Crompton Instruments Integra Ri3 Digital Meters Communications Guide

Integra Ri3 Digital Meters Communications Guide
Crompton Instruments
1 Integra Ri3 Digital Meter Modbus Protocol implementation 3
1.1 Modbus Protocol Overview 3
1.2 Input Registers 3 Ri3 Input Registers 4
1.3 Modbus Protocol Holding Registers and Digital meter set up 6
1.3.1 Ri3 MODBUS Protocol Holding Register Parameters 6
2 RS485 General Information 9
2.1 Half Duplex 9
2.2 Connecting the Instruments 10
2.3 A and B terminals 10
2.4 Troubleshooting 11
3 MODBUS Protocol General Information 12
3.1 MODBUS Protocol Message Format 12
3.2 Serial Transmission Modes 13
3.3 MODBUS Protocol Message Timing (RTU Mode) 14
3.4 How Characters are Transmitted Serially 14
3.5 Error Checking Methods 15
3.5.1 Parity Checking 15
3.5.2 CRC Checking 15
3.6 Function Codes 16
3.7 IEEE floating point format 16
3.8 MODBUS Protocol Commands supported 18
3.8.1 Read Input Registers 18
3.9 Holding Registers 19
3.9.1 Read Holding Registers 19
3.9.2 Write Holding Registers 20
3.10 Exception Response 20
3.11 Exception Codes 21
3.11.1 Table of Exception Codes 21
3.12 Diagnostics 21
4 RS485 Implementation of Johnson Controls Metasys 22
4.1 Application details 22
4.1.1 Metasys release requirements 22
4.1.2 Support for Metasys Integration 22
4.1.3 Support for Crompton Integra Digital meter operation 22
4.1.4 Design considerations 22
4.2 Ri3 Digital meter METASYS N2 Point Mapping table 23
2 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
1 Integra Ri3 Digital Meter Modbus Protocol implementation
1.1 Modbus Protocol Overview
This section provides basic information for interfacing the Integra Digital meter to a Modbus Protocol network. If background information or more details of the Integra implementation is required please refer to section 2 and 3 of this document. Integra offers the option of an RS485 communication facility for direct connection to SCADA or other communications systems using the Modbus Protocol RTU slave protocol. The Modbus Protocol establishes the format for the master's query by placing into it the device address, a function code defining the requested action, any data to be sent, and an error checking field. The slave's response message is also constructed using Modbus Protocol. It contains fields confirming the action taken, any data to be returned, and an error-checking field. If an error occurs in receipt of the message, Integra will make no response. If the Integra is unable to perform the requested action, it will construct an error message and send it as the response. The electrical interface is 2-wire RS485, via 3 screw terminals. Connection should be made using twisted pair screened cable (Typically 22 gauge Belden 8761 or equivalent). All "A" and "B" connections are daisy chained together. The screens should also be connected to the “Gnd” terminal. To avoid the possibility of loop currents, an Earth connection should be made at only one point on the network. Line topology may or may not require terminating loads depending on the type and length of cable used. Loop (ring) topology does not require any termination load. The impedance of the termination load should match the impedance of the cable and be at both ends of the line. The cable should be terminated at each end with a 120 ohm (0.25 Watt min.) resistor. A total maximum length of 3900 feet (1200 metres) is allowed for the RS485 network. A maximum of 32 electrical nodes can be connected, including the controller. The address of each Integra can be set to any value between 1 and 247. Broadcast mode (address 0) is not supported. The maximum latency time of an Integra Digital meter is 60ms i.e. this is the amount of time that can pass before the first response character is output. The supervisory programme must allow this period of time to elapse before assuming that the Integra Digital meter is not going to respond. The format for each byte in RTU mode is: Coding System: 8-bit per byte Data Format: 4 bytes (2 registers) per parameter.
Floating point format ( to IEEE 754) Most significant register first (Default). The default may be changed if required -
See Holding Register "Register Order" parameter. Error Check Field: 2 byte Cyclical Redundancy Check (CRC) Framing: 1 start bit
8 data bits, least significant bit sent first
1 bit for even/odd parity (or no parity)
1 stop bit if parity is used; 1 or 2 bits if no parity Data Coding All data values in the INTEGRA Ri3 Digital meters are transferred as 32 bit IEEE 754 floating point numbers, (input and output) therefore each INTEGRA Digital meter value is transferred using two MODBUS Protocol registers. All register read requests and data write requests must specify an even number of registers. Attempts to read/write an odd number of registers prompt the INTEGRA Digital meter to return a MODBUS Protocol exception message. However, for compatibility with some SCADA systems, Integra Digital meters will respond to any single input or holding register read with an instrument type specific value
The INTEGRA Ri3 can transfer a maximum of 40 values in a single transaction, therefore the maximum number of registers requestable is 80. Exceeding this limit prompts the INTEGRA Ri3 to generate an exception response.
Data Transmission speed is selectable between 2400, 4800, 9600, 19200 and 38400 baud.
1.2 Input Registers
Input registers are used to indicate the present values of the measured and calculated electrical quantities. Each parameter is held in two consecutive 16 bit registers. The following table details the 3X register address, and the values of the address bytes within the message. A tick () in the column indicates that the parameter is valid for the particular wiring system. Any parameter with a cross (X) will return the value Zero. Each parameter is held in the 3X registers. Modbus Protocol Function Code 04 is used to access all parameters.
3 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
Address
(Register)
Parameter
Number
Ri3 Input Register
Parameter
Modbus
Protocol Start
Address Hex
3 Ø 3 Ø 1
Ø
Description
Units
Hi
Byte
Lo
Byte
4 W 3 W 2
W
30001
1
Phase 1 line to neutral volts.
Volts
00
00

30003
2
Phase 2 line to neutral volts.
Volts
00
02

30005
3
Phase 3 line to neutral volts.
Volts
00
04

30007
4
Phase 1 current.
Amps
00
06

30009
5
Phase 2 current.
Amps
00
08

30011
6
Phase 3 current.
Amps
00
0A

30013
7
Phase 1 power.
Watts
00
0C

30015
8
Phase 2 power.
Watts
00
0E

30017
9
Phase 3 power.
Watts
00
10

30019
10
Phase 1 volt amps.
VoltAmps
00
12

30021
11
Phase 2 volt amps.
VoltAmps
00
14

30023
12
Phase 3 volt amps.
VoltAmps
00
16

30025
13
Phase 1 volt amps reactive.
VAr
00
18

30027
14
Phase 2 volt amps reactive.
VAr
00
1A

30029
15
Phase 3 volt amps reactive.
VAr
00
1C

30031
16
Phase 1 power factor (1).
None
00
1E

30033
17
Phase 2 power factor (1).
None
00
20

30035
18
Phase 3 power factor (1).
None
00
22

30037
19
Phase 1 phase angle.
Degrees
00
24

30039
20
Phase 2 phase angle.
Degrees
00
26

30041
21
Phase 3 phase angle.
Degrees
00
28

30043
22
Average line to neutral volts.
Volts
00
2A

30047
24
Average line current.
Amps
00
2E

30049
25
Sum of line currents.
Amps
00
30

30053
27
Total system power.
Watts
00
34

30057
29
Total system volt amps.
VA
00
38

30061
31
Total system VAr.
VAr
00
3C

30063
32
Total system power factor (1).
None
00
3E

30067
34
Total system phase angle.
Degrees
00
42

30071
36
Frequency of supply voltages.
Hz
00
46

30073
37
Import Wh since last reset (6).
Wh/kWh/MWh
00
48

30075
38
Export Wh since last reset (6).
Wh/kWH/MWh
00
4A

30077
39
Import VArh since last reset (6).
VArh/kVArh/MVArh
00
4C

30079
40
Export VArh since last reset (6).
VArh/kVArh/MVArh
00
4E

30081
41
VAh since last reset (6).
VAh/kVAh/MVAh
00
50

30083
42
Ah since last reset(7).
mAh/Ah/kAh
00
52

30085
43
Total system power demand (4).
Watts
00
54

30087
44
Maximum total system power demand (4).
Watts
00
56

30101
51
Total system VA demand.
VA
00
64

For example, to request:- Amps 1 Start address = 0006 No of registers = 0002 Amps 2 Start address = 0008 No of registers = 0002 Each request for data must be restricted to 40 parameters or less. Exceeding the 40 parameter limit will cause a Modbus Protocol exception code to be returned.
Ri3 Input Registers
4 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
Address
(Register)
Parameter
Number
Ri3 Input Register
Parameter
Modbus
Protocol Start
Address Hex
3 Ø 3 Ø 1
Ø
Description
Units
Hi
Byte
Lo
Byte
4 W 3 W 2
W
30103
52
Maximum total system VA demand.
VA
00
66

30105
53
Neutral current demand.
Amps
00
68

30107
54
Maximum neutral current demand.
Amps
00
6A

30201
101
Line 1 to Line 2 volts.
Volts
00
C8

30203
102
Line 2 to Line 3 volts.
Volts
00
CA

30205
103
Line 3 to Line 1 volts.
Volts
00
CC

30207
104
Average line to line volts.
Volts
00
CE

30225
113
Neutral current.
Amps
00
E0

30235
118
Phase 1 L/N volts THD
%
00
EA

30237
119
Phase 2 L/N volts THD
%
00
EC

30239
120
Phase 3 L/N volts THD
%
00
EE

30241
121
Phase 1 Current THD
%
00
F0

30243
122
Phase 2 Current THD
%
00
F2

30245
123
Phase 3 Current THD
%
00
F4

30249
125
Average line to neutral volts THD.
%
00
F8

30251
126
Average line current THD.
%
00
FA

30255
128
-Total system power factor (5).
Cos Ø
00
FE

30259
130
Phase 1 current demand.
Amps
01
02

30261
131
Phase 2 current demand.
Amps
01
04

30263
132
Phase 3 current demand.
Amps
01
06

30265
133
Maximum phase 1 current demand.
Amps
01
08

30267
134
Maximum phase 2 current demand.
Amps
01
0A

30269
135
Maximum phase 3 current demand.
Amps
01
0C

30335
168
Line 1 to line 2 volts THD.
%
01
4E

30337
169
Line 2 to line 3 volts THD.
%
01
50

30339
170
Line 3 to line 1 volts THD.
%
01
52

30341
171
Average line to line volts THD.
%
01
54

Notes:
1. The power factor has its sign adjusted to indicate the nature of the load. Positive for capacitive and negative for inductive.
2. There is a user option to select either k or M for the energy prefix.
3. The same user option as in 2 above gives a prefix of none or k for Amphours
4. The power sum demand calculation is for import power only
5. The negative total system power factor is a sign inverted version of parameter 32, the magnitude is the same as parameter 32.
6. There is a user option to select None, k or M for the energy prefix.
7. The same user option as in 6 above gives a prefix of milli, none or k for Amphours
5 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
Address
(Register)
Parameter
Number
Parameter
Modbus Protocol
Start Address
Hex
Valid range
Mode High Byte
Low
Byte
40001
1
Demand Time
00
00
Read minutes into first demand calculation. When the Demand Time reaches the Demand Period then the demand values are valid.
ro
40003
2
Demand Period
00
02
Write demand period: 0, 5, 8, 10, 15, 20, 30 or 60 minutes, default 60. Setting the period to 0 will cause the “phase # current demand” parameters to show the “phase # current” values, and “Maximum phase # current demandto show the maximum value of
the “phase # current”
parameter since last demand reset.
r/w
40007
4
System Volts
00
06
Read system voltage, VLL for 3P3W, VLN for others.
ro
40009
5
System Current
00
08
Write system current, limited to 1 to 9999A. Requires password, see parameter 13
r/wp
40011
6
System Type
00
0A
Write system type: 3p4w = 3, 3p3w = 2 & 1p2w = 1 Requires password, see parameter 13
r/wp 40013
7
Relay Pulse Width
00
0C
Write relay on period in milliseconds: 60, 100 or 200, default 200.
r/w
40015
8
Password Lock
00
0E
Write any value to password lock protected registers. Read password lock status: 0 = locked. 1 = unlocked. Reading will also reset the password timeout back to one minute.
r/w
1.3 Modbus Protocol Holding Registers and Digital meter set up
Holding registers are used to store and display instrument configuration settings. All holding registers not listed in the table below should be considered as reserved for manufacturer use and no attempt should be made to modify their values. The holding register parameters may be viewed or changed using the Modbus Protocol. Each parameter is held in two consecutive 4X registers. Modbus Protocol Function Code 03 is used to read the parameter and Function Code 16 is used to write. Write to only one parameter per message.
1.3.1 Ri3 MODBUS Protocol Holding Register Parameters
6 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
Address
(Register)
Parameter
Number
Parameter
Modbus Protocol
Start Address
Hex
Valid range
Mode High Byte
Low
Byte
40019
10
Network Parity Stop
00
12
Write the network port parity/stop bits for MODBUS Protocol, where: 0 = One stop bit and no parity, default. 1 = One stop bit and even parity. 2 = One stop bit and odd parity. 3 = Two stop bits and no parity. Requires a restart to become effective.
r/w
40021
11
Network Node
00
14
Write the network port node address: 1 to 247 for MODBUS Protocol, default
1. Requires a restart to become effective. Note, both the MODBUS Protocol and Johnson Controls node addresses can be changed via the display setup menus.
r/w
40023
12
Pulse Divisor
00
16
Write pulse divisor index: n = 2 to 6 in Wh/l0^n, default 3.
r/w
40025
13
Password
00
18
Write password for access to protected registers. Read zero. Reading will also reset the password timeout back to one minute. Default password is 0000.
r/w
40029
15
Network Baud Rate
00
1C
Write the network port baud rate for MODBUS Protocol, where: 0 = 2400 baud. 1 = 4800 baud. 2 = 9600 baud, default. 3 = 19200 baud. 4 = 38400 baud. Requires a restart to become effective
r/w
40031
16
Energy Units Prefix
00
1E
Write the units prefix for energy output values. 0 = unit, e.g. Wh. But mAh for ampere hours. 1 = k, e.g. kWh, default. But Ah for ampere hours. 2 = M, e.g. MWh. But kAh for ampere hours.
r/w
40033
17
Low Power Limit Override
00
20
0 = limit on 1% symbol off 1 = limit off 1% symbol on Default = 0
r/w
40037
19
System Power
00
24
Read the total system power, e.g. for 3p4w returns System Volts x System Amps x 3.
ro
7 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
Address
(Register)
Parameter
Number
Parameter
Modbus Protocol
Start Address
Hex
Valid range
Mode High Byte
Low
Byte
40041
21
Register Order
00
28
Write the value 2141 in the required register order.
r/w
40043
22
Serial Number Hi
00
2A
Read the first product serial number.
ro
40045
23
Serial Number Lo
00
2C
Read the second product serial number.
ro
40087
44
Relay Energy Type
00
56
Write MODBUS Protocol input parameter for pulse relay: 0 = relay off, 37 = Import Wh or 39 = Import VArh, default 37.
r/w
40217
109
Reset Logged Data
00
D8
Write code to reset data group. Code 1 for Energy. Code 2 for Demand Maximums. Code 3 for Demand Maximums and Demand Time.
r/w
Register Order controls the order in which the Integra Digital meter receives or sends floating-point numbers: - normal or reversed register order. In normal mode, the two registers that make up a floating point number are sent most significant register first. In reversed register mode, the two registers that make up a floating point number are sent least significant register first. To set the mode, write the value '2141.0' into this register - the instrument will detect the order used to send this value and set that order for all Modbus Protocol transactions involving floating point numbers.
It is perfectly feasible to change Integra Digital meter set-up using a general purpose Modbus Protocol master, but often easier to use the Integra Digital meter display or Integra Digital meter configurator software, especially for gaining password protected access. The Integra Digital meter configurator software has facilities to store configurations to disk for later retrieval and rapid set up of similarly configured products.
Password
Some of the parameters described above are password protected and thus require the password to be entered at the Password register before they can be changed. The default password is 0000. When the password has been entered it will timeout in one minute unless the Password or Password Lock register is read to reset the timeout timer. Once the required changes have been made to the protected parameters the password lock should be reapplied by
a) allowing the password to timeout, or b) writing any value to the Password Lock register, or c) power cycling the instrument.
8 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
PARAMETER
Mode of Operation
Differential
Number of Drivers and Receivers
32 Drivers, 32 Receivers
Maximum Cable Length
1200 m
Maximum Data Rate
10 M baud
Maximum Common Mode Voltage
12 V to –7 V
Minimum Driver Output Levels (Loaded)
+/– 1.5 V
Minimum Driver Output Levels (Unloaded)
+/– 6 V Drive Load
Minimum 60 ohms
Driver Output Short Circuit Current Limit
150 mA to Gnd, 250 mA to 12 V 250 mA to –7 V
Minimum Receiver Input Resistance
12 kohms
Receiver Sensitivity
+/– 200 mV
2 RS485 General Information
Some of the information in this section relates to other Integra Digital meter product families, and is included to assist where a mixed network is implemented. RS485 or EIA (Electronic Industries Association) RS485 is a balanced line, half-duplex transmission system allowing transmission distances of up to 1.2 km. The following table summarises the RS-485 Standard:
Further information relating to RS485 may be obtained from either the EIA or the various RS485 device manufacturers, for example Texas Instruments or Maxim Semiconductors. This list is not exhaustive.
2.1 Half Duplex
Half duplex is a system in which one or more transmitters (talkers) can communicate with one or more
receivers (listeners) with only one transmitter being active at any one time. For example, a “conversation” is
started by asking a question, the person who has asked the question will then listen until he gets an answer or until he decides that the individual who was asked the question is not going to reply.
In a 485 network the “master” will start the “conversation” with a “query” addressed to a specific “slave”, the
“master” will then listen for the “slave’s” response. If the “slave” does not respond within a pre-defined period, (set by control software in the “master”), the “master” will abandon the “conversation”.
9 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
2.2 Connecting the Instruments
If connecting an RS485 network to a PC use caution if contemplating the use of an RS232 to 485 converter together with a USB to RS485 adapter. Consider either an RS232 to RS485 converter, connected directly to a suitable RS232 jack on the PC, or use a USB to RS485 converter or, for desktop PCs a suitable plug in RS485 card. (Many 232:485 converters draw power from the RS232 socket. If using a USB to RS232 adapter, the adapter may not have enough power available to run the 232:485 converter.) Screened twisted pair cable should be used. For longer cable runs or noisier environments, use of a cable
specifically designed for RS485 may be necessary to achieve optimum performance. All “A” terminals should be connected together using one conductor of the twisted pair cable, all “B” terminals should be
connected together using the other conductor in the pair. The cable screen should be connected to the “Gnd” terminals. A Belden 9841 (Single pair) or 9842 (Two pair) or similar cable with a characteristic impedance of 120 ohms is recommended. The cable should be terminated at each end with a 120 ohm, quarter watt (or greater) resistor. Note: Diagram shows wiring topology only. Always follow terminal identification on Integra Digital meter product label.
There must be no more than two wires connected to each terminal, this ensures that a “Daisy Chain or
“straight line” configuration is used. A “Star” or a network with “Stubs (Tees)” is not recommended as
reflections within the cable may result in data corruption.
2.3 A and B terminals
The A and B connections to the Integra Digital meter products can be identified by the signals present on them whilst there is activity on the RS485 bus:
10 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
2.4 Troubleshooting
Start with a simple network, one master and one slave. With Integra Digital meter products this is
easily achieved as the network can be left intact whilst individual instruments are disconnected by removing the RS485 connection from the rear of the instrument.
Check that the network is connected together correctly. That is all of the “A’s” are connected together,
and all of the “B’s” are connected together, and also that all of the “Gnd’s” are connected together.
Confirm that the data “transmitted” onto the RS485 is not echoed back to the PC on the RS232 lines.
(This facility is sometimes a link option within the converter). Many PC based packages seem to not perform well when they receive an echo of the message they are transmitting. SpecView and PCView (PC software) with a RS232 to RS485 converter are believed to include this feature.
Confirm that the Address of the instrument is the same as the “master” is expecting. If the “network” operates with one instrument but not more than one check that each instrument has a
unique address.
Each request for data must be restricted to 40 parameters (20 in the case of the older Integra 1000 or
2000) or less. Violating this requirement will impact the performance of the instrument and may result in a response time in excess of the specification.
Check that the MODBUS Protocol mode (RTU or ASCII) and serial parameters (baud rate, number of
data bits, number of stop bits and parity) are the same for all devices on the network.
Check that the “master” is requesting floating-point variables (pairs of registers placed on floating
point boundaries) and is not “splitting” floating point variables.
Check that the floating-point byte order expected by the “master” is the same as that used by Integra
Digital meter products. (PCView and Citect packages can use a number of formats including that supported by Integra Digital meter).
If possible obtain a second RS232 to RS485 converter and connect it between the RS485 bus and an
additional PC equipped with a software package, which can display the data on the bus. Check for the existence of valid requests.
11 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
First Byte
Last
Byte
Slave
Address
Function
Code
Start
Address
(Hi)
Start
Address
(Lo)
Number
of
Points
(Hi)
Number
of
Points
(Lo)
Error
Check
(Lo)
Error
Check
(Hi)
3 MODBUS Protocol General Information
Communication on a MODBUS Protocol Network is initiated (started) by a “Master” sending a query to a
“Slave”. The “Slave“, which is constantly monitoring the network for queries addressed to it, will respond by
performing the requested action and sending a response back to the ”Master”. Only the “Master” can initiate a query.
In the MODBUS Protocol the master can address individual slaves, or, using a special “Broadcast” address, can initiate a broadcast message to all slaves. The Integra Digital meter do not support the broadcast address.
3.1 MODBUS Protocol Message Format
The MODBUS Protocol defines the format for the master’s query and the slave’s response. The query contains the device (or broadcast) address, a function code defining the requested action, any data to be sent, and an error-checking field. The response contains fields confirming the action taken, any data to be returned, and an error-checking field. If an error occurred in receipt of the message then the message is ignored, if the slave is unable to perform the requested action, then it will construct an error message and send it as its response. The MODBUS Protocol functions used by the Integra Digital meters copy 16 bit register values between master and slaves. However, the data used by the Integra Digital meter is in 32 bit IEEE 754 floating point format. Thus each instrument parameter is conceptually held in two adjacent MODBUS Protocol registers. Query The following example illustrates a request for a single floating point parameter i.e. two 16-bit Modbus Protocol Registers.
Slave Address: 8-bit value representing the slave being addressed (1 to 247), 0 is reserved for the
broadcast address. The Integra Digital meters do not support the broadcast address.
Function Code: 8-bit value telling the addressed slave what action is to be performed. (3, 4, 8 or
16 are valid for Integra Digital meter)
Start Address (Hi): The top (most significant) eight bits of a 16-bit number specifying the start address
of the data being requested.
Start Address (Lo): The bottom (least significant) eight bits of a 16-bit number specifying the start
address of the data being requested. As registers are used in pairs and start at zero, then this must be an even number.
Number of Points (Hi): The top (most significant) eight bits of a 16-bit number specifying the number of
registers being requested.
Number of Points (Lo): The bottom (least significant) eight bits of a 16-bit number specifying the number
of registers being requested. As registers are used in pairs, then this must be an even number.
Error Check (Lo): The bottom (least significant) eight bits of a 16-bit number representing the error
check value.
Error Check (Hi): The top (most significant) eight bits of a 16-bit number representing the error
check value.
12 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
First Byte
Last Byte
Slave
Address
Functio n Code
Byte
Count
First
Register
(Hi)
First
Register
(Lo)
Second
Register
(Hi)
Second
Register
(Lo)
Error
Check
(Lo)
Error
Check
(Hi)
First Byte
Last Byte
Slave
Address
Function
Code
Error
Code
Error
Check
(Lo)
Error
Check
(Hi)
Response The example illustrates the normal response to a request for a single floating point parameter i.e. two 16-bit Modbus Protocol Registers.
Slave Address: 8-bit value representing the address of slave that is responding. Function Code: 8-bit value which, when a copy of the function code in the query, indicates
that the slave recognised the query and has responded. (See also Exception
Response). Byte Count: 8-bit value indicating the number of data bytes contained within this response First Register (Hi)*: The top (most significant) eight bits of a 16-bit number representing the first
register requested in the query. First Register (Lo)*: The bottom (least significant) eight bits of a 16-bit number representing the
first register requested in the query. Second Register (Hi)*: The top (most significant) eight bits of a 16-bit number representing the
second register requested in the query. Second Register (Lo)*: The bottom (least significant) eight bits of a 16-bit number representing the
second register requested in the query. Error Check (Lo): The bottom (least significant) eight bits of a 16-bit number representing the
error check value. Error Check (Hi): The top (most significant) eight bits of a 16-bit number representing the error
check value. * These four bytes together give the value of the floating point parameter requested.
Exception Response If an error is detected in the content of the query (excluding parity errors and Error Check mismatch), then an error response (called an exception response), will be sent to the master. The exception response is identified by the function code being a copy of the query function code but with the most-significant bit set. The data contained in an exception response is a single byte error code.
Slave Address: 8-bit value representing the address of slave that is responding. Function Code: 8 bit value which is the function code in the query OR'ed with 80 hex, indicating
that the slave either does not recognise the query or could not carry out the action requested.
Error Code: 8-bit value indicating the nature of the exception detected. (See “Table Of
Exception Codes“ later).
Error Check (Lo): The bottom (least significant) eight bits of a 16-bit number representing the error
check value.
Error Check (Hi): The top (most significant) eight bits of a 16-bit number representing the error
check value.
3.2 Serial Transmission Modes
There are two MODBUS Protocol serial transmission modes, ASCII and RTU. Integra Digital meters do not support the ASCII mode.
In RTU (Remote Terminal Unit) mode, each 8-bit byte is used in the full binary range and is not limited to ASCII characters as in ASCII Mode. The greater data density allows better data throughput for the same baud rate, however each message must be transmitted in a continuous stream. This is very unlikely to be a problem for modern communications equipment. The format for each byte in RTU mode is:
13 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
Coding System:
Full 8-bit binary per byte. In this document, the value of each byte will be shown as two hexadecimal characters each in the range 0-9 or A-F.
Line Protocol:
1 start bit, followed by the 8 data bits. The 8 data bits are sent with least significant bit first.
User Option Of Parity And Stop Bits:
No Parity and 2 Stop Bits No Parity and 1 Stop Bit Even Parity and 1 Stop Bit. Odd Parity and 1 Stop Bit.
User Option of Baud Rate:
4800 ; 9600 ; 19200 ; 38400 (older Integra Digital meters do not support 38400 but do offer 2400 instead)
Start 1 2 3 4 5 6 7 8
Parit
y
Stop
Start 1 2 3 4 5 6 7 8
Stop
Stop
Start 1 2 3 4 5 6 7 8
Stop
The baud rate, parity and stop bits must be selected to match the master’s settings.
3.3 MODBUS Protocol Message Timing (RTU Mode)
A MODBUS Protocol message has defined beginning and ending points. The receiving devices recognises
the start of the message, reads the “Slave Address” to determine if they are being addressed and knowing
when the message is completed they can use the Error Check bytes and parity bits to confirm the integrity of the message. If the Error Check or parity fails then the message is discarded. In RTU mode, messages starts with a silent interval of at least 3.5 character times. The first byte of a message is then transmitted, the device address.
Master and slave devices monitor the network continuously, including during the ‘silent’ intervals. When the
first byte (the address byte) is received, each device checks it to find out if it is the addressed device. If the device determines that it is the one being addressed it records the whole message and acts accordingly, if it is not being addressed it continues monitoring for the next message. Following the last transmitted byte, a silent interval of at least 3.5 character times marks the end of the message. A new message can begin after this interval. In the Integra 1000 and 2000, a silent interval of 60msec minimum is required in order to guarantee successful reception of the next request. The entire message must be transmitted as a continuous stream. If a silent interval of more than 1.5 character times occurs before completion of the message, the receiving device flushes the incomplete message and assumes that the next byte will be the address byte of a new message. Similarly, if a new message begins earlier than 3.5 character times following a previous message, the receiving device may consider it a continuation of the previous message. This will result in an error, as the value in the final CRC field will not be valid for the combined messages.
3.4 How Characters are Transmitted Serially
When messages are transmitted on standard MODBUS Protocol serial networks each byte is sent in this order (left to right):
Transmit Character = Start Bit + Data Byte + Parity Bit + 1 Stop Bit (11 bits total): Least Significant Bit (LSB) Most Significant Bit (MSB)
Transmit Character = Start Bit + Data Byte + 2 Stop Bits (11 bits total):
Integra Digital meters additionally support No parity, One stop bit.
Transmit Character = Start Bit + Data Byte + 1 Stop Bit (10 bits total):
14 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
Start of Query
Query received
by slave
Start of Response
Response
Slave Processing Time
Query Transmission Time
Response Transmission Time
Response
Query
The master is configured by the user to wait for a predetermined timeout interval. The master will wait for this period of time before deciding that the slave is not going to respond and that the transaction should be
aborted. Care must be taken when determining the timeout period from both the master and the slaves’
specifications. The slave may define the ‘response time’ as being the period from the receipt of the last bit
of the query to the transmission of the first bit of the response. The master may define the ‘response time’
as period between transmitting the first bit of the query to the receipt of the last bit of the response. It can be seen that message transmission time, which is a function of the baud rate, must be included in the timeout calculation.
3.5 Error Checking Methods
Standard MODBUS Protocol serial networks use two error checking processes, the error check bytes mentioned above check message integrity whilst Parity checking (even or odd) can be applied to each byte in the message.
3.5.1 Parity Checking
If parity checking is enabled – by selecting either Even or Odd Parity - the quantity of “1’s” will be counted in the data portion of each transmit character. The parity bit will then be set to a 0 or 1 to result in an Even or Odd total of “1’s”. Note that parity checking can only detect an error if an odd number of bits are picked up or dropped in a
transmit character during transmission, if for example two 1’s are corrupted to 0’s the parity check will not
find the error. If No Parity checking is specified, no parity bit is transmitted and no parity check can be made. Also, if No Parity checking is specified and one stop bit is selected the transmit character is effectively shortened by one bit.
3.5.2 CRC Checking
The error check bytes of the MODBUS Protocol messages contain a Cyclical Redundancy Check (CRC) value that is used to check the content of the entire message. The error check bytes must always be present to comply with the MODBUS Protocol, there is no option to disable it. The error check bytes represent a 16-bit binary value, calculated by the transmitting device. The receiving device must recalculate the CRC during receipt of the message and compare the calculated value to the value received in the error check bytes. If the two values are not equal, the message should be discarded. The error check calculation is started by first pre-loading a 16-bit register to all 1’s (i.e. Hex (FFFF)) each successive 8-bit byte of the message is applied to the current contents of the register. Note: only the eight bits of data in each transmit character are used for generating the CRC, start bits, stop bits and the parity bit, if one is used, are not included in the error check bytes. During generation of the error check bytes, each 8-bit message byte is exclusive OR'ed with the lower half of the 16 bit register. The register is then shifted eight times in the direction of the least significant bit (LSB), with a zero filled into the most significant bit (MSB) position. After each shift the LSB prior to the shift is extracted and examined. If the LSB was a 1, the register is then exclusive OR'ed with a pre-set, fixed value. If the LSB was a 0, no exclusive OR takes place. This process is repeated until all eight shifts have been performed. After the last shift, the next 8-bit message byte is exclusive OR'ed with the lower half of the 16 bit register, and the process repeated. The final contents of the register, after all the bytes of the message have been applied, is the error check value. In the following pseudo code “ErrorWord” is a 16-bit value representing the error check values.
BEGIN ErrorWord = Hex (FFFF) FOR Each byte in message ErrorWord = ErrorWord XOR byte in message FOR Each bit in byte LSB = ErrorWord AND Hex (0001)
15 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
Code
MODBUS Protocol name
Description
03
Read Holding Registers
Read the contents of read/write location (4X references)
04
Read Input Registers
Read the contents of read only location (3X references)
08
Diagnostics
Only sub-function zero is supported. This returns the data element of the query unchanged.
16
Pre-set Multiple Registers
Set the contents of read/write location (4X references)
Data Hi Reg,
Hi Byte.
Data Hi Reg,
Lo Byte.
Data Lo Reg,
Hi Byte.
Data Lo Reg,
Lo Byte.
SEEE EEEE
EMMM
MMMM
MMMM MMMM
MMMM MMMM
IF LSB = 1 THEN ErrorWord = ErrorWord – 1 ErrorWord = ErrorWord / 2 IF LSB = 1 THEN ErrorWord = ErrorWord XOR Hex (A001) NEXT bit in byte NEXT Byte in message END
3.6 Function Codes
The function code part of a MODBUS Protocol message defines the action to be taken by the slave. Integra Digital meters support the following function codes:
3.7 IEEE floating point format
The MODBUS Protocol defines 16 bit “Registers” for the data variables. A 16-bit number would prove too restrictive, for energy parameters for example, as the maximum range of a 16-bit number is 65535. However, there are a number of approaches that have been adopted to overcome this restriction. Integra Digital meters use two consecutive registers to represent a floating-point number, effectively expanding the range to +/- 1x1037. The values produced by Integra Digital meters can be used directly without any requirement to “scale” the values, for example, the units for the voltage parameters are volts, the units for the power parameters are watts etc. What is a floating point Number? A floating-point number is a number with two parts, a mantissa and an exponent and is written in the form
1.234 x 105. The mantissa (1.234 in this example) must have the decimal point moved to the right with the number of places determined by the exponent (5 places in this example) i.e. 1.234x 105 = 123400. If the exponent is negative the decimal point is moved to the left. What is an IEEE 754 format floating-point number? An IEEE 754 floating point number is the binary equivalent of the decimal floating-point number shown above. The major difference being that the most significant bit of the mantissa is always arranged to be 1 and is thus not needed in the representation of the number. The process by which the most significant bit is
arranged to be 1 is called normalisation, the mantissa is thus referred to as a “normal mantissa”. During
normalisation the bits in the mantissa are shifted to the left whilst the exponent is decremented until the most significant bit of the mantissa is one. In the special case where the number is zero both mantissa and exponent are zero. The bits in an IEEE 754 format have the following significance:
Where: S represents the sign bit where 1 is negative and 0 is positive E is the 8-bit exponent with an offset of 127 i.e. an exponent of zero is represented by 127, an
exponent of 1 by 128 etc. M is the 23-bit normal mantissa. The 24th bit is always 1 and, therefore, is not stored. Using the above format the floating point number 240.5 is represented as 43708000 hex:
16 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
Data Hi Reg,
Hi Byte
Data Hi Reg,
Lo Byte
Data Lo Reg,
Hi Byte
Data Lo Reg,
Lo Byte
43
70
80
00
Data Hi Reg,
Hi Byte
Data Hi Reg,
Lo Byte
Data Lo Reg,
Hi Byte
Data Lo Reg,
Lo Byte
0100 0011
0111 0000
1000 0000
0000 0000
The following example demonstrates how to convert IEEE 754 floating-point numbers from their hexadecimal form to decimal form. For this example, we will use the value for 240.5 shown above Note that the floating-point storage representation is not an intuitive format. To convert this value to decimal, the bits should be separated as specified in the floating-point number storage format table shown above. For example:
From this you can determine the following information.
The sign bit is 0, indicating a positive number.  The exponent value is 10000110 binary or 134 decimal. Subtracting 127 from 134 leaves 7, which is
the actual exponent.
The mantissa appears as the binary number 11100001000000000000000
There is an implied binary point at the left of the mantissa that is always preceded by a 1. This bit is not stored in the hexadecimal representation of the floating-point number. Adding 1 and the binary point to the beginning of the mantissa gives the following:
1.11100001000000000000000 Now, we adjust the mantissa for the exponent. A negative exponent moves the binary point to the left. A positive exponent moves the binary point to the right. Because the exponent is 7, the mantissa is adjusted as follows:
11110000.1000000000000000 Finally, we have a binary floating-point number. Binary bits that are to the left of the binary point represent the power of two corresponding to their position. For example, 11110000 represents (1 x 27) + (1 x 26) + (1 x 25) + (1 x 24) + (0 x 23)+ (0 x 22) + (0 x 21)+ (0 x 20) = 240. Binary bits that are to the right of the binary point also represent a power of 2 corresponding to their position. As the digits are to the right of the binary point the powers are negative. For example: .100 represents (1 x 2-1) + (0 x 2-2)+ (0 x 2-3) + … which equals 0.5. Adding these two numbers together and making reference to the sign bit produces the number +240.5.
17 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
Data Hi Reg,
Hi Byte
Data Hi Reg,
Lo Byte
Data Lo Reg,
Hi Byte
Data Lo Reg,
Lo Byte
Field Name
Example (Hex)
Slave Address
01
Function
04
Starting Address High
00
Starting Address Low
00
Number of Points High
00
Number of Points Low
02
Error Check Low
71
Error Check High
CB
Field Name
Example (Hex)
Slave Address
01
Function
04
Byte Count
04
Data, High Reg, High Byte
43 Data, High Reg, Low Byte
66
Data, Low Reg, High Byte
33
Data, Low Reg, Low Byte
34
Error Check Low
1B
Error Check High
38
For each floating point value requested two MODBUS Protocol registers (four bytes) must be requested. The received order and significance of these four bytes for Integra Digital meters is shown below:
3.8 MODBUS Protocol Commands supported
All Integra Digital meters support the “Read Input Register” (3X registers), the “Read Holding Register” (4X registers) and the “Pre-set Multiple Registers” (write 4X registers) commands of the MODBUS Protocol RTU
protocol. All values stored and returned are in floating point format to IEEE 754 with the most significant register first.
3.8.1 Read Input Registers
MODBUS Protocol code 04 reads the contents of the 3X registers. Example The following query will request ‘Volts 1’ from an instrument with node address 1:
Note: Data must be requested in register pairs i.e. the “Starting Address“ and the “Number of Points” must be even numbers to request a floating point variable. If the “Starting Address” or the “Number of points” is odd then the query will fall in the middle of a floating point variable the product will return an error message. The following response returns the contents of Volts 1 as 230.2. But see also “Exception Response” later.
18 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
Field Name
Example (Hex)
Slave Address
01
Function
03
Starting Address High
00
Starting Address Low
00
Number of Points High
00
Number of Points Low
02
Error Check Low
C4
Error Check High
0B
Field Name
Example (Hex)
Slave Address
01
Function
03
Byte Count
04
Data, High Reg, High Byte
3F
Data, High Reg, Low Byte
80
Data, Low Reg, High Byte
00
Data, Low Reg, Low Byte
00
Error Check Low
F7
Error Check High
CF
3.9 Holding Registers
3.9.1 Read Holding Registers
MODBUS Protocol code 03 reads the contents of the 4X registers. Example The following query will request the prevailing ‘Demand Time’:
Note: Data must be requested in register pairs i.e. the “Starting Address“ and the “Number of Points” must be even numbers to request a floating point variable. If the “Starting Address” or the “Number of points” is odd then the query will fall in the middle of a floating point variable the product will return an error message.
The following response returns the contents of Demand Time as 1, But see also “Exception Response” later.
19 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
Field Name
Example (Hex)
Slave Address
01
Function
10
Starting Address High
00
Starting Address Low
02
Number of Registers High
00
Number of Registers Low
02
Byte Count
04
Data, High Reg, High Byte
42
Data, High Reg, Low Byte
70
Data, Low Reg, High Byte
00
Data, Low Reg, Low Byte
00
Error Check Low
67
Error Check High
D5
Field Name
Example (Hex)
Slave Address
01
Function
10
Starting Address High
00
Starting Address Low
02
Number of Registers High
00
Number of Registers Low
02
Error Check Low
E0
Error Check High
08
Field Name
Example (Hex)
Slave Address
01
Function
10 OR 80 = 90
Exception Code
01
Error Check Low
8D
Error Check High
C0
3.9.2 Write Holding Registers
MODBUS Protocol code 10 (16 decimal) writes the contents of the 4X registers. Example The following query will set the Demand Period to 60, which effectively resets the Demand Time:
Note: Data must be written in register pairs i.e. the “Starting Address“ and the “Number of Points” must be
even numbers to write a floating point variable. If the “Starting Address” or the “Number of points” is odd
then the query will fall in the middle of a floating point variable the product will return an error message. In general only one floating point value can be written per query
The following response indicates that the write has been successful. But see also “Exception Response” later.
3.10 Exception Response
If the slave in the “Write Holding Register” example above, did not support that function then it would have
replied with an Exception Response as shown below. The exception function code is the original function code from the query with the MSB set i.e. it has had 80 hex logically ORed with it. The exception code indicates the reason for the exception. The slave will not respond at all if there is an error with the parity or CRC of the query. However, if the slave can not process the query then it will respond with an exception. In this case a code 01, the requested function is not support by this slave.
20 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
Exception
Code
MODBUS
Protocol name
Description
01
Illegal
Function
The function code is not supported by the product
02
Illegal Data
Address
Attempt to access an invalid address or an attempt to read or write part of a floating point value
03
Illegal Data
Value
Attempt to set a floating point variable to an invalid value
05
Slave Device
Failure
An error occurred when the instrument attempted to store an update to it’s configuration
Field Name
Example (Hex)
Slave Address
01
Function
08
Sub-Function High
00
Sub-Function Low
00
Data Byte 1
AA
Data Byte 2
55
Error Check Low
5E
Error Check High
94
Field Name
Example (Hex)
Slave Address
01
Function
08
Sub-Function High
00
Sub-Function Low
00
Data Byte 1
AA
Data Byte 2
55
Error Check Low
5E
Error Check High
94
3.11 Exception Codes
3.11.1 Table of Exception Codes
Integra Digital meters support the following function codes:
3.12 Diagnostics
MODBUS Protocol code 08 provides a number of diagnostic sub-functions. Only the “Return Query Data” sub-function (sub-function 0) is supported on Integra Digital meters. Example The following query will send a diagnostic “return query data” query with the data elements set to Hex(AA) and Hex(55) and will expect these to be returned in the response:
Note: Exactly one register of data (two bytes) must be sent with this function. The following response indicates the correct reply to the query, i.e. the same bytes as the query.
21 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
4 RS485 Implementation of Johnson Controls Metasys
These notes briefly explain Metasys and Crompton Instruments Integra Digital meter integration. Use these notes with the Metasys Technical Manual, which provides information on installing and commissioning Metasys N2 Vendor devices.
4.1 Application details
The Integra Digital meter is an N2 Vendor device that connects directly with the Metasys N2 Bus. This implementation assigns key electrical parameters to ADF points, each with override capability. Components requirements
Integra Digital meter with RS485 card and N2 port available.  N2 Bus cable.
4.1.1 Metasys release requirements
Metasys Software Release 12.04 or later  NCM-361-8 or Metasys Extended Architecture NAE35,NAE45,NAE55
Integra Digital meters may be compatible with earlier releases of N2 software, but Johnson Controls only supports integration issues on the above.
4.1.2 Support for Metasys Integration
Primary Contact: Mr Martin Langman Service Support Manager Unit 1 ,Kestrel Rd Trafford Park M17 1SF England Email: martin.langman@jci.com Direct Tel +44 (0) 161 848 6674 Fax +44 (0) 161 848 7196
4.1.3 Support for Crompton Integra Digital meter operation
This is available via local sales and service centre.
4.1.4 Design considerations
When integrating the Integra Digital meter equipment into a Metasys Network, keep the following considerations in mind. Make sure all Integra Digital meter equipment is set up, started and running properly before attempting
to integrate with the Metasys Network.
A maximum of 32 devices can be connected to any one NCM N2 Bus segment, or up to 100 devices if
repeaters are used.
From the instrument set-up screen, the Coms option must be set to N2, then the address set to the
required value. All port settings will then be set automatically, see below.
Device Address 1-255 Port Set-up: Baud Rate 9600 Duplex Half Word Length 8 Stop Bits 1 Parity None Interface RS485
22 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
Name
Units
ADFPoint
V1
V 1 V2
V 2 V3
V 3 A1
A
4
A2
A
5
A3
A 6 KP1
kW 7 KP2
kW 8 KP3
kW 9 KVA1
kVA
10
KVA2
kVA
11
KVA3
kVA
12
KVAR1
kVAr
13
KVAR2
kVAr
14
KVAR3
kVAr
15
PF1 16
PF2 17
PF3 18
PA1
Degree
19
PA2
Degree
20
PA3
Degree
21
AN A 22
V12 V 23
V23 V 24
V31 V 25
VLNAVG V 26
AAVG A 27
ASUM A 28
VLLAVG V 29
KPSUM
kW
30
KVASUM
kVA
31
KVARSUM
kVAr
32
PFTOT 33
PATOT
Degree
34
FREQ
Hz
35
LO_EGY_IMP_POW*
0.1kWh
36
HI_EGY_IMP_POW*
100MWh
37
LO_EGY_EXP_POW*
0.1kWh
38
HI_EGY_EXP_POW*
100MWh
39
LO_EGY_IMP_VAR*
0.1kVArh
40
HI_EGY_IMP_VAR*
100MVArh
41
LO_EGY_EXP_VAR*
0.1kVArh
42
HI_EGY_EXP_VAR*
100MVArh
43
LO_EGY_VA*
0.1kAh
44
HI_EGY_VA*
100MVAh
45
LO_EGY_AMP*
0.1Ah
46
HI_EGY_AMP*
100kAh
47
KPSUM_DMD
kW
48
KPSUM_MAX_DMD
kW
49
KVASUM_DMD
kVA
50
KVASUM_MAX_DMD
kVA
51
A1_DMD A 52
A1_MAX_DMD
A
53
4.2 Ri3 Digital meter METASYS N2 Point Mapping table
23 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Crompton Instruments
A2_DMD A 54
A2_MAX_DMD
A
55
A3_DMD A 56
A3_MAX_DMD
A
57
AN_DMD A 58
AN_MAX_DMD
A
59
V1_THD % 60
V2_THD % 61
V3_THD % 62
VLNAVG_THD
%
63
V12_THD % 64
V23_THD % 65
V31_THD % 66
VLLAVG_THD
%
67
A1_THD % 68
A2_THD % 69
A3_THD % 70
AAVG_THD
%
71
RESET 72
Reset
OverrideValue
Energy
1011
DemandMax
1012
DemandTimeBase
1013
Tyco Electronics, the TE logo and INTEGRA are trademarks. CROMPTON is a trademark of Crompton Parkinson Ltd. and is used by Tyco Electronics under license. Other Trademarks or company names mentioned herein are the property of their respective owners.
All of the above information, including drawings, illustrations and graphic design, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
Tyco Electronics UK Ltd Crompton Instruments
Freebournes Road, Witham Essex CM8 3AH England
Tel: +44 (0) 1376 509509 Fax: +44 (0) 1376 509511 www.crompton-instruments.com
Override RESET with the following values to perform a reset.
* Units shown are for the k energy prefix, they will be 1000 times larger for the M energy prefix, and 1000 times smaller for the no prefix condition.
Note, ADF points are one-based in the JCI compliance test software but zero-based on the network.
24 CI-3K75504 CI-3K75504 Ri3 Communications Guide Rev 03 Sep-13
Loading...