EVFDR Series Fluorescent Luminaires
Applications:
ɀ EVFDR luminaires are suitable for wet locations and marine environments, above and below deck, where hazardous vapors, gases or dusts are present ɀ Ideally suited for use on offshore drilling/ production platforms and on shipboard in hazardous areas
ɀ For mounting where headroom is limited ɀ For hazardous areas where watertightness
and corrosion resistance are required
Features:
ɀ Exterior surfaces finished with gray epoxy enamel for corrosion resistance
ɀ Exterior hardware stainless steel ɀ All joints sealed and gasketed for
watertightness ɀ Vibration resistant
-shock mounts
-sockets are spring loaded for tight lamp
contact connection ɀ Heavy duty glass lamp tubes for maximum strength and impact resistance
ɀ All exterior materials are non-sparking ɀ C-type beam clamps provide quick and
easy mounting ɀ Luminaire is adjustable 30° either side of fixture axis, allowing for control of light output ɀ Beam clamp support is adjustable allowing beam clamp to be located to suit structure ɀ Low profile – luminaire height is 7 standard mounting, 11 mounting option – for maximum clearance where headroom is critical ɀ Provides cool light with natural color rendition ɀ Continuous and uniform illumination made possible by mounting end to end (no space needed between luminaires for relamping) – see page 859 for relamping information ɀ Relamping is accomplished without tools. Quarter-turn fastener allows end of luminaire to be lowered quickly. Cable supports end of luminaire while relamping – both hands are free. Threaded lamp tube cover provides quick and easy access to lamp and receptacle ɀ Reflectors can be removed or replaced with only a screwdriver
ɀ Ballast housing readily accessible ɀ Minimum weight – copper-free aluminum
construction throughout ɀ Type P ballast furnished in compliance with NEC ɀ Standard electronic ballast for 32 watt and 40 watt rapid start. ɀ Standard energy efficient electromagnetic ballast (40W slimline, 60W and 110W) is standard. ɀ Low temperature ballasts are standard on 32WT8, 40W slimline, 60W and 110W. 32 watt and 40 watt low temperature ballasts are rated for 0°F. 60 and 100 watt low temperature ballasts are rated for –20°F.
11
16with shock
Standard Materials:
ɀ Housing – copper-free aluminum ɀ Exposed hardware – stainless steel
13
16with
ɀ
Cl. I, Div. 1, Groups C,D
ɀ
Cl. I, Zone 1 Group IIB
ɀ
Cl. II, Div 1, Groups E,F,G
ɀ
Cl. III, Simultaneous Presence
Options:
ɀ Furnished with lamps – add suffix S714 to Cat. No. ɀ Furnished with safety cable for high vibration areas - add suffix S715 to Cat. No. ɀ Beam clamps with shock mounts are available for ease of installation and resistance to vibration – add suffix KIT40 to Cat. No. ɀ Beam clamps only – add suffix KIT41 to Cat. No. ɀ Low Temperature Electromagnetic Ballast: 40W rapid start rated 0°F - add suffix BY to Cat. No. ɀ Emergency lighting battery unit – add suffix
S799 to Cat. No.
Size Ranges:
ɀ 2-lamp only
Electrical Rating Ranges:
ɀ 32, 40, 60 and 110W
Certifications and Compliances:
ɀ NEC and CEC:
Class I, Division 1 Group C,D Class I, Zone 1 Group IIB Class II Groups E,F,G Class III Simultaneous Presence (Cl. and Cl. II)
ɀ UL Standards
844 Hazardous (Classified) Locations
1598 Luminaires 1598A Marine Locations ɀ CSA Standards
C22.2 No. 137
Temperature Performance Data:
2-Lamp
110W T4 90°C
(Based on 40°C Ambient)
32, 40W T5 75°C
60W T5 75°C
Class I Class II Zone 1
ɀ
Marine & Wet Locations
ɀ
3,3R,4,4X: IP66
Supply Wire
EVFDR
Furnished For Hub Line Volts 2-Lamp Use With Size 60 Hz.* Cat. #
32 watt, T-8 medium Bi-pin 265MA lamps
40 watt, T-12 medium 3/4 110-125 EVFDR22082 Bi-pin rapid start 3/4 277 EVFDR22087 430MA lamps†
60 watt, T-12 recessed 3/4 110-125 EVFDR22062 contact, 800MA lamps 3/4 277 EVFDR22067
110 watt, T-12 recessed 3/4 110-125 EVFDR22072 contact, 1500MA lamps† 3/4 277 EVFDR22077
For 220 volt 50 hz, 240 volt 50 hz or 240 volt 60 hz operation change the last ‘‘2’’ in the 120 volt 60 hz catalog number to a ‘‘9’’
*
and add ‘‘/220 50’’, ‘‘/240 50’’ or ‘‘/240 60’’ respectively. ie. For a 2 lamp, 40 watt rapid start fixture for 220 volt 50 hz operation order an EVFDR22089/220 50. † 50 Hz. not available.
Standard Finishes:
ɀ All exterior metal components – gray epoxy enamel ɀ Reflectors – white epoxy powder coat
3
4 120-277 EVFDR22029/UNV
3
4 347 EVFDR22029/347
862
US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright©2006 Cooper Crouse-Hinds