CRE C2S Technical documentation

Page 1
1
Part number :
A25 Z0 9 0004 G-EN
Last update :
January 2016
C2S
“Synchronization and safety
column”
CRE Technology believes that all information provided herein is correct and reliable and reserves the right to update at any time. CRE Technology does not assume any responsibility for its use. E & O E.
Page 2
Chapitre
: CRE Technology
2
1. CRE Technology
130 Allée Charles-Victor Naudin Zone des Templiers – Sophia Antipolis 06410 – BIOT FRANCE
Phone: +33 492 38 86 82 Fax: +33 492 38 86 83
Website: http://www.cretechnology.com
Email: info@cretechnology.com
NOTE
Read this entire manual and all other publications pertaining to the work to be performed before installing, operating, or servicing this equipment. Apply all plant and safety instructions and precautions. Failure to follow instructions can cause personal injury and/or property damage. Motors, turbines and any other type of generator must be equipped with protections (overspeed, high temperature, low pressure,…depending on the power plant). Any changes of the normal use of the equipment can cause human and material damage. For further information, please contact your CRE technology distributor or the After-Sales Service Team.
Technical support: +33 492 38 86 86 (8H30-12H00 / 14H00-18H00 GMT+1) Email: support@cretechnology.com
SKYPE: support-cretechnology.com
INFORMATION
You can download the most up-to-date version of this documentation and different other documentations relating to C2S on our web site: http://www.cretechnology.com.
All CRE Technology products are delivered with one year warranty, and if necessary we will be happy to come on site for product commissioning or troubleshooting. The company also provide specific trainings on our products and softwares.
C2S – CRE Technology – Official Technical documentation
Page 3
Chapitre
: CRE Technology
3
Technical documentation history
Date
Version
Comments
NA
H
Never released
03/29/16
I
- “CE” gaskets reference deleted.
- Note about non-CE marked gasket deleted
C2S – CRE Technology – Official Technical documentation
Page 4
Chapitre
: CRE Technology
4
TABLE CONTENT
1. CRE TECHNOLOGY ................................................................................................................................................. 2
2. INTRODUCTION ..................................................................................................................................................... 5
3. OPERATION ........................................................................................................................................................... 6
3.1 PUTTING INTO SERVICE ........................................................................................................................................ 6
3.2 AUTO/MANUAL MODE ....................................................................................................................................... 6
3.3 AUTHORISING SYNCHRO-CHECK RELAY ..................................................................................................................... 6
3.4 MICRO-SHUNTS ................................................................................................................................................. 7
4. CONFIGURATION - FACTORY SETTINGS ................................................................................................................. 8
4.1 POTENTIOMETERS .............................................................................................................................................. 8
4.2 MICRO-SHUNTS ................................................................................................................................................. 8
5. PUTTING INTO SERVICE – CONTROL ...................................................................................................................... 9
6. EMC PRECAUTION - CE MARK CONFORMITY ....................................................................................................... 10
7. WIRING DIAGRAM ............................................................................................................................................... 11
8. ENVIRONMENT – CHARACTERISTICS ................................................................................................................... 12
9. SIZE ..................................................................................................................................................................... 13
10. MOUNTING ..................................................................................................................................................... 14
11. CRE TECHNOLOGY, WHERE TO FIND US ........................................................................................................... 15
C2S – CRE Technology – Official Technical documentation
Page 5
Chapitre
: Introduction
5
2. Introduction
This second generation microprocessor module, created by C.R.E., is a module for manual coupling which integrates a synchronisation column and the syncheck authorisation relay. The synchronisation column allows visualisation of phase, frequency and voltage difference between one or several gensets to be coupled to a bus bar or reference bus. The authorisation relay allows safe coupling only when the conditions meet the requirements of the installation.
This new version of C2S features the following functions:
CE mark conformity, thanks to a new electronic and mechanical design No external DC power supply which is on the generator voltage measure Vgen. Reduced size allowing use of DIN92 format tools. Measurement of generator voltage and reference bus in 100, 230 or 400VAC with 3 different
references:
* For 100 VAC, ordering reference A25Z0.
* For 230 VAC, ordering reference A25Z1.
* For 400 VAC, ordering reference A25Z2.
Display of phase difference between the generator to be coupled and the reference bus by a 18
LEDs synchronoscope (360°).
Display of frequency difference between the generator to be coupled and the reference bus by a
17 LEDs bargraph (+/-5Hz), the frequency set at 50 or 60 Hz.
Display of voltage difference between the generator to be coupled and the reference bus by a 17
LEDs bargraph (+/-20%).
Display by LEDs of the following information:
* Presence of generator voltage (VGEN). * Presence of reference bus voltage (VBUS). * Voltage difference fault (Delta V). * Synchronisation/coupling in automatic mode (AUTO). * Closed coupling authorisation relay (RELAIS).
Coupling authorisation in manual mode by an isolated contact check, frequency and voltage
difference).
Possibility by microshunt authorise the closure of the circuit breaker if Vbus=0 and if Vgenerator is
between 85% and 115% of Vnominal.
C2S – CRE Technology – Official Technical documentation
Page 6
Chapitre
: Operation
6
3. Operation
3.1
Putting into service
The Synchronisation and Safety Column (C2S) is powered by the generator voltage on Vgen terminals 4 and
5.
WARNING : The module C2S is powered from 60% of nominal generator voltage value, and up to 115% as a maximum. Not damage the C2S, Voltage must not exceed 115%.
3.2
Auto/Manual Mode
The bargraphs and signalling of the C2S module function as follows:
In manual mode (terminals 6-7 open), all the displays and functions are in order. The "AUTO" LED
is not lit.
In automatic mode (terminals 6-7 closed), the synchronoscope and the 2 differential bargraphs
(voltmeter and frequency meter) are in order. The "Auto" LED is lit and all the other information LEDs are not in order. The relay will never be activated.
WARNING : The synchronoscope only comes back on line if the frequency difference is less than 0.5Hz.
Synchronoscope: When the synchronoscope turn clockwise, the genset is faster than the busbar,
so slow down the speed. If any led of the synchronoscope is lit the frequency difference is more than 0.5 Hz and it is displayed on the frequency bargraph.
Frequency Bargraph: If the frequency bargraph Delta Hz displays negative difference then
accelerate the genset.
Voltage Bargraph: If the voltage bargraph Delta V displays negative difference then raise the
genset voltage.
3.3
Authorising synchro-check relay
The relay authorising manual coupling is activated in the following conditions (all in the same time):
Frequency difference remaining within the limits of +/- 0,1Hz (no adjustment to be made).
Phase difference remaining within the setting limits of the RV1 "Phase difference" potentiometer (from +/­5° to +/-20°).
Voltage difference remaining within the setting limits of the RV2 "Voltage difference" potentiometer (from +/-2.5% to +/-20%).
Bus and generator voltages greater than 85% and less than 115% of their nominal value.
Bus and generator frequencies contained between 45Hz and 65Hz.
C2S – CRE Technology – Official Technical documentation
Page 7
Chapitre
: Operation
7
3.4
Micro-shunts
The micro-shunt JP1 configures the C2S to authorise the closure of the output relay when no voltage is present on the bus and the generator voltage is correct (between 85% and 115% of the nominal value). The JP2 micro-shunt allows a self-test of all the module's LEDs when the system is powered up.
WARNING : The LEDs test lasts approximately 8 seconds.
C2S – CRE Technology – Official Technical documentation
Page 8
Chapitre
: Configuration - Factory settings
8
4. Configuration - Factory settings
To access potentiometers and micro-shunts, it is necessary to remove the back cover of the module.
WARNING : Check that no voltage is present on the terminal trip before removing the cover.
4.1
Potentiometers
Note : The RV1 potentiometer is factory configured and should not be altered.
- RV2 "phase difference" Potentiometer: This potentiometer enables the adjustment of the allowed phase difference between +/-5° (fully counter-clockwise) and +/-20° (fully clockwise).
Factory setting 10°.
- RV3 "voltage difference" Potentiometer: This potentiometer enables the adjustment of the
allowed voltage difference between +/-2.5% (fully counter-clockwise) and +/-20% (fully clockwise).
Factory setting 10%.
4.2
Micro-shunts
- Micro-shunt JP1: The micro-shunt JP1 configures the C2S to authorise the closure of the output relay when no voltage is present on the bus and the generator voltage is correct (between 85% and 115% of the nominal value). WITH: Closure of the relay if VBUS=0 or VBUS=VGEN WITHOUT: Closure of the relay only if VBUS=VGEN
Factory setting: WITHOUT.
-Micro-shunt JP2: The micro-shunt JP2 enables a self-test of all the module's LEDs when the system
is powered up. WITH: Self-test in order Factory setting : WITHOUT.
C2S – CRE Technology – Official Technical documentation
Page 9
Chapitre
: Putting into service – Control
9
5. Putting into service – Control
- Disconnect the wires from the coupling authorisation relay's isolated contact (terminals 8-9), so as to prevent the coupling of the generator with the bus.
- Feed the C2S module with generator voltage Vgen, on terminals 4 and 5. Generator voltage to be coupled and the bus voltage should both be present.
- Check the relationship between the phases applied in VGEN (terminals 4-5) and VBUS (terminals 2-3) on the C2S
WARNING:
- 2 opposite phases generate a 180° coupling.
- Different phases on VGEN and VBUS generate a +/-120° coupling.
- Check that the voltage presence LEDs for the generator (VGEN) and the (VBUS) are lit. They light up as soon as their corresponding voltage reaches a level between 85% and 115% of their nominal value. If one of these 2 LEDs is not lit, then the output relay will never be activated.
- The LED "voltage difference fault" (Delta V) indicates that the voltage difference between the generator and the bus is greater than the RV2 potentiometer "voltage difference" setting. This difference is displayed on the differential voltmeter. If this LED is lit, the authorisation relay will never be activated.
- The automatic mode LED (AUTO) indicates that the synchronisation and coupling are carried out by the automatic synchroniser. If this LED is lit, the other information LEDs are inhibited. The voltage and frequency bargraphs and the synchronoscope remain on line. In this mode, the output relay will never be activated.
- The closed coupling authorisation relay LED (RELAIS) lights up when the output relay is activated. The relay and this LED remain activated as long as the phase, frequency and voltage differences are within the pre-set limits. If the micro-shunt JP1 is in place, when VBUS=0 and VGEN is present, or equally, the relay and the LED are activated.
C2S – CRE Technology – Official Technical documentation
Page 10
Chapitre
: EMC precaution - CE mark conformity
10
6. EMC precaution - CE mark conformity
The C2S version A25Zx is conformed to European CE mark requirements. Here below some tips to use the C2S.
- Faraday cage effect:
The C2S is painted with a conductive paint. We recommend maintaining surface contact between the C2S casing and the switchboard housing.
If the back cover needs to be removed, replace it and screws must be fully tightened.
For IP65 protection use a gasket (preferably conductive to ensure EMC). For more details about the positioning and the dimensions (in mm) of the gasket, refer to the following diagram.
-Equipotentiality: To assure an efficient potential ground line between the C2S and the switchboard, we recommend connecting the switchboard ground direct to the C2S's terminal ground on the back cover (see connection diagram below).
- Shielding connection:
To avoid EM interference we recommend connecting shielding of signals wires on terminals 1 and 10.
C2S – CRE Technology – Official Technical documentation
Page 11
Chapitre
: WIring Diagram
11
7. WIring Diagram
The voltage VGEN of the generator to be coupled is connected by 2 wires on terminals 1 and 2. The voltage VBUS of the reference bus is connected by 2 wires on terminals 3 and 4. If the supplying voltages are greater than the C2S nominal inputs, use reducing transformers.
WARNING : Check carefully that the phases connected on the generator voltage are the same as those connected on the reference bus voltage and in the same order. Remember that 2 opposite phases generate a 180° coupling and that different phases on the generator voltage and the bus voltage generate a +/-120° coupling.
C2S – CRE Technology – Official Technical documentation
Page 12
Chapitre
: Environment – Characteristics
12
Ordering
reference
Measuring range
Voltage max
A25Z0
100V 15%
130V
A25Z1
230V 15%
275V
A25Z2
400V 15%
480V
Ordering
reference
Measuring range
Voltage max
A25Z0
100V 15%
130V
A25Z1
230V 15%
275V
A25Z2
400V 15%
480V
Ordering
reference
Voltage supply
Voltage max
A25Z0
100V 15%
130V
A25Z1
230V 15%
275V
A25Z2
400V 15%
480V
8. Environment – Characteristics
Alternative input voltages:
Generator measuring voltage (VGEN) and power supply: 50 and 60 Hz (maximum consumption
<4VA).
Reference bus measuring voltage (VBUS): 50 and 60 Hz (maximum consumption <0,1VA).
Operating temperature: -25 à +85°C
Humidity: Tropic-proof circuits for normal operation in humid conditions.
Tightness: Front panel IP65 Protection with a gasket (preferably conductive to ensure EMC – refer
chapter 6).
to
Weight: 0,9 Kg
Size - Mounting : see plan in annexe
Voltage supply :
Alternative voltage on terminals 4 & 5 (Vgen), 50 and 60 Hz (maximum consumption <4VA).
Output relay contact :
Cutting power: 2000VA resistive load Nominal voltage /Maximal cutting voltage 250VCA/440VCA Nominal cutting current 8A
WARNING : Differential voltage bargraph is flashing when one or both of the voltage is out of ranges above and not at zero.
C2S – CRE Technology – Official Technical documentation
Page 13
Chapitre
: Size
13
9. Size
C2S – CRE Technology – Official Technical documentation
Page 14
Chapitre
: Mounting
14
10. Mounting
C2S – CRE Technology – Official Technical documentation
Page 15
Chapitre
: CRE TECHNOLOGY, where to find us
15
130 Allée Charles-Victor Naudin Zone des Templiers – Sophia Antipolis 06410 – BIOT FRANCE
Phone: +33 492 38 86 82 Fax: +33 492 38 86 83
Website: http://www.cretechnology.com
Email: info@cretechnology.com
Technical support: +33 492 38 86 86 (8H30-12H00 / 14H00-18H00 GMT+1) Email: support@cretechnology.com
SKYPE: support-cretechnology.com
11. CRE TECHNOLOGY, where to find us
SARL au Capital de 300.000 Euros - RCS Antibes: 7488 625 000 15 N°TVA FR54 488 625 583
Access to CRE Technology
C2S – CRE Technology – Official Technical documentation
Page 16
Chapitre
: CRE TECHNOLOGY, where to find us
16
Head office: FRANCE
Official Distributors
Agents
Found our entire distributors list into the world, www.cretechnology.com tab “DISTRIBUTEURS”
CRE Technology distributo rs
CRE Technology retains all copyrights in any text, graphic images, and software owned by CRE Technology and hereby authorizes you to electronically copy documents published herein solely for the purpose of transmitting or viewing the information.