3L
35-150W LMV Series
Photometric Data
Champ®H.I.D. Luminaires
Lamp: 100W/E-17 high pressure sodium (HPS)
Total bare lamp lumens: 9500
To determine number and placement of luminaires, see Lighting Selector Guide, pages 665 to 689.
NOTE: All data provided is for high pressure sodium luminaires with 100W/E-17 clear lamps. Use
conversion factors (multipliers) shown below for other lamp types and wattages. Consult Cooper
Crouse-Hinds for additional photometric data on any
Champ
Series luminaire.
Luminaire with Globe and Dome Reflector
Multipliers (for use with
candlepower curves only).
Luminaire
Series
LMVS 35 0.24
Luminaire spacing ratio: 2.0
Con-
Lamp
version
Watts
Factors
50 0.42
70 0.67
150 1.68
Coefficient of Utilization
Effective Floor Cavity Reflectance 20%
% Reflectance Room Cavity Ratio
Eff. Cell Wall 12345
80 30 .691 .579 .487 .408 .346
70 30 .676 .568 .479 .403 .340
50 30 .647 .548 .464 .390 .332
30 30 .623 .529 .450 .379 .322
10 30 .598 .510 .436 .367 .341
0 0 .568 .471 .391 .319 .263
% Reflectance Room Cavity Ratio
Eff. Cell Wall 678910
80 30 .300 .259 .225 .199 .165
70 30 .295 .255 .223 .196 .165
50 30 .288 .248 .217 .192 .161
30 30 .280 .243 .210 .186 .157
10 30 .272 .237 .206 .182 .152
0 0 .223 .187 .158 .136 .107
50 .722 .628 .545 .473 .413
10 .663 .537 .441 .358 .296
50 .705 .613 .534 .463 .403
10 .650 .531 .436 .355 .293
50 .671 .585 .511 .442 .387
10 .627 .514 .426 .349 .289
50 .641 .560 .489 .424 .371
10 .605 .501 .416 .342 .284
50 .614 .537 .470 .407 .356
10 .584 .488 .407 .335 .279
50 .366 .324 .288 .261 .226
10 .253 .215 .180 .156 .127
50 .358 .318 .282 .256 .221
10 .249 .212 .179 .156 .126
50 .343 .305 .271 .246 .214
10 .246 .209 .177 .154 .124
50 .330 .292 .261 .237 .206
10 .242 .205 .175 .152 .122
50 .317 .282 .251 .228 .199
10 .238 .202 .172 .149 .120
Isofootcandle Chart: Luminaire with Globe and Dome
Reflector
Isofootcandle Chart: Luminaire with Globe and 30°
Angle Reflector
Isofootcandle charts show illumination in footcandles on work plane 10
feet below light center. Multiply by factor shown to convert to other
mounting heights.
Height (Ft.) Factor Height (Ft.) Factor
6 2.78 14 0.51
8 1.56 16 0.39
12 0.70
742