Crescend Technologies P25XXHA3 User Manual

INSTALLATION AND OPERATING
MANUAL
P25 Series UHF
CONTINUOUS DUTY
POWER AMPLIFIER
Crescend Technologies
140 E. State Parkway
Schaumburg, IL 60173
Tel: 847-908-5400 Fax: 847-908-5408
sales@crescendtech.com
www.crescendtech.com
040003A010 Rev B
User Manual
040003A010 Rev B Page 2 of 25
User Manual
040003A010 Rev B Page 3 of 25
1 GENERAL DESCRIPTION
1.1 INTRODUCTION
This manual contains installation and operating information for the Crescend High Power Amplifier. The manual is organized into multiple sections as follows:
1 GENERAL DESCRIPTION .................................................................................................................... 3
1.1 INTRODUCTION .................................................................................................................. 3
1.2 PRODUCT DESCRIPTION ................................................................................................... 3
2 INSTALLATION ..................................................................................................................................... 5
2.1 INSTALLATION INSTRUCTIONS ......................................................................................... 5
2.2 INITIAL STARTUP ................................................................................................................ 6
3 OPERATING INFORMATION ............................................................................................................... 7
3.1 INTRODUCTION .................................................................................................................. 7
3.2 STATUS INDICATORS AND MONITOR CONNECTOR ...................................................... 7
3.3 DETAILED STATUS INDICATOR AND MONITOR CONNECTOR INFORMATION ............ 9
3.4 DIGITAL COMMUNICATION INTERFACE (RS232) ...........................................................13
3.5 POWER SET CONTROL .....................................................................................................17
4 TROUBLESHOOTING ..........................................................................................................................18
4.1 INTRODUCTION .................................................................................................................18
4.2 TROUBLESHOOTING .........................................................................................................18
4.3 RETURN FOR SERVICE PROCEDURES...........................................................................20
4.3.1 OBTAINING RMA ........................................................................................................20
4.3.2 REPACKAGING FOR SHIPMENT ..............................................................................20
5 MAINTENANCE ...................................................................................................................................21
5.1 INTRODUCTION .................................................................................................................21
5.2 PERIODIC MAINTENANCE .................................................................................................21
5.3 CLEANING AIR INLETS/OUTLETS .....................................................................................21
6 RF ENERGY EXPOSURE ....................................................................................................................22
6.1 RF ENERGY EXPOSURE AWARENESS, CONTROL INFORMATION, AND OPERATIONAL
INSTRUCTIONS FOR COMPLIANCE WITH FCC RF EXPOSURE LIMITS ........................................22
6.2 FEDERAL COMMUNICATION COMMISSION REGULATIONS .........................................22
6.3 RF EXPOSURE COMPLIANCE, CONTROL GUIDELINES AND OPERATING
INSTRUCTIONS ...................................................................................................................................22
1.2 PRODUCT DESCRIPTION
The Crescend Technologies High Power UHF RF power amplifier is designed for paging and other applications that use a single carrier constant envelope waveform. The amplifier is designed to be powered from either an external +48 VDC source or an optional internal AC power supply. Model
User Manual
040003A010 Rev B Page 4 of 25
GA amplifiers cover the 406.1-420 MHz band without retuning. Model HA amplifiers cover the 450-454MHz, 456-462.5375MHz, 462.7375-467.5375MHz, 467.7375-470 -470MHz band without retuning. Amplifier specifications are shown in Table 1-1. There are seven input ranges available as shown in Table 1-2. Closed loop power control is used to maintain a constant output power under varying voltage, signal input level, frequency and output load conditions. Several design features work to protect the amplifier under adverse conditions.
The amplifier is designed to fit into 5.25 inches (3RU) of vertical 19-inch rack space. The front panel includes LED indicators for monitoring status and alarm conditions. This information is also accessible via a monitor connector on the rear of the amplifier. The fan assembly draws ambient air in from the front and blows the air across the heat sink fins out the back of the amplifier.
NOTE: The manufacturer’s rated output power of this equipment (see Table 1-1) is specified
for single carrier operation using constant-envelope modulation. This equipment is NOT designed for multiple-carrier operation, nor is it intended to be used with non­constant envelope modulation waveforms.
Table 1-1 Amplifier Specifications
Specification
Value
Instantaneous Bandwidth
406.1-420 MHz (GA models), 450-454MHz, 456-
462.5375MHz, 462.7375-467.5375MHz, 467.7375-470 ­470MHz (HA models)
Output Power Range
25 W - 250 W
Input Impedance
50 Ohms
Output Impedance
50 Ohms
Table 1-2 Amplifier Input Power Ranges
Input Power Designator Code
Input Power Range
Nominal Gain (250W Output)
R2GA, R2HA
0.2 - 0.5 W
28.5 dB
R5GA, R5HA
0.5 - 1 W
25.0 dB
1GA. 1HA
1 - 2 W
22.0 dB
2GA, 2HA
2- 5 W
18.5 dB
5GA, 5HA
5 - 10 W
15.0 dB
10GA, 10HA
10 - 20 W
12.0 dB
20GA, 20HA
30 - 40 W
8.5 dB
User Manual
040003A010 Rev B Page 5 of 25
2 INSTALLATION
2.1 INSTALLATION INSTRUCTIONS
The amplifier is designed for installation in a rack that permits access to the rear of the unit for connection of RF and monitor/control cables, and DC power cables or AC line cord if the unit incorporates the internal AC power supply option. The amplifier must have a minimum of 3 inches of open space in front and to the rear of the chassis to allow adequate air flow and ventilation. If installed in a closed or multi-unit rack, the operating ambient temperature within the rack environment may be greater than the room ambient. The equipment installation must be compatible with the +60°C maximum temperature rating of the amplifier. Caution should be exercised when rack mounting the amplifier to avoid creation of a hazardous condition due to uneven mechanical loading. Avoid “top-heavy” or cantilever installations which may cause the equipment rack to become unbalanced. Consideration should be given to the connection of the equipment to the AC or DC supply circuit and the effect that overloading of the circuits might have on overcurrent protection and supply wiring. Consideration of the appropriate current rating (10A for 110-125VAC operation, 20A for +48VDC operation) should be used in addressing this concern. Caution should be exercised with supply connections which are not direct connections to the branch circuit (e.g. use of power outlet strips). Reliable grounding of rack-mounted equipment should always be maintained.
To install the amplifier, proceed as follows:
1. Mount the amplifier in equipment rack and secure in place.
2. Connect a properly sized 50 Ohm cable and load (antenna) to the RF OUT connector on rear of amplifier.
3. Connect the transceiver/exciter output to RF IN connector on rear of amplifier.
4. If monitoring of PA is desired, connect alarm cable to MONITOR connector on rear of amplifier module. See section 3 for more details about monitor pins.
5. Connect a ground cable to the rear panel stud of the amplifier. A UL Listed ground bonding conductor assembly is recommended, such as Harger p/n UBC61411/4KIT5, UBC61811/4KIT5, or UBC63211/4KIT5. These ground cable interfaces consist of Harger p/n 6-6R1 ring tongue lugs crimped to various lengths of Harger p/n 6XLPE133G/YS #6 AWG ground cable.
6. If the unit is the 48 VDC version, measure the DC output voltage of the external power supply. DC voltage should be +48 +/- 0.5VDC. Turn off the DC voltage.
NOTE:
Make sure power supply DC is well filtered and well behaved with minimal voltage
overshoot.
Keep DC cables as short as possible (recommend no greater than 2 feet) to
minimize inductive voltage transients.
Size DC cables properly to handle the load current to minimize voltage drop during
times of transmission when current draw is highest.
WARNING:
Turn off external primary DC power before connecting DC power cables. Connect positive primary power wire (+48VDC) to terminal marked +48VDC and
User Manual
040003A010 Rev B Page 6 of 25
negative primary power wire to GND terminal next to it on rear of amplifier.
7. Check your work before applying DC voltage to the system. Make certain all connections are tight and the DC wires are going to the correct terminals.
8. If the unit has the optional internal AC power supply: Connect an unpowered AC cord to AC plug on rear of amplifier.
9. Refer to Section 2.2 for initial start-up procedures.
2.2 INITIAL STARTUP
To perform the initial start-up, proceed as follows:
1. Check to ensure that all input and output cables are properly connected and tightened.
NOTE: Use high quality coaxial cable and connectors. Properly install all connectors for
reliability.
CAUTION: Before applying power, make sure that the input and output of the amplifier are
properly terminated in 50 ohms. Do not operate the amplifier without a load attached. Refer to Table 1-2 for input power requirements. Excessive input power will damage the amplifier.
NOTE: The output coaxial cable between the amplifier and antenna must be 50 Ohm cable
and adequately sized to handle the rated power level with additional stresses from high VSWR taken into account. The shield of the 50 Ohm coaxial cable must be connected to ground at the entrance of the building in which the equipment is installed. This should be done in accordance with applicable national electrical installation codes. In the U.S., this is required by Section 820.93 of the National Electrical Code, ANSI/NFPA 70.
2. Apply 48 VDC from your power supply or AC mains power (depending on whether amplifier has the optional internal AC power supply) to the amplifier with the supplied line cord. After a short delay, the fans will power on. Check that all fans are running.
3. Visually check the indicators on the front of the amplifier and verify the following:
a. The PWR ON indicator (green) is on. b. All other LED indicators (red and yellow) are off.
4. Set the external exciter power level so that it is within the specified input power range and apply the RF signal to the amplifier input port. The amplifier will deliver nominally 250W at the output connector. The green exciter drive status LED will illuminate when the RF drive is detected. This LED is meant to give the user a general indication that the exciter is active and is delivering output power when troubleshooting an alarm condition. However, it does not indicate that the minimum input power level has necessarily been reached.
5. Remove the RF input signal. The output power will drop to zero. Only the Power On indicator will be illuminated. The amplifier is ready to use.
User Manual
040003A010 Rev B Page 7 of 25
3 OPERATING INFORMATION
3.1 INTRODUCTION
This section contains general amplifier operating information
3.2 STATUS INDICATORS AND MONITOR CONNECTOR
The amplifier status indicators and alarms are described in Table 3-1 and Table 3-2.
Table 3-1 High Power UHF Amplifier Status LED Indicators
STATUS LED
FUNCTION
PWR ON
Green LED. Illumination indicates unit is powered on
EXCITER DRIVE
Green LED. Illumination indicates RF input power has been applied
CHECK FAN
Red LED. Illumination indicates low fan speed or a locked rotor
HIGH TEMP
Red LED. Activates when the amplifier exceeds a safe operating temperature. Unit shuts down until safe operating temperature returns
HIGH VSWR
Red LED. Activates when load VSWR > 3:1. Amplifier shuts down. Alarm active until RF input removed and reapplied
HIGH INPUT
Yellow LED. Illumination indicates RF input power exceeds safe level (~125%) of rated input power. Alarm active until RF input removed
LOW OUTPUT
Yellow LED. Can activate if power drops due to low gain or minimum specified input level is not applied
Table 3-2 Monitor Connector Description
PIN NO
NAME
DESCRIPTION
1
POWER CTL
Output Power Level Control. POWER CTL signal is pulled up internally to 10V and pulled down by POWER SET
potentiometer located on front panel. To ensure the full adjustment range of output power from 250W to 25W with POWER CTL signal, make sure POWER SET is turned fully clock wise (refer to section 3.5 for details).
Both POWER CTL analog input and POWER SET potentiometer can be disabled by digital communication interface if either “PS=***\r” or “PM=***\r” command is sent to the amplifier (refer to Table 3-7 in section 0 for details).
2
REV PWR
Reverse Power Voltage
3
GND
Ground Return
4
HI TEMP
Alarm - High Temperature Amplifier Shutdown
5
RXD
RS232 Interface Received Data
6
GND
Ground Return
User Manual
040003A010 Rev B Page 8 of 25
PIN NO
NAME
DESCRIPTION
7
HI INPUT
Alarm - RF Input Power Above Maximum Rating
8
CHECK FAN
Alarm - Low fan speed or locked rotor detected
9
PA FAULT
Alarm - Low Output Power, RF Input Power Above Maximum Rating, High Temperature Amplifier Shutdown, High VSWR or No Power Supply Voltage
10
FWD PWR
Forward Power Voltage
11
HI VSWR
Alarm - High VSWR
12
RF DRIVE
Minimum RF Input Drive Indicator
13
TXD
RS232 Interface Transmitted Data
14
GND
NOT FOR EXTERNAL CONNECTION - DO NOT USE
15
LOW PWR
Alarm - Low Output Power
Figure 3-1 DSUB-15 Connector Pin Numbers
Loading...
+ 16 hidden pages