eLLB20 Series
Recessed Mount
Fluorescent Luminaires
Class I, Div.2, Groups A,B,C,D
Class I, Zone 1, Groups IIC
ATEX Certified
Cl. II, Div 2, Groups F,G
Cl. II, Div 1, Groups E,F,G (Canada)
Wet Locations
Enclosure Type 4X and IP66
6L
Features & Benefits:
ɀ One piece welded housing with fitted cover
frame. The cover frame is an integral part of
the housing to seal out dust & moisture.
ɀ Adjustable mounting clamps:
- permanently attached and adjustable
through the cover frame for easy
installation.
- allow recess mounting in ceilings from
25mm to 100mm (1⍯ to 4⍯ approx) thick for
maximum mounting flexibility.
ɀ Support lugs (M8 x .6) to secure the
luminaire to ceiling structural support
members for safety.
ɀ Frameless tempered glass lens:
ɀ Isolating switch turns off power to the
ballast and lamps when the lens is opened
for added safety.
ɀ 4 entries (2 on each end) supplied with (2)
3
⁄4” NPT adapter hubs and extra large wire
well for feedthrough and tandem applications
without the need for separate junction boxes.
ɀ Electronic ballast:
ɀ Uses T8 linear fluorescent lamps for high
efficiency and reduced operating costs.
ɀ 5 wire terminal block and through wiring are
standard for quick and easy balancing of
lighting loads on 3 phase systems.
1
⁄4⍯) thick for added safety.
- 6mm (
- interior hinge for maximum dust shedding.
- fitted with captive screws for ease of lamp
replacement and maintenance.
- high power factor (95%) for energy
efficiency, more luminaires per circuit and
supply voltage flexibility.
- features 2 channel circuitry for safety - if
one lamp fails the 2nd lamp remains in
operation.
Applications:
eLLB series luminaires are used:
ɀ For flush or surface ceiling mounting.
ɀ In cleanroom areas where it is important to
have smooth, flush surfaces.
ɀ Where extreme cleanliness is required as in
pharmaceutical, chemical and electronics
manufacturing facilities, as well as in paint
shops and spray booths.
ɀ For tough environmental conditions
involving corrosives, water, dust and extreme
temperatures.
ɀ In areas that require lamps to reach full
illumination immediately.
ɀ Indoor & outdoor ordinary or hazardous
areas.
ɀ For Wet locations and areas with hose
down / wash down requirements.
Adjustable Mounting Clamps
Hinged Glass Lens
Certifications &
Compliances:
NEC :
ɀ Class I, Division 2, Groups A,B,C,D
ɀ Class I, Zone 1 AEx ed IIC
ɀ Class II, Division 2, Groups F, G
ɀ UL Listed
CEC:
ɀ Class I, Division 2, Groups A,B,C,D
ɀ Class I, Zone 1 Ex eds IIC
ɀ Class II, Division 1 Groups E,F,G
ɀ cUL Listed
Enclosure
ɀ Type 4X
ɀ IP66
UL Standards
ɀ 2279 Hazardous (Classified) Locations
ɀ 1598 Luminaires
CSA Standards
ɀ C22.2 No. 9
ɀ CAN/CSA-E60079-0:02
ɀ CAN/CSA-E60079-1:02
ɀ CAN/CSA-E60079-7
ɀ CAN/CSA-E61241-1-1:02
ATEX
ɀ ATEX Directive
94/9/EC
ɀ Type of Protection
ɀ EC-Type
Examination
Certificate
Standard Materials:
ɀ One piece welded housing and cover
frame - sheet steel or stainless steel
ɀ Lens - 6mm (1/4⍯) thick tempered glass
ɀ Gaskets - Silicone
ɀ External hardware - stainless steel
Standard Finishes:
ɀ Sheet steel - White epoxy coat
ɀ Lens - Clear
ɀ Stainless steel - Natural
US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright©2006 Cooper Crouse-Hinds
II 2 G
II 2 D T80°C
EEx ed IIC T4
EEx ed ib IIC T4
(CG-variant)
DMT 02 ATEX E 069
855
6L
eLLB20 Series
Recessed Mount
Fluorescent Luminaires
Class I, Div.2, Groups A,B,C,D
Class I, Zone 1, Groups IIC
ATEX Certified
Cl. II, Div 2, Groups F,G
Cl. II, Div 1, Groups E,F,G (Canada)
Wet Locations
Enclosure Type 4X and IP66
Ratings (Electrical / Size):
Sources/Wattages
ɀ Two 32W or 17W T8 Linear Fluorescent
Voltages
ɀ 120-240V, 50-60 Hz.
ɀ 110-230VDC
Hub Size
ɀ Four 25mm entries, 2 on each end, 3
plugged.
3
⁄4” NPT adapter hubs provided
ɀ Two
standard, for feed-through or tandem wiring.
Terminals
ɀ 5 wire terminal block, one on each end
(L1, L2, L3, N, Ground)
ɀ Two 6mm2 (#10 AWG) maximum per
terminal
Temperature Performance Data:
Minimum Starting Temperature: -20°C
Watts
Two 17W T8 lamps 50°CT4 T660°C
Two 32W T8 lamps 50°CT4 T660°C
Accessories:
ɀ3⁄4⍯ NPT adapter hub STM2
Mounting Accessories:
ɀ Eye Bolt for Support Lugs 2 2480 002 000
ɀ Hexagon Screw for Support Lugs 2 2480 054 000
Ordering Information:
Hub
Size Wattage/Lamp Voltage/Hz
3
⁄4⍯ NPT Two 17 Watt T8 Rapid Start
3
⁄4⍯ NPT Two 32 Watt T8 Rapid Start
IEC / CENELEC certified luminaires are available. Consult factory.
120-240V, 50-60 Hz
110-230 VDC .18A eLLB20 2217/U240 eLLB20 2217SS/U240
120-240V, 50-60 Hz
110-230 VDC .34A eLLB20 4232/U240 eLLB20 4232SS/U240
Ambient
Temp.
Operating
Current
Cl. I, Div. 2
Cl. I, Zone 1 & 2 Class II
Catalog Number
Epoxy Coated
Steel Enclosure
Supply
Wire Temp
Stainless Steel
Enclosure
Dimensions (Inches) and Weights:
Item Weight
eLLB20 2217 33 lbs.
eLLB20 4232 48 lbs.
856