iLux
®
Integrated Lighting Systems w/infiNET
™
Introduction
Features and Functions
The iLux® units, CLSI-C6RF and CLSI-C6MRF, are
wall-mounted complete integrated lighting systems that can
function as standalone devices and/or be part of a Crestron®
solution total control system network (Cresnet®). The units
are functionally identical except that the CLSI-C6MRF
includes a built-in motion sensor.
CLSI-C6MRF with Cover Open (Shown in Almond)
Specifications
Following are specifications for the iLux units.
CLSI-C6RF & CLSI-C6MRF Specifications
SPECIFICATION
Power Requirements Line Power, 230 VAC, 50/60Hz
Load Ratings*
Max load per channel
Min load per channel
Max load per unit
Load Types* Incandescent, magnetic low voltage,
800 W/VA
(3.5 Amps @ 230 VAC) expandable
via Expansion Modules
(sold separately)
25 W/VA
(0.108 Amps @ 230 VAC)
2200W/VA
(10 Amps @ 220 VAC)
2300W/VA
(10 Amps @ 230 VAC)
2400W/VA
(10 Amps @ 240 VAC)
neon/cold cathode,
2-wire dimmable fluorescent, and
non-dim lighting (also: electronic low
voltage, 3- and 4-wire fluorescent,
high-inrush switching, and 277V via
CLS-EXP series expansion modules;
sold separately)
(Continued in next column)
DETAILS
CLSI-C6RF & CLSI-C6MRF Specifications (Continued)
SPECIFICATION
Cresnet Power Available
for Local Devices
IR Receiver For use with Crestron IR remote
RF Wireless
RF Transceiver
Range (typical)
Gateway
Motion Detector
(CLSI-C6MRF only)
Type
Range
Default MNET ID 1F
Environmental
Temperature
Humidity 10% to 90% RH
Overall Dimensions:
Height
Width
Depth
Weight 647 g (23 oz)
* Additional load types can be controlled and load ratings can be increased via
optional CLSI-EXP expansion modules. Refer to the Crestron Web site
www.crestron.com for details.
10 W Max. External power supplies
sold separately.
(sold separately).
2-way RF, 2.4 GHz ISM Channels
11-26 (2400 to 2483.6 MHz), IEEE
802.15.4 compliant
46 meters (150 feet) indoor, 76
meters (250 feet) outdoor; subject
to site-specific conditions; range is
increased by adding additional
devices or C2NI-MNETRPT
repeater
Requires a C2N-MNETGW RF
gateway
Infrared
6 to 9 meters at 1.2 meter
elevation
(20 to 30 feet at 4-foot elevation)
0° to 40° C (32° to 104° F)
(non-condensing)
114 mm (4.48 in)
226 mm (8.89 in)
63 mm (2.47 in) for CLSI-C6
66 mm (2.60 in) for CLSI-C6M
DETAILS
Physical Description
The following illustration shows the overall dimensions for
the CLSI-C6RF and CLSI-C6MRF.
CLSI-C6MRF Overall Dimensions
Crestron Electronics, Inc. Installation Guide – DOC. 6417B
15 Volvo Drive Rockleigh, NJ 07647 (2013967)
Tel: 888.CRESTRON 09.10
Fax: 201.767.7576 Specifications subject to
www.crestron.com change without notice.
iLux™ Integrated Lighting Systems w/infiNET
™
Regulatory Compliance
This product is listed to applicable UL Standards and
requirements by Underwriters Laboratories Inc.
As of the date of manufacture, the CLS-C6RF has been
tested and found to comply with specifications for CE
marking and standards per EMC and Radiocommunications
Compliance Labelling.
Important Notes
Read before installation.
• Codes: Install in accordance with all local and
national electrical codes.
• Wiring: Use copper wire only. For supply
connections, use wires rated for at least 75°C.
• Lighting Load Types: incandescent, magnetic
low voltage, neon/cold cathode, dimmable
2-wire fluorescent, and non-dim lighting
(also: electronic low voltage, 3-wire and 4-wire
fluorescent, high inrush switching, and 277V via
expansion modules; sold separately).
• Temperature: The iLux units are designed for use
where temperatures are between 0° to 40° C
(32° to 104° F).
• Wallboxes: The iLux units mount in standard
wallboxes; 89 mm (3.5 inches) deep, minimum.
• Make certain that power is turned off, and
ensure that there is at least 114 mm (4.5 inches) of
open space above and below the electrical box
location to permit heat dissipation.
• Four 22 mm (7/8-inch) pan head Phillips screws
(supplied)
If the planned configuration includes connection to shade
controllers, keypads, and/or a Crestron 2-Series control
system, the following items are also required. Refer to the
latest version of the Crestron CLSI-C6RF iLux Integrated
Lighting System w/infiNET Operations Guide (Doc. 6418),
for detailed configuration options.
• Cresnet network cable(s) (not supplied)
• Terminal block connector(s) (two supplied)
Check that any required Cresnet wiring has been installed
and verified. Then, use the following procedure to install
the iLux unit (CLSI-C6MRF is shown in the illustrations).
1. Feed the wires (power line from the distribution
panel, load wires, plus any required Cresnet
cables) through the holes in the wallbox. Then
install the box in the wall.
2. Hold the rear of the CLSI-C6MRF unit and
remove the front panel and cover assembly by
carefully pulling out and up from the bottom edge.
Installation
WARNING: Turn off power at the distribution panel
circuit breaker. Installing with power on can result in
serious personal injury and damage to the device.
CAUTION: To reduce the risk of overheating and possible
damage to other equipment, do not install to control a
receptacle or a motor-operated appliance.
NOTE: The CLSI-C6RF units require a neutral wire for
operation. If no neutral is present, contact a licensed
electrician for installation.
The following tools/hardware are required for installation.
• An electrical wallbox, 89 mm (3.5 inches) deep,
minimum (not supplied).
• Phillips torque screwdriver (not supplied)
2 • iLux™ Integrated Lighting Systems w/infiNET™: CLSI-C6RF & CLSI-C6MRF Installation Guide – DOC. 6417B
3. Remove the control panel overlay from the unit (it
is held in place by small tabs and lifts off) to
reveal the upper mounting screw holes.
4. Refer to the following diagram for connection of
the AC wiring. All wires to be inserted in the
screw terminals should be stripped 11 mm
(7/16-inch), and screws should be tightened to
between 0.90 to 1.13 Newton meters (8 to 10
in.-lbs). The maximum wire size is 4.00 mm
(12 AWG).
5. Connect each load wire to the corresponding
LOAD terminals on the unit, connect the power
line hot wire from the circuit breaker to the HOT
terminal on the unit, connect all neutral wires to
the NEUTRAL terminal on the unit, and connect
all ground wires to the
unit.
(ground) terminal on the
2