Crane D1088, D1089 Installation, Operating And Maintanance Instructions

INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS
THERMOSTATIC MIXING VALVES
D1088 & D1089
INTRODUCTION
Are self-acting Thermostatic Mixing Valves designed to blend hot and cold water, to ensure a constant, safe outlet temperature and prevent scalding.
Design and manufactured to comply with
Have been independently tested and
certified as meeting the requirements of the D08 specification under the TMV3 scheme.
The D1089 includes right angle isolation
valves.
Both the D1088 & D1089 thermostatic
mixing valves are certified under the BuildCert TMV2 & TMV3 schemes and are WRAS approved products listed in the WRAS Approvals Directory:
- BuildCert Approval Number (TMV3):
BC1802/1016 (for TMV3)
- BuildCert Approval Number (TMV2):
BC1801/1016 (for TMV2)
- WRAS Scheme Approval Number:
1301096 (WRAS)
D1089
D1088
THERMOSTATIC MIXING VALVES: D1088 & D1089
2
TECHNICAL SPECIFICATION
Factory Setting
41°C
Temperature Setting Range
30°C to 50°C
Minimum Hot to Mix Temperature
10°C
Temperature Stability
±2°C
Maximum Working Pressure
10 Bar
Min Flow Rate
5 l/min
Table 1
GENERAL INSTALLATION – TMV2 & TMV3
These instructions are issued as guidelines only and may not cover all installation conditions – if unsure please contact our Technical Helpline before installation.
Crane FS products are designed for installation and use within suitably designed systems
reflecting CIBSE, BSRIA and HVAC guidelines. Particular care should be taking with regards to accessibility to valve for setting/adjustment, tube cutting, jointing & bracketing/supports.
The thermostatic mixing valve must be installed in accordance with the regulations of the
local water company and the Water Supply (Water Fittings) Regulations 1999.
The D1088 & D1089 are suitable for single outlet applications only.
The D1088 & D1089 can be installed in any orientation.
Flush hot & cold supply pipework before connection.
For the D1088, where isolation valves are not supplied, isolation valves in the water supply
inlets should be fitted as close as practical to the TMV.
For D1088, wafer strainers are supplied as shown in figure 5.
For D1089, strainers are supplied and located in the isolation valve body.
TMV3
The D1088 and D1089 have been approved as TYPE 3 valves under the TMV3 scheme. They have been designed and manufactured for use in Healthcare and Commercial installations and complying with NHS Estates requirements D 08.
LIMITS OF USE
The D1088 & D1089 have been approved for use on the following designated systems.
Code Operating Pressure Application
HP-S, LP-S High Pressure Shower Temperature 41ºC
HP-W, LP-W High Pressure Washbasin Temperature 41ºC
HP-B, LP-B High Pressure Bidet Temperature 38ºC
HP-T44, LP-T44 High Pressure Bath Fill Temperature 44ºC
HP-T46, LP-T46 High Pressure
Bath Fill (assisted) Temperature 46ºC
Table 2 - Mixed Water Temperature
Note 1 - HP: High Pressure LP: Low Pressure Note 2 - 15mm not acceptable for LP Tub Fill, LP-T44 & LP-T46.
3
THERMOSTATIC MIXING VALVES: D1088 & D1089
INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS
CONDITIONS OF USE
Operating Pressure Range High Pressure Low Pressure
Maximum Static Pressure 10 bar 10 bar
Flow Pressure - Hot & Cold 1 to 5 bar 0.2 - 1 bar
Hot Supply Temperature 52 to 65ºC 52 to 65ºC
Cold Supply Temperature 5 to 20ºC 5 to 20ºC
Table 3 - Normal Conditions of Use for Type 3 Valves
Note 1: The valve may perform adequately outside the conditions in table 3 but the TMV3 scheme approval does
not apply.
Note 2: The highest flow rates will be achieved under balanced pressure conditions, but the pressure at the valve inlets must be within a ratio of 2:1 under flow conditions and the size and layout of pipe work and fittings must take this into account.
PRE-COMMISSIONING CHECKS
Follow this method for adjusting the water temperature:
1. Remove the maroon plastic protective cap on top of the valve with a
screw-driver.
2. Back-out the nut, using a monkey spanner:
- To increase the temperature turn anti-clockwise
- To decrease the temperature turn clockwise
- To set the valve to a maximum mixed water temperature in
accordance with the valve application (See Table 4).
Once the correct outlet temperature is set the internal mechanism must be tested at least 3 times by:
Alternately isolate the hot & cold water supply. This causes the internal
piston to travel its full stroke and will ensure correct operation of the valve.
With hot & cold isolation valves and the terminal outlet fully open retest
the flow temperature. If the set temperature has moved, repeat the commissioning process.
A fail safe test must be carried out by isolating the cold
supply. Once isolated, the flow must reduce, within a couple of seconds, to a trickle - depending on site conditions, supply temperature/pressure.
Then repeat fail safe test isolating the hot supply. Once
isolated, the flow must reduce to a trickle within a couple of seconds – depending on site conditions.
If either the cold or hot fail safe function does not operate, check;
- Supply pressures
- Supply temperatures
- Hot water supply is at least 10ºC above required mix temperature,
i.e. minimum hot to mix temperature
Figure 1 - D1088 pictured,
cap removal
Figure 2 - D1088 pictured,
temperature setting
Screw driver
Screw
The blue plastic protective cap
Nut
THERMOSTATIC MIXING VALVES: D1088 & D1089
4
COMMISIONING
Since the installed supply conditions are likely to be different from those applied in the laboratory tests, it is appropriate, at commissioning, to carry out some simple checks and tests on each mixing valve to provide a performance reference point for future in-service tests.
a) The designation (TMV3) of the Thermostatic Mixing Valve matches the intended application.
b) The supply pressures are within the range of operating pressures for the designation of
the valve.
c) The supply temperatures are within the range permitted for the valve and within guidance
information on the prevention of legionella etc.
d) Record the temperature of the hot and cold water supplies.
e) Record the temperature of the mixed water at the largest draw-off flow rate.
f) Record the temperature of the mixed water at a smaller draw-off flow rate.
g) Isolate the cold water supply to the mixing valve and monitor the mixed water temperature.
h) Record the maximum temperature achieved as a result of (g) and the final
stabilised temperature.
Note: The final stabilised mixed water temperature should not exceed the values in the following table. i) Use recording equipment such as a thermometer etc. used for the measurements.
Application Mixed Water Temperature
Bidet 40°C
Shower 43°C
Washbasin 43°C Bath (44°C Fill) 46°C Bath (46°C Fill) 48°C
Table 4 - Guide to Maximum Stabilised Temperatures Recorded During Site Tests
Loading...
+ 8 hidden pages