EVFDR Series
Fluorescent Luminaires
Photometric Data and Dimensions
6L
Luminaire: All EVFDR Luminaires
Lamp: 2-40/T-12, 2-60/T-12, 2-110/T-12
Zonal Degrees: 0-30 0-40 0-60 0-90
Zonal Lumens: 1416 2352 4263 5863
Total Bare Lamp Lumens: 8600
To determine number and placement of luminaires,
see Lighting Selector Guide, pages 665 to 689.
NOTE: All data provided is
for two 60 watt, T-12
recessed contact 800MA
cool white lamps
(EVFDR22062). For other
wattages use the following
conversion factors:
32W .67
40W, Rapid Start .73
40W, Slimline .70
110W, Cool White 1.60
Example: Zonal lumens for
EVFDR226 fixture, across
the axis, for 40-50° is 1,060.
Zonal lumens for
EVFDR223 fixture, across
Coefficient of Utilization
Effective Floor Cavity Reflectance 20%
% Reflectance Room Cavity Ratio
Eff. Ceil. Wall 12345
50 .735 .645 .570 .506 .452
80 30 .700 .594 .512 .442 .387
10 .670 .551 .466 .394 .339
50 .714 .627 .557 .494 .440
70 30 .682 .580 .501 .435 .380
10 .653 .542 .458 .388 .334
50 .673 .593 .528 .468 .420
50 30 .647 .554 .482 .418 .368
10 .624 .520 .444 .378 .327
50 .636 .562 .501 .446 .401
30 30 .616 .530 .463 .403 .354
10 .596 .502 .430 .368 .319
50 .603 .533 .477 .425 .383
10 30 .585 .507 .444 .388 .343
10 .570 .483 .416 .358 .311
0 0 .551 .465 .399 .340 .294
% Reflectance Room Cavity Ratio
Eff. Ceil. Wall 678910
50 .408 .368 .332 .304 .266
80 30 .344 .305 .271 .243 .207
10 .298 .262 .228 .202 .169
50 .398 .360 .325 .297 .260
70 30 .338 .299 .267 .240 .206
10 .293 .258 .226 .201 .168
50 .380 .344 .311 .285 .250
50 30 .327 .289 .259 .233 .199
10 .287 .252 .221 .197 .164
50 .364 .328 .299 .274 .240
30 30 .317 .282 .251 .226 .193
10 .281 .246 .217 .193 .160
50 .348 .316 .286 .263 .231
10 30 .306 .274 .244 .220 .188
10 .274 .241 .213 .189 .157
0 0 .259 .226 .198 .175 .144
the axis, is 40-50° is: 1,060
× .70 ⍧ 742
Dimensions