Damper Frame
1
⁄2 in.-14 NPSM
Damper
Blade
Damper
Tie Bar
Spring Rod
Document Number 452723
®
Field Installation Instructions for End Switch Kit #851038
These instructions apply to the field installation of end
switch kits on Greenheck model WD Backdraft Dampers.
These end switch kits can be used in conjunction with
MP-100, MP-200, and MP-300 Series actuators.
End switches are typically wired to a fan and/or to a light
serving as an open/not open indicator. When the damper
is powered open, one of the damper blades makes
contact with the spring rod of the end switch which in
turn makes a connection allowing power to flow to the
fan and/or light. This set up would be used when it is
desirable to ensure that the damper is fully open before
the fan starts.
When the end switch is utilized to delay start up of
Vari-Green® or other ECM fan motors (electronically
commutated motor), a magnetic fan starter is required.
Instructions:
1. Position end switch such that the back side of
damper blade trips the spring rod.
2. Mount end switch bracket to damper frame or
ductwork using
#10 x 1⁄2 in. self-drilling sheet metal screws
For use on WD series Dampers
Part # Qty. Description
1 1 End switch mounting bracket
Damper
Tie Bar
2 1 End switch
3 2 #6-32NC x 1½ in. machine screws with
4 2 #10 x ½ in. self-drilling sheet metal
UL/CSA Rating L67
15 Amps: 125, 250, or 480 VAC
0.25 Amps: 250 VDC
0.50 Amps: 125 VDC
nuts (packaged in end switch housing)
screws
3
End Switch Kit
Damper Frame
2
1
⁄2 in.-14 NPSM
3
Fan or
Light
L
1
L
2
N.C.
End
Switch
Note: Some actuators are multi-tap, use correct connections per
actuator wiring diagram.
Common
N.O.
Green
M
Damper
Actuator
Alternative wiring diagram
Wiring Illustration
Damper
Blade
Damper
Tie Bar
3
1
Spring Rod
4
End Switch Installation On
WD-100 Series Dampers
Damper Frame
4
Spring Rod
1
End Switch Installation On
2
1
⁄2 in.-14 NPSM
WD-200 & 300 Series Dampers
Copyright © 2015 Greenheck Fan Corporation
#452723 End Switch Rev 6 June 2015
Damper
Blade
3