CR Magnetics CR5300 Data Sheet

CR Magnetics, Inc. 3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com E-mail: sales@crmagnetics.com
Another HUNTINGTON ELECTRIC Company
46
Transducers
C
DC Voltage Transducer
DIN RAIL / PANEL MOUNT, RMS
1 - 0-1 VDC
5- 0-5 VDC 10 - 0-10 VDC 50 - 0-50 VDC
150 - 0-150 VDC
200 - 0-200 VDC
Ranges available up to and including
600 VDC
Single Element
1 - 200 VDC Input Range
Add suffix for input range
If you need a relay output, use a CR3395.
See Section E for Details.
The CR5300 Series, DC Voltage Transducers and Transmitters, are designed to provide an output DC signal that is proportional to the input DC voltage. These devices are especially suited for applications with a current shunt to monitor DC current.
Applications
Power Supply over/under sensing Battery chargers and systems Mobile applications Power sensing
Features
Output isolated from input Available with 0-5 VDC, 0-10 VDC or 4 - 20 mADC outputs 35mm DIN rail or panel mount
Connection diagram printed on case
Regulatory Agencies
Approved to 61010B-1 Approved to CAN/CSA-C22.2, No. 1010.1-92 Meets IEC 61010-1 and BS EN 61010-1
CR5310 with Resistor Application is shown below.
PART NUMBERS
CR5310
-
Single Element with
±
5 VDC output
CR5311
-
Single Element with
±
10 VDC output
CR5320
-
Single Element with 4 - 20 mADC output
E199795
Transducers
C
CR Magnetics, Inc. 3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com E-mail: sales@crmagnetics.com
Another HUNTINGTON ELECTRIC Company
47
SPECIFICATIONS
DC Voltage Transducer
NOTE: The building installation must have a switch or circuit-breaker that is in close proximity and within easy reach of the operator. The switch or circuit breaker shall be marked as the disconnecting device for the equipment.
DIN RAIL / PANEL MOUNT, RMS
CR5310
0 - ±5 VDC Output
CR5320
4 - 20 mADC Output
CONNECTION DIAGRAM
Basic Accuracy:...................... 0.5 %
Calibration:............................. RMS Calibrated
Thermal Drift:.......................... 200 PPM/°C
Operating Temperature:.......... 0°C to +60°C
Installation Catagory:.............. CAT II
Pollution Degree:.................... 2
Response Time:.................... 250 ms. max.,0-90% FS
Altitude:................................. 2000 Meters Max.
MTBF:............................. Greater than 100 K hours
Insulation Voltage:................... 2500 VDC
Supply Voltage:............................... 24 VDC ±10%
Frequency Range:.......................... DC only
Output Load:......±5
or ±10
VDC...... 2 K or greater
4-20 mADC........... 0 - 300
Supply Current:
CR5310:......................Typical 10mA Max 15mA
CR5320:......................Typical 35mA Max 35mA
Torque Specs.:................ 3.0 inch lbs. (0.4Nm)
Weight:.............................0.5 lbs.
OUTLINE DRAWING
2
(31
(20)
Dimensions for All CR5300 Series (shown)
0.20 (5.1)
(36) 0.14
1 2 3 4
2.874 (73)
3.268 (83)
(3.5)
9
1.06
8
(26.8)
7 6 5
1.
0.79
1.16
(29.5)
1.42
(36)
Loading...