7F
XJG-EMT Conduit Expansion
Joints With Internal Grounding
For EMT Conduit
Application:
XJG expansion couplings are used with EMT
Conduit:
ɀ without the need for an external bonding
jumper and clamps
ɀ to couple together two (2) sections of
conduit subject to longitudinal movement
ɀ in long conduit runs to permit linear
movement caused by thermal expansion and
contraction.
ɀ on long conduit runs to prevent conduit
from buckling and ensuing circuit failures
ɀ indoors or outdoors where conduit
expansion occurs and there are wide
temperature ranges
ɀ in conduit runs that cross structural joints
ɀ in conduit runs to prevent damage to
conduit supports such as in a building or on
a bridge
ɀ with optional redundant visible
grounding strap
Standard Materials and
Finishes
Body
ɀ Steel-electrogalvanized
ɀ Copper-free aluminum - natural
Reducer
1
⁄2⍯ through 1⍯ - Steel - electrogalvanized
ɀ
1
⁄4⍯ through 4⍯ -
ɀ 1
electrogalvanized and aluminum paint
Gland Nut
1
⁄2⍯ through 1⍯ - Steel - electrogalvanized
ɀ
1
⁄4⍯ through 4⍯ -
ɀ 1
electrogalvanized and aluminum paint
Packing
®
ɀ Teflon
Washer
ɀ Steel - electrogalvanized
Gasket
ɀ Vellum
Bushing
ɀ
ɀ 1
electrogalvanized and aluminum paint
Ground Springs
ɀ Phosphor bronze - electrogalvanized
Ground Strap
ɀ Braided tinned copper
U-Bolts
ɀ Malleable iron – electrogalvanized
(trademark of E.I. DuPont Co.)
1
⁄2⍯ through 1⍯ - Steel - electrogalvanized
1
⁄4⍯ through 4⍯ -
Options:
Available with redundant† ground strap for
visible indication of grounding – order
separately (BJ Series)
Size Ranges:
ɀ1⁄2⍯ through 4⍯ conduit size
ɀ 4⍯ maximum conduit movement
Certifications and
Compliances:
ɀ UL Standard: 514B
ɀ CSA Standard: C22.2 No. 18
ɀ NEC Articles 250-77 and 300-7 (b)
ɀ NEMA FB1
Feraloy
Feraloy
Feraloy
®
iron alloy -
®
iron alloy -
®
iron alloy -
XJG-EMT – for use with EMT conduit
Conduit Conduit Catalog Bonding A B
Size Movement Number Jumper Diameter Length
1
⁄2⍯ 4⍯ XJG14-EMT BJ14 13⁄4⍯ 103⁄4⍯
3
⁄4⍯ 4⍯ XJG24-EMT BJ24 21⁄8⍯ 11⍯
1⍯ 4⍯ XJG34-EMT BJ34 27⁄16⍯ 111⁄2⍯
11⁄4⍯ 4⍯ XJG44-EMT BJ44 31⁄8⍯ 151⁄4⍯
11⁄2⍯ 4⍯ XJG54-EMT BJ54 35⁄8⍯ 151⁄2⍯
2⍯ 4⍯ XJG64-EMT BJ64 43⁄4⍯ 151⁄2⍯
21⁄2⍯ 4⍯ XJG74-EMT BJ74 47⁄8⍯ 183⁄4⍯
3⍯ 4⍯ XJG84-EMT BJ84 53⁄8⍯ 197⁄8⍯
31⁄2⍯ 4⍯ XJG94-EMT BJ94 65⁄8⍯ 211⁄4⍯
4⍯ 4⍯ XJG104-EMT BJ104 65⁄8⍯ 211⁄4⍯
* Teflon®is a registered trademark of E.I. DuPont Co.
† XJG expansion couplings use a metallic bushing and ground springs to create a high integrity internal ground connection.
External ground straps offer a redundant ground path and easy visible indication of ground
Maximum Optional
XJG shown with optional bonding jumper
174
US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright©2006 Cooper Crouse-Hinds