6L
EVF Series
Fluorescent
Luminaires
Application:
EVF luminaires are used in areas
where hazardous fumes, gases,
or dusts are present.
EVF luminaires with S718 option
are designed specifically for use
inside paint spray booths where
hazardous fumes, gases, and
paint residue are present. This
includes powder paint process
areas.
EVF luminaires with S718 option
are also suitable for use in wet
locations.
Features:
All EVF luminaires
ɀ Provide cool, even light with
natural color rendition
ɀ Reduce relamping schedule
(long lamp life)
ɀ Continuous and uniform
illumination made possible by
mounting end to end (no space
needed between luminaires for
relamping)
ɀ No special tools required for
relamping. Threaded lamp tube
cover provides quick and easy
access for relamping
ɀ Threaded joints on lamp tube
and wiring chamber covers
permit easy access for lower
maintenance costs
ɀ Reflectors can be removed or
replaced with only a screwdriver
ɀ Easy to install. Factory sealed
and wired luminaire facilitates
installation
ɀ Standard electronic ballast for
32 watt and 40 watt rapid start
luminaires.
ɀ Standard energy efficient
ballast for 40 watt slimline, 60
watt and 110 watt luminaires.
ɀ Low temperature ballast is
supplied as standard on 32 watt
T8 (0°F), 40 watt slimline (0°F);
60 watt and 110 watt
luminaires(–20°F).
ɀ All exposed hardware is
stainless steel for maximum
protection against corrosion, and
for longer luminaire life
ɀ Copper-free aluminum
construction throughout means
lighter luminaire weight, easier
installation, and excellent
corrosion resistance
ɀ All exterior materials are nonsparking
ɀ Type P ballasts furnished in
compliance with NEC
ɀ Heavy-duty glass lamp tubes
provide maximum strength and
impact resistance to protect
lamps
ɀ
Cl. I, Div 1, Groups C,D
ɀ
Cl. I, Zone 1 Group IIB
ɀ
Cl. II, Div 1, Groups E,F,G
ɀ
Cl. III, Simultaneous Presence
3-lamp 2-lamp with angle reflector
ɀ
Paint Spray (Suffix S718)
ɀ
Wet Locations (Suffix S718)
ɀ
3,3R, IP54 (Suffix S718)
EVF
Furnished For Hub Line Volts 1-Lamp 2-Lamp 3-Lamp 4-Lamp
Use With Size 60 Hz.* Cat. # Cat. # Cat. # Cat. #
32 watt, T-8 medium3⁄4⍯ 120-277 EVF21029/UNV EVF22029/UNV EVF23029/UNV EVF24029/UNV
Bi-pin 265MA lamps
40 watt, T-12 medium 3/4⍯ 110-125 EVF21082 EVF22082 EVF23082 EVF24082
Bi-pin rapid start 3/4⍯ 277 EVF21087 EVF22087 EVF23087 EVF24087
430MA lamps† 3/4⍯ 347 EVF21089/347 EVF22089/347 EVF23089/347 EVF24089/347
40 watt, T-12 single
pin, slimline
425MA lamps
60 watt, T-12 recessed
contact, 800MA lamps†
110 watt, T-12 recessed
contact, 1500MA lamps†
* For 220 volt 50 hz, 240 volt 50 hz or 240 volt 60 hz operation change the last ‘‘2’’ in the 120 volt 60 hz catalog number to a ‘‘9’’ and add
‘‘/220 50’’, ‘‘/240 50’’ or ’’/240 60’’ respectively.
ie. For a 2 lamp, 40 watt rapid start luminaire for 220 volt 50 hz operation order an EVF22089/220 50.
† 50 Hz not available.
EVF luminaires with S718
option
ɀ All joints sealed
ɀ Inside paint booth mounting
capabilities provide greater
flexibility in luminaire placement,
avoids necessity of complicated
design and installation work, and
improves task lighting control
ɀ Smooth simple design makes it
easy to remove any accumulated
deposits of paint residue
Mounting
Accessories:
Various hazardous area fittings
are used to mount EVF
luminaires. The fittings shown on
page 859 support the unwired
(relamping) end. For the wired
(ballast) end any of the luminaire
hangers for hazardous locations
(listed in Section 7L) can be
used. CPS conduit outlet bodies
with hub covers (listed in Section
4F) are also suitable
3
⁄4⍯ 347 EVF21029/347 EVF22029/347 EVF23029/347 EVF24029/347
3
⁄4⍯ 110-125 EVF21032 EVF22032 EVF23032 EVF24032
3
⁄4⍯ 277 EVF21037 EVF22037 EVF23037 EVF24037
3
⁄4⍯ 347 EVF21039/347 EVF22039/347 EVF23039/347 EVF24039/347
3
⁄4⍯ 110-125 EVF21062 EVF22062 EVF23062 EVF24062
3
⁄4⍯ 277 EVF21067 EVF22067 EVF23067 EVF24067
3
⁄4⍯ 347 EVF21069/347 EVF22069/347 EVF23069/347 EVF24069/347
3
⁄4⍯ 110-125 EVF21072 EVF22072 EVF23072 EVF24072
3
⁄4⍯ 277 EVF21077 EVF22077 EVF23077 EVF24077
3
⁄4⍯ 347 EVF21079/347 EVF22079/347 EVF23079/347 EVF24079/347
Options:
ɀ For suitability for wet locations
and locations having deposits of
readily combustible paint residue
– add Cat. No. Suffix S718
Corro-free
ɀ
coat – add Cat. No. Suffix S752
ɀ With 45° angle reflectors in lieu
of straight down reflectors – add
Cat. No. Suffix S369
ɀ Clear disposable polyester
tube wrap – consult Cooper
Crouse-Hinds
ɀ Fused – add suffix S658‡
ɀ Furnished with lamps - add
suffix S714.
ɀ Low temperature
electromagnetic ballast for 40
watt T12 rapid start luminaires
rated for 0°F - add suffix BY.
TM
epoxy powder
Size Ranges:
ɀ 1, 2, 3, and 4-lamp
Electrical Rating
Standard Materials:
ɀ Copper-free aluminum except
sheet aluminum reflectors
Standard Finishes:
ɀ Natural except reflectors
ɀ Reflectors – white epoxy
powder coat
Certifications and
Compliances:
ɀ NEC and CEC:
Class I, Division 1 Group C, D
Class I, Zone 1 Group IIB
Class II Group E, F, G
Class III
Simultaneous Presence (Cl. I
and Cl. II)
Paint Spray (S718)
ɀ UL Standards:
844 Hazardous (Classified)
Locations
1598 Luminaires
ɀ CSA Standards:
C22.2 No. 137
Ranges:
ɀ 32 to 110 watts
Temperature Performance Data: (Based on 40°C Ambient)
Lamp Class I/Class II/Zone 1 Supply
Type 1 Lamp 2 Lamp 3 Lamp 4 Lamp Wire
32/40W T5 T5 T5 T5 75°C
60W T5 T5 T5 T5 75°C
110W T4 T4 T4 T4 90°C
When ordering fuses for luminaires,
‡
option S658, you must specify the operating
voltage. S658 cannot be ordered with /MT in
the catalog number.
858
US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright©2006 Cooper Crouse-Hinds