Crompton Instruments 120 Catalog Page

34
Application:
Relaying and metering
Frequency:
50 – 400Hz
Insulation Level:
600 Volts, 10kV BIL full wave
• Multi ratios available upon request
• Order mounting bracket kit separately
• Approximate weight: 11 lbs
Model 120
Window Diameter 5.75”
120 – 201 200:5 1.2 1.2 2.4 4.8 4.8 0.053 2.0 2.0 120 – 301 300:5* C10 0.3 0.6 1.2 2.4 2.4 0.063 2.0 2.0 120 – 401 400:5* C10 0.3 0.3 0.6 1.2 2.4 0.080 2.0 2.0 120 – 501 500:5* C20 0.3 0.3 0.3 0.6 1.2 0.137 2.0 2.0 120 – 601 600:5* C20 0.3 0.3 0.3 0.6 0.6 0.165 2.0 2.0 120 – 801 800:5* C20 0.3 0.3 0.3 0.3 0.6 0.220 2.0 1.5 120 – 102 1000:5* C20 0.3 0.3 0.3 0.3 0.3 0.309 1.5 1.5 120 – 122 1200:5* C50 0.3 0.3 0.3 0.3 0.3 0.371 1.5 1.33 120 – 152 1500:5* C50 0.3 0.3 0.3 0.3 0.3 0.464 1.5 1.0 120 – 162 1600:5* C50 0.3 0.3. 0.3 0.3. 0.3 0.494 1.33 1.0 120 – 202 2000:5* C50 0.3 0.3 0.3 0.3 0.3 0.592 1.33 1.0 120 – 252 2500:5* C50 0.3 0.3 0.3 0.3 0.3 0.740 1.0 0.8 120 – 302 3000:5* C50 0.3 0.3 0.3 0.3 0.3 0.888 1.0 0.8 120 – 352 3500:5 C20 0.3 0.3 0.3 0.3 0.3 0.964 1.0 0.8 120 – 402 4000:5* C50 0.3 0.3 0.3 0.3 0.3 1.102 1.0 0.8
ANSI metering class at 60Hz
Secondary winding resistance (0HMS @ 75˚C
Continuous thermal rating factor
@30˚C @55˚C
Catalogue Current
Relay
Number Ratio Class
B0.1 B0.2 B0.5 B0.9 B1.8
Approvals
CSA 223647
UL 257877