6F
Conduit Sealing Fittings
Chico Sealing Compound
and Fiber see pages 155–156
Cl. I, Div. 1 & 2, Groups A, B, C, D
Cl. II, Div. 1, Groups E, F, G
Cl. II, Div. 2, Groups F, G
Cl. III
Explosionproof
Dust-Ignitionproof
Applications:
6F
EYS and EZS sealing fittings:
• Restrict the passage of gases, vapors or flames from one portion
of the electrical installation to another at atmospheric pressure and
normal ambient temperatures
• Limit explosions to the sealed off enclosure
• Limit precompression or pressure "piling" in conduit systems
Sealing fittings are required:
• At each entrance to an enclosure housing an arcing or sparking
device when used in Class I, Division 1 and 2 hazardous locations.
To be located as close as practicable and, in no case, more than
18" from such enclosures
• At each conduit entrance of 2" size or larger to an enclosure or
fitting housing terminals, splices or taps when used in Class I,
Division 1 hazardous locations. To be located as close as
practicable and, in no case, more than 18" from such enclosures
• In conduit systems when leaving Class I, Division 1 or Division 2
hazardous locations
• In cable systems when the cables either do not have a
gas/vaportight continuous sheath or are capable of transmitting
gases or vapors through the cable core when those cables leave
the Class I, Division 1 or Division 2 hazardous locations
Features:
EYS and EZS sealing fittings include:
• Minimum turning radius
• Large openings with threaded closures to provide easy access to
conduit hubs for making dams
• Integral bushings in conduit hubs to protect conductor insulation
from damage
• Taper-tapped hubs to ensure ground continuity
EYS sealing fittings are available for installation in either vertical only
or in both horizontal or vertical positions.
EZS sealing fittings for installation at any angle; the covers with
opening for sealing compound can be properly positioned to accept
the compound.
Certifications and Compliances:
• NEC/CEC:
EYS1-3, 11-31, 16-36, 116-316
Class I, Division 1 & 2, Groups A, B, C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
EYS41-101, 416-1016
Class I, Division 1 & 2, Groups B, C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
EYS29, 4-014, 46-0146
EZS1-8, 16-86
Class I, Division 1 & 2, Groups C, D
Class II, Division 1, Groups F, G
Class II, Division 2, Groups F, G
Class III
• UL Standard: 1203
• CSA Standard: C22.2
Sealing fittings are approved for use in hazardous locations only when Chico®X fiber and
Chico A sealing compound or Chico SpeedSeal are used to make the seal.
Standard Materials:
• Bodies – Feraloy®iron alloy and/or ductile iron
• Plugs – Feraloy iron alloy and/or steel
• Removable nipples – steel
140
Standard Finishes:
• Feraloy iron alloy and ductile iron – electrogalvanized and
aluminum acrylic paint
• Steel – electrogalvanized
Options:
Description Suffix
Copper-free aluminum bodies, nipples and enclosures SA
Size Ranges:
•1/2" – 6"
Ordering Information - EYS
Vertical
female
For Sealing in Vertical Positions Only
Hub
Size
1
3
1 EYS3* EYS36* 3
Female
Hub Cat. #
/2 EYS1* EYS16* 1
/4 EYS2* EYS26* 2
For Sealing in Vertical or Horizontal Positions
Hub
Female Hub
Size
Cat. #
1
/2 EYS11* EYS116* 11
3
/4 EYS21* EYS216* 22
1 EYS31* EYS316* 33
11/4 EYS41 EYS416 68
1
1
/2 EYS51 EYS516 103/4 121/4
2 EYS61 EYS616 19 223/4
21/2 EYS71 EYS716 251/2 30
3 EYS81 EYS816 56 64
31/2 EYS91 EYS916 72 82
4 EYS101 EYS1016 95 110
*Available in copper-free aluminum – to order, add suffix SA to Cat. No.
Vertical
male &
female
Male & Female
Hub Cat. #
Male & Female
Hub Cat. # Vertical Horizontal
Vertical or
horizontal
female
Approximate Internal
Volume in Cubic Inches
3
/4
Approximate Internal
Volume in Cubic
Inches
Vertical or
horizontal
male & female
3
/4
1
/2
Dimensions (In Inches)
EYS 16 Series
Size a b
1
/2
39/32 11/4 15/8 311/16 11/4 15/32
3
/4
312/16 11/2 129/32 311/16 11/2 11/4
1
5
/16 13/4 23/8 45/16 13/4 13/8
4
Turning
Radius a b
EYS 46 Series
11/4
51/16 23/16 123/32 51/16 23/16 123/32
11/2
51/2 27/16 21/16 51/2 27/16 21/16
1
2
/4 325/16 61/4 325/16
6
21/2
71/2 31/2 211/16 71/2 31/2 211/16
1
3
/2 41/4 35/16 81/2 41/4 35/16
8
31/2
93/16 43/4 37/16‡9
3
4
/4 51/4 311/16‡9
9
1
5
6
‡With cover removed.
/16 61/2 419/32‡
11
1
/8 75/8 511/32‡
12
EYS 116 Series
Turning
Radius
EYS 116 Series
3
/16 43/4 37/16‡
3
/4 51/4 311/16‡
Chico Sealing Compound
and Fiber see pages 155–156
Cl. I, Div. 1 & 2, Groups C, D
Cl. II, Div. 1, Groups E, F, G
Cl. II, Div. 2, Groups F, G
Cl. III
Explosionproof
Dust-Ignitionproof
6FConduit Sealing Fittings
Ordering Information - EYS
Vertical or horizontal male & female
For Sealing in Vertical or Horizontal Positions
Hub
Size
1
1
2 EYS6* EYS66* 19 223/4
21/2 EYS7* EYS76* 251/2 30
3 EYS8* EYS86* 56 64
31/2 EYS9* EYS96* 72 82
4 EYS10* EYS106* 95 110
5 EYS012 EYS0126 200 222
6 EYS014 EYS0146 290 315
*Available in copper-free aluminum – to order, add suffix SA to Cat. No.
Female
Hub
Cat. #
1
/4 EYS4* EYS46* 68
1
/2 EYS5* EYS56* 103/4 121/4
Male &
Female
Hub
Cat. # Vert. Horiz.
Approximate Internal
Volume in Cubic Inches
1
/2
Ordering Information - EZS
Male & female hub
For Sealing at Any Angle
Female
Hub
Hub
Size
Cat. #
1
/2 EZS1 EZS16 61/4 61/4
3
/4 EZS2 EZS26 61/2 61/2
1 EZS3 EZS36 101/4 101/4
11/4 EZS4 EZS46 121/2 121/2
11/2 EZS5 EZS56 141/2 141/2
2 EZS6 EZS66 46 46
1
2
/2 EZS7 EZS76 55 55
3 EZS8 EZS86 90 90
Male &
Female
Hub
Cat. # Vert. Horiz.
Approximate Internal
Volume in Cubic Inches
6F
EYS
Elbow seal
For Sealing in Vertical Positions
Hub
Size Cat. #
3
/4 EYS29 13/4
Approximate
Internal Volume
in Cubic Inches
Dimensions
In Inches
EYS 16 Series
EYS Elbow Seal
Size a b
3
/4
311/16 13/4 17/8
EYS 46 and
EYS 116 Series
Turning Radius
(Vertical)
EYS Elbow Seal EZS Series
EZS Series
Size a b c
1
/2
43/16 35/8 21/2 17/8
3
/4
43/16 35/8 21/2 17/8
15
1
11/4
11/2
2
21/2
3
†With cover removed.
/16 331/32 321/8
4
51/16 413/32 325/16
53/16 49/16 31/4 211/32
1
/16 513/32 53/16 39/32
7
715/16 527/32 53/16 33/8
5
/8 61/2 57/8 37/8
8
Turning
Radius†
141