Crestron CLT-1DIM8 User Manual

CLT- & CLX-1DIM8

Functional Summary

The Crestron 1-Feed, 8-Dimmer Terminal Block and Module (CLT-1DIM8 and CLX-1DIM8, respectively), are considered a single entity and must be used together. They ship separately to permit termination of the field wiring to the CLT-1DIM8 prior to installation of the CLX-1DIM8, as described in this guide. They can be mounted in any Crestron Automation Enclosure (CAEN­Series Enclosures). The terminal block is designed to terminate the circuit feed (HOT and NEUTRAL) and distribute the controlled circuits (LOAD) to the fixtures. The module connects to the terminal block and performs dimming control of eight incandescent, magnetic low voltage, neon, cold cathode, or dimmable 2-wire fluorescent lighting loads. The maximum load is 16 amps for any controlled circuit, limited to 16 amps total per module. The unit requires 120VAC 60 Hz, 1 phase input voltage. An oversize heat sink dissipates heat efficiently. There are LEDs on the module to indicate communication to a Cresnet
network, input power to the module, and
output power to the load.

Industry Compliance

This product is Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc.
NOTE: Modules and terminal blocks must be installed into the lowest available spaces and continue toward the top of the enclosure.
Terminal Block & Module Locations (Single-wide Enclosure)
GROUNDING
TERMINAL
BLOCK
TERMINAL
BLOCK
MODULE
Terminal Block & Module Locations (Double-wide Enclosure)
(E103692)
TERMINAL BLOCK
(LEFT)
MODULE
TERMINAL BLOCK
(RIGHT)

Installation

Terminal block and module must be mounted into a Crestron Automation Enclosure by a licensed electrician, in accordance with all national and local codes.
CAUTION: This equipment is for indoor use only and needs to be air-cooled. Mount in a well­ventilated area. The ambient temperature must be 32°F to 104°F (0°C to 40°C). The relative humidity must be 0% to 90% (non-condensing).
Terminal blocks are installed along the left side of single­wide enclosures and along the outside edges (left and right sides) of double-wide enclosures. Modules are installed along the right side of single-wide enclosures and side-by-side in the center of double-wide enclosures. When installing modules and terminal blocks in a double­wide enclosure, be sure to invert units on the right side so that they can be properly wired. Refer to the illustrations shown in the next column when considering the location of terminal blocks and modules within an enclosure.
Crestron Electronics, Inc. Installation Guide – DOC. 5985B
15 Volvo Drive Rockleigh, NJ 07647 (2002067) Tel: 888.CRESTRON 05.05 Fax: 201.767.7576 Specifications subject to www.crestron.com change without notice.
GROUNDING TERMINAL BLOCKS
Terminal Block & Module Crestron CLT- & CLX-1DIM8
NOTE: Unless otherwise indicated, the lighting system specified in this guide is modular, requiring assembly in the field by the contractor and/or electrician.
If you require a UL Listed panel, Crestron offers this service through its UL Listed panel shop. This includes complete in factory system configuration and assembly by Crestron for an additional 10% charge.

Terminal Block Installation and Field Wiring

1. Use the two supplied self-tapping pan Phillips screws (8B x ¼ length) to secure the terminal block and the appropriate (left or right) wiring label to the Crestron Automation Enclosure. The wiring label lies beneath the terminal block as shown in the two wiring diagrams on this page.
NOTE: Both left and right wiring labels are provided. The left-side labels are common for both single and double-wide enclosures. The right-side labels are only used in double-wide enclosures since the modules and terminal blocks along the right side must be inverted when mounting.
does not trip and that the proper lighting loads are energized.
Wiring Diagram of the Terminal Block to the Feed and Load(s)(Single-wide and Left Side Double-wide Enclosures)
BYPASS JUMPER
HOT
(FROM 15
OR 20 AMP
CIRCUIT
BREAKER)
NEUTRAL
GND
TO
LOAD(S)
GROUNDING
TERMINAL
BLOCK
AREA FOR
MODULE
LOCATION
LABEL
CAUTION: Bypass jumpers are provided to allow testing of circuits and to protect the module during installation. When properly secured by nine screws, the jumper on the black and red section of the terminal block shorts the hot to dim (1 – 8) so that all circuits are energized. Furthermore, the jumper on the white section of the terminal block ties all neutrals together. Do not remove any bypass jumpers until all feed and load wiring has been completed, the circuit has been tested for electrical faults, and the module has been installed. Refer to “Module Installation” on next page.
NOTE: Use copper conductors only – rated 75°C
2. With the circuit breaker turned off, connect the circuit feed (HOT and NEUTRAL) and controlled circuit (LOAD) wires to the terminal block per the markings provided on the wiring label (as shown in the diagrams on this page). Terminal blocks accept one 14 - 10 AWG wire. Wires should be stripped to ½ inch. Tighten terminal blocks to 9 in-lbs. Do not over tighten.
3. Grounding terminal blocks are available in the cabinet for termination of ground wires. Tighten to 35 in-lbs. (14 – 10 AWG), 40 in-lbs. (8 AWG), or 45 in-lbs. (6 – 4 AWG).
4. Test the circuit for electrical faults by turning on the circuit breaker and checking that the breaker
LEFT SIDE
WIRING LABEL
TERMINAL
BLOCK
Wiring Diagram of the Terminal Block to the Feed and Load(s) (Right Side Double-wide Enclosures)
BYPASS JUMPER
GND
NEUTRAL
HOT
(FROM 15
OR 20 AMP
CIRCUIT
BREAKER)
GROUNDING
TERMINAL
BLOCK
TERMINAL
BLOCK
RIGHT SIDE
WIRING LABEL
AREA FOR
MODULE
LOCATION
LABEL
TO
LOAD(S)
2 Terminal Block & Module: CLT- & CLX-1DIM8 Installation Guide – DOC. 5985B