Please check the delivery. Despite the fact that all products from Emotron are
carefully inspected and packed, transport damage may occur:
•Your shipment should contain the Emotron DCM, a current transformer,
2x terminal covers (option*) and this instruction manual.
•Check carefully that the equipment ordered complies with the pump
motor’s input voltage and that the current transformer rating is as stated on
the delivery note.
•Check that the contents have not been damaged during transport.
•If something is missing, or has been damaged, contact the supplier as well as
the forwarding agent within 48 hours of receipt.
NOTE: If in doubt contact your supplier before installing or commissioning
the product.
Emotron AB 01-2120-01r2Inside the Box3
4Inside the BoxEmotron AB 01-2120-01r2
2Safety
•Study this manual thoroughly before installing and using the Emotron
DCM.
•The Emotron DCM must be installed by qualified personnel.
•Always disconnect supply circuits prior to installing.
•The installation must comply with standard and local regulations.
•Pay special attention to the information in this chapter and the parts marked
WARNING and CAUTION in the chapter on operation.
•Check that the Emotron DCM and the equipment are correctly connected
before being taken into use.
•Should questions or uncertainties arise, please contact your local sales outlet
or see Chapter 12 page 59, Service.
•Faults that arise due to faulty installation or operation are not covered by the
warranty.
NOTE: Removing or tampering with the seal on the housing will invalidate
the warranty.
Emotron AB 01-2120-01r2Safety5
6SafetyEmotron AB 01-2551-01r4
3Introduction
This instruction manual describes the installation and commissioning of the
Emotron DCM. The Emotron DCM is a control unit that remotely controls
submersible pump equipment. Level sensors are not needed to initiate start and
stop. The pump stops automatically when it begins to snore (draw air), when
the pit has been pumped free from water. During a pumping operation, the
Emotron DCM measures the length of the run period and uses this to determine the length of the rest period. The longer the run period, the shorter the
rest period. As a result the run and the rest periods are continuously adapted to
the rate of flow.
Two Emotron DCM can be connected in parallel to control two submersible
pumps and allow independent operation and display of monitored values (see
Chapter 7).
This instruction manual contains complete instructions for the installation and
use of the Emotron DCM. Please read the entire manual before installing or
using the DCM. Pay special attention to the Safety chapter in this manual and
the parts marked WARNING and CAUTION.
3.1Description
The Emotron DCM measures the input power by measuring voltage and current. This gives a reliable measurement of pump motor load over the total load
range.
As an option a level switch can be used to trigger a start; either to override the
pause time in case of high level or as the sole means to trigger a start.
The Emotron DCM is connected to the pump motor supply cable with a type
CTM current transformer. The same Emotron DCM is suitable for small and
large induction pump motors and the only accessory needed is the CTM current transformer (a primary standard current transformer is also necessary when
the motor current is greater than 100 A).
The Emotron DCM is enclosed in a recyclable PC/ABS plastic housing. At the
front is the operator’s panel which comprises an LCD display and a set of six
keys. The connection terminals are at the top and bottom of the unit front
panel. The unit should be mounted on a standard DIN-rail.
The Emotron DCM is very easy to use. The “Auto set” function makes it possible to adjust the unit (stop level) automatically by pressing just one key.
Emotron AB 01-2120-01r2Introduction7
The Emotron DCM always stops the pump as soon as it starts to snore (draw
air) and restarts it after a calculated pause time or in response to a high-level
switch-over.
The Emotron DCM is able to check:
•Phase sequence.
•Phase voltage asymmetry.
•Current from current transformer(s).
•Temperature on pump motor.
•Undervoltage and Overvoltage (at start up).
The Emotron DCM gives information about:
•Delay time before restarting after the pump has stopped.
•Pumping time since the latest pump start.
•High-level pumping time since the pump started as a result of high-level
switch-over.
•Measured power as a percentage of the DCM’s measurement range.
•Measured voltage.
•Measured peak power as a percentage of the DCM’s measurement range.
•Time counter for total pumping time.
•Start counter - total number of times pump has started.
The Emotron DCM can be connected in parallel for a dual-pump system:
•Alternating
•MASTER/SLAVE function
•If there is a breakdown in one of the pumps, the other pump starts to
operate.
8IntroductionEmotron AB 01-2120-01r2
4Getting Started
4.1Please note the safety section
1. Pay special attention to the safety section in this manual and parts marked
WARNING and CAUTION.
2. Check that the pump motor/supply voltage corresponds to the values on the
Emotron DCM product label at the side of the unit.
3. Make a note of the pump motor’s rated current from its nameplate. Confirm
that the current transformer(s) supplied is of the correct size according to
Table 1, on page 15 and Table 2, on page 17 in this manual.
4.2Connection and setup before start
1. Connect the Emotron DCM according to Chapters 5 and 6 and Fig. 13
(alternatively, for dual-pumps, Chapter 7 and Fig. 15 and 16).
2. Make sure all safety measures have been implemented and switch on the
supply voltage.
3. Follow Quick setup - flow chart Fig. 4, page 13 for single-pump system and
Fig. 5, page 14 for dual pumps.
The purpose of Getting Started is to achieve quick setup and to initiate the stop
function. The Emotron DCM stops the pump when the water level has
dropped to such a low level that the pump begins to snore (draw air). On intake
of air the pump motor power drops below the stop level (see Fig. 1, page 10 and
Fig. 2, page 11) and then the Emotron DCM stops the pump.
Emotron AB 01-2120-01r2Getting Started9
Fig. 1Pump operation
Power pump motor
Set power level
Normal pump load power
Stop level
Pump begins to
draw air (snore)
Time
If the Emotron DCM has been used previously, some parameters may have been
changed. In such a case, go to Chapter 6 and perform a complete setup for
single-pump system installation (alternatively, Chapter 7 for dual-pump system
installation).
On the following pages is a description for the single-pump setup in general. In
the event of an alarm during setup, see Chapters 8 and 9. For dual-pump setup,
see Chapter 7, Dual-Pump System Installation.
10Getting StartedEmotron AB 01-2120-01r2
4.3Auto set performed at normal pumping -
NEXT
ENTERENTER
SET
AUTO
Power pump motor
Auto set is pressed
Normal pump load power (window 04)
Stop level (window 11)
Power level
when snoring
Time
Snore margin (window 12)
pumping water
1. Check that the amount of water is sufficient for pumping about 30 seconds
without snoring.
2. Switch on the supply voltage to the Emotron DCM and set any pump system control equipment to the on position, “1” or Auto. The pump should
now be pumping water without snoring. If the pump does not start, press
the button on the Emotron DCM.
3. Step with the button to window 13 and check that the line is shown at
the top of the display (¯). If not, press , then press to confirm.
AUTO
4. When the pump is working in steady state, press until “SEt” is shown
on the display. The stop level is now set.
The stop function is now initiated and the Emotron DCM controls the pump.
Adjustments can be made according to Section 6.2, page 30. See also section 6.3
and 6.4.
SET
Fig. 2Auto set performed at normal pumping
Emotron AB 01-2120-01r2Getting Started11
4.4Auto set performed at snoring – pumping a
NEXT
ENTERENTER
SET
AUTO
SET
AUTO
Power pump
Auto set is pressed
Normal pump load power (window 04)
Stop level (window 11)
Power level
when snoring
Time
Snore margin (window 12)
mix of air and water
1. Set the pump system control equipment to the off position or “0”, and
switch on the supply voltage to the Emotron DCM.
2. Step to window 13 with the button and press so that the line is
shown at the bottom of the display (_). Then press to confirm the setting. The Emotron DCM is now ready for Auto set at snoring.
3. Set the pump system control equipment to the on position, “1” or Auto to
start the pump. If necessary, press to start the pump.
4. Run the pump until it starts to snore.
5. Press until “SEt” is shown on the display. The stop level is now set, thus
stopping the pump when snoring.
The stop function is now initiated and the Emotron DCM controls the pump.
Adjustments can be made according to Section 6.2, page 30. See also Sections
6.3 and 6.4.
Fig. 3Auto set performed at snoring
12Getting StartedEmotron AB 01-2120-01r2
4.5Quick setup - flow chart
Place the pump in the pit
Set window 13 to ( ),
Is pump
snoring?
NO
Is pump
running?
Press the
button for 3
seconds (while the
pump is stopped)
until SEt is shown
in the window.
NO
YES
Press the
Does window
00 indicate
an alarm?
NO
Check the
troubleshooting
procedure, see
YES
Set window 13
Press the key for 3 s until
SEt is shown in the window . The stop
level (window 11) is set automatically .
YES
and switch the power on.
The stop level
(window 11) is
set to 0.
button
SET
AUTO
SET
AUTO
Chapter 9.
to ( ), see Table
8.
see Table 8.
SET
AUTO
SET
AUTO
Assuming all settings are
in default
Fig. 4Quick setup for single-pump system (the pump will start and stop during
Emotron AB 01-2120-01r2Getting Started13
setup)
Place both pumps in the pit and
switch the power on.
Both pumps will start running now .
Set the Emotron MASTER DCM
window 71 to 2, see Table 8.
Set the Emotron SLAVE DCM
window 71 to 3.
Continue from here with the
Quick Setup for Single Pump on
the MASTER, see Fig. 4.
Press the key on the SLAVE.
Continue from here with the
Quick Setup for Single Pump
on the SLAVE, see Fig. 4.
Fig. 5Quick setup for dual-pump system (the pumps will start and stop during
setup).
14Getting StartedEmotron AB 01-2120-01r2
5Installation
The Emotron DCM may only be installed and commissioned by an authorized
person according to standard and local regulations. Pay special attention also to
the Safety chapter in this manual and the parts marked WARNING and CAUTION.
The Emotron DCM should be mounted on a standard DIN rail 46277,
35 mm. See “Technical Data” for maximum operating temperature range,
dimensions etc. Before installing, make sure that no voltage is applied to the
equipment and that the voltage rating of the Emotron DCM, as shown on the
rating plate on the side of the unit, corresponds to the motor/line voltage.
5.1Choice of current transformer
Depending on pump motor size, the Emotron DCM should be used with one
or two current transformers. For pump motors with a rated current up to
100 A, use a single CTM current transformer. The possible combinations of
CTM current transformers and the number of windings are listed in Table 1.
Table 1Table for selection of current transformer for motors with a rated current
up to 100 A
Rated motor
current
0.4 to 1.0 A10
1.01 to 2.00 A5
2.01 to 3.0 A3
3.1 to 5.0 A2
5.1 to 10 A1
10.1 to 12.5 A24
12.6 to 25 A12
26 to 50 A1
51 to 100 A1
Emotron AB 01-2120-01r2Installation15
Choice of current transformer and number of windings for
different pump motor sizes.
CTM010CTM025CTM050CTM0100
NOTE: The current transformer must be linked to the phase connected to
L1
L2
L3
1
2
S1
S2
M
3
DCM
2 windings
CTM025
1
2
terminal 9 (L1).
Fig. 6Example: CTM 025 with 2 windings for a 12 A pump motor
Fig. 7Example: 1, 2 and 3 windings, see also note on page 16
16InstallationEmotron AB 01-2120-01r2
For larger motors (rated current > 100 A), use two current transformers - one
outer, standard transformer, and one CTM010 with two windings. Table 2
shows the choice of transformers (standard + CTM010) and number of windings for currents exceeding 100 A.
Table 2Table for selection of current transformers for motors with a rated current
greater than 100 A
Rated motor current
101 to 150 A
151 to 250 A
251 to 500 A
501 to 999 A
Current transformers
Number of windings
150:5 + CTM010
1 + 2
250:5 + CTM010
1 + 2
500:5 + CTM010
1 + 2
1000:5 + CTM010
1 + 2
The following examples illustrate the choice of current transformer(s):
Example A. Pump motor has a rated current of 6.9 A. According to Table 1,
choose CTM010 with one (1) winding.
Example B. Pump motor has a rated current of 108 A. According to Table 2,
choose a standard current transformer 150:5 with one (1) winding and a
CTM010 with two (2) windings.
NOTE: The current transformer must be linked to the phase connected to
terminal 9 (L1).
In order to ensure accurate calibration of the Emotron DCM, it is essential that
you use the correct CTM (and, additionally, a standard current transformer)
and apply the exact number of wirings in accordance with the tables above.
Emotron AB 01-2120-01r2Installation17
L1
L2
L3
1
2
S1
S2
M
3
DCM
2 windings
CTM010
500:5
S1S2
1 winding
Fig. 8Example of a CTM 010 with 2 windings and a primary transformer
500:5 with 1 winding for a 260 A pump motor. See also note on page 17
NOTE! The current transformer(s) must be used according to Table 1 or Table
2. Make sure to apply the correct number of winding to the transformers.
18InstallationEmotron AB 01-2120-01r2
5.2The operator’s panel
The operator’s panel comprises an LCD display and a set of six keys on the front
panel of the Emotron DCM. The display provides five digits and eight symbols,
see Fig. 9. The symbols are explained in Table 3, page 20.
The two smaller digits on the left of the display show the window number. Each
window (e.g. 00, 01, 02) contains a parameter (e.g. 125, 0.99, on, OFF) whose
value is shown by the three larger digits or characters to the right. When the
value is greater than 999 all five digits are used to display the parameter value,
alternating with the window number. For example, the window number 21 is
displayed for 2 seconds and then the value 12345 is displayed for 2 seconds.
Fig. 9The display
•When the Emotron DCM is turned on, a self test is performed for 3 seconds
and all characters and symbols on the display are shown.
•During an alarm the entire display flashes.
•If “oor” (out of range) is shown on the display, this means that the value is
too high to be shown on the display.
Emotron AB 01-2120-01r2Installation19
Table 3Symbols on the LCD display
SymbolMeaning
Flashing when alarm triggered.
Indicates when the value is a time.
Parameter settings are locked.
VVolt
mAMilliampere
mMinutes
SSeconds
%Percent
Table 4Function of the keys
KeyFunction
RESET/STARTResets a latched alarm/Starts the pump motor.
Auto set
NEXTProceed to the next window.
-
+
ENTERConfirms the adjustments made.
The stop level is automatically set when the button is pressed
for 3 s.
Decrease the displayed value. For fast incremental decrease,
press the button for 6 s.
Increase the displayed value. For fast incremental increase,
press the button for 6 s.
20InstallationEmotron AB 01-2120-01r2
5.3Description of functions
The menu structure is described in Fig. 10, page 22. Detailed information is to
be found in Table 8, page 53.
On delivery, the Emotron DCM is pre-programmed with the default settings
shown in Table 8, page 53.
One minute after any front panel button is pressed, the Emotron DCM returns
to:
•Window 00 if an alarm has been triggered.
•Window 01 if the pump is paused. When the DCM is SLAVE it displays
_ _ _.
•Window 02 if the pump is pumping. When the DCM is MASTER and its
SLAVE is pumping it displays _ _ _.
•Window 03 if the pump is pumping and it started as a result of a high-level
switch-over.
Emotron AB 01-2120-01r2Installation21
0202
0101
0000
0303
9999
6161
7171
7272
7373
4242
4141
2121
2323
2424
2222
1212
1111
1313
0404
0505
3232
3131
0909
5151
5252
5353
0707
0808
0606
Fig. 10 Menu structure of the Emotron DCM (see also Table 8, page 53.). The
windows 21, 22, 72 and 73 are not shown when the DCM is a SLAVE
(dual-pump system).
NOTE: The Emotron DCM is designed to work with a pit volume which is ≥
the capacity of the pump (in litres). The operator can decide at what pit
volume the DCM should start pumping using window 21.
Start volume = pump capacity [litres/min] x time constant in window 21
[min]. Window 21 has a selectable value from 1.0 – 10.0 minutes.
The volume in the pit at
pump start after pause
time is equal to pump
capacity (litres/min) multiplied by level setting
(window 21).
Examples 1 and 2:
Pump capacity
600 (litres/min) x 1
(Value in window 21) =
600 litres in the pit when
the pump starts to pump.
Example 3:
Pump capacity 600
(litres/min) x 2.3 (value in
window 21) = 1380 litres
in the pit when the pump
starts to pump.
Fig. 11 Pump cycle example with different level settings in window 21
Emotron AB 01-2120-01r2Installation23
NOTE: See note on page 22.
When there is liquid in the pit
A1=Motor load when the pump does not snore (window 13 is set to (¯)).
A2=Stop level if Auto set is pressed when the pump does not snore (window 11).
A3=Snore margin (window 12).
When there is NO liquid in the pit
B1=Motor load when the pump is snoring/dry pumping (window 13 is set to (_)).
B2=Stop level if Auto set is pressed when the pump is snoring/dry pumping (window 11).
B3= Snore margin (window 12).
Power
A1
A3
A2
B2
B3
B1
Time
Fig. 12 Type of Auto set
24InstallationEmotron AB 01-2120-01r2
5.4Connection terminals
There are 13 connection terminals on the front panel of the Emotron DCM.
Table 5Labelling and functions of connection terminals.
TerminalLabelFun ction
1S1Current transformer input (CTM xxx), blue wire.
2S2Current transformer input (CTM xxx), brown wire.
Digital input for closing contact. High-level switch or
3DIG
4SGNDSignal ground for terminals 3 and 5.
5TEMP
6ALARM
7CCommon input for alarm and pump relay.
8PUMP
9L1Supply voltage L1.
10(not used)
11L2Supply voltage L2.
12(not used)
13L3Supply voltage L3.
external reset/Auto set. In dual-pump applications
terminal 3 is also used for communication between
the two DCMs.
Input for motor thermistor (PTC), thermal contact, and/
or any voltage-free opening contact or motor protection relay.
Alarm relay output. (The DCM MASTER uses this
terminal in series with the high-level switch.
Operation of relay pump motor (control signals for start
and stop equipment).
Emotron AB 01-2120-01r2Installation25
26InstallationEmotron AB 01-2120-01r2
6Single-Pump System Installation
!
L1
L2
L3
N
Thermocontact
S1 S2Dig SGND TempPumpCAllarm
L3L2L1
CTM xxx
L1
Number of primary and secondary windings see Table 2
Number of primary windings see Table 1
Alternativ anslutning
Exceeding 100 Amps
Upto 100 Amp
SS
L1
Standard
transformer
CTM 010
DCM
A
A
Selection, see Manual:
Digital Input connection
Dig and SGND, term. 3 and 4.
K1
F1
UVW
M
Autoset
Reset
High level
K1
Alarm
1
2
345
6
7
8
91113
Max 240VAC
Thermistor PTC
-
+
F1
Stop
Max. 10 A
CAUTION: Before carrying out any work, check that any automatic
control equipment, etc., is disconnected from the power supply
and cannot become live.
Fig. 13 Single-pump system installation example (alternatively see Chapter 13).
Emotron AB 01-2120-01r2Single-Pump System Installation27
6.1Single-pump system connection
6.1.1Supply voltage connection (L1, L2 & L3)
Connect the Emotron DCM (3-phase installation only) directly to the pump
motor supply cable via terminals 9 (L1), 11 (L2), and 13 (L3). Make the connection ahead of the contactor of the motor, to ensure that the DCM also
receives power when the motor is not in use. When motor fuses larger than
10 A are used, the DCM (power consumption 6 VA) must be fused independently, see Fig. 13, page 27.
6.1.2Current transformer connection (S1 & S2)
Connect the current transformer CTM xxx to terminal 1 (S1, blue wire) and
terminal 2 (S2, brown wire). The transformer MUST be linked to the phase
connected to terminal 9 (L1), see Fig. 13.
When two current transformers are used (for motors with a rated current greater
than 100 A), always connect the CTM010 to the DCM and one outer standard
current transformer with 2 primary windings through the CTM010, see Fig. 8
and 13 and Table 2, page 17.
NOTE: Before connecting the current transformer(s), study the choice of
current transformers carefully to determine the correct number of
windings. The current transformer MUST be linked to the phase connected
to terminal 9 (L1), see Fig. 13, page 27.
In order to ensure accurate calibration of the Emotron DCM, it is essential that
you use the correct CTM and apply the exact number of windings in accordance with Table 1, page 15 or Table 2, page 17.
6.1.3Alarm relay connection (ALARM & C)
Terminals 6 and 7 are the alarm relay connections. Terminal 6 (ALARM) is the
alarm relay output. Terminal 7 (C) is the common input for the alarm relay.
When powered off, the alarm relay is NC (normally closed). When powered on, NC or NO (normally open) can be selected, see Table 8, window 51.
28Single-Pump System InstallationEmotron AB 01-2120-01r2
6.1.4Operation relay connection (PUMP & C)
Terminals 7 and 8 are the operating relay connections that control the start and
stop equipment for the pump motor.
Terminal 8 (PUMP) is an operating relay output. Terminal 7 (C) is the common input for the operating relay, see Fig. 13, page 27.
When powered off, the operating relay is NO. When powered on, NC or NO
can be selected, see Table 8, page 53 and window 52.
6.1.5Digital input connection (DIG & SGND)
Terminals 3 (DIG) and 4 (SGND) are connections for a closing contact
between DIG and SGND.
The three functions that can be initiated by the digital input are:
1. High-level switch (to enable immediate start of the pump).
2. External reset.
3. External Auto set.
See Fig. 13, Table 8, page 53 and window 53.
6.1.6Temperature-measuring input connection
(TEMP & SGND)
Terminals 4 and 5 are the temperature-measuring input and/or motor protection contact connections. The motor protection relay can be connected in series
with the temperature sensor. Terminal 5 (TEMP) is for a PTC-type thermistor
or thermo contact. Terminal 4 (SGND) is the signal ground for the
temperature-measuring input. See Fig. 13, Table 8 and windows 31 and 32.
Emotron AB 01-2120-01r2Single-Pump System Installation29
6.2Detailed setup for single-pump system
NEXT
ENTERENTER
WARNING: The pump starts and stops during setup. Make sure
that all safety measures have been implemented before
switching on the supply voltage and starting the pump in order
to avoid personal injury.
NOTE: To prevent involuntary starting and stopping of the pump during
setup steps 1 to 13, disconnect the wire on terminal 8.
Setting up of the EmotronDCM
The steps below illustrate examples of how to program the DCM. When the
power is turned on, press to proceed to the next window, press or
to increase or decrease the value, and press to confirm the new value in
each window. See Table 8. For quick setup, see Chapter 4.
Install the Emotron DCM according to Chapter 5, page 15.
1. Place the pump in the pit and switch the power on.
2. Check window 71 if the value is 1 (single-pump system).
3. In window 13 select the type of Auto set. Set the window to (
is pumping without snoring (there is liquid in the pit). Set the window to
(_) if the pump is snoring (no liquid in the pit) (see Fig. 2, 3 and 12).
-
) if the pump
4. In window 22 set the maximum pause time between 0-720 minutes. See
section 6.4, page 32.
5. In window 23 set the required start-up delay between 1-170 s. Start-up
delay time is the time between the pump starting and the time when snoring
is detected (no liquid in the pit).
6. In window 24 set the required stop delay between 1-90 seconds. The stop
delay is the time between the pump starting to snore and the time when the
pump motor stops.
7. In window 31, if the pump has a temperature sensor and/or motor protection, set the temperature monitoring to (on). If not, set the window to
(OFF). See Section 8.5, page 42 and Fig. 13, page 27.
30Single-Pump System InstallationEmotron AB 01-2120-01r2
8. In window 32 if window 31 is set to (on), choose temperature alarm latched
SET
AUTO
SET
AUTO
ENTER
ENTER
(on) or temperature alarm not latched (OFF). See section 8.5.
9. In window 41 the permitted phase asymmetry is set between 5% and 50%.
Phase asymmetry monitoring is turned off by pressing -, when the window
shows 5%. To turn the monitoring on again press + and select a value, see
Section 8.2, page 41.
10. In window 42, if the window 41 value is between 5% and 50%, choose
phase asymmetry alarm latched (on) or phase asymmetry alarm not latched
(OFF). See section 8.2.
11. In window 51 set the alarm relay contact function to NO (normally open)
or NC (normally closed), see Section 6.1.3, page 28.
12. In window 52 set the operating relay contact function, see section 6.1.4.
13. In window 53 set the required function for the digital input (DIG). Value:
(1) high-level switch, (2) external reset, (3) external Auto set.
14. Connect the start and stop equipment to terminal 8, see Fig. 13, page 27.
15. Check that the pump is pumping in accordance with the setting in window
13 (set the stop level in window 11 to 0 (default) if the pump stops before or
during the Auto set). Press the button and hold for 3 seconds until
“SEt” appears in the window. The stop level (window 11) becomes meas-
ured power (window 04) minus snore margin (window 12) if window 13 is
-
set to (
). The stop level (window 11) becomes measured power (window
04) plus snore margin (window 12) if window 13 is set to (_), see Fig. 2, 3,
12 and 14.
16. Change the level setting in window 21 between 1-10 for shorter or longer
pump cycles and levels in the pit. A low value gives shorter pump cycles and
lower level in the pit. See Fig. 11 and 14.
17. It is possible to avoid unintentional changes of set parameters. Set window
09 to 369 and confirm with . A padlock is shown in the window. If the
value 369 is re-entered in window 09, confirmed by , the settings are
unlocked.
Emotron AB 01-2120-01r2Single-Pump System Installation31
Pit volume
window 21=1.0
window 21=2.0
window 21=4.8
Time
Pausing
Pumping
[min
Fig. 14 Relative volume in the pit at pump start
6.3Adjustment of stop level
The stop level can always be adjusted in the following way:
1. Change the snore margin (window 12) and perform a new Auto set. The
new stop level will be set in relation to the snore margin. See examples in
Fig. 2, page 11 and Fig. 3, page 12.
2. Change the stop level directly in window 11.
6.4Start conditions and pause time
adjustment
In normal operation there are two starting options:
1. Pump start after remaining pause time (window 01).
2. Pump start at high level switch (window 53 = “1”). This requires connection
of a high-level switch according to Section 6.1.5, page 29.
The pump will also start if a non-latched alarm disappears or the button is
pressed during pause.
Calculation of pause time is based on previous pumping and pause times and is
controlled by the two parameters, level setting (window 21), and maximum
32Single-Pump System InstallationEmotron AB 01-2120-01r2
pause time (window 22). The parameters can be adjusted to achieve desired
ENTER
magnitudes of pause times, start level and number of starts per hour. See Fig.
11, page 23, and 14, page 32.
The level setting in window 21 is set for shorter or longer pumping and pause
cycles. Higher values increase the calculated pause time and the amount of accumulated water.
The level setting is best adjusted after a few pumping cycles in order to adjust
the pause time, and hence the start level in the pit. See schematic pump cycle
example in Fig. 11 and 14.
Maximum pause time for the pump is set in window 22. The calculated pause
time will be limited to this value. In some applications the inflow may increase
rapidly during a pause. To prevent overflow in these situations the maximum
pause time can be set in accordance with the circumstances.
6.5Returning to the default settings
1. To return to the default settings go to window 99.
2. If any value differs from the default values (see Table 8). “Usr” (set by the
user) is displayed in the window.
3. Press to return to the default settings. “dEF” (default setting) is shown
in the window. Confirm by pressing .
NOTE: Also, windows 6, 7 and 8 are set to 0.
Emotron AB 01-2120-01r2Single-Pump System Installation33
34Single-Pump System InstallationEmotron AB 01-2120-01r2
7Dual-Pump System Installation
!
CAUTION: Before carrying out any work, check that any automatic
control equipment, etc., is disconnected from the power supply
and cannot become live.
NOTE: Some useful hints and examples are given in Chapter 6, page 27,
Single-Pump System Installation.
NOTE: The dual-pump DCM system must not be installed in a pit of
extremely small diameter or width. This will result from time to time in the
DCMs failing to detect the stop/minimum level.
Fig. 15 Dual-pump application
Emotron AB 01-2120-01r2Dual-Pump System Installation35
Fig. 16 Dual-pump example (alternatively, see the Appendix, Chapter 13)
7.1Dual-pump system connection
(Parallel connection of two Emotron DCMs)
7.1.1Dual-pump supply connection (L1, L2 & L3)
Connect the main voltage from each pump to the respective DCM as described
in Section 6.1.1, page 28. See Fig. 16.
7.1.2Dual-pump current transformer connection
(S1 & S2)
Connect the current transformers (CTMs) from each pump to the respective
DCM as described in Section 6.1.2, page 28. See Fig. 16.
36Dual-Pump System InstallationEmotron AB 01-2120-01r2
7.1.3Dual-pump alarm relay connection (ALARM & C)
Terminals 6 and 7 on the DCM SLAVE are the alarm relay connections. These
terminals indicate an alarm if a fault is detected by the DCM MASTER or the
DCM SLAVE. See Fig. 16. When powered off, the alarm relay is NC (normally
closed). When powered on, NC or NO (normally open) can be selected. See
Table 8, page 53, window 51.
7.1.4Dual-pump communication and digital input
connection (DIG & SGND)
Terminals 3 (DIG) and 4 (SGND) are connections for closing contacts and for
communicating between the DCM MASTER and the DCM SLAVE. The digital input can be used for high-level switch or external reset. The high-level
switch must be connected in series with the DCM MASTER terminal 6
(ALARM) and terminal 3 (C). When external reset is chosen use the pulse signal. Connect terminal 3 (DIG) on the DCM MASTER to terminal 3 (DIG) on
the DCM SLAVE. Connect terminal 4 (SGND) on the DCM MASTER to terminal 4 (SGND) on the DCM SLAVE. See Fig. 16 and Table 8, page 53, window 53.
7.1.5Dual-pump operation relay connection (PUMP)
Connect the control signals for the start and stop equipment for each pump to
the respective DCM as described in Section 6.1.4, page 29. See Fig. 16.
7.1.6Dual-pump temperature-measuring input
connection (TEMP & SGND)
Connect the temperature sensor and/or motor protection for each pump to the
respective DCM as described in Section 6.1.6. See Fig. 16.
Emotron AB 01-2120-01r2Dual-Pump System Installation37
7.2Detailed setup for dual-pump system
NEXT
ENTERENTER
(always use two Emotron DCMs)
WARNING: The pumps start and stop during setup. Make sure
that all safety measures have been implemented before
switching on the supply voltage and starting the pumps in order
to avoid personal injury.
NOTE: To prevent involuntary starting and stopping of the pumps during
setup steps 1 to 14, disconnect the wire on terminal 8 on both DCMs.
Setting up of the Emotron DCM
The steps below illustrate examples of how to program the DCM. When the
power is turned on, press to proceed to the next window, press or
to increase or decrease the value and press to confirm the new value in each
window. For quick setup, see Chapter 4.
1. In window 71 set the required function: dual-pump control MASTER (2)
for one of the DCMs and for the other DCM dual-pump control SLAVE
(3). The DCM MASTER must be the DCM that is wired for MASTER, see
Fig. 16, page 36.
2. In window 72 on the MASTER DCM, set the condition for alternating the
pumps. Alternate by each pump cycle (on). The SLAVE DCM starts only
when the DCM MASTER shows fault codes (OFF).
3. In window 73 on the MASTER DCM, set the condition for pump start-up
on the high-level switch. Both pumps start (on). One pump starts (OFF).
4. In window 13 select the type of Auto set (on both DCMs). Set the window
-
to (
) if the pump is pumping without snoring (there is liquid in the pit).
Set the window to (_) if the pump is snoring (no liquid in the pit); see Fig.
12, page 24.
5. In window 22 on the MASTER DCM, set the maximum pause time
between 0 - 720 minutes.
6. In window 23 on both DCMs, set the required start-up delay between 1170 seconds. Start-up delay time is the time between the pump starting and
the time when snoring is detected (no liquid in the pit).
38Dual-Pump System InstallationEmotron AB 01-2120-01r2
7. In window 24 on both DCMs, set the required stop delay between 1-90 sec-
SET
AUTO
SET
AUTO
SET
AUTO
SET
AUTO
onds. Stop delay time is the time between the pump starting to snore and
the time when the pump motor stops.
8. In window 31 on both DCMs, if the pump has temperature sensor and/or
motor protection, set temperature monitoring to (on). If not, set the window to (OFF). See Section 8.5, page 42.
9. In window 32 on both DCMs if window 31 is set to on. Temperature alarm
latched (on). Temperature alarm not latched (OFF). See Section 8.5.
10. In window 41 on both DCMs, set the permitted phase asymmetry to
between 5% and 50%. Phase asymmetry is turned off by pressing -, when
the window shows 5%. To turn the monitoring on again, press + and select a
value. See Section 8.2, page 41.
11. In window 42 on both DCMs if window 41 value is between 5 and 50%
choose phase asymmetry alarm latched (on) or phase asymmetry alarm not
latched (OFF) See Section 8.2.
12. In window 51 on the SLAVE DCM, set the alarm relay contact function to
NO (normally open) or NC (normally closed), see Section 7.1.3, page 37.
13. In window 52 on both DCMs, set the operating relay contact function. See
Section 7.1.5.
14. In window 53 on both DCMs, set the required function for the digital input
(DIG), value (1) high-level switch, (2) external reset, see Section 7.1.4, page
37.
15. Connect the start and stop equipment to terminal 8, see Fig. 16, page 36.
16. Check that one of the pumps is running according to the setting in window
13 and that the other pump is not running (set the stop level in window 11
to 0 (default) if the pump stops before or during the Auto set). Press the
button for 3 seconds until “SEt” is shown in the window. Press the but-
ton on the other DCM. Wait until the start delay has elapsed. Press the
button for 3 seconds until “SEt” is shown in the window. The stop level
becomes measured power (window 04) minus snore margin (window 12) if
window 13 is set to (¯). The stop level becomes measured power (window
04) plus snore margin (window 12) if window 13 is set to (_). See Fig. 1, 2
and 12.
Emotron AB 01-2120-01r2Dual-Pump System Installation39
17. Change the level setting in window 21 on the MASTER DCM between 1 -
ENTER
ENTER
ENTER
10 for shorter or longer pump cycles and level in the pit. A low value gives
shorter pump cycles and lower level in the pit, see Fig. 11, page 23 and 14,
page 32.
18. It is possible to avoid unintentional changes to set parameters. Set window
09 to 369 in each DCM and confirm with . A padlock is shown in the
window. If the value 369 is re-entered in window 09 and confirmed by
the settings are unlocked.
7.3Returning to the default settings
1. To return to the default settings go to window 99.
2. If any value differs from the default values (see Table 8), “Usr” (set by the
user) is displayed in the window.
3. Press to return to the default settings. “dEF” (default setting) is shown
in the window. Confirm by pressing .
NOTE: Also, windows 6, 7 and 8 are set to 0.
40Dual-Pump System InstallationEmotron AB 01-2120-01r2
8Protection and Alarm
When an error occurs, the triangular alarm sign starts to flash and the alarm
relay is activated.
Window 00 becomes active and gives the information about the alarm according to the alarm list, see Table 6, page 43.
Alarm in a dual-pump application
The fault code is shown in window 00 of the respective DCM, the alarm relay is
only set on terminal 6 of the DCM SLAVE when an error occurs. If a latched
alarm occurs it must be reset on the respective DCM by pressing the button or, if specified as digital input, by an external reset.
8.1Phase sequence (F1)
When the DCM is first switched on, phases L1, L2 and L3 are checked for correct phase sequence.
If the wrong phase sequence is detected, an F1 alarm is generated and the
ALARM relay on terminal 6 is activated. The pump will not start. Switch the
power off and shift phase L2 and L3.
NOTE: Do not shift L1, only shift phase L2 and L3.
8.2Phase asymmetry (F2)
The permitted phase asymmetry is set in window 41, see Table 8, page 53. Any
failure shorter than 5 seconds is ignored. When phase asymmetry is detected an
F2 alarm is generated and the ALARM relay on terminal 6 is activated. The
pump will be stopped.
If window 42 is set to on, the alarm can be reset by pressing the button or
by using the external reset signal.
Emotron AB 01-2120-01r2Protection and Alarm41
8.3Checking the current (F3)
SET
AUTO
SET
AUTO
When is pressed the DCM checks the measured current from the current
transformer (CTM), see Table 1, page 15 or 2, page 17.
The measured current at terminals S1 and S2 is displayed in window 61. If the
measured current is below 10 mA or above 60 mA, an F3 alarm is generated and
the alarm relay is activated. The pump will be stopped.
8.4Operating fault (F4)
If the pump is snoring and the high-level switch gives the signal to pump, this is
a fault situation and an F4 alarm is generated and the ALARM relay is activated.
If communication between the DCM MASTER and the DCM SLAVE is interrupted an F4 alarm is generated and the ALARM relay is activated. See Fig. 16,
page 36 and Section 7.1.4, page 37.
8.5Temperature input (F5)
Temperature monitoring on pump motor
The Emotron DCM can use either an input thermistor (PTC) signal or thermo
contact (terminal 5). To activate temperature monitoring, set window 31 to
“on”.
When the pump motor gets hot, the excess temperature generates an F5 alarm
and activates the ALARM relay and the pump will be stopped.
It is also possible to connect a motor protection relay to generate an F5 alarm.
See Fig. 13, page 27 and Fig. 16, page 36.
If window 32 is set to on, the alarm can be reset by pressing the RESET button
or by using the external reset signal.
8.6Undervoltage (LU)/Overvoltage (OU) alarm
When the Emotron DCM is first switched on, the voltages on phases L1, L2
and L3 are checked.
If the wrong phase voltage is detected, an LU (undervoltage) or OU (overvoltage) alarm is generated and the ALARM relay is activated. The pump will not
start. Switch the power off. Check that the line voltage corresponds to the voltage range of the DCM according to the rating plate on the side of the unit.
The product is designed to comply with the RoHS directive, and should be
handled and recycled in accordance with local legislations.
10.1EU (European Union) specifications
EN 61000-6-3
EMC
Electrical safetyEN 60947-5-1
Rated insulated voltage690 V
Rated impulse withstand voltage4000 V
Pollution degree2
Terminals 3, 4 and 5 are basic insulated from the line and relay terminals.
EN 61000-6-2
EN 61000-4-5
50Technical DataEmotron AB 01-2120-01r2
10.2US specifications
FCC (Federal Communications Commission)
This equipment has been tested and found to comply with the limits for a class
A digital device pursuant to Part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference, in which
case, the user will be required to correct the interference at their own expense.
10.3Canada specifications
DOC (Department of communications)
This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus as set out in the Canadian Interference-Causing
Equipment Regulations. Le présent appareil numérique n’émet pas de bruits
radioélectriques dépassant les limites applicables aux appareils numériques de la
classe A prescrites dans le Règlement sur le brouillage radioélectrique édicté par
le ministère des Communications du Canada.
Emotron AB 01-2120-01r2Technical Data51
52Technical DataEmotron AB 01-2120-01r2
11Window Parameters
Table 8Window parameters and defaults
WindowFunctionValueDefault
Alarm indication. Flashes
00
01
02
03
04
when alarm present (window
becomes active only on alarm).
Symbol flashing.
Remaining time to next pump
start. Standard window during
pause. When the DCM is
SLAVE - - - appears.
Symbol flashing and m
(min) or s (second).
Pumping Time (PT) since the
last pump start. Displayed
when pumping. When the DCM
is MASTER and the DCM
SLAVE is pumping - - - appears.
Symbol flashing and m
(min) or s (seconds).
Pumping Time (PT) after last
pump start when the pump is
started on high-level switch.
Displayed when pumping after
high-level switch.
Symbol flashing and m
(min) or s (seconds).
Measured power as percentage of the DCM’s measurement range.
Symbol %.
See Table 6,
page 43.
720 - 15
min.
900 to 0 s
0 to 90 s.
15 - 720
min.
12 to 999 h
0 to 900 s
15 - 720
min.
12 to 999 h
0 to 125%
Custom
setting
Master Slave
Emotron AB 01-2120-01r2Window Parameters53
Table 8Window parameters and defaults
WindowFunctionValueDefault
Custom
setting
Master Slave
05
Measured line voltage.
Symbol V.
0 to 999 V
Measured peak power as percentage of the DCM measurement range. Press - and + (in
06
this window) simultaneously
0 to 125%0%
for 3 seconds to reset the
value.
Symbol %.
Total pumping time in hours.
Press - and + (in this window)
07
simultaneously for 3 seconds
0-999990
to set the value to 0.
Symbol .
Total number of pump starts.
08
Press - and + (in this window)
simultaneously for 3 seconds
0-999990
to set the value to 0.
Parameter lock.
09
Symbol . Is displayed when
0 to 999
parameter is locked.
11Stop level. Symbol %.0 to 125%0%
12Snore margin. Symbol %.0 to 125%4%
Type of Auto set. Auto set when
the pump is snoring (_)
13
(No liquid in the pit).
Auto set when the pump is not
snoring (
-
)
-
) or (_)(-)
(
(Liquid in the pit).
54Window ParametersEmotron AB 01-2120-01r2
Table 8Window parameters and defaults
WindowFunctionValueDefault
Pit volume and level setting,
see Fig. 11, page 23 and Fig.
21
22
23
14, page 32. See also note on
page 22. NOTE! The window is
not shown when the DCM is
SLAVE.
Maximum pause time.
NOTE! The window is not
shown when the DCM is
SLAVE. Symbol .
Start-up delay.
Symbol .
1.0 to 10.01.0
0 to 900 s
15 - 720
min.
1to170s5s
600 s
Custom
setting
Master Slave
24
31
32
41Phase asymmetry permitted.
42
Emotron AB 01-2120-01r2Window Parameters55
Stop delay.
Symbol .
High temperature on pump
motor or motor protection
alarm, terminal 5 (on). Turn off
(OFF).
Latched alarm, terminal 5 (on).
Alarm not latched (OFF). Can
only be used when window 31
is (on).
Phase asymmetry latched
alarm (on). Phase asymmetry
alarm not latched. (OFF) Can
be used when window 41 is set
between 5-50%.
1to90s2s
on / OFFOFF
on / OFFOFF
OFF/ 5 to
50%
on / OFFOFF
10%
Table 8Window parameters and defaults
WindowFunctionValueDefault
Alarm relay (terminal 6
ALARM).
51
52
53
61
71
72
NC: normally closed,
NO: normally open.
The window isn’t shown when
DCM is MASTER
Operating relay to control the
pump motors contactor
(terminal 8 PUMP).
NC: Relay contact is closed
when pump is pumping.
NO: Relay contact is open
when pump is pumping.
Digital input for closing
contact:
1 High-level switch
2External reset
3 External Auto set (not used
in dual-pump system).
Measured current on the
terminals S1 and S2.
Desired DCM function:
1 Single-pump system
2 Dual-pump system MASTER
3 Dual-pump system SLAVE.
Pump alternating:
(on) Alternate by each pump
cycle (OFF) The SLAVE DCM
only starts when the DCM
MASTER indicates a fault code.
NOTE! The window is not
shown when the DCM is
SLAVE.
NC/NONO
NC/NONC
1
0-70 mA
1, 2, 31
on/OFFOFF
Custom
setting
Master Slave
56Window ParametersEmotron AB 01-2120-01r2
Table 8Window parameters and defaults
WindowFunctionValueDefault
Pump starts on high-level
switch. (on) Both pumps start.
73
99
(OFF) one pump starts.
NOTE! Window is not shown
when the DCM is SLAVE.
Default settings (dEF). User
adjustments mode (USr).
on/OFFOFF
dEF/USrdEF
Custom
setting
Master Slave
Emotron AB 01-2120-01r2Window Parameters57
58Window ParametersEmotron AB 01-2120-01r2
12Service
This manual is valid for the following model:
Emotron DCM (as from software version r1d)
NOTE: The Emotron DCM does not contain any user-serviceable parts.
Breaking the seal over the front panel and housing will invalidate the
warranty.
Document number:01-2120-01
Document version:r2
Date of release:2009-03-10
Emotron AB reserves the right to alter product specifications without prior
notification. No part of this document may be reproduced without permission
from Emotron AB.
For more information contact your local sales outlet or visit us at:
www.emotron.com
Protected by utility patents EP 1027759 and US 6879260
Emotron AB 01-2120-01r2Service59
60ServiceEmotron AB 01-2120-01r2
13Appendix
Thermo-
contact
S1 S2Dig SGND TempPumpCAllarm
L3L2L1
CTM xxx
L1
Number of primary and secondary windings see Table 2
Number of primary windings see Table 1
Alternativ anslutning
Exceeding 100 Amps
Upto 100 Amp
SS
L1
Standard
transformer
CTM 010
DCM
A
A
Selection, see Manual:
Digital Input connection
Dig and SGND, term. 3 and 4.
K1
F1
U
V
W
M
Autoset
Reset
High level
K1
Alarm
1
2
3
4
5
6
7
8
9
11
13
Max 240VAC
Thermistor PTC
-
+
F1
Stop
Max. 10 A
Fig. 18 Single-pump system installation example (Figur 13)
Emotron AB 01-2120-01r2Appendix61
Fig. 19 Dual-pump example (Figur 16)
62AppendixEmotron AB 01-2120-01r2
Emotron AB, Mörsaregatan 12, SE-250 24 Helsingborg, Sweden
Tel: +46 42 16 99 00, Fax: +46 42 16 99 49
E-mail: info@emotron.se
Internet: www.emotron.com
Emotron AB 01-2120-01r2 2009-03-10
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.