Crestron CLS-SLVS1, CLS-SLVS1W, CLS-SLVS1A, CLS-SLVS1B User Manual

CLW-SW1, SWS1, & SLVS1(W/A/B)

Introduction

Features and Functions

The CLW-SW1 (-SW1) is a stand-alone wall box switch that can also act as a Cresnet Crestron® control processor. The -SW1 includes two isolated, non-polarized Cresnet wires (plus a ground wire) for connecting to a Cresnet system over a twisted pair wire with shield.
The CLW-SW1 features a three-position mode selection switch. Refer to “Operation ” on page 5 for more information. In the absence of Cresnet communications, the switch can still be used to control a load.
The CLW-SWS1 (-SWS1) is similar to the -SW1 with the added capability of working with a slave unit (CLW-SLVS1) in a multi-switch / single circuit application.
The CLW-SLVS1 (-SLVS1) is a slave unit that when used in conjunction with the -SWS1 acts as an additional switch control point in a multi-switch / single circuit application. It does not connect to a Cresnet system and cannot be used without a -SWS1. The -SLVS1 does not have a mode selection switch and is not programmable. It emulates the operation of the -SWS1 to which it is connected unless the mode selection switch of the master is set to “OFF”.
These switches are available in white, almond, and black. White units are designated by part numbers ending in “W”. Almond units are designated by part numbers ending in “A”. Black units are designated by part numbers ending in “B”. Each switch can be covered with a decorative faceplate (not supplied).

Specifications

Following are specifications for the -SW1, -SWS1, and
-SLVS1.
CLW-SW1, CLW-SWS1, & CLS-SLVS1 Specifications
SPECIFICATION DETAILS
Power Requirements Line Power, 120 VAC, 60 Hz
Default Net ID SW1: 82
Switch Type Single-Pole, Single-Throw
Load Type Incandescent, Tungsten Halogen,
®
device that reports to a
SWS1: 83
Fluorescent / High Intensity Discharge (HID), Electronic Low Voltage, Magnetic Low Voltage, Neon / Cold Cathode, General Purpose Fan
CLW-SW1, CLW-SWS1, & CLS-SLVS1 Specifications (Continued)
SPECIFICATION DETAILS
2-Series Control System Update File
Load Ratings3
Incandescent / Tungsten Halogen
Magnetic Low Voltage4 -SW1: 1000VA/750W
Neon / Cold Cathode4 -SW1: 1000VA/750W
Electronic Low Voltage -SW1: 1000W
Fluorescent / High Intensity Discharge (HID)
General Purpose Fan -SW1: 3.0A
Minimum Load 40W / 0.5A
Operating Temperature and Humidity
Dimensions and Weight -SW1 and -SWS1:
1. The latest software versions can be obtained from the Crestron
2. Crestron 2-Series control systems include the AV2 and PRO2.
3. Refer to Derating Charts for Multigang Installations on page 3.
4. VA ratings are for input power to the transformer. If you do not
1,2
website. Refer to the NOTE following these footnotes.
Consult the latest Crestron Product Catalog for a complete list of 2-Series control systems.
know the input power requirement of the transformer, use the bulb’s wattage rating to determine proper rating.
Version 3.117 or later
-SW1: 1000W
-SWS1: 1000W
-SLVS1: N/A
-SWS1: 1000VA/750W
-SLVS1: N/A
-SWS1: 1000VA/750W
-SLVS1: N/A
-SWS1: 1000W
-SLVS1: N/A
-SW1: 8A
-SWS1: 8A
-SLVS1: N/A
-SWS1: 3.0A
-SLVS1: N/A
32°F to 104°F (0°C to 40°C ) 10 to 90% Relative Humidity (Non-Condensing)
Height: 4.13 in (10.48 cm) Width: 2.38 in (6.03 cm) Depth: 1.91 in (4.85 cm) Weight: 4.4 oz (0.61 kg)
-SLVS1: Height: 4.13 in (10.48 cm) Width: 1.75 in (4.45 cm) Depth: 1.91 in (4.85 cm) Weight: 3.6 oz (0.50 kg)
NOTE: Crestron software and any files on the website are for Authorized Crestron dealers and Crestron Authorized Independent Programmers (CAIP) only. New users may be required to register to obtain access to certain areas of the site (including the FTP site).
(Continued on next column)
Crestron Electronics, Inc. Installation Guide – DOC. 6251A
15 Volvo Drive Rockleigh, NJ 07647 2009753 Tel: 888.CRESTRON 07.06 Fax: 201.767.7576 Specifications subject to www.crestron.com change without notice.
CLW-SW1, SWS1, & SLVS1(W/A/B)
)
Physical Description
The -SW1 and -SWS1 contain one large pushbutton, a light emitting diode (LED) with software adjustable brightness*, and a three-position slider-switch, shown after this paragraph. Line voltage connections are made at the rear of the switch. Three Class 2 low voltage wires, located on the front of the switch, provide a Cresnet connection to a control system. The wires can be routed to the bottom of the unit for placement outside of the wall box. The -SLVS1 is similar to the -SW1 and -SWS1 but does not have the slider-switch or the Class 2 low voltage wires.
* LED brightness can only be adjusted through Crestron programming
software.
CLW-SW1/SWS1 (L) and CLW-SLVS1 (R) shown in white
Physical view of CLW-SW1/SWS1 (clockwise from top; Top, Side, and Front)
1.75 in
(4.45 cm)
Physical view of CLW-SLVS1 (clockwise from top; Top, Side, and Front)
1.75 in
(4.45 cm)
3.28 in
(8.32 cm)
3.81 in
(9.68 cm)
4.13 in
(10.48 cm)
1.91 in
(4.85 cm)
2.70 in
(6.86 cm
1.50 in
(3.81 cm)
The -SW1, -SWS1, and -SLVS1 mount in a standard wallbox and are covered using a decorative faceplate (not included).

Industry Compliance

This product is Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc.
2.38 in
(6.03 cm)
3.28 in
(8.32 cm)
3.81 in
(9.68 cm)
(10.48 cm)
4.13 in
1.91 in
(4.85 cm)
1.50 in
(3.81 cm)
2.70 in
(6.86 cm)
E239013
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
CAUTION: Changes or modifications not expressly approved by the manufacturer responsible for compliance could void the user’s authority to operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning
2 Stand Alone Wall Box Switch: CLW-SW1, SWS1, & SLVS1 Installation Guide – DOC. 6251A
CLW-SW1, SWS1, & SLVS1(W/A/B)
the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and
receiver.
Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV
technician for help.

Important Notes

Read before installation.
Codes: Install in accordance with all local and national electrical codes.
Alternate wiring methods may be used for the Class 2 wiring connection. The 2002 National Electrical Code (Article 725-55) prohibits Class 2 conductors of the -SW1, -SWS1, and -SLVS1 to occupy the same outlet box as the power conductors. The exception is Part D of Section
725.55 of the 2002 National Electrical Code, which allows a device’s power conductors to be installed near (0.25 inch minimum spacing) associated Class 2 conductors in the same outlet box. Consult the 2002 National Electrical Code Handbook and your local electrical inspector before proceeding.
Do not use the supplied butt-splice connectors if the Class 2 conductors are to be installed in the wallbox with the power conductors. Use approved connectors (supplied by others) to make Class 2 connections inside the wallbox.
recommends using 3 ½” deep wallboxes. Several devices can be installed in one wall box (multigang). This requires the removal of side sections (shown below) and the derating of the switching device. For a smooth appearance, one­piece multigang faceplates (not supplied) can be installed.
Other Switch Devices: Mechanical 3- or 4-way switches will not work with the -SW1, -SWS1, or -SLVS1.
Spacing: If mounting one device above another, leave at least 4 ½” vertical space between them.

Multigang Installations

In multigang installations, several controls are grouped horizontally in one wallbox. For a smooth appearance, one-piece multigang faceplates (not supplied) can be installed.
1. When combining controls in a wallbox, remove inner side sections prior to wiring (refer to the following figure).
Inner Sections of Multiganged Switches
REMOVE INNER SECTIONS
CAUTION: TO REDUCE THE RISK OF
OVERHEATING AND POSSIBLE DAMAGE TO OTHER EQUIPMENT, DO NOT INSTALL TO CONTROL A RECEPTACLE.
Wiring: Use copper wire only. For supply connection, use wires rated for at least 75°C.
Load Type: The -SW1, -SWS1, and -SLVS1 are designed for use with permanently installed incandescent, fluorescent (non-dimmable), low voltage, neon/cold cathode, HID, general purpose fan, or tungsten halogen lighting.
Temperature: The -SW1, -SWS1, and -SLVS1 are designed to be used where temperatures are between 32° to 104°F (0° to 40°C).
Wallboxes: Devices mount in standard
The load capacity must also be derated. The following charts provide derating information for various applications.
Derating Information for Incandescent, Tungsten Halogen, and Electronic Low Voltage Applications
Part Number No Side
-SW1 1000W 600W 400W
-SWS1 1000W 600W 400W
-SLVS1 No Derating Necessary
DO NOT REMOVE OUTER SECTIONS
Removed
One Side Removed
Two Sides
Removed
wallboxes. For easy installation, Crestron
Installation Guide – DOC. 6251A Stand Alone Wall Box Dimmer: CLW-SW1, SWS1, & SLVS1 3
CLW-SW1, SWS1, & SLVS1(W/A/B)
Derating Information for Magnetic Low Voltage and Neon/Cold Cathode Applications
Part
Number
-SW1
-SWS1
-SLVS1
* VA ratings are for input power to the transformer. If you do not
know the input power requirement of the transformer, use the bulb’s wattage rating to determine proper rating.
Derating Information for Fluorescent/HID Applications
Part
Number
-SW1
-SWS1
-SLVS1
Derating Information for General Purpose Fans
Part
Number
-SW1
-SWS1
-SLVS1
No Side
Removed
1000VA/750W 600VA/450W 400VA/300W
1000VA/750W 600VA/450W 400VA/300W
No Side
Removed
8A 5A 3A
8A 5A 3A
No Side
Removed
3A 3A 3A
3A 3A 3A
*
One Side Removed
No Derating Necessary
One Side Removed
No Derating Necessary
One Side Removed
No Derating Necessary
Two Sides
Removed
Two Sides
Removed
Two Sides
Removed
2. To remove a side section, bend the side section back and forth with a pair of pliers until the section breaks off from the mounting plate. Use a file or sandpaper to remove any excess metal.

Prewire for Master Application

Each device has two Class 2 low voltage wires (plus a ground wire) that provide a Cresnet connection over shielded twisted-pair to a Crestron control system. These wires are routed to the bottom of the device for connection outside of the wallbox. The low voltage wires are pulled from each device location to the Crestron control system or a Crestron connection block device. Use #22 AWG, twisted, shielded, 2-conductor wire. Wiring can be daisy chained, T-tapped, or home run back to the control system. Refer to the following wiring diagram.
NOTE: The GRAY (Cresnet) wires are not polarized. These wires can be connected to either the Y or Z line on a Cresnet port.
NOTE: The BLACK wire (Cresnet ground) should not be grounded with the GREEN (Ground) wire on the
-SW1/-SWS1.
NOTE: Crestron recommends using Cresnet-DM cable for connecting the -SW1 and -SWS1 to the Cresnet network.

Installation

WARNING: Turn off power at the circuit breaker. Installing with power on can result in serious personal injury and damage to the device.
NOTE: The -SW1, -SWS1 require a neutral wire for operation. If no neutral is present, contact a licensed electrician for installation, otherwise the device will not work.
NOTE: The -SWS1 must be installed in the same wallbox that contains the connections to the load.
NOTE: New installations should be checked for short circuits prior to installing the -SW1, -SWS1, or -SLVS1. With power off, close the circuit and restore power. If the load does not work or a breaker trips, check and correct the wiring or fixture (if necessary). Install the -SW1,
-SWS1, or -SLVS1 only when the short is no longer present. The warranty is void if the -SW1, -SWS1, or
-SLVS1 is installed and operated with a shorted load.
When installing a -SW1 or a -SWS1 without a slave, follow the instructions in “Wiring a -SW(S)1 (No Slaves)” below. If wiring a -SWS1 with a -SLVS1, refer to “Wiring a -SWS1 with One or More
-SLVS1s” on the next page.
Wiring Diagram of CLW device to Cresnet

Wiring a -SW(S)1 (No Slaves)

The following describes the installation of a stand-alone
-SW1 or -SWS1.
1. Turn power off at the circuit breaker.
2. Pull Class 2 low voltage wires through a hole in the drywall located outside of the electrical box, to the Crestron control system or a Crestron connection block device. Leave wires outside of the wallbox for connection to the -SW1 or
-SWS1.
NOTE: Alternate wiring methods may be used for the Class 2 wiring connection. Refer to
4 Stand Alone Wall Box Switch: CLW-SW1, SWS1, & SLVS1 Installation Guide – DOC. 6251A
CLW-SW1, SWS1, & SLVS1(W/A/B)
section 725-55, Part D of the 2002 National Electric Code.
3. Wire the switch as shown in Figure 1 on page 8.
NOTE: The RED (Load) and BLACK (Hot) wires are #14 AWG. The BLUE (Slave) and WHITE (Neutral) wires are #18 AWG. The GREEN (Ground) wire is #16 AWG. The GRAY (Cresnet) wires are #22 AWG. The BLACK wire (Cresnet ground) paired with the GRAY (Cresnet) wires is #22 AWG.
NOTE: Since the -SWS1 is installed without a
-SLVS1, the BLUE lead (Slave) should be capped.
Other Wiring
For another scenario that may be encountered during installation, refer to Figure 2 on page 8.
4. Splice the gray wires of the -SW1 or -SWS1 to the Class 2 low voltage wires connected to the Crestron control system or a Crestron connection block device. Push the wires and the splices into a hole in the drywall to provide the necessary separation.
5. Push all power wires back into the wallbox and fasten the device to the wallbox with the provided screws.
6. Attach decorative faceplate.
7. Restore power at the circuit breaker.
Wiring a -SWS1 with One or More
-SLVS1s
NOTE: The -SWS1 must be installed in the same wallbox that contains the connections to the load.
The following describes installation of a -SWS1 master with a -SLVS1 slave.
1. Turn power off at the circuit breaker.
2. Pull Class 2 low voltage wires through a hole in the drywall located outside of the electrical box, to the Crestron control system or a Crestron connection block device. Leave wires outside of the wallbox for connection to the -SW1 or
-SWS1.
3. Wire the switches as shown in Figure 3 on page 8.
NOTE: Do not connect the BLUE (Slave) wire to the Black (Hot) or RED (Load) wires.
NOTE: The RED (Load) and BLACK (Hot) wires are #14 AWG. The BLUE (Slave) and WHITE (Neutral) wires are #18 AWG. The GREEN (Ground) wire is #16 AWG. The GRAY (Cresnet) wires are #22 AWG. The BLACK wire (Cresnet ground) paired with the GRAY (Cresnet) wires is #22 AWG.
NOTE: If a -SWS1 is installed without a
-SLVS1, the BLUE lead (Slave) should be capped.
NOTE: The WHITE (Neutral) connection on the -SLVS1 is optional and is only required for operation of the LED. If the neutral is not available, the white lead should be capped off.
4. Splice the gray wires of the -SWS1 to the Class 2 low voltage wires connected to the Crestron control system or a Crestron connection block device. Push the wires and the splices into a hole in the drywall to provide the necessary separation.
5. Push all power wires back into the wallbox and fasten the devices to their respective wallboxes with the provided screws.
6. Attach decorative faceplates.
7. Restore power at the circuit breaker.

Operation

The -SW1, -SWS1, and -SLVS1 have one large pushbutton. The -SW1 and -SWS1 also have a three­position mode selection switch. The function of the pushbutton is determined by the position of the mode selection switch. Refer to the following diagram.
NOTE: The -SLVS1 does not have a mode selection switch. It emulates the operation of the -SWS1 to which it is connected unless the mode selection switch of the master is set to “OFF”.
NOTE: Alternate wiring methods may be used for the Class 2 wiring connection. Refer to section 725-55, Part D of the 2002 National Electric Code.
Installation Guide – DOC. 6251A Stand Alone Wall Box Dimmer: CLW-SW1, SWS1, & SLVS1 5
CLW-SW1, SWS1, & SLVS1(W/A/B)
h
Buttons of CLW-SW1, -SWS1, and -SLVS1

Setup & Programming

Required Software

Button
Mode Selection Switc (-SW1 & -SWS1 Only)
OFF
When the mode selection switch is in the “OFF” position, the pushbutton will not have any function and the load is disconnected from the power source. This must be used when changing light bulbs to ensure that the load is fully disconnected from power.
ADJ
When the switch is in the ADJ position, pressing and holding the pushbutton will set a delay time for deactivating the load when the switch is in the PRE position. To set the delay time, press and hold the pushbutton for the desired amount of time delay and release. When the pushbutton is released, the LED will flash three times to confirm the time delay setting. When done, return the switch to the PRE position.
Software
TASK REQUIRED SOFTWARE VERSION
Program control system to operate CLW-SW1.
Upload program and firmware.
Program with simple wizards for lighting systems using a CLW-SW1 (optional but recommended).
SIMPL™ Windows® version
2.07.32 or later with SIMPL+ Cross Compiler version 1.1 or later and Library update 387 or later; Also requires Crestron Database version 18.1.5 or later.
Crestron Toolbox 1.02.29 or later.
Crestron D3 Pro™ version 2.1.7 or later with D3 Pro Templates version 2.0.1 or later. Refer to software release notes or Crestron website for other required Crestron software packages.

Setup

The Net ID of the CLW-SW1 has been factory set to 82. The Net IDs of multiple CLW-SW1 devices in the same system must be unique. Net IDs are changed from a personal computer (PC) via the Crestron Toolbox. When setting the Net ID, the Net ID of each unit must match an ID code specified in the SIMPL Windows program.
For more details, refer to the Crestron Toolbox help file.
NOTE: If a time delay is not set, the delayed-off feature is disabled by default.
PRE
When the switch is in the PRE position, the load can be manually activated and deactivated with the pushbutton. Pressing the pushbutton will deactivate the load after a delay that was set when the switch was in the ADJ mode. During the delay, the LED will flash. Tapping the pushbutton during the delay will deactivate the load without a delay.
NOTE: The device may be warm to the touch during operation. This is normal.

D3 Pro

Crestron D3 Pro Software provides all the tools necessary to create a complete Crestron Lighting System for residential applications. The lighting system includes the control system program, touchpanel screens and keypad programming, documentation, and real-time lighting adjustment capabilities. As with all Crestron software, the D3 Pro software provides extensive right-click and drag­and-drop functionality, in addition to convenient keyboard shortcuts for frequently used functions and commands.
For additional details, download D3 Pro from the Crestron website and examine the extensive help file.

SIMPL Windows

SIMPL Windows is Crestron’s premier software for programming Crestron control systems.
NOTE: While SIMPL Windows can be used to program the CLW-SW1, it is recommended to use D3 Pro for configuring a Crestron lighting system.
In Configuration Manager, incorporate a CLW-SW1 into the system by dragging the CLW-SW1 from the
6 Stand Alone Wall Box Switch: CLW-SW1, SWS1, & SLVS1 Installation Guide – DOC. 6251A
CLW-SW1, SWS1, & SLVS1(W/A/B)
Lighting | Wall Dimmers/Switches (Cresnet CLW Series) folder of the Device Library and dropping it in the System Views. Double click a device to open the “Device Settings” window and change the Net ID if required. The ID code specified in the SIMPL Windows program must match the Net ID of each unit.
In Programming Manager, assign signal names to program the CLW-SW1 to operate with the control system.
For additional details, download SIMPL Windows from the Crestron website and examine the extensive help file.
Installation Guide – DOC. 6251A Stand Alone Wall Box Dimmer: CLW-SW1, SWS1, & SLVS1 7
CLW-SW1, SWS1, & SLVS1(W/A/B)

Appendix: Wiring Diagrams

Following are wiring diagrams for circuits that may be found when installing a switch:

Stand-Alone Installations

Figure 1: Wiring a CLW-SW(S)1
To continue a circuit past a switched light fixture to one or more duplex receptacles, connect the switch as shown in the following diagram.
Figure 2: Adding a Duplex Receptacle Past a Switched Light Fixture

Master-Slave Installation

Figure 3: Wiring a CLW-SW1 with a CLW-SLVS1
8 Stand Alone Wall Box Dimmer: CLW-SW1, SWS1, & SLVS1 Installation Guide – DOC. 6251A
CLW-SW1, SWS1, & SLVS1(W/A/B)

Return and Warranty Policies

Merchandise Returns / Repair Service

1. No merchandise may be returned for credit, exchange, or service without prior authorization from CRESTRON. To obtain warranty service for CRESTRON products, contact an authorized CRESTRON dealer. Only authorized CRESTRON dealers may contact the factory and request an RMA (Return Merchandise Authorization) number. Enclose a note specifying the nature of the problem, name and phone number of contact person, RMA number, and return address.
2. Products may be returned for credit, exchange, or service with a CRESTRON Return Merchandise Authorization (RMA) number. Authorized returns must be shipped freight prepaid to CRESTRON, 6 Volvo Drive, Rockleigh, N.J. or its authorized subsidiaries, with RMA number clearly marked on the outside of all cartons. Shipments arriving freight collect or without an RMA number shall be subject to refusal. CRESTRON reserves the right in its sole and absolute discretion to charge a 15% restocking fee, plus shipping costs, on any products returned with an RMA.
3. Return freight charges following repair of items under warranty shall be paid by CRESTRON, shipping by standard ground carrier. In the event repairs are found to be non-warranty, return freight costs shall be paid by the purchaser.

CRESTRON Limited Warranty

CRESTRON ELECTRONICS, Inc. warrants its products to be free from manufacturing defects in materials and workmanship under normal use for a period of three (3) years from the date of purchase from CRESTRON, with the following exceptions: disk drives and any other moving or rotating mechanical parts, pan/tilt heads and power supplies are covered for a period of one (1) year; touchscreen display and overlay components are covered for 90 days; batteries and incandescent lamps are not covered.
This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer. Purchasers should inquire of the dealer regarding the nature and extent of the dealer's warranty, if any.
CRESTRON shall not be liable to honor the terms of this warranty if the product has been used in any application other than that for which it was intended, or if it has been subjected to misuse, accidental damage, modification, or improper installation procedures. Furthermore, this warranty does not cover any product that has had the serial number altered, defaced, or removed.
This warranty shall be the sole and exclusive remedy to the original purchaser. In no event shall CRESTRON be liable for incidental or consequential damages of any kind (property or economic damages inclusive) arising from the sale or use of this equipment. CRESTRON is not liable for any claim made by a third party or made by the purchaser for a third party.
CRESTRON shall, at its option, repair or replace any product found defective, without charge for parts or labor. Repaired or replaced equipment and parts supplied under this warranty shall be covered only by the unexpired portion of the warranty.
Except as expressly set forth in this warranty, CRESTRON makes no other warranties, expressed or implied, nor authorizes any other party to offer any warranty, including any implied warranties of merchantability or fitness for a particular purpose. Any implied warranties that may be imposed by law are limited to the terms of this limited warranty. This warranty statement supersedes all previous warranties.
Trademark Information All brand names, product names, and trademarks are the sole property of their respective owners. Windows is a registered trademark of Microsoft Corporation. Windows95/98/Me/XP and WindowsNT/2000 are trademarks of Microsoft Corporation.
Installation Guide – DOC. 6251A Stand Alone Wall Box Switch: CLW-SW1, SWS1, & SLVS1 9
CLW-SW1, SWS1, & SLVS1(W/A/B)
This page is intentionally left blank.
10 Stand Alone Wall Box Switch : CLW-SW1, SWS1, & SLVS1 Installation Guide – DOC. 6251A
Loading...