Crompton Instruments 810 Series Data Sheet

Web: www.crompton-instruments.com • Email: crompton.info@tycoelectronics.com 2002
38
Transformers
Performance
Tape Wound Current Transformers
810 Series Measuring and Protection
Features
Substantial tag terminals or flexible leads
Measuring Duty ranges up to 3000A
Protection Duty Classes 5P10 and 10P10
Special designs to customers requirements
ABS American Bureau of Shipping Approved
Designed to highest standards, 810 Series transformers have accuracy classes, outputs and performance to IEC 60044-1:1999 for measuring and protective duties.
Overload withstand to: BS3938 - IEC185
Operating voltage: 660V a.c. maximum Test voltage: 2500V a.c. System frequency: 50/60Hz or 400Hz Service temperature: -40°C to +70°C Insulation class: BS2757 class Y
(Maximum 90°C)
The Crompton 810 Series provides a comprehensive range of Measuring and Protective duty ring current transformers for installation where traditional reliability, accuracy and quality are required.
Class X Current Transformers
In balanced earth fault protection systems, correct operation depends on the accuracy of the current transformers. Class 5P and 10P are suitable where the definite minimum times is greater than 0.2 seconds. For shorter operating time, transient conditions may require current transformers to have cross sectional areas many times greater than those of steady state faults.
The following information is required. (a) Turns ratio (b) Knee point voltage (c) Maximum excitation current (d) Secondary circuit resistance
Construction
High grade silicon iron cores are carefully selected, then insulated and protected by a polypropylene or polycarbonate covering on which the secondary winding is toroidally wound by precision machines. The P.V.A. coated copper wire is additionally protected by a layer of half-lapped plasticised P.V.C tape. A second layer of self bonding P.V.C. tape is applied and vulcanised to provide a
tough moisture-resistant coating. A substantial terminal block with tag terminal
and M6 screws and nuts is standard but M4 screws or insulated flex leads (normally 600mm) can be supplied. Integral fixing feet are normally provided but a busbar mount clamp or a plain ring may be specified.
Mounting Plain ring Plain ring Foot Foot Busbar Busbar Winding Flexible Tag Flexible Tag Tag Flexible
Termination leads terminals terminals leads terminals leads * Busbar mounted types - 944 and 947 have bore diameter ‘A’ reduced by 6mm.
Code -940 -941 -942 -943 -944* -947*
Style
Web: www.crompton-instruments.com • Email: crompton.info@tycoelectronics.com 2002
Transformers
Model Primary VA at class Approximate 5 amp Dimensions (mm's) Weight
Type Current 3 1 0.5 A* B C D E F Kgs
812 40 2 - - 20 60 48 66 40 75 0.48 812 50 2.5 - - 20 60 48 66 40 75 0.48 812 60 2.5 - - 20 60 48 66 40 75 0.48 812 75 5 - - 20 60 48 66 40 75 0.50 812 80 5 - - 20 60 48 66 40 75 0.50
814 100 5 - - 42 84 35 90 52 85 0.50 814 120 5 2.5 - 42 84 35 90 52 85 0.55 814 150 7.5 5 - 42 84 35 90 52 85 0.55 814 200 10 5 - 42 84 35 90 52 85 0.60 814 250 10 5 - 42 84 35 90 52 85 0.65 814 300 10 5 - 42 84 35 90 52 85 0.70 814 400 20 10 5 42 84 35 90 52 85 0.75
816 500 20 15 5 74 112 30 118 66 105 0.65 816 600 20 15 5 74 112 30 118 66 105 0.70 816 750 20 15 5 74 112 30 118 66 105 0.70 816 800 30 20 10 74 112 30 118 66 105 0.70
818 1000 40 30 15 98 142 33 148 81 125 0.85 818 1200 50 30 15 98 142 33 148 81 125 0.90 818 1500 50 30 20 98 142 33 148 81 125 1.05 818 1600 50 30 20 98 142 33 148 81 125 1.15 818 2000 60 45 30 98 142 33 148 81 125 1.30
819 2500 60 45 30 114 170 36 176 95 140 1.55 819 3000 60 45 30 114 170 36 176 95 140 1.70 819 4000 60 45 30 110 172 39 178 97 140 2.00 819 5000 60 45 30 110 172 39 178 97 140 2.30
Selection Table
Accuracies comply with IEC 60044-1:1999 Busbar fixings are not available on Models 812 and 813 * Busbar mounted types 944 and 947 have bore diameter ‘A’ reduced by 6mm.
Measuring Current Transformers
Current Transformers can be manufactured to meet specific dimensional and accuracy requirements. All enquiries should be directed to a local sales centre stating all current, accuracy and dimensional requirements.
Measuring Current Transformers will be coded 811-94 and Protection Current Transformers 81P-94.
Tape Wound Current Transformers
810 Series Measuring
Dimensions of standard 5A current transformers given in mm
1A current transformer dimensions may vary by up to 10%.
25.4
S1 S2
M6 screws
and nuts supplied
E
D
A F
B
C
Web: www.crompton-instruments.com • Email: crompton.info@tycoelectronics.com 2002
40
Transformers
Model Primary VA Approximate 5 amp Dimensions (mm's) Weight
Type Current Burden A* B C D E F Kgs
81A 100 2.5 38 140 76 150 78 125 5.4
5 38 140 142 150 78 125 10.8
150 2.5 38 140 54 150 78 125 3.6
5 38 140 98 150 78 125 7.2
200 2.5 38 140 54 150 78 125 3.6
5 38 140 76 150 78 125 5.4
250 2.5 38 140 54 150 78 125 3.6
5 38 140 54 150 78 125 3.6
300 2.5 38 140 32 150 78 125 1.8
5 38 140 54 150 78 125 3.6
81B 400 2.5 53 140 32 150 78 125 1.8
5 53 140 54 150 78 125 3.3
500 2.5 53 140 32 150 78 125 1.9
5 53 140 54 150 78 125 3.4
600 2.5 53 140 32 150 78 125 2.0
5 53 140 54 150 78 125 3.5
81C 750 5 63 114 42 124 65 105 1.4
7.5 63 114 66 124 65 105 2.0
10 63 114 66 124 65 105 2.0
800 5 63 114 42 124 65 105 1.4
7.5 63 114 66 124 65 105 2.0
10 63 114 66 124 65 105 2.0
1000 5 63 114 37 124 65 105 1.3
7.5 63 114 42 124 65 105 1.5
10 63 114 66 124 65 105 2.1
1200 5 63 114 37 124 65 105 1.4
7.5 63 114 42 124 65 105 1.6
10 63 114 66 124 65 105 2.2
81D 1500 5 73 132 35 142 74 125 1.5
7.5 73 132 35 142 74 125 1.5
10 73 132 57 142 74 125 2.5
1600 5 73 132 35 142 74 125 1.6
7.5 73 132 35 142 74 125 1.6
10 73 132 57 142 74 125 2.6
81E 2000 5 82 148 30 158 82 125 1.7
7.5 82 148 35 158 82 125 2.0 10 82 148 47 158 82 125 2.6 15 82 148 57 158 82 125 3.2
2500 5 80 150 30 160 83 125 1.8
7.5 80 150 35 160 83 125 2.1 10 80 150 35 160 83 125 2.1 15 80 150 47 160 83 125 2.8
3000 5 78 152 30 162 84 125 2.1
7.5 78 152 35 162 84 125 2.5 10 78 152 35 162 84 125 2.5 15 78 152 47 162 84 125 3.2
Selection Table
Accuracies comply with IEC 60044-1:1999 Accuracy Class 5P10 Busbar fixings are not available on Model 81A * Busbar mounted types 944 and 947 have bore diameter ‘A’ reduced by 6mm.
Tape Wound Current Transformers
810 Series Protection
Dimensions of standard 5A current transformers given in mm
1A current transformer dimensions may vary by up to 10%.
25.4
S1 S2
M6 screws
and nuts
supplied
E
D
A
F
B
C
Web: www.crompton-instruments.com • Email: crompton.info@tycoelectronics.com 2002
41
Transformers
Selection Table (continued)
Accuracies comply with IEC 60044-1:1999 Accuracy Class 10P10 Busbar fixings are not available on Model 81F * Busbar mounted types 944 and 947 have bore diameter ‘A’ reduced by 6mm.
Model Primary VA Approximate 5 amp Dimensions (mm's) Weight
Type Current Burden A* B C D E F Kgs
81F 100 5 32 102 93 112 59 105 3.30
7.5 32 102 115 112 59 105 4.50 10 36 140 119 150 78 125 9.25
150 5- 32 102 61 112 59 105 2.10
7.5 32 102 93 112 59 105 3.35 10 36 140 75 150 78 125 5.60
200 5 32 102 56 112 59 105 1.95
7.5 32 102 77 112 59 105 2.80 10 32 102 93 112 59 105 3.40 15 36 140 97 150 78 125 7.50
250 5 32 102 51 112 59 105 1.75
7.5 32 102 61 112 59 105 2.15 10 32 102 83 112 59 105 3.00 15 36 140 75 150 78 125 5.70
300 5 32 102 46 112 59 105 1.55
7.5 32 102 61 112 59 105 2.20 10 32 102 72 112 59 105 2.65 15 36 140 75 150 78 125 5.75
81G 400 5 47 100 56 110 58 105 1.45
7.5 47 100 83 110 58 105 2.25 10 47 100 93 110 58 105 2.55 15 51 140 75 150 78 125 5.15
500 5 47 100 51 110 58 105 1.35
7.5 47 100 83 110 58 105 2.30 10 47 100 88 110 58 105 2.50 15 51 140 75 150 78 125 5.15
600 5 44 103 49 113 60 105 1.25
7.5 44 103 59 113 60 105 1.55 10 44 103 86 113 60 105 2.35 15 44 103 96 113 60 125 2.71
81H 800 5 58 115 44 125 66 105 1.20
7.5 58 115 66 125 66 105 1.95 10 58 115 66 125 66 105 1.95 15 58 115 93 125 66 105 2.90
1000 5 58 115 39 125 66 105 1.10
7.5 58 115 44 125 66 105 1.30 10 58 115 66 125 66 105 2.10 15 58 115 76 125 66 105 2.45
1200 5 58 115 39 125 66 105 1.20
7.5 58 115 44 125 66 105 1.40 10 58 115 66 125 66 105 2.20 15 58 115 66 125 66 105 2.20
81J 1500 5 71 131 34 141 74 124 1.25
7.5 71 131 34 141 74 125 1.25 10 71 131 56 141 74 125 2.30 15 71 131 56 141 74 125 2.30
1600 5 68 134 37 144 75 125 1.30
7.5 68 134 37 144 75 125 1.30 10 68 134 59 144 75 125 2.35 15 68 134 59 144 75 125 2.35
81K 2000A 5 78 149 33 159 83 125 1.35
7.5 78 149 38 159 83 125 1.65 10 78 149 50 159 83 125 2.35 15 78 149 60 159 83 125 3.00
2500A 5 78 149 33 159 83 125 1.50
7.5 78 149 38 159 83 125 1.85 10 78 149 38 159 83 125 1.85 15 78 149 50 159 83 125 2.55
3000A 5 78 152 30 162 84 125 2.10
7.5 78 152 35 162 84 125 2.50 10 78 152 35 162 84 125 2.50 15 78 152 47 162 84 125 3.20
Tape Wound Current Transformers
810 Series Protection
Dimensions of standard 5A current transformers given in mm
1A current transformer dimensions may vary by up to 10%.
25.4
S1 S2
M6 screws
and nuts supplied
E
D
A F
B
C
7
Web: www.crompton-instruments.com • Email: crompton.info@tycoelectronics.com 2002
42
Transformers
Model Primary VA Approximate Dimensions
Type Current Burden K* L M
81L 100 5 40 108 90
150 5 40 108 68 200 7.5 40 108 73 300 10 40 108 68 400 10 61 112 90 500 10 61 112 73 600 10 61 112 73
800 15 81 145 60 1000 15 81 145 53 1200 15 81 145 45 1600 15 94 153 49 2000 15 117 163 66 2500 15 114 166 59 3000 15 114 166 59
* Busbar mounted types 944 and 947 have bore diameter reduced by 6mm.
Model 81L Dimensions (mm's)
Accuracy Class 10P10
Tape Wound Current Transformers
810 Series Protection
Fixing feet or Busbar clamps available on request