Crompton M20 User Manual

Emotron M20
Shaft Power Monitor
Instruction manual
English
Contents
1 Inside the Box............................................................................. 3
2 Safety .......................................................................................... 4
4 Getting Started ........................................................................... 7
4.1 Please note ................................................................................................. 7
4.2 Connection and set-up before first start ................................................... 7
4.3 First start ..................................................................................................... 8
4.4 Manual setting of alarm levels, alternative A ........................................... 9
4.5 Manual setting of alarm levels, alternative B ........................................ 10
4.6 Manual setting of alarm levels, alternative C ........................................ 10
5 Wiring ........................................................................................ 11
5.1 Alternative example for single-phase connection ................................. 13
5.2 Example - digital input ............................................................................. 14
6 Selection of Current Transformer ........................................... 14
6.1 Motors less than 100 A........................................................................... 14
6.2 Motors greater than 100 A ..................................................................... 17
7 Operation .................................................................................. 19
7.1 Overview ................................................................................................... 19
7.2 Window menu .......................................................................................... 20
7.3 How to change a value ............................................................................ 21
8 Programming ............................................................................ 22
8.1 Set measurement unit, kW or HP ........................................................... 22
8.2 Setting rated motor power and current (window 41 and 42) ............... 24
8.3 Setting number of phases (window 43) ................................................. 25
8.4 Monitor function (window 05)................................................................. 25
8.5 Setting the Start Delay (window 31)....................................................... 27
Emotron AB 01-2151-01r4 1
8.6 Setting alarm levels with Auto set ........................................................... 28
8.7 Setting the Response Delay (windows 32 and 34)................................ 29
9 Advanced Features .................................................................. 31
9.1 Setting alarm levels manually (windows 11-14) .................................... 31
10 Troubleshooting ....................................................................... 41
11 Technical Data ......................................................................... 43
12 Parameter List.......................................................................... 47
13 Service ...................................................................................... 50
2 Emotron AB 01-2151-01r4

1 Inside the Box

Please check the delivery. Despite the fact that all products from Emotron are carefully inspected and packed, transport damage may occur:
Your shipment should contain the Emotron M20 shaft power monitor, a current transformer, 2x terminal covers (option*) and this instruction manual.
Check carefully that the equipment ordered complies with the motor’s input voltage and that the current transformer rating is as stated on the delivery packaging.
Check that the contents have not been damaged during shipping.
If something is missing, or has been damaged, contact the supplier as well as the forwarding agent within 48 hours of receipt.
NOTE: If in doubt contact your supplier before installing or commissioning the product.
Shaft P
Emotron M20
ower Monitor
M20
In
s
tr
u
c
t io
n
m
a
n
u
E
a
n
l
glish
*)
Emotron AB 01-2551-01r4 Inside the Box 3

2Safety

Study this manual thoroughly before installing and using the monitor.
The monitor must be installed by qualified personnel.
Always disconnect supply circuits prior to installing.
The installation must comply with standard and local regulations.
Pay special attention to the information in this chapter and the parts marked CAUTION in the Operation and Programming chapters.
Check that the monitor and the equipment are correctly connected before it is taken into use.
Should questions or uncertainties arise, please contact your local sales outlet or see chapter 13, Service.
Faults that arise due to faulty installation or operation are not covered by the warranty.
NOTE: Removing or tampering with the seal on the housing will invalidate the warranty.
4Safety Emotron AB 01-2551-01r4

3 Description

This instruction manual describes the installation and commissioning of the Emotron M20 shaft power monitor. The Emotron M20 supervises induction motor driven equipment and provides warnings when abnormal conditions are detected. It protects for example, pumps and other equipment. The M20’s abil­ity to provide reliable monitoring and protection ensures that production equip­ment is optimized and expensive breakdowns and interruptions are minimized.
The Emotron M20 uses the motor as its own sensor and no external sensors or extra cabling are required. Due to the special method of subtracting motor power losses, the monitor is able to accurately measure the shaft power supplied by the motor to the application. This advanced technique allows the M20 to monitor only the “application” load rather than the “total” motor load, which includes the varying motor losses.
The shaft power is calculated by measuring motor input power, and subtracting the motor power loss calculated using a unique principle. The shaft power out­put is indicated on the monitor display in kW or HP, or as a percentage of rated power. Calculating shaft power gives more reliable supervision than non-linear techniques, such as current and phase angle measurements. Current measure­ment is only sufficient at high motor loads and phase angle only at low loads. Input power is sometimes called true or real power. Input power is linear, but ignores motor power loss.
The M20’s analogue output and two relay outputs allow the combination of direct and indirect control. The unit offers high accuracy in the event of very small load variations. The analogue output signal can be used to scale the machine load to represent the actual working range.
The monitor is very easy to install and set up and should be mounted on a standard DIN rail. It is also very easy to use. The “Auto set” function makes it possible to adjust the monitor automatically by pressing just one key.
The M20 provides complete flexibility in terms of the type of protection required for your application. You may select either overload and underload protection or simply overload with pre-alarm or underload with pre-alarm. Independent response delays can be selected for both overload and underload protection. Additional flexibility is provided in the form of programmable out­put relays, number of start attempts, number of reversing attempts etc.
Emotron AB 01-2551-01r4 Description 5
The Emotron M20 shaft power monitor offers advanced multi-function moni­toring and a display for load indication and parameter setting. It is ideal for protecting many different applications including pumps in general, centrifugal pumps, magnetic pumps, screw and impeller pumps, mixers, scrapers, crushers, conveyor systems, etc.
For further information, please see www.emotron.com.
6Description Emotron AB 01-2551-01r4

4 Getting Started

NEXT
ENTER
NEXT

4.1 Please note

1. Pay special attention to the safety section in this manual and parts marked CAUTION.
2. Check that motor/supply voltage corresponds to values on the monitor product label at the side of the unit.
3. Make a note of the motor’s rated power and full load amps from its name­plate. Confirm that the current transformer supplied is of the correct size according to tables 1 and 2 in chapter 6 of this manual.

4.2 Connection and set-up before first start

1. Connect the Emotron M20 according to chapter 5 and Fig. 1.
2. Make sure all safety measures have been taken and switch on the supply voltage.
3. Use the key to scroll through the menu. Press and hold the key and
ENTER
press the key to scroll back.
4. Set rated motor power and current in windows 41 and 42. Additional set­tings to be programmed are discussed in chapter 8.
5. Set monitor function in window 05, overload and underload or only under­load or only overload. See chapter 12, Parameter list, for range and default values.
6. Set start delay and response delay in window 31 and 32/34.
7. Compare all set values with the parameter list in chapter 12 to confirm that all relevant values are set. Advanced features will be found in chapter 9.
Emotron AB 01-2551-01r4 Getting Started 7

4.3 First start

SET
AUTO
CAUTION: Make sure that all safety measures have been taken before switching on the supply voltage and starting the motor/machine in order to avoid personal injury.
1. Start the motor/machine and let it run at normal load, until the Start Delay has expired.
AUTO
2. Press for 3 seconds.
Hint!
Short-circuit the output relays during the set-up; this prevents the equipment from stopping unintentionally.
More Hints!
The monitor can be set in three different ways:
1. Automatically by pressing the Auto set key as described above. The Auto set
2. If Auto set is used as above, the margins can be re-adjusted manually (win-
SET
function performs a measurement (momentarily) of the actual load and sets relevant alarm levels for this actual load plus/minus the “margins” (Default; Max +16% and Min -16%).
dows 21-24). When the margin values are changed a new Auto set must always be performed to activate the changes and the new margins. More information is provided in chapter 9, Advanced Features.
3. Manual setting of alarm levels (windows 11-14). The alarm levels can be set manually, without using the Auto set. See sections Manual setting of alarm levels, alternative A, B and C.
NOTE: If any window parameter is manually adjusted, the display will flash the new value to indicate that a change has been made. The Enter key must be pressed for the M20 to accept this new value.
8 Getting Started Emotron AB 01-2551-01r4
4.4 Manual setting of alarm levels,
alternative A
Running and setting at normal load
Start the motor/machine or pump and let it run at normal load, until the Start Delay (window 31) has expired.
Read off the load on the monitor display, e.g. 65%, window 01 (or kW/HP).
Set the max. main alarm level to something between e.g. 70-85% in window
11. This must be set to the actual application requirements, maximum load for machine/process.
Set the min. main alarm level to something between e.g. 60-45% in window
14. This must also be set to the actual application requirements.
See also Fig. 7 in section 8.4, Over- and underload monitor.
Emotron AB 01-2551-01r4 Getting Started 9
4.5 Manual setting of alarm levels,
alternative B
Running and setting at maximum load as well as at minimum load
Start the motor/machine or pump and let it run at maximum load, until the Start Delay has expired. E.g. fill the conveyor with maximum allowed goods.
Read off the load on the monitor display, e.g. 85% (window 01).
Set the max. main alarm level to something between e.g. 90-95% in window
11. This must be set to the actual application requirements, maximum load for both machine and processes.
Then run the motor/machine and let it run at minimum load, e.g. idling, until the Start Delay has expired.
Read off the load on the monitor display, e.g. 30%.
Set the min. main alarm level to something between e.g 25-20% in window
14. This must also be set to the actual application requirements.
See also Fig. 7 in section 8.4, Over- and underload monitor.
4.6 Manual setting of alarm levels,
alternative C
It is also possible to approximately calculate or estimate the alarm levels. If e.g. the motor used is 22 kW, 22 must be set in window 41. This means that each percentage point corresponds to 220 W (22 kW/100 = 220 W), and the alarm limits in window 11- 14 can be set in steps of 220 W. If the max. alarm level is set to 80% in this example, the monitor will emit an alarm and stop the machine at approx. max. 17.6 kW shaft output power.
NOTE: If the pre-alarm is not used, the values for Min. pre-alarm and Max. pre-alarm can be set to 0 (window 13) and 125% (window 12) respectively. This will eliminate pre-alarm warning indications in the monitor display when not in use.
See also Setting alarm levels manually in chapter 9, Advanced Features.
10 Getting Started Emotron AB 01-2551-01r4

5 Wiring

The following wiring diagram provides an example of how the M20 can be con­nected to control the start/stop circuit of a three-phase motor, Fig. 1. Co nnec­tions to a single-phase motor are described later in this manual (Fig. 2) as are the programming changes necessary for such applications. The default setting for the M20 is 3-phase.
1. The current transformer CTMxxx must be placed in the same phase that is connected to terminal 9, phase L1, see Fig. 1. Failure to follow this require­ment will result in the monitor failing to function.
2. For single-phase connection see fig 2.
When using DC voltage, terminal 6 should be connected to negative polarity (ground) and terminal 5 to positive polarity (max. 48 VDC). See also Alterna­tive auxiliary circuit (Fig. 16) in chapter 9.
Note: The current transformer (CTMxxx) must be placed in the same phase that is connected to terminal 9, phase L1, see Fig. 1.
Emotron AB 01-2551-01r4 Wiring 11
L1 L2 L3
NOTE: In power down, both relays are always N.O.
9
3
4
L1
A+ A-
11
L2
M20
13
L3
S2S1
1
2
6
C
7
R1
8
R2
5
DIG
Max. 240 VAC (alt. 0 VDC-)
CTMxxx
Please see CTM
K1
UVW
information on Page 11.
NOTE: Monitor voltage see Note below.
-Reset
-Auto set
- Block
K1
{
PRE­ALARM
Stop
Start
K1
N (alt. 48 VDC+)
M
Fig. 1 Connection example
NOTE: If the START/STOP is connected as per Fig. 1, it is recommended that terminals 6 and 7 be bypassed during programming. After the programming is completed the bypass must be taken out. Make sure that the monitor voltage range e.g. 3x380-500 VAC matches the connected motor/line voltage, e.g. 3x 400 V.
Please use the enclosed plastic (rubber) insert (if ordered, optional) to cover the monitor terminals.
12 Wiring Emotron AB 01-2551-01r4
5.1 Alternative example for single-phase
connection
This wiring example shows the connections required for single-phase applica­tions.
Refer to Fig. 1 for the remaining wiring.
L1 N
CTMxxx
K1
9
3
M20
S1 S2
1
4
C
A-A+
R1
R2
2
L1
11
L2
13
L3
NOTE: Monitor
DIG
6
7
8
5
voltage, see note below.
L
N
M
Fig. 2 Single-phase connection example.
NOTE: In Fig. 2 make sure that the monitor voltage range e.g. 1x100-240 VAC matches the connected motor/“line – neutral” voltage, e.g. 1x 230 V.
Emotron AB 01-2551-01r4 Wiring 13

5.2 Example - digital input

The digital input uses terminals 5 (DIG) and 6 (C - reference). Either a VAC or a VDC signal may be used. Connect + to terminal 5 (DIG) and - to terminal 6 for VDC signal. Please note the polarity when DC voltage is used. See also
Fig1
and terminal 6: Max. 240 VAC (or 0 VDC-) and on terminal 5: N (or 48 VDC+).
VAC VDC
M20 M20
See also chapter 9, Advanced Features.
6
C
DIG
5
~
Max 240 VAC
~
DIG
6
C
5
-
Max 48 VDC
+
Note polarity!
Fig. 3 Wiring example for digital input.

6 Selection of Current Transformer

6.1 Motors less than 100 A

1. Check the rated motor current on the motor plate.
2. Compare this value with the current in Table 1.
3. From Table 1, select the current transformer and the appropriate number of windings.
Fig. 5 shows the different types of current transformer (CT) windings. In Fig. 5:1 the motor wire is just drawn through the CT, in the text and tables below this is described as 1 (one) winding. Fig. 5:2 shows a CT with 2 windings and Fig. 5:3, 3 windings. In other words the number windings is equal to the number of times the motor wire “L1” is drawn through the hole of the current transformer.
NOTE: Maximum length of the CTM cable is 1 m (39 inches).
14 Selection of Current Transformer Emotron AB 01-2551-01r4
Example
Rated motor current = 12 A.
Select 10.1-12.5 A from the first column in Table 1.
This gives: CTM025 with 2 windings (the motor wire is drawn through the CT’s hole twice).
Table 1 Motors and CT less than 100 A
CURRENT TRANSFORMER TYPE and
RATED MOTOR
CURRENT [A]
CTM 010 CTM 025 CTM 050 CTM 100
0.4 – 1.0 10
1.01 – 2.0 5
2.01 – 3.0 3
3.1 – 5.0 2
5.1 – 10.0 1
10.1 – 12.5 2
12.6 –25 1
26 – 50 1
51 – 100 1
NUMBER OF WINDINGS
In order to ensure an accurate calibration of the M20, it is essential that you use the correct CTM and apply the exact number of windings in accordance with the above table.
NOTE: Normally the appropriate Current Transformer will have been ordered and shipped with the M20. Check that this is the case; contact the supplier if in doubt.
Emotron AB 01-2551-01r4 Selection of Current Transformer 15
L1 L2 L3
CTM025
1
S1
P2
2
S2
M20
2 windings
M
3
Fig. 4 Example CTM 025 with 2 windings for a 12 A motor
NOTE: The current transformer connection and orientation are not polarity sensitive, but must be connected to the same phase that is being referenced for terminal 9 of the M20.
P2
1
2
5:1 5:2 5:3
Fig. 5 Example 1, 2 and 3 windings.
16 Selection of Current Transformer Emotron AB 01-2551-01r4

6.2 Motors greater than 100 A

1. Check the rated motor current on the motor plate.
2. Compare this value with the current in Table 2.
3. Select the primary and secondary current transformer and the appropriate number of windings from the columns in Table 2.
Please note that the ratio of the primary transformer must be exactly as provided in the table below, otherwise the monitor power calculations will be inaccurate. This will affect power readings, settings etc.
Example
Rated motor current = 260 A.
Select 251-500 A from the first column in Table 2.
This gives:
- Primary transformer 500:5, 1 winding. (The motor wire is drawn through the primary transformer once).
- CTM010 with 2 windings. (The wire from the primary transformer is drawn through the hole in the CT, "CTM10", twice).
Table 2 CT greater than 100 A.
RATED MOTOR
CURRENT [A]
101 – 150
151 – 250
251 – 500
501 – 999
NOTE: Check that the appropriate Current Transformers has been ordered and shipped with the M20. Contact the supplier if in doubt.
Emotron AB 01-2551-01r4 Selection of Current Transformer 17
CURRENT TRANSFORMER TYPE and
NUMBER OF PRIMARY WINDINGS
150:5 + CTM 010
1+ 2
250:5 + CTM 010
1+ 2
500:5 + CTM 010
1+2
1000:5 + CTM 010
1+ 2
L1 L2 L3
CTM010
1
S1
P2
2
S2
2 windings
1 winding
S1 S2
500:5
M20
M
3
Fig. 6 Example of a CTM 010 with 2 windings and a primary transformer
500:5 with 1 winding for a 260 A motor.
NOTE: The transformer connection and orientation are not polarity sensi­tive, but must be connected to the same phase that is being referenced for terminal 9 of the M20.
18 Selection of Current Transformer Emotron AB 01-2551-01r4

7 Operation

2123
Make sure the enclosed plastic (rubber) insert (if ordered, optional) covers the monitor terminals before you start programming.

7.1 Overview

Control Terminals
1 S1 Current transformer input 2 S2 Current transformer input 3 + Analogue output 4 - Analogue output 5 DIG External RESET or AUTO SET
or Block Pre-Alarm 6 C Common: RELAY, DIG 7 R1 Main Alarm Relay 1* 8 R2 Pre-Alarm Relay 2
AUTO SET Key
Press for 3 seconds during normal and stable load to apply the automatic setting of the alarm levels. Not avail­able if Parameter Locked.
12
123
%
Display
Function (window) number
1
Function Value
!
Warning signal Start, response delay or
block timer active Parameter locked
VVoltage indicator A Current indicator mA Milliampere indicator kW Kilowatt indicator SSecond indicator % Per cent indicator
NEXT Key
Proceeds to next window. If no key is pressed for 1 minute the display returns to window 01 automatically. Scroll back by pressing and holding ENTER at the same time as the NEXT key is pressed.
ENTER Key
RESET Key
To r es et ALA RM
+/- Keys
For increasing and decreasing value
Monitor Supply Terminals
9 L1 Motor phase 11 L2 Motor phase 13 L3 Motor phase
* For alternative relay function, see Special functions
in chapter 9.
Confirm (save) changes.
After Power up window 01 appears, the actual load value is shown.
Default view (example shows 54% load):
01
54
%
Use the NEXT key to scroll through the function menu.
Emotron AB 01-2551-01r4 Operation 19

7.2 Window menu

Alarm indication
00
Start window
01
02
03
04
05
Measured shaft power
Measured line voltage
Measured current
Parameter Lock
Monitor Function
Factory defaults
Analogue Output
99
91
11
12
11
12
13
Block Timer
Digital Input
Relay function
Pre-Alarm Relay 2
Main Alarm Relay 1
Alarm at no motor current Main Alarm Latch
82
81
65*
64
63
62
61
14
21
OVER- and UNDERLOAD
22
21
OVERLOAD
22
UNDERLOAD
23
24
31
Number Of Phases
Rated Current
Rated Motor Power
43
42
41
32
33
34
35*
36*
* See Special functions in chapter 9, Advanced Features
MAX Main Alarm
MAX Pre-Alarm
13
MIN Pre-Alarm
MIN Main Alarm
14
MAX Main Alarm margin
MAX Pre-Alarm margin
MIN Pre-Alarm margin
23
MIN Main Alarm margin
24
Start Delay
Response Delay Max
Hysteresis
Response Delay Min
Pause/Reverse time
Autoreset (start attempts)
20 Operation Emotron AB 01-2551-01r4
The Alarm window only appears if an Alarm output is active.
NEXT
ENTER
NEXT
NEXT
ENTER
NEXT
The Actual Load window appears after power up.
00
01
Use the key to scroll through the menu. Scroll back by pressing and
holding at the same time as the key is pressed.
ENTER
The Actual Load window (or alternative alarm window) will appear auto­matically if no keys are pressed for longer than 1 minute.
If the Parameter Lock is on, only windows (if alarm active)
020403
01
Window selects the monitor function, see section 8.4.
05
are visible.
00

7.3 How to c hange a value

Example: setting the rated motor current in window 42.
1. Press until the window number 42 appears.
42
5.6
A
2. Press or until the desired value is reached (e.g. 23 A), value flashes.
42
23
A
3. Press to confirm and save the change, value stops flashing.
NOTE: If the value is NOT to be changed, press the key.
CAUTION: In order to avoid personal injury, make sure that all safety measures have been taken before switching on the supply voltage and starting the motor/machine.
Emotron AB 01-2551-01r4 Operation 21
NEXT

8Programming

8.1 Set measurement unit, kW or HP

8.1.1 Selecting the unit of measurement

The unit of measurement can be set to kilowatts or horsepower both as absolute or relative values. This setting is valid for the alarm levels, rated motor power and the actual load read-out in window 01.
Measurement
unit
Kilowatt relative value (def.)* % kW %
Horsepower absolute value HP HP HP
Horsepower relative value* % HP %
Kilowatt absolute value kW kW kW
Read-out
load
window 01
Rated power
window 41
Alarm levels
windows
11, 12, 13, 14
* Measured shaft power as % of rated power.
CAUTION: In order to avoid personal injury, make sure that all safety measures have been taken before switching on the supply voltage and starting the motor/machine.
22 Programming Emotron AB 01-2551-01r4
Programming
RESET
1. Go to window 01.
2. Press and hold and simultaneously for 3 seconds.
3. The next unit of measurement is set and appears for 2 sec (see examples).
Repeat to select the desired measurement unit according to the table.
Horsepower: absolute value
RESET
For 2 seconds Read-out example
HP
01
3.52
Horsepower: relative value*
Kilowatt: absolute value
Kilowatt: relative value* (default)
HP
kW
kW
%
* Measured shaft power as % of rated power.
01
01
01
12
%
4.62
kW
12
%%
Emotron AB 01-2551-01r4 Programming 23
8.2 Setting rated motor power and current
ENTER
ENTER
(window 41 and 42)
The rated motor power and the rated motor current must be set in windows 41 and 42.
Example motor plate:
TYPE: T56BN/4 NR: 948287 Prot. IP: 54 Serv: S1 Cos ϕ: 0.78 Is. Cl:F
V:Y/Δ Hz HP kW RPM A:Y/Δ
240/415 50 3 2.2 1400 5.6/9.4 260/440 60 3 2.2 1680 5.8/9.1
ASYNCHRONOUS THREE-PHASE MOTORS

8.2.1 Programming

1. Go to window 41 (default = 2.2 kW).
2. Press or to set the rated motor power as indicated on the motor plate (see example).
3. Press to confirm the change.
4. Go to window 42 (default = 5.6 A).
5. Press or to set the rated motor current as indicated on the motor plate (see example).
6. Press to confirm the change.
24 Programming Emotron AB 01-2551-01r4

8.3 Setting number of phases (window 43)

ENTER
The number of phases must be set according to the number of motor phases. Default is 3 phases, see also chapter 5, Wiring.

8.3.1 Programming

1. Go to window 43 (default = 3PH).
43
3PH
2. Press or to set the number of phases to 1 if a single-phase motor is used.
3. Press to confirm the change.
43
1PH

8.4 Monitor function (window 05)

Monitor
(Protection)
OVER- and UNDER­LOAD (default)
OVERLOAD
UNDERLOAD
If separate output relays are required for overload and underload alarms, please refer to chapter 9 and chapter 12.
Emotron AB 01-2551-01r4 Programming 25
Indication in
window 05
Alarm
MAX Main Alarm Relay 1 (NC): 6-7
MAX Pre-Alarm Relay 2 (NO): 6-8
MIN Pre-Alarm Relay 2 (NO): 6-8
MIN Main Alarm Relay 1 (NC): 6-7
MAX Main Alarm Relay 1 (NC): 6-7
MAX Pre-Alarm Relay 2 (NO): 6-8
MIN Pre-Alarm Relay 2 (NO): 6-8
MIN Main Alarm Relay 1 (NC): 6-7
Output Relay
(default)
Overload and underload Monitor
ENTER
P/%
START UNDERLOAD OVERLOAD
MAX Main alarm [11]
MAX Pre-alarm [12]
OPERATION AREA
Auto set level Normal load
MIN Pre-alarm [13]
MIN Main alarm [14]
Start delay [31]
Relay 1 Main alarm
Relay 2 Pre-alarm
Fig. 7 Overload and underload monitor.
Response delay [34] [32]
MAX Main
MAX Pre-alarm margin [22]
MIN Pre-alarm margin [23]
Main Alarm latch=ON [61]
alarm margin [21]
MIN Main alarm margin [24]
t/s
Programming
1. Go to window 05. The default selection is Overload and Underload monitor.
2. Press or to select underload or overload monitor.
_
05
_
OVER- and UNDERLOAD UNDERLOAD
3. Press to confirm the change.
26 Programming Emotron AB 01-2551-01r4
05
_
OVERLOAD
_
05

8.5 Setting the Start Delay (window 31)

ENTER
To avoid false alarms during start up a Start Delay must be set to allow the motor and machine to speed up and to allow the power in-rush currents.
Programming
1. Determine in seconds how long it takes for the motor and machine to reach speed and for the power in-rush to pass. This will be the Start Delay.
2. Go to window 31 (default = 2.0 s).
3. Press or to set the determined Start Delay time in seconds.
4. Press to confirm the change.
If the monitor is being used on a self-priming pump, it may also be necessary to set the Start Delay long enough to allow the pump to become fully primed.
Example: Start Delay 2.0 s
31
2.0
S
Fig. 8 Start Delay.
P
t
Start Delay [31]
Emotron AB 01-2551-01r4 Programming 27

8.6 Setting alarm levels with Auto set

SET
AUTO
The Auto set command performs a measurement (momentarily) of the actual motor load and automatically sets the relevant alarm levels depending on the selected monitor function.
Protection
(Monitor function
window 05)
OVER- and UNDERLOAD (Default)
OVERLOAD
UNDERLOAD
Alarm
MAX Main Alarm
MAX Pre­Alarm
MIN Pre­Alarm
MIN Main Alarm
MAX Main Alarm
MAX Pre­Alarm
MIN Pre­Alarm
MIN Main Alarm
Margin
Value
(Default
margins)
16%
8%
8%
16%
16%
8%
8%
16%
Margins
(Windows)
21: MAX Main Alarm margin
22: MAX Pre­Alarm margin
23: MIN Pre­Alarm margin
24: MIN Main Alarm margin
21: MAX Main Alarm margin
22: MAX Pre­Alarm margin
23: MIN Pre­Alarm margin
24: MIN Main Alarm margin
Alarm Level at
Auto set
Normal machine load + Window 21
Normal machine load + Window 22
Normal machine load - Window 23
Normal machine load - Window 24
Normal machine load + Window 21
Normal machine load + Window 22
Normal machine load - Window 23
Normal machine load - Window 24
Programming
1. Start the motor and let it run at the normal machine load until the Start Delay has expired.
AUTO
2. Press for 3 seconds. This can be done in any window.
SET
28 Programming Emotron AB 01-2551-01r4
3. The display shows “SEt”, to confirm that the Auto set level has been meas-
SET
AUTO
ENTER
ured and the alarm levels have been set. The display reverts to window 01.
3 seconds
AUTO
SET
SEE
01
40
%
4. If the alarm levels are too high or too low, readjust the appropriate MAR­GINS (see table) and perform a new Auto set. Alternatively, alarm levels can be set manually, see chapter 9.
8.7 Setting the Response Delay (windows 32
and 34)
A Response Delay allows the machine to remain in an over- or underload condi­tion for a specific time before the alarm relays are activated. Set the response delay for the overload condition in window 32 (max.), and set the response delay for the underload condition in window 34 (min.). The default value for both windows are 0.5 s. The valves may be adjusted upwards to avoid triggering a “false alarm”.
Programming
1. Determine in seconds the response delay required for both overload and underload conditions. This is normally determined by the unique properties and behaviour of each application.
2. Go to window 32 (overload, default = 0.5 s).
3. Press or to set the determined Response Delay time in seconds.
4. Press to confirm the change.
The response delay for the underload condition (min.) is set in window 34 in a similar way.
Emotron AB 01-2551-01r4 Programming 29
Example: Response Delay
32
0.5
S
P
Alarm level
34
0.5
S
Alarm
Fig. 9 Response Delay.
Response Delay [32]
t
30 Programming Emotron AB 01-2551-01r4

9 Advanced Features

9.1 Setting alarm levels manually (windows
11-14)
The alarm levels can be set manually, without using the Auto set. These levels can also be readjusted, e.g. for fine-turning, after an Auto set has been per­formed. See also section 4.3 to 4.6.
Protection (Monitor function
window 05)
OVER- and UNDERLOAD (Default)
OVERLOAD
UNDERLOAD
Alarm levels (Window) Default
11: MAX Main Alarm 100%
12: MAX Pre-Alarm 100%
13: MIN Pre-Alarm 0%
14: MIN Main Alarm 0%
11: MAX Main Alarm 100%
12: MAX Pre-Alarm 100%
13: MIN Pre-Alarm 0%
14: MIN Main Alarm 0%
Emotron AB 01-2551-01r4 Advanced Features 31
Setting margins (windows 21-24)
The margins for the Auto set can be changed manually. After the adjustment, the Auto set action must be performed again.
Protection (Monitor function
window 05)
Window Default
21: MAX Main Alarm margin 16%
OVER- and UNDERLOAD (Default)
22: MAX Pre-Alarm margin 8%
23: MIN Pre-Alarm margin 8%
24: MIN Main Alarm margin 16%
OVERLOAD
UNDERLOAD
21: MAX Main Alarm margin 16%
22: MAX Pre-Alarm margin 8%
23: MIN Pre-Alarm margin 8%
24: MIN Main Alarm margin 16%
Setting hysteresis (window 33)
The hysteresis of an alarm level prevents the alarm relay “chattering” if the load fluctuates even in a normal “stable” condition. This also applies to a pre-alarm. This feature is normally only used if the main alarm latch (window 61) is set to Off. Default = 0%.
P/%
MAX Main Alarm level [11]
Hysteresis [33]
MIN Main Alarm level [14]
t/s
Relay 1 MAIN Alarm
Fig. 10 Hysteresis
32 Advanced Features Emotron AB 01-2551-01r4
Setting main alarm latch (window 61)
The main alarm latch keeps the main alarm output active, even if the alarm con­dition has been removed. A latched alarm output can be reset by:
•The reset key
External reset via digital input (see window 81).
Switching off the power to the monitor (see also Wiring).
Default = Off.
Setting alarm at no motor current (window 62)
The alarm at no motor current gives an alarm if the motor current goes down to zero (62 = on). Default = Off (No alarm at no motor current).
Setting relay output (window 63 and 64 alt. 65)
The relay outputs R1 and R2 can be set to NO or NC contacts.
NOTE: If the power to the load monitor is switched off, the relay contacts are always in position NO.
If separate output relays are required for overload (max., relay R1) and under­load (min., relay R2), see Special functions in chapter 9 and chapter 12.
Setting digital input (window 81)
The digital input can be set for:
RES: External RESET (Default)
AU: External Auto set To perform an Auto set with an external signal.
bLo: Block Pre-Alarm
Emotron AB 01-2551-01r4 Advanced Features 33
To reset an alarm.
To block the Pre-Alarm function and start the Block timer. If the input is high a Pre-Alarm is blocked, i.e. it is neglected. See also window 82.
Setting block timer (Window 82)
To set the timer for the blocking time after the Block command is released (see also window 81). Default = 0.0 sec.
P/%
MAX Main Alarm level [11]
MAX Pre-Alarm level [12]
Auto set level
t/s
Relay 1 Main alarm
Relay 2 Pre-alarm
Pre-Alarm Blocked
Block signal high on terminal 5 DIG [81] Block timer [82]
Fig. 11 Block timer
Setting analogue output (window 91)
The analogue output provides an analogue signal of either 0-20 mA or 4-20 mA which represents the motor shaft power. The signal can be inverted (20-0 or 20­4 mA). Full scale: rated motor power, see Fig. 12. To set P-span/scaling (full scale) see Fig. 13.
34 Advanced Features Emotron AB 01-2551-01r4
91
P
SHAFT
100%
4.20
20.4
20.0
0.20
0%
Fig. 12
4.20
04 20
Output
mA
Emotron AB 01-2551-01r4 Advanced Features 35
Setting analogue output load range: P-span (window 92-93)
With windows 92 and 93 the full scale of the analogue output can be set accord­ing to the minimum and maximum load (P-span).
1. In window 91, press RESET and + for two seconds until “on” shows. Win­dows 92 and 93 are now active.
P shaft
100%
70%
20%
92= 20% 93= 70%
92= 0% 93= 100%
0
0
6
14
20
Output
mA
Fig. 13
2. Set the lowest load value in window 92 (e.g. 20%)
3. Set the highest load value in window 93 (e.g. 70%)
The full scale of the analogue output is now set between 20% and 70% load. See Fig. 13. To deactivate: Press RESET and + for two seconds until “Off” shows in window 91.Windows 92 and 93 are now inactive.
Locking parameters (window 04)
To avoid the parameter settings being changed unintentionally, the program­ming can be locked by entering the code “369” in window 04. Now only Load [01], Voltage [02] and Current [03] can be checked. Follow the same procedure to unlock the monitor. The Auto set key is disabled when parameters are locked. Auto set via digital input is always active if window 81 is set to AU (Auto set).
36 Advanced Features Emotron AB 01-2551-01r4
01
24
%
NOTE: The symbol appears in all windows.
Resetting to factory defaults (window 99)
The factory defaults are reset by entering “dEF” in window 99. If window 99 shows “USr” it indicates that the settings have been changed to user specific set­tings.
View alarm message (window 00)
In an alarm condition, the window 00 appears automatically. The window indi­cates the following alarm conditions. Window 00 flashes at all times.
Undervoltage, switch off the supply!
Overvoltage, switch off the supply!
No motor current Window 62 = on
00
00
00
!
F
!
F
!
FO
^
^
Pre-Alarm MAX level reached
Alarm MAX level reached
Pre-Alarm MIN level reached
00
00
00
!
LU
!
0U
!
F0
Out Of Range. This message appears only in window 01 (actual load) or 03 (actual current)
00
!
FO
Alarm MIN level reached
01
!
OOO
When the monitor is switched on (power up), the voltage on phases L1, L2 and L3 is checked. If the wrong voltage is detected, an LU (undervoltage) or OU (overvoltage) alarm is generated. No relay alarm will be indicated or activated.
Emotron AB 01-2551-01r4 Advanced Features 37
Special functions (windows 35, 36 and 65)
Special functions are separate relays for overload and underload alarm/stop, start attempts and a reverse function with start attempts:
Window 65 = 0, Normal M20
Window 65 = 1, Separate relays for overload and underload alarm (DLM)
Window 65 = 2, Reverse function
Window 65 = 0 “Normal M20”
R1
R2
Max/Min Main alarm
Max/Min Pre-alarm
Window 65 = 1 “Separate relays over-/underload alarm” (max/min)
R1
R2
Max Main alarm
Min Main alarm
Window 65 = 2 “Reverse function”
R1
R2
Forward
Reverse
Fig. 14 Window 65 and relay functions
In all three cases the number of start attempts after a main alarm may be set in window 36. The pause time between start attempts may be set in window 35. This time is also used as the time to run the motor in the reverse direction when window 65=2.
The reverse function can be used to reverse e.g. a screw conveyor or pump when a “jam” occurs. Reversing the motor may remove the blockage. Should one reverse cycle not be enough to release the material, the M20 will repeat this operation up to a maximum of 5 cycles (window 36, 0-5 start attempts). Relay R1 = forward, relay R2 = reverse.
NOTE: For special handling of analogue output in reverse mode, see below.
The analogue output will go to its maximum e.g. 20 mA when the number of allowed start attempts has elapsed.
Resetting an alarm
A reset will cause the start attempt counter to be reset (new start attempts may be performed).
38 Advanced Features Emotron AB 01-2551-01r4
NOTE: In order to accomplish the above result, it will be necessary for a forward and reversing motor starter to be installed. See Fig. 15 Example of connection with a forward and reversing motor starter (contactor).
For more information contact your local sales outlet or visit us at:
www.emotron.com
L1 L2 L3
Alarm/Stop 20 mA
}
(Blocking)
Max 240 VAC (alt. 0 VDC-)
6
7
8
5
CTMxxx
9
3
M20
S1 S2
1
4
A-A+
2
L1 C
11
L2
13
L3
R1
R2
DIG
K1
K2
UVW
M
K1 K2 Reset
FWD
Window Function Range
35 Reverse time 3-90 s
36 Star t attempts 0-5
65 Relay function 2=reverse
REV
N (alt. 48 VDC+)
Fig. 15 Example of connection with a forward and reversing motor starter (contac-
tor).
NOTE: In Fig. 15, R1 and R2 (K1 and K2) must not be energized/on at the same time as this will generate a short circuit. Therefore it is important that window 65 = 2 before the relays are connected to the contactors.
Emotron AB 01-2551-01r4 Advanced Features 39
Alternative auxiliary circuit
L1 L2 L3
CTMxxx
UVW
9
3
4
L1
A+ A-
11
L2
M20
13
L3
1
C
R1
R2
S2S1
2
DIG
6
7
8
5
0VDC-
OUT
24VDC+
M
Fig. 16 Example of auxiliary circuit when VDC is used.
The example above can be used when a high VDC signal output is required.
40 Advanced Features Emotron AB 01-2551-01r4

10 Troubleshooting

Ensure that the installation has been correctly carried out, e.g. check the termi­nals and that the cables are properly stripped. The monitor is maintenance-free.
However, you should regularly check wirings and terminals etc.
Problem Solution
- Check the connection of the current transformer(s).
Window 01 always shows zero load, even if the motor is running
Window 01 shows an improper power value when the motor is run­ning
Window 03 shows an improper value for the phase current
The monitor never gives an alarm
- Check that the value of the rated motor power in window 41 is the same as the rated motor power on the motor plate.
- Check that window 03 shows a phase current value that agrees with with the rated motor current.
- Check that the motor is not oversized for its applica­tion, check power transmission and gear ratio.
- Check that there is a load on the motor during normal operation.
- Check that the change in motor load is greater than about 3% (window 01).
- Check that the current transformer is connected in phase L1.
- Check that the current transformer has been selected as per Tables 1 and 2.
- Check that the number of windings is as per Tables 1 and 2.
- Check that the value of the motor current in window 42 is the same as the value of the motor current on the motor plate.
- Check that window 01 shows a value greater than zero.
- Check the alarm levels in windows 11 to 14. If in­correct readjust the levels or perform an Auto set.
Emotron AB 01-2551-01r4 Troubleshooting 41
Problem Solution
- Check the alarm levels in windows 11 to 14. If incorrect readjust the levels or perform an
The monitor always gives an alarm
Window 00 shows “LU” or “OU”. Under- or over­voltage alarm.
Window 01 shows “oor”. “Out Of Range” alarm.
Window 03 shows “oor”. “Out Of Range” alarm.
Over and undervoltage is not detected
The alarm relays are not switching
Not all windows are shown
Auto set.
- Check if the monitor is programmed for “latched alarm” (window 61=on). If so reset the monitor by pressing the reset key.
Switch off the supply:
- Check that the supply voltage agrees with the voltage range on the monitor type plate.
- The measured shaft power is higher than 125% of the rated motor power programmed in window 41.
- The measured motor current is higher than 125% of the rated motor current programmed in window
42.
This is only detected at monitor power up and not dur­ing continued operation. The relays will not trip, only indication in the display.
- Check that the wire links between terminals 6 and 7 are removed as per “Wiring”.
When the special functions are used (windows 35, 65 etc.) blocked windows for settings are not shown.
42 Troubleshooting Emotron AB 01-2551-01r4

11 Technical Data

45x90x115 mm (1.77" x 3.54" x 4.53")
Dimensions
35mm
(WxHxD)
45mm (1.77’‘)
(1.38)’‘
26mm
(1.02)’‘
115mm(4.53) ’‘
Mounting 35 mm DIN rail 46277
Weight 0.30 kg (10.5 oz)
Supply voltage (±10%)
1x100-240 VAC, 3x100-240 VAC, 3x380-500 VAC or 3x525­690 VAC
Frequency 50 or 60 Hz
Current input
Power consump­tion
Current transformer; CTM 010, 025, 050 and 100. Input 0­55 mA. (>100 A extra transformer needed)
Max. 6 VA
Start-up delay 1-999 s
Hysteresis 0-50% of rated motor power
Response delay max
Response delay min
0.1-500 s
0.1-500 s
Relay output 5 A/240 VAC Resistive, 1.5 A/240 VAC Pilot duty/AC12
Analogue output Max. load 500 ohm
Digital input
Max. 240 VAC or 48 VDC. High: 24 VAC/DC, Low: <1 VAC/DC. Reset >50 ms
Fuse Max. 10 A
2
single core
Terminal wire size
Use 75°C copper (CU) wire only. 0.2-4.0 mm (AWG12). 0.2-2.5 mm
2
flexible core (AWG14), stripped
length 8 mm (0.32")
’‘
90mm(3.54)
Emotron AB 01-2551-01r4 Technical Data 43
Ter minal tig hten­ing torque
Accuracy
Repeatability ±1 unit 24h; +20°C (+68°F)
Temperature toler­ance
Operating temper­ature
Storage tempera­ture
Protection class IP20
RoHS directive 2002/95/EC
Approved to CE (up to 690VAC), UL and cUL (up to 600 VAC)
0.56-0.79 Nm (5-7 lb-in)
±2%, ±1 unit cos phi>0.5; excl. current transformer; +20°C (+68°F)
max 0.1%/°C
-20 to +50°C (-4°F to +122°F)
-30 to +80°C (-22°F to +176°F)
Article
number
01-2520-20 Emotron M20 1x100-240/3x100-240 VAC
01-2520-40 Emotron M20 3x380-500 VAC
01-2520-50 Emotron M20 3x525-690 VAC
Designation
Technical Data for Current Transformer (CT)
Type
CTM 010 27 (35) x Ø48 mm 0.20 kg 35mm DIN rail 46277
CTM 025 27 (35) x Ø48 mm 0.20 kg 35mm DIN rail 46277
CTM 050 27 (35) x Ø48 mm 0.20 kg 35mm DIN rail 46277
CTM 100 45 (58) x Ø78 mm 0.50 kg 35mm DIN rail 46277
44 Technical Data Emotron AB 01-2551-01r4
Dimensions
(WxØ)
Weight* Mounting
* Weight including 1m (39 inch) cable. Please note that max. length of the
CTM cable is 1 m and this cable cannot be extended.
4.3
17
27
35
48
45
35
Fig. 17 Current Transformer CTM xxx.
Accessories and documentation
Article
number
01-2471-10 Current Transformer (CT) CTM010, max. 10 A
01-2471-20 Current Transformer (CT) CTM025, max. 25 A
01-2471-30 Current Transformer (CT) CTM050, max. 50 A
01-2471-40 Current Transformer (CT) CTM100, max. 100 A
01-2368-00 Front Panel Kit 1 (2x terminal covers included)
01-4136-01 2x Terminal covers
01-2551-00 Instruction manual (Swedish)
01-2551-01 Instruction manual (English)
01-2551-02 Instruction manual (German)
01-2551-03 Instruction manual (Dutch)
01-2551-04 Instruction manual (Spanish)
01-2551-08 Instruction manual (French)
01-2551-09 Instruction manual (Russian)
Designation
10.3
42
78
Emotron AB 01-2551-01r4 Technical Data 45
Dismantling and disposal
The product is designed to comply with the RoHS directive, and shall be hand­led and recycled in accordance with local legislations.
EU (European Union) specifications
EMC EN 61000-6-3, EN 61000-6-2
EN 61000-4-5 Electrical safety EN 60947-5-1 Rated insulated voltage 690 V Rated impulse withstand voltage 4000 V Pollution degree 2 Terminals 3, 4, 5, 6, 7 and 8 are basic insulated from the line. Terminals 3 and 4 are basic insulated from terminals 5, 6, 7 and 8.
US specifications
FCC (Federal Communications Commission). This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference, in which case the user will be required to cor­rect the interference at their own expense.
Canadian specifications
DOC (Department of Communications). This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus as set out in the Canadian Interference-Causing Equipment Regulations. Le présent appareil numérique n'ément pas de bruits radio-électriques dépassant les limites applicables aux appareils numériques de la Classe A prestite dans le Régelement sur le brouillage radioélectrique édicté du Canada.
46 Technical Data Emotron AB 01-2551-01r4

12 Parameter List

Window Function Range Default Custom Symbol
00 Alarm indication
Measured shaft power in % of rated power
Measured shaft
01
02 Measured line voltage 90-760 V V
03 Measured current 0.00-999 A A
04 Parameter lock 0-999
05 Monitor function
11
12
power in kW
Measured shaft power in % of rated power
Measured shaft power in HP
MAX Main Alarm (relay R1)
MAX Pre-Alarm (relay R2)
0-125 %
0-745 kW
0-125 %
0-999
OVER- and UNDERLOAD, OVERLOAD, UNDERLOAD
0-125 100 %
0-745 2.2 kW
0-125 100 %
0-999 3
0-125 100 %
0-745 2.2 kW
0-125 100 %
0-999 3
OVERLOAD and UNDER­LOAD
Emotron AB 01-2551-01r4 Parameter List 47
Window Function Range Default Custom Symbol
0-125 0 %
13
14
21
22
23
24
31 Star t d el ay 1-999 2 s
32
33 Hysteresis 0-50 0 %
34
35* Pause/Reverse time 3-90 5 s
36*
41 Rated m oto r po wer
42 Rated current 0.01-999 5.6 A
43 Number of phases 1PH/3PH 3PH
61 Main alarm latch on/OFF OFF
MIN Pre-Alarm (relay R2)
MIN Main Alarm (relay R1)
MAX Main Alarm margin
MAX Pre-Alarm margin
MIN Pre-Alarm margin
MIN Main Alarm margin
Response delay over­load
Response delay underload
Autoreset (start attempts)
0-745 0 kW
0-125 0 %
0-999 0
0-125 0 %
0-745 0 kW
0-125 0 %
0-999 0
0-100 16 %
0-100 8 %
0-100 8 %
0-100 16 %
0.1-500 s 0.5 s
0.1-500 s 0.5 s
0-5 0
0.10-745 2.2 kW
0.13-999 3
48 Parameter List Emotron AB 01-2551-01r4
Window Function Range Default Custom Symbol
62
63 Main Alarm relay R1 nc/no nc
64 Pre-Alarm relay R2 nc/no no
65* Relay function
81 Digital input rES/AU/bLo rES
82 Block timer 0.0-90 0.0 s
91 Analogue output
92**
93**
99 Factory defaults dEF/USr dEF
Alarm at no motor current
Analogue output low value
Analogue output high value
on/OFF OFF
0 = M20 1 = DLM 2 = Reverse
0.20/4.20/
20.0/20.4
0-100
0-125
0
0.20
* See Special functions in chapter 9.
** See Set analogue output range in chapter 9.
Emotron AB 01-2551-01r4 Parameter List 49

13 Service

This manual is valid for the following model:
Emotron M20 (from software version R3b)
Document number: 01-2551-01
Document version: r4
Date of release: 2008-05-15
Emotron AB reserves the right to alter product specifications without prior notification. No part of this document may be reproduced without permission from Emotron AB.
For more information contact your local sales outlet or visit us at:
www.emotron.com
Protected by utility patents EP 1027759 and US 6879260
50 Service Emotron AB 01-2551-01r4
Emotron AB, Mörsaregatan 12, SE-250 24 Helsingborg, Sweden
Tel: +46 42 16 99 00, Fax: +46 42 16 99 49
E-mail: info@emotron.se
Internet: www.emotron.com
Emotron AB 01-2151-01r4 2008-05-15
Emotron M20
Reverse function
Addendum
English
Emotron M20 Shaft Power Monitor
Special functions (windows 35, 36 and 65) ”Reverse function”
This instruction is valid for Emotron M20, 01-2551-01, (from software version R3B).
The reverse function can be used to reverse (drive back­wards) motor driven equipment such as e.g. a screw con­veyor when a “jam” occurs. With this function the M20 can be used to prevent expensive stops and breakdowns in machinery for example; blocked chip feeder, jammed lime feeder, blocked slurry pump or in other similar applications.
In the case of a screw conveyor or chip feeder, for instance, when an overload or jam-up occurs, the Emotron M20 reverses the “conveyor” automatically. Normally this would clear the jammed material and then enable the conveyor to feed forward again.
Should one reverse cycle (drive backwards) not be enough to release the material, the monitor will repeat this operation up to a maximum of five start attempts. If the conveyor is still jammed, the monitor stops the conveyor motor/ machine from any further operation and an alarm is given. The conveyor would then have to be cleaned manually and the monitor reset. The number of start attempts and the reverse time can be set. If set number of start attempts is enough to release the material the conveyor will feed forward again, and reset the previous number of start attempts, but only after the conveyor has fed forward for least 60 seconds
if the selected start and response delay time has elapsed.
and
Wiring, Programming and Operation
CAUTION: Study thoroughly section 2 Safety in the Emotron M20 Instruction manual before installing and using the monitor. Please note that the machine starts and stops automatically during set-up and running when the reverse function is used!
For wiring, programming and operation see the correspond­ing sections in the Installation manual for the M20. See also under 9 Advanced Features and the headline Special func­tions (windows 35, 36 and 65) as well as the special connec­tion example in Figure 1 (this example can also be found at the end of this instruction).
NOTE: To implement the above Reverse function, it will be necessary for a forward and reversing motor starter (contactors) to be installed.
Relay R1 and R2 (K1 and K2) must not be energized/on at the same time as this will generate a short circuit. Therefore it is important that window 65 = “2” before the relays are connected to the contactors and it is also recommended that the Forward and Reverse contactors are also electrically interlocked.
The output relay contacts, terminals 6, 7 and 8 connect to the motor control circuit and to the respective contactor; i.e. terminal 7 to K1 (R1) = Forward and terminal 8 to K2 (R2) = Reverse (see fig. 1). Terminal 5 can be used for external reset and has the same function as the reset button on the front of the monitor.
Analogue output
In this Reverse function application the analogue output will go to its maximum 20 mA when the number of allowed start attempts has elapsed. The output signal can for example be used as an input to PLC´s or similar equipment to handle the alarm etc. If a potential free relay contact is required, the following external relay is recommended as an accessory:
Schrack / Tyco RT174012 12 VDC (10A 250VAC)
Camden DIN-rail relay socket C 250 3P
Please note that an external alarm relay connected to the analogue output must be specified as the above relay coil voltage, resistance, power etc to ensure correct operation and life time.
Set the monitor as follows
(First perform settings according to the applicable parts of the M20 Monitor installation manual):
1. In this application it is unusual that both overload and underload monitoring is used and unless the underload is required in some other function window 5 should be
-
set to monitor overload only (
).
2. Start the motor/machine and let it run at normal load until the start delay has elapsed - the machine load is shown in the monitor display.
3. Press the “Auto set” button for 3 seconds.
4. Adjust start attempts (window 36), start delay (window
31), response delay (window 32, alt 34 at min), reverse time (window 35) etc. as required.
It is also possible to set the alarm level manually, see the manual and chapter 4 Getting Started.
Operation – Alarm
When an overload occurs for longer than the selected response delay (window 32), the following sequence takes place if there are still some start attempts available:
1. Motor is switched-off and stands for 3 seconds.
2. Motor is reversed during chosen reversal time, window 35 (If the monitor senses an overload during reversal the motor will stop).
3. Once again, the motor is switched-off and stands for 3 seconds.
4. Motor re-starts automatically in forward mode.
For a prolonged jam-up, the monitor will carry out the max­imum of reverse cycles set in window 36. If this does not clear the blockage, the motor is switched-off and the ana­logue output will go to its maximum 20 mA “permanent” stop and alarm. When this occurs, the conveyor/machine must be cleaned manually and the monitor reset, either by
1 Emotron AB 01-4481-01r1
the reset button or by the digital input. When reset, the monitor can once again perform the number of reverse cycles set in window 36.
Reset of the monitor can be done in three ways:
Reset button
Digital input, set for “rES”, window 81
Switch-off the supply voltage, 3-phase.
Important! If the monitor senses an overload during reversal, after start and response delay has elapsed, the motor will be stopped immediately even if the reversal time is set for a longer time. The monitor will then try to run in the forward direction again. If the load returns to a normal running level before the start delay has elapsed (i.e. the jammed material
L1 L2 L3
clears), the monitor will reverse the motor/feeder until the selected time has concluded.
If the reversal time is set to a shorter time period than the start and response delay together, the reverse mode will be completed after the selected reverse time has concluded, independently of the set response delay. In this case the response delay only has an effect on forward running.
When the conveyor has fed forward for at least 60 seconds with normal conditions and no alarm, the previous number of start attempts (reverse cycles) are reset automatically although only if selected start and response delay time has concluded.
Alarm/Stop 20 mA
}
(Blocking)
CTMxxx
K1
UVW
M
K2
9
11
3
L1 C
4
A-A+
L2
M20
13
L3
S1 S2
2
1
K1 K2 Reset
FWD
R1
R2
6
7
8
5
DIG
REV
Window Function Range
35 Reverse time 3-90 s
36 Start attempts 0-5
65 Relay function 2=reverse
Max 240 VAC (alt. 0 VDC-)
N (alt. 48 VDC+)
Fig. 1 Example of connection with a forward and reversing
motor starter (contactor).
Emotron AB 01-4481-01r1 2
Emotron AB, Mörsaregatan 12, SE-250 24 Helsingborg, Sweden
Tel: +46 42 16 99 00, Fax: +46 42 16 99 49
E-mail: info@emotron.se
Internet: www.emotron.com
Emotron AB 01-4481-01r1 06-30-2008
Loading...