646 .563 .495 .433 .381
10 .625 .535 .462 .396 .343 50 .640 .576 .520 .464 .418
50 30 .622 .547 .454 .423 .374
10 .606 .521 .433 .391 .341 50 .615 .556 .502 .450 .406
30 30 .601 .532 .472 .415 .367
10 .587 .511 .446 .386 .337 50 .594 .537 .487 .437 .394
10 30 .581 .517 .461 .406 .361
10 .570 .499 .439 .381 .333
0 0 .557 .487 .426 .368 .321
% Reflectance Room Cavity Ratio Eff. Ceil. Wall 678910
50 .396 .357 .322 .294 .256
80 30 .343 .304 .270 .242 .205
10 .305 .268 .234 .207 .172 50 .390 .352 .317 .290 .252
70 30 .340 .301 .268 .240 .205
10 .302 .266 .233 .207 .172 50 .378 .342 .309 .282 .247
50 30 .334 .295 .264 .237 .201
10 .300 .264 .231 .206 .171 50 .368 .332 .301 .276 .241
30 30 .328 .292 .259 .233 .199
10 .298 .261 .230 .204 .169 50 .358 .325 .294 .269 .235
10 30 .322 .288 .256 .231 .196
10 .294 .259 .228 .202 .168
0 0 .283 .247 .217 .192 .157
854
US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright©2006 Cooper Crouse-Hinds