CR Magnetics CR9300 Data Sheet

Relays and Switches
E
CR Magnetics, Inc. 3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com E-mail: sales@crmagnetics.com
Another HUNTINGTON ELECTRIC Company
75
Current Switch Normally Open
The CR9300 Series is a low cost, self powered, fixed set-point Current Switch designed for applications that require an on-off indication of current flow. Current levels above the guaranteed full-on level will turn the output to full on. The Current Switch is recommended only for applications where the continuous operating current is above the rated full on level of 350 mA. Operation below this point will not drive the output device full-on and derate the output ratings. The unit is available with a NPN or PNP output transistor for switching DC and a SCR output for switching AC. Connections can be made directly to items such as a PLC or electromechanical relay. Note that connections made directly to an in­ductive device such as an electromechanical relay will require a customer sup­plied clamping diode for DC operation or a snubber network for AC operation.
Applications
Continuity Proving Switch
Features
Low Cost Low Fixed Trip Point Fully Isolated Reverse Output Polarity Protected Self-Powered
Specifications
Rated Full-on: 0.350 AAC RMS Turn-on Time: 100 ms. max. @ rated full-on Turn-off Time: 250 ms. max. to 80% of Vce Maximum sense current: Continuous: 100 AAC
1 Second: 500 AAC Frequency*: 50 to 400 Hz Operating Temperature: -30° C to +60° C Storage Temperature: -55° C to +85° C Weight 0.08 LBS.
*All specifications for operation at 60 Hz only
Regulatory Agencies
DC SWITCHING (-NPN or -PNP)
Vce (full off): 30 VDC max. Isink (full on): 120 mADC max.@ rated full-on Vce (reverse polarity voltage): 1.2 VDC @
100 mADC Vce (full on): 1.5 VDC @ 120 mADC Isink Off state leakage current: 5ua @ 30 VDC
(typical)
AC SWITCHING (-ACA)
Off state voltage: 240 VAC RMS max. Minimum holding current: 10 mA On state current: 0.8 AAC RMS max. continuous Off state leakage: 50 ua @ 240 VAC max. Peak Non-Repetitive Surge Current:
8 AAC RMS (1 cycle, 60 Hz.)
CR9300 Series
OUTLINE DRAWING
PART NUMBER
CR❑❑❑❑ - ❑❑❑ - ❑ CURRENT SWITCH
9321 .27 dia. Window 9350 .61 dia. Window
NPN Transistor Output PNP Transistor Output ACA AC Output
ELECTRICAL CONNECTIONS
M MountingCase
(Optional)
CR9350 CR9321
V+
VAC
BLACK
BLACK
I sink
RED +
Vce
BLACK -
-NPN
ORANGE +
BLACK -
-PNP-ACA
V+
Vce
I source