SPECIFICATIONS
DC Voltage Transducer
NOTE: The building installation must have a switch or circuit-breaker that is in close proximity and within easy reach of the operator. The switch or circuit breaker
shall be marked as the disconnecting device for the equipment.
DIN RAIL / PANEL MOUNT, RMS
CR5310
0 - ±5 VDC Output
CR5320
4 - 20 mADC Output
CONNECTION DIAGRAM
Basic Accuracy:...................... 0.5 %
Calibration:............................. RMS Calibrated
Thermal Drift:.......................... 200 PPM/°C
Operating Temperature:.......... 0°C to +60°C
Installation Catagory:.............. CAT II
Pollution Degree:.................... 2
Response Time:.................... 250 ms. max.,0-90% FS
Altitude:................................. 2000 Meters Max.
MTBF:............................. Greater than 100 K hours
Insulation Voltage:................... 2500 VDC
Supply Voltage:............................... 24 VDC ±10%
Frequency Range:.......................... DC only
Output Load:......±5
or ±10
VDC...... 2 K Ω or greater
4-20 mADC........... 0 - 300 Ω
Supply Current:
CR5310:......................Typical 10mA Max 15mA
CR5320:......................Typical 35mA Max 35mA
Torque Specs.:................ 3.0 inch lbs. (0.4Nm)
Weight:.............................0.5 lbs.
OUTLINE DRAWING
1.