INSTALLATION
02
CRANE FLUID SYSTEMS DOUBLE REGULATING AND COMMISSIONING VALVES
03
CRANE FLUID SYSTEMS DOUBLE REGULATING AND COMMISSIONING VALVES
I
NSTALLATION AND OPERATING INSTRUCTIONS
TEMPERATURE / PRESSURE RATING
DP931/DP933/DP934 - when used with compression fittings
These instructions are issued as guidelines only and do not cover all installed conditions – if
unsure please contact our Technical Helpline before installation.
• Crane products are designed for installation and use within suitably designed systems
reflecting CIBSE, BSRIA and HVAC guidelines. Particular care should be taking
with regards to;
- accessibility to valve for setting/adjustment
- tube cutting
- jointing
- bracketing/supports
• where possible the D921/D923 should be installed in a run of pipework of the same
nominal diameter and with the flow in the correct direction. There is no requirement for
straight lengths of pipework for DRVs
• the D931/D933/D934 and the DP931/DP933/DP934 must be installed in a run of
pipework of the same nominal diameter and with the flow direction as indicated
on the body.
- to ensure flow measurement accuracy, it is essential that the pipework on the inlet
and outlet is straight, is of the same diameter as the valve and has a minimum length
equivalent to 5 diameters on the inlet and 2 diameters on the outlet
- Note: the requirement for 5 and 2 clear diameters are minimum requirements. Where
possible longer lengths should be achieved
- if installed near to pump outlet, it is essential that the straight lengths of pipework
between pump and valve inlet is a minimum of 10 diameters, greater if possible
• the DP931/DP933/DP934 Companion Valves should be installed in the opposite pipework
to the DPCV, ie. DPCV installed in return pipework – Companion Valve installed in flow
pipework. The Companion Valve should be connected to the DPCV via the impulse tube
(supplied with the DPCV). If required an isolation valve can be installed in the
impulse tube
• for the DP931/DP933/DP934 because the impulse tube is connected with a compression
fitting, the temperature and pressure ratings are limited to PN16 rating as follows. If the
valve is used separately, ie impulse tube connection blanked off, the full pressure rating
applies, ie PN25.
• end connections are as follows;
- for sizes ½” to 2”, D921/D923/D931/D933/D934 have female ISO 228-1 parallel threads
suitable for connection to threaded steel pipework. ½” and ¾”, when used with the
compression adaptor, are suitable for connection to BSEN1057- half hard copper.
- the DP931/DP933/DP934 have male threaded ends to ISO228-1 parallel, therefore
require a flat face sealing gasket suitable for the service.
TEMPERATURE ˚C -10 to 30 65 120
PRESSURE (BAR) 16 10 5
D921/D923/D931/D933/D934 - when not used with compression fittings
TEMPERATURE ˚C -10 to 100 110 120
PRESSURE (BAR) 25 23.4 21.8
D921/D922/D931/D933/D934 when used with compression fittings
TEMPERATURE ˚C -10 to 30 65 120
PRESSURE (BAR) 16 10 5