4L
EVM HazardȿGard®H.I.D.
Luminaires
Photometric Data
Lamp: 100W/E-231⁄2 mercury vapor – (MV)
Total bare lamp lumens: 4200
To determine number and placement of luminaires, see Lighting
Selector guide, pages 665 to 689
Luminaire With Globe and Without Guard
NOTE: Photometric data was
developed using a 100 watt
diffuse mercury vapor lamp
(4,200 lumens). For other
diffuse lamps, use the following
conversion factors (multipliers):
175W MV – 2.05; 70W MH –
1.33; 100W MH – 1.85; 175W
MH (metal halide) – 3.33.
Multipliers are for use with
candela curve only.
Luminaire spacing ratio is 1.30.
Coefficient of Utilization
Effective Floor Cavity Reflectance 20%
% Reflectance Room Cavity Ratio
Eff. Ceil. Wall 12345
50 .694 .584 .503 .439 .386
80 30 .644 .516 .428 .361 .311
10 .600 .459 .369 .302 .253
50 .660 .556 .479 .418 .368
70 30 .615 .493 .410 .347 .297
10 .572 .441 .355 .291 .244
50 .596 .501 .432 .377 .334
50 30 .559 .450 .375 .317 .274
10 .526 .405 .328 .270 .227
50 .538 .451 .389 .339 .302
30 30 .509 .410 .342 .290 .250
10 .481 .373 .302 .249 .210
50 .485 .405 .349 .305 .271
10 30 .461 .371 .310 .263 .223
10 .439 .341 .277 .228 .193
0 0 .410 .313 .251 .204 .171
% Reflectance Room Cavity Ratio
Eff. Ceil. Wall 678910
50 .347 .312 .282 .259 .230
80 30 .273 .241 .214 .192 .166
10 .220 .192 .165 .147 .125
50 .331 .298 .270 .248 .220
70 30 .262 .231 .206 .185 .162
10 .211 .184 .160 .143 .121
50 .300 .272 .246 .227 .203
50 30 .241 .212 .190 .172 .150
10 .197 .171 .149 .134 .113
50 .272 .245 .225 .207 .185
30 30 .222 .196 .175 .158 .138
10 .183 .158 .139 .124 .105
50 .246 .224 .203 .188 .169
10 30 .202 .180 .160 .146 .127
10 .168 .147 .129 .115 .096
0 0 .148 .128 .111 .099 .082
Lamp: 100W/E23
Total bare lamp lumens: 4200
To determine number and placement of luminaires, see Lighting
Selector guide, pages 665 to 689
1
⁄2 mercury vapor – (MV)
Luminaire With Globe, Dome Reflector and Without
Guard
NOTE: Photometric data was
developed using a 100 watt
diffuse mercury vapor lamp
(4,200 lumens). For other
diffuse lamps, use the following
conversion factors (multipliers):
175W MV – 2.05; 70W MH –
1.33; 100W MH – 1.85; 175W
MH (metal halide) – 3.33.
Multipliers are for use with
candela curve only.
Luminaire spacing ratio is 1.25.
Coefficient of Utilization
Effective Floor Cavity Reflectance 20%
% Reflectance Room Cavity Ratio
Eff. Ceil. Wall 12345
50 .715 .637 .570 .509 .458
80 30 .688 .596 .521 .455 .401
10 .665 .562 .483 .413 .359
50 .699 .624 .560 .500 .448
70 30 .675 .586 .514 .450 .396
10 .652 .556 .478 .410 .356
50 .668 .598 .539 .481 .434
50 30 .648 .568 .500 .438 .388
10 .631 .540 .468 .404 .353
50 .640 .576 .519 .465 .420
30 30 .624 .550 .487 .428 .379
10 .609 .527 .459 .398 .348
50 .615 .554 .502 .450 .407
10 30 .602 .533 .474 .418 .372
10 .589 .514 .450 .391 .343
0 0 .575 .500 .436 .377 .329
% Reflectance Room Cavity Ratio
Eff. Ceil. Wall 678910
50 .414 .375 .340 .313 .275
80 30 .358 .319 .286 .259 .222
10 .318 .282 .247 .222 .187
50 .407 .369 .335 .308 .271
70 30 .354 .315 .283 .256 .222
10 .315 .278 .246 .221 .187
50 .394 .358 .325 .299 .264
50 30 .347 .309 .278 .252 .217
10 .312 .275 .244 .219 .185
50 .383 .346 .316 .292 .257
30 30 .340 .304 .273 .248 .214
10 .308 .272 .242 .217 .183
50 .371 .338 .307 .284 .251
10 30 .333 .299 .268 .244 .210
10 .304 .269 .240 .215 .181
0 0 .292 .257 .227 .204 .170
798
US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright©2006 Cooper Crouse-Hinds
EVM HazardȿGard®H.I.D.
Photometric Data
Luminaires
Isofootcandle Chart: Luminaire With Globe and 30°
Angle Reflector, Without Guard
1
Lamp: 150W/E-23
Total bare lamp lumens: 16,000
To determine number and placement of luminaires, see Lighting
Selector Guide, pages 665 to 689.
⁄2 high pressure sodium (HPS)
Luminaire With Globe and Without Guard
NOTE: Photometric data was
developed using a 150 watt
clear high pressure sodium
lamp (16,000 lumens). For
other clear lamps, use the
following conversion factors
(multipliers): 50W HPS – .25;
70W HPS – .40; 100W HPS –
.59. Multipliers are for use
with candela curve only.
Luminaire spacing ratio is
0.80.
4L
Lamp: 100W/E-231⁄2 diffuse mercury vapor (MV)
Total bare lamp lumens: 4200
To determine number and placement of luminaires, see Lighting
Selector Guide, pages 665 to 689.
Illumination in footcandles on work plane 10 feet below light center.
Multiply by factor shown to convert to other mounting heights.
Height (Ft.) Factor Height (Ft.) Factor
6 2.78 9 1.23
7 2.04 11 0.83
8 1.56 12 0.70
Coefficient of Utilization
Effective Floor Cavity Reflectance 20%
% Reflectance Room Cavity Ratio
Eff. Ceil. Wall 12345
50 .695 .579 .494 .410 .382
80 30 .644 .509 .417 .326 .305
10 .599 .450 .356 .262 .246
50 .659 .549 .469 .387 .363
70 30 .613 .484 .397 .311 .291
10 .570 .431 .341 .251 .236
50 .592 .491 .419 .344 .327
50 30 .555 .439 .360 .279 .265
10 .522 .393 .312 .229 .218
50 .531 .438 .373 .304 .292
30 30 .502 .396 .325 .250 .240
10 .474 .358 .284 .207 .200
50 .476 .390 .331 .267 .260
10 30 .451 .355 .291 .222 .217
10 .429 .325 .257 .184 .181
0 0 .399 .295 .230 .159 .159
% Reflectance Room Cavity Ratio
Eff. Ceil. Wall 678910
50 .342 .306 .278 .265 .233
80 30 .266 .234 .209 .198 .168
10 .212 .184 .160 .153 .127
50 .324 .292 .265 .253 .222
70 30 .254 .223 .201 .191 .163
10 .202 .176 .155 .149 .123
50 .292 .263 .240 .231 .203
50 30 .232 .203 .184 .177 .150
10 .187 .162 .143 .139 .114
50 .262 .236 .218 .210 .185
30 30 .211 .186 .167 .162 .138
10 .172 .148 .132 .129 .105
50 .234 .213 .195 .191 .167
10 30 .190 .169 .152 .149 .125
10 .156 .135 .121 .118 .096
0 0 .135 .116 .103 .103 .081
US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright©2006 Cooper Crouse-Hinds
799