2.5Amplifier Summary Alarm and Power Cutback Control10
3.1Introduction11
3.2Location of Status Indicators11
3.3Initial Start-Up12
General Description
Section 2
Installation
Section 3
General Operating Information
Page No.
Section 4
Principles of Operation
4.1Introduction13
4.2RF Input Signal13
4.3RF Output Load13
4.4Functional Description13
4.4.1Main RF Path13
4.4.2Loop Control13
4.4.3VSWR Protection13
4.4.4Thermal Protection13
4.5Amplifier Cooling13
Copyright Crescend Technologies2
040003A005 Rev 1
TABLE OF CONTENTS (Continued)
Section 5
Par. No.
5.1Introduction14
5.2Periodic Maintenance14
5.3Cleaning Air Inlets/Outlets14
5.4Test Equipment Required for Test15
5.5Performance Test15
6.1Introduction16
6.2Troubleshooting16
6.3Return for Service Procedure17
6.3.1Obtaining an RMA17
6.3.2Repackaging for Shipment17
Maintenance
Section 6
Troubleshooting
Page No.
Figure
1-1C7 Series Single Amplifier, Front View4
1-2C7 Series Single Amplifier, Rear View5
2-1FPR-5 Rack, Front Right View9
2-2C7 Series Amplifiers in Rack, Rear View10
3-1C7 Series Status Indicators, Front Panel11
5-1Amplifier Test Setup diagram15
2-1Summary Alarm Connection10
3-1C7 Series Amplifier Status Indicators11
5-1Periodic Maintenance14
5-2Test Equipment Required15
6-1Troubleshooting16
C7 Series Amplifier Functional Specifications6
Spurious and Harmonics
7
Copyright Crescend Technologies3
040003A005 Rev 1
1.GENERAL DESCRIPTION
1.1.INTRODUCTION
This manual contains information and procedures for installation, operation, and
maintenance of Crescend’s C7 Series Continuous Duty Power Amplifier. The manual is
organized into six sections as follows:
The Crescend Technologies C7 Series of RF power amplifiers are designed for trunking
and conventional repeater applications. Rack mountable and designed to accept a range
of input powers for a given rated output power, each amplifier covers a broad range of
frequencies without retuning. Closed loop power control is used to maintain a constant
output power under varying voltage, signal input, frequency and output load conditions.
Several design features work to protect the amplifier under adverse conditions.
Having the same features as our popular Crescend C5 models, the design of the C7
amplifiers allows for up to 5 amplifiers in 4U of rack space. Designed to be fully modular
and space efficient, the 5-pack series also provides continuous duty operation. Rack FPR-5
sold separately.
The C7 front panel (Figure 1-1) includes status LED indicators for DC and Alarm
conditions. RF Input, RF Output, DC and summary alarm connections are found on the
back of the amplifier (Figure 1-2).
Copyright Crescend Technologies4
040003A005 Rev 1
Figure 1-1.C7 Series Single Amplifier, Front View
Figure 1-2.C7 Series Single Amplifier, Rear View
1.3.FUNCTIONAL AND PHYSICAL SPECIFICATIONS
Functional and physical specifications for the C7 Series amplifiers are listed in Tables 1-1
and 1-2.
1.4.EQUIPMENT CHANGES
Crescend Technologies, Inc. reserves the right to make minor changes without notice,
including, but not necessarily limited to, component substitution and circuitry changes.
Such changes may or may not be incorporated in this manual, although it is our intention to
keep each manual as up-to-date as possible. To that end, we ask that you, our customer,
share information with us acquired in field situations, which might be of assistance to
another user.
Copyright Crescend Technologies5
040003A005 Rev 1
Table 1-1. C7 Series Amplifier Functional Specifications
Frequency Range:See Table 1-2 (Range Set at Factory)
Operating Voltage:+13.8 ±0.7 Vdc
Current Consumption:See Table 1-2
Duty Cycle:100%
Power Input:See Table 1-2 (Range Set at Factory)
Power Output (Single Carrier Operation):See Table 1-2 (Range Set at Factory)
Input Return Loss:-10 dB (Maximum)
Spurious & Harmonics:See Table 1-2
Input/Output Impedance:50 Ohms (Nominal)
Load VSWR Tolerance:VSWR Protected above 2.5:1 (Nominal)
Input/Output Connector:Type N Female
Vertical Mounting:7.0 in
Horizontal Mounting:3.4 in
Depth:19.0 in
Weight:10 lbs (4.6 kg) (Nominal)
Cooling Method:Fan Forced Air Over Heat Sink
Operating Temp. Range:-30 °C to +60 °C
Storage & Transport:-40 °C to +70 °C
Humidity:80% at +40 °C (Non-Condensing)
Altitude:10,000 Feet (Maximum)
INDICATORS
Front Panel Display:
DC ON (Green), LOW OUTPUT (Red),
HIGH VSWR (Red), OVER TEMP (Red)
SUMMARY ALARM
Alarm and Pins:
Summary of Low Output, High VSWR and
Over Temp Alarms
Copyright Crescend Technologies6
040003A005 Rev 1
Table 1-2. Frequency Ranges, Input/Output Power, Current, Spurious and Harmonics
Manufacturer’s Rated Output Power of this Equipment is for Single Carrier
Operation.
All specifications above apply at +13.8 ± 0.1 VDC operating voltage,
ambient temperature of 25°C ± 5°C.
Copyright Crescend Technologies7
040003A005 Rev 1
2.INSTALLATION
2.1.INTRODUCTION
This section contains installation recommendations, unpacking, inspection, and installation
instructions for the C7 Series of amplifiers. Carefully read all the material in this section
prior to equipment unpacking or installation. Also read and review the operating procedures
in Section 3 prior to installing the equipment. It is important that the licensee perform these
tasks correctly and in good faith. If applicable, carefully read Parts 73 and 74 of the Federal
Communications Commission (FCC) rules to determine how they apply to your installation.
2.2.ELECTRICAL SERVICE RECOMMENDATIONS
Crescend Technologies recommends that proper AC line conditioning and surge
suppression be provided on the primary AC input to the +13.8 VDC power source. All
electrical service should be installed in accordance with the National Electrical Code, any
applicable state or local codes, and good engineering practice. Special consideration
should be given to lightning protection of all systems in view of the vulnerability of most
transmitter sites to lightning. Lightning arrestors are recommended in the service entrance.
Straight, short ground runs are recommended. The electrical service must be well
grounded. Each amplifier should have its own circuit breaker.
2.3.UNPACKING AND INSPECTION
This equipment has been operated, tested and calibrated at the factory. Only in the event
of severe shocks or other mistreatment should any substantial readjustment be required.
Carefully open the container(s) and remove the amplifier module(s). Retain all packing
material that can be reassembled in the event that the unit must be returned to the factory.
CAUTION:
Exercise care in handling equipment during inspection to
prevent damage caused by rough or careless handling.
Visually inspect the amplifier module for damage that may have occurred during shipment.
Check for evidence of water damage, bent or warped chassis, loose screws or nuts, or
extraneous packing material in the connector or fans. Inspect the rear panel connector for
bent connector pins. If the equipment is damaged, a claim should be filed with the carrier
once the extent of any damage is assessed. We cannot stress too strongly the importance
of IMMEDIATE careful inspection of the equipment and the subsequent IMMEDIATE filing
of the necessary claims against the carrier if necessary. If possible, inspect the equipment
in the presence of the delivery person. If the equipment is damaged, the carrier is your first
area of recourse. If the equipment is damaged and must be returned to the factory, write or
phone for a return authorization. Crescend may not accept returns without a return
authorization. Claims for loss or damage may not be withheld from any payment to
Crescend, nor may any payment due be withheld pending the outcome thereof. WE
CANNOT GUARANTEE THE FREIGHT CARRIER’S PERFORMANCE.
Copyright Crescend Technologies8
040003A005 Rev 1
2.4.INSTALLATION INSTRUCTIONS
The C7 amplifier is designed for installation in a rack (Figures 2-1 and 2-2) that permits
access to the rear of the rack for connection of DC power, RF, and monitor cable. The
amplifier must have a minimum of 3 inches of open space in front of and behind the rear fan
to allow adequate ventilation.
To install the amplifier proceed as follows:
1. Install FPR-5 subrack into a 19 inch equipment rack using the front and rear
mounting points
2. Install amplifier in subrack and secure in place with two thumbscrews on front
panel.
3. Connect a 50 ohm antenna cable and load to the RF OUT connector on rear of
amplifier.
4. Connect the transceiver/exciter output to RF IN connector on rear of amplifier.
5. If monitoring of PA is desired, connect alarm cable to “ALARM” pin on rear of
amplifier module. See section 2.5 for more details.
6. Measure primary DC input voltage. DC input voltage should be +13.8 +/- 0.1VDC.
Turn off DC voltage.
WARNING: Turn off external primary DC power before connecting DC power cables.
7. Connect positive primary power wire (+13.8VDC) to terminal marked +13.8VDC
and negative primary power wire to GND terminal on rear of amplifier.
8. Check your work before applying DC voltage to the system. Make certain all
connections are tight and the DC wires are going to the correct terminals.
9. Refer to Section 3 for initial start-up procedures.
NOTE:
1. Make sure power supply DC is well filtered and well behaved with minimal
voltage overshoot.
2. Keep DC wires as short as possible to minimize inductance induced voltage
transients.
3. Size DC Wires properly to handle the load current to minimize voltage drop.
Copyright Crescend Technologies9
Figure 2-1. FPR-5 Rack, Front Right View
040003A005 Rev 1
Figure 2-2. C7 Series Amplifiers in Rack, Rear View
2.5. AMPLIFIER SUMMARY ALARM
The summary alarm connections is made through a filtered feedthrough connector on the
rear of the amplifier (see Table 2-1).
Table 2-1. Summary Alarm Connection
PINFUNCTIONDESCRIPTIONCONDITION
Alarm: < 1 VDC
Normal Operation: > 8 VDC
(up to Vcc)
Alarm: < 1 VDC
Normal Operation: 4 - 5 VDC
ALARM
Summary
Alarm
Indicates when:
1. The output power is low,
or
2. VSWR cutback is
activated, or
1.8 kOhm between pin and ground,
3. Thermal cutback is
activated
<500 pF
(TTL compatible)
APPROPRIATE
LOAD
> 10 kOhm,
< 100pF
Copyright Crescend Technologies10
040003A005 Rev 1
3.GENERAL OPERATING INFORMATION
3.1.INTRODUCTION
This section contains operating instructions for the C7 amplifier.
3.2.LOCATION OF STATUS INDICATORS
The location and function of the C7 amplifier status indicators and is shown in Figure 3-1
and described in detail in Table 3-1.
Figure 3-1. C7 Series Status Indicators, Front Panel
Table 3-1. C7 Series Amplifier Status Indicators
STATUS LEDFUNCTION
DC ON
LOW OUTPUT
Green LED. Illumination indicates DC Power has been applied.
Red LED. Activates when the output power drops to approximately
80-85% of set output power.
HIGH VSWR
Red LED. Activates when load VSWR exceeds approximately
2.5:1.
HIGH TEMP
Red LED. Activates when the amplifier exceeds a safe operating
temperature.
Copyright Crescend Technologies11
040003A005 Rev 1
3.3.INITIAL STARTUP
To perform the initial start-up, proceed as follows:
Check to ensure that all input and output cables are properly connected and tightened.
Note: Use high quality coaxial cable and connectors. Properly install and solder all
connectors for reliability.
CAUTION:
Before applying power, make sure that the input and output of the
amplifier are properly terminated in 50 ohms.
amplifier without a load attached.
Refer to Table 1-2 for input
Do not operate the
power requirements. Excessive input power will damage the
amplifier.
NOTE:
The output coaxial cable between the amplifier and the antenna
must be 50 ohm coaxial cable.
2. Apply DC power to the amplifier. Verify that the power supply measures 13.8 ± 0.1VDC.
The fan will come on immediately for a few seconds and then turn off.
3.Visually check the indicators on each amplifier module, and verify the following:
a.The DC PWR ON indicator (green) should be on.
b.All ALARM LED indicators (red) should be off.
4.Turn on external exciter/transceiver and apply RF input signal. The fan should turn on
after approximately 3 seconds.
5.Turn off RF input signal. The fan should continue running, but turn off after
approximately 6-8 seconds.
Copyright Crescend Technologies12
040003A005 Rev 1
4.
4.1.INTRODUCTION
This section contains principles of operation of the C7 Series of RF Power Amplifiers.
4.2.RF INPUT SIGNAL
The amplifiers are set at the factory to work over different input power ranges. The
available range of inputs for different frequency ranges may be found in Table 1-2.
4.3.RF OUTPUT LOAD
The load impedance should be as good as possible (VSWR <1.2:1) in the working band for
good power transfer to the load and maximum amplifier efficiency.
4.4.FUNCTIONAL DESCRIPTION
The amplifier is a single channel CW amplifier that operates in various frequency bands
from 30 MHz to 942 MHz. The amplifier specifications are listed in Tables 1-1 and 1-2.
4.4.1.MAIN RF PATH
The typical main RF path consists of an input attenuator, rf amplifier , rf detectors and
harmonic filter. The circuitry becomes active upon the sensing of rf input power. This
occurs when rf input reaches approximately 3 dB below the low end of the input power
range.
PRINCIPLES OF OPERATION
4.4.2.LOOP CONTROL
The loop control circuitry works to maintain a constant output power versus variations in
DC voltage, rf input power, frequency and load. A coupled detector at the output
monitors the final RF output level and generates a DC voltage proportional to the RF
output level. This voltage is fed back to the controller. The circuitry compares this voltage
to a reference voltage and varies the gain of the amplifier to maintain a constant output.
4.4.3.VSWR PROTECTION
Reflected power is detected at the output of the amplifier and compared to forward
power. When reflected power reaches an equivalent VSWR of approximately 2.5:1, the
amplifier output is reduced to protect the finals and the front panel HIGH VSWR LED
activates. The higher the load VSWR, the more the output power is reduced.
4.4.4.THERMAL PROTECTION
The heat sink temperature is monitored with a thermostat. When the heat sink
temperature reaches an unsafe level, the output power of the amplifier is reduced by
approximately 50%. This keeps the channel on the air while still providing some short
term protection until the customer can address the underlying cooling issue.
4.5.AMPLIFIER COOLING
The amplifier is cooled with forced air over a large heat sink. The fan draws in ambient air
from the front. It is important to maintain a minimum clearance of 3 inches in front of and
behind the amplifier to allow for best cooling of the amplifier.
Copyright Crescend Technologies13
040003A005 Rev 1
5.MAINTENANCE
5.1.INTRODUCTION
This section contains periodic maintenance and performance test information for the C7
Series. It also contains a list of test equipment required to perform various tests.
NOTE:
Check your sales order and equipment warranty before attempting to service
or repair the unit. Do not break the seals on equipment under warranty or the
warranty will be null and void. Do not return equipment for warranty or repair
service until proper shipping instructions are received from the factory.
5.2.PERIODIC MAINTENANCE
Periodic maintenance requirements are listed in Table 5-1. Table 5-1 also lists the intervals
at which the tasks should be performed.
WARNING: Wear proper eye protection to avoid eye injury when using
compressed air.
Table 5-1. Periodic Maintenance
TASKINTERVALACTION
Clean Air Vents/Check
Fan
Inspect Cables and
Connectors and General
Site Conditions
30 DaysInspect and clean per paragraph 5-3.
Verify fan is working properly.
6 MonthsInspect signal and power cables for
frayed insulation and proper attachment.
Check RF connectors to make sure that
they are tight. Inspect the lightning
protection system and ground at the site.
5.3.CLEANING AIR INLETS/OUTLETS
The air inlets and outlets should be checked every 30 days and cleaned if necessary. If the
equipment is operated in a severe dust environment, it should be checked and cleaned
more often. If dust and dirt are allowed to accumulate, the cooling efficiency will be
diminished. Using either compressed air or a brush with soft bristles, loosen and remove
accumulated dust and dirt from the air inlet panels.
Check that the fan is running smoothly. A slow running or noisy fan may indicate an
imminent fan failure. Replace immediately with a similar to insure long term reliability.
Heat is one of the biggest factors in reducing the reliability of your amplifier. Make sure the
fan has access to cool and clean airflow within the rack.
Copyright Crescend Technologies14
040003A005 Rev 1
5.4.TEST EQUIPMENT REQUIRED FOR TEST
Test equipment required to test the amplifier performance is listed in Table 5-2. Equivalent
test equipment may be substituted for any item.
NOTE:
All RF test equipment must be calibrated to 0.05 dB resolution. Any deviation
from the nominal attenuation must be accounted for and factored into all
output readings.
Table 5-2. Test Equipment Required (or equivalent)
EQUIPMENTMANUFACTURERMODEL
Signal Generator (1)H.P.8657B
30 dB Attenuator, 200 Watt (1)Tenuline8322
DC power supply (1)H.P6673A
Spectrum Analyzer (1)H.P.8560E
Power Meter (1)HPE4418A
Power Meter (1)HPE4419A
Power Sensor (3)HP8481A
Pad (3)Mini-CircuitsNAT-20
Coupler (2)Narda3020A
Coupler Load (1)
Lab Amplifier (1)AR30W1000M7
5.5.PERFORMANCE TEST
Performance testing may be conducted to ensure that the amplifier system meets the
operational specifications listed in Tables 1-1 and 1-2. The test equipment required to
perform the testing is listed in Table 5-2 and the test setup is shown in Figure 5-1.
Watt MeterWatt Meter
20
dB
S
e
n
s
e
Lo
ad
30 dB
Signal
Generator
Lab
Amplifier
S
S
e
e
n
n
s
s
e
e
20
20
dB
dB
CouplerUUTCouplerAttenuator
Power
Supply
Figure 5-1. Amplifier Test Setup Diagram
Spectrum
Analyzer
Copyright Crescend Technologies15
040003A005 Rev 1
6.TROUBLESHOOTING
6.1.INTRODUCTION
This section contains a list of potential problems and suggested actions to be taken. If the
suggested corrective action does not eliminate the problem, please contact your Crescend
factory for further instructions.
NOTE: Check your sales order and equipment warranty before attempting to
service or repair the unit. Do not break the seals on equipment under warranty
or the warranty will be null and void. Do not return equipment for warranty or
repair service until proper shipping instructions are received from the factory.
6.2.TROUBLESHOOTING
Refer to Table 6-1 for troubleshooting suggestions. It has been found that in some cases it
may be necessary to power cycle an amplifier (turn DC power off and back on without RF
applied) to clear an alarm.
Table 6-1. Troubleshooting
INDICATORLED STATUSOUTPUT POWER STATUSPOSSIBLE CAUSESUGGESTED ACTIONS
(Green)
LOW
OUTPUT
(Red)
HIGH VSWR
(Red)
OVER TEMP
(Red)
OffNo powerNo voltage at unit1.Check power supply voltageDC ON
OnSet powerNormal operation1.No action required
On (all other
alarm LEDs
off)
On (together
with HIGH
VSWR alarm
LED)
OnLess than set powerOutput load VSWR is
OnLess than set power
Less than set power
Frequency is out of
range
The input power is
below the low end of
the rated input range
Power supply voltage
is too low
Problem inside
amplifier
Output load VSWR is
much above 2.5:1
above 2.5:1
Fan is not rotating1.Check if +13 VDC is present
Power supply voltage
is too low causing
insufficient air flow
Operating
temperature of
amplifier is exceeding
safe level. Note:
When unit cools, LED
turns off and output
returns to rated power
1.Check frequency
1.Check input power
1.Check power supply voltage
at amplifier DC connector
during key-up
1.Send the unit back to factory
1.Turn off amplifier (or remove
RF input)
2.Check output connections
and cables for integrity and
tightness
3.Check antenna, combiner,
etc. for proper return loss
1.Turn off amplifier (or remove
RF input)
2.Check output connections
and cables for integrity and
tightness
3.Check antenna, combiner,
etc. for proper return loss
across the FAN leads
2.Check if anything is
physically stopping rotation
3.If fan has failed, replace fan
with same or similar fan
1.Check power supply voltage
2.Make sure that air access to
front and rear of unit is
unimpeded (3 inches min)
3.Verify that air vents are
clear of dust and dirt and
that fan(s) are operating
properly. Replace fan if
necessary
4.Check ambient temperature
(not to exceed spec - see
Table 1-2)
Copyright Crescend Technologies16
040003A005 Rev 1
6.3.RETURN FOR SERVICE PROCEDURES
When returning products to Crescend, the following procedures will ensure optimum
response.
6.3.1.OBTAINING AN RMA
A Return Material Authorization (RMA) number must be obtained prior to returning
equipment to the factory for service. Please contact our Customer Service Department
at 800-872-6233 to obtain this number. Failure to obtain this RMA number may result in
considerable delays in receiving repair service.
6.3.2.REPACKAGING FOR SHIPMENT
To ensure safe shipment of the amplifier, it is recommended to use the packaging
designed for the amplifier. The original packaging material is reusable. If it is not
available, contact Crescend’s Customer Service Department for packing materials and
information.
Copyright Crescend Technologies17
040003A005 Rev 1
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.