Creston CLSI-C6RF, CLSI-C6MRF INSTALLATION

iLux
®
Integrated Lighting Systems w/infiNET

Introduction

Features and Functions

The iLux® units, CLSI-C6RF and CLSI-C6MRF, are wall-mounted complete integrated lighting systems that can function as standalone devices and/or be part of a Crestron® solution total control system network (Cresnet®). The units are functionally identical except that the CLSI-C6MRF includes a built-in motion sensor.
CLSI-C6MRF with Cover Open (Shown in Almond)

Specifications

Following are specifications for the iLux units.
CLSI-C6RF & CLSI-C6MRF Specifications
SPECIFICATION
Power Requirements Line Power, 230 VAC, 50/60Hz
Load Ratings* Max load per channel
Min load per channel
Max load per unit
Load Types* Incandescent, magnetic low voltage,
800 W/VA (3.5 Amps @ 230 VAC) expandable via Expansion Modules (sold separately)
25 W/VA (0.108 Amps @ 230 VAC)
2200W/VA (10 Amps @ 220 VAC)
2300W/VA (10 Amps @ 230 VAC)
2400W/VA (10 Amps @ 240 VAC)
neon/cold cathode, 2-wire dimmable fluorescent, and non-dim lighting (also: electronic low voltage, 3- and 4-wire fluorescent, high-inrush switching, and 277V via CLS-EXP series expansion modules; sold separately)
(Continued in next column)
CLSI-C6RF & CLSI-C6MRF Specifications (Continued)
SPECIFICATION
Cresnet Power Available for Local Devices
IR Receiver For use with Crestron IR remote
RF Wireless RF Transceiver
Range (typical)
Gateway
Motion Detector (CLSI-C6MRF only) Type Range
Default MNET ID 1F
Environmental Temperature
Humidity 10% to 90% RH
Overall Dimensions: Height
Width Depth
Weight 647 g (23 oz)
* Additional load types can be controlled and load ratings can be increased via
optional CLSI-EXP expansion modules. Refer to the Crestron Web site www.crestron.com for details.
10 W Max. External power supplies sold separately.
(sold separately).
2-way RF, 2.4 GHz ISM Channels 11-26 (2400 to 2483.6 MHz), IEEE
802.15.4 compliant 46 meters (150 feet) indoor, 76
meters (250 feet) outdoor; subject to site-specific conditions; range is increased by adding additional devices or C2NI-MNETRPT repeater
Requires a C2N-MNETGW RF gateway
Infrared 6 to 9 meters at 1.2 meter elevation (20 to 30 feet at 4-foot elevation)
0° to 40° C (32° to 104° F)
(non-condensing)
114 mm (4.48 in) 226 mm (8.89 in) 63 mm (2.47 in) for CLSI-C6 66 mm (2.60 in) for CLSI-C6M

Physical Description

The following illustration shows the overall dimensions for the CLSI-C6RF and CLSI-C6MRF.
CLSI-C6MRF Overall Dimensions
Crestron Electronics, Inc. Installation Guide – DOC. 6417B
15 Volvo Drive Rockleigh, NJ 07647 (2013967) Tel: 888.CRESTRON 09.10 Fax: 201.767.7576 Specifications subject to www.crestron.com change without notice.
iLux™ Integrated Lighting Systems w/infiNET

Regulatory Compliance

This product is listed to applicable UL Standards and requirements by Underwriters Laboratories Inc.
As of the date of manufacture, the CLS-C6RF has been tested and found to comply with specifications for CE marking and standards per EMC and Radiocommunications Compliance Labelling.

Important Notes

Read before installation.
Codes: Install in accordance with all local and national electrical codes.
Wiring: Use copper wire only. For supply connections, use wires rated for at least 75°C.
Lighting Load Types: incandescent, magnetic low voltage, neon/cold cathode, dimmable 2-wire fluorescent, and non-dim lighting (also: electronic low voltage, 3-wire and 4-wire fluorescent, high inrush switching, and 277V via expansion modules; sold separately).
Temperature: The iLux units are designed for use where temperatures are between 0° to 40° C (32° to 104° F).
Wallboxes: The iLux units mount in standard wallboxes; 89 mm (3.5 inches) deep, minimum.
Make certain that power is turned off, and ensure that there is at least 114 mm (4.5 inches) of open space above and below the electrical box location to permit heat dissipation.
Four 22 mm (7/8-inch) pan head Phillips screws (supplied)
If the planned configuration includes connection to shade controllers, keypads, and/or a Crestron 2-Series control system, the following items are also required. Refer to the latest version of the Crestron CLSI-C6RF iLux Integrated Lighting System w/infiNET Operations Guide (Doc. 6418), for detailed configuration options.
Cresnet network cable(s) (not supplied)
Terminal block connector(s) (two supplied)
Check that any required Cresnet wiring has been installed and verified. Then, use the following procedure to install the iLux unit (CLSI-C6MRF is shown in the illustrations).
1. Feed the wires (power line from the distribution panel, load wires, plus any required Cresnet cables) through the holes in the wallbox. Then install the box in the wall.
2. Hold the rear of the CLSI-C6MRF unit and remove the front panel and cover assembly by carefully pulling out and up from the bottom edge.

Installation

WARNING: Turn off power at the distribution panel circuit breaker. Installing with power on can result in serious personal injury and damage to the device.
CAUTION: To reduce the risk of overheating and possible damage to other equipment, do not install to control a receptacle or a motor-operated appliance.
NOTE: The CLSI-C6RF units require a neutral wire for operation. If no neutral is present, contact a licensed electrician for installation.
The following tools/hardware are required for installation.
An electrical wallbox, 89 mm (3.5 inches) deep, minimum (not supplied).
Phillips torque screwdriver (not supplied)
2 iLux™ Integrated Lighting Systems w/infiNET™: CLSI-C6RF & CLSI-C6MRF Installation Guide – DOC. 6417B
3. Remove the control panel overlay from the unit (it is held in place by small tabs and lifts off) to reveal the upper mounting screw holes.
4. Refer to the following diagram for connection of the AC wiring. All wires to be inserted in the screw terminals should be stripped 11 mm (7/16-inch), and screws should be tightened to between 0.90 to 1.13 Newton meters (8 to 10 in.-lbs). The maximum wire size is 4.00 mm (12 AWG).
5. Connect each load wire to the corresponding LOAD terminals on the unit, connect the power line hot wire from the circuit breaker to the HOT terminal on the unit, connect all neutral wires to the NEUTRAL terminal on the unit, and connect all ground wires to the unit.
(ground) terminal on the
2