Wet Locations
Expansion/Deflection Coupling and Expansion Joint Internally Grounded
Application:
XJGD combination fittings are used with rigid metal conduit and IMC: ɀ to accommodate axial expansion, angular misalignment and parallel misalignment ɀ to couple together two (2) sections of conduit subject to longitudinal movement ɀ to maintain a ground connection
the need for an external bonding jumper and clamps
ɀ in long conduit runs to prevent conduit from buckling and causing circuit failures ɀ indoors or outdoors where conduit expansion occurs and there are wide temperature swings
ɀ in conduit runs that cross structural joints ɀ in conduit runs to prevent damage to
conduit supports such as in a building or on a bridge
Standard Materials:
ɀ Body, Hubs, Gland Nut, Washer, Bushing –
®
Feraloy
ɀ Packing – Teflon ɀ Gasket – vellum ɀ Ground Spring – phosphor bronze ɀ Outer Jacket – molded neoprene ɀ Jacket Clamps – stainless steel ɀ Inner Sleeve – molded plastic ɀ Ground Straps – tinned copper braid
®
Standard Finishes:
Feraloy
®
– electrogalvanized
ɀ
Certifications and Compliances:
ɀ UL standard: 514B
without
XJGD Ordering Information
Hub Size Movement Number Diameter Length
1 4 XJGD34 3
11⁄4 4 XJGD44 41⁄4 181⁄8
11⁄2 4 XJGD54 41⁄2 185⁄8
2 4 XJGD64 415⁄16 191⁄4
21⁄2 4 XJGD74 55⁄16 203⁄4
3 4 XJGD84 515⁄16 215⁄8
31⁄2 4 XJGD94 61⁄2 215⁄8
4 4 XJGD104 8 273⁄4
Maximum Conduit Catalog A B
15
16 173⁄4