WARNING: CANCER AND REPRODUCTIVE HARM
www.P65Warnings.ca.gov
. (000393a)
INTRODUCTION AND SAFETY
DANGER
Using a generator indoors CAN KILL YOU IN MINUTES.
Generator exhaust contains carbon monoxide. This is
a poison you cannot see or smell.
NEVER use inside a home
or garage, EVEN IF doors
and windows are open.
Only use OUTSIDE and
far away from windows,
doors, and vents.
Introduction
Thank you for purchasing a CRAFTSMAN product. This
unit has been designed to provide high-performance,
efficient operation, and years of use when maintained
properly.
WARNING: Consult Manual. Read and understand manual completely before using product. Failure to completely understand manual
and product could result in death or serious
injury. (000100a)
If any section of the manual is not understood, contact
your nearest Service Dealer, or contact CRAFTSMAN at 1888-331-4569, or WWW.CRAFTSMAN.COM with any
questions or concerns.
The owner is responsible for proper maintenance and
safe use of the equipment. Before operating, servicing or
storing this generator:
• Study all warnings in this manual and on the product
carefully.
• Become familiar with this manual and the unit before
use.
• Refer to the Assembly section of the manual for instructions on final assembly procedures. Follow the instructions completely.
Save these instructions for future reference. ALWAYS
supply this manual to any individual that will use this
machine.
The information in this manual is accurate based on
products produced at the time of publication. The manufacturer reserves the right to make technical updates,
corrections, and product revisions at any time without
notice.
Safety Rules
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in
this manual, and on tags and decals affixed to the unit
are, therefore, not all inclusive. If using a procedure, work
method or operating technique that the manufacturer
does not specifically recommend, verify that it is safe for
others. Also make sure the procedure, work method or
operating technique utilized does not render the equipment unsafe.
Throughout this publication, and on tags and decals
affixed to the generator, DANGER, WARNING, CAUTION
and NOTE blocks are used to alert personnel to special
instructions about a particular operation that may be
hazardous if performed incorrectly or carelessly. Observe
them carefully. Their definitions are as follows:
DANGER: Indicates a hazardous situation which,
if not avoided, will result in death or serious
injury.
WARNING: Indicates a hazardous situation
which, if not avoided, could result in death or
serious injury.
CAUTION: Indicates a hazardous situation
which, if not avoided, could result in minor or
moderate injury.
NOTE: Notes contain additional information important to a
procedure and will be found within the regular text of this
manual.
These safety warnings cannot eliminate the hazards that
they indicate. Common sense and strict compliance
with the special instructions while performing the
action or service are essential to preventing accidents.
Safety Symbols and Meanings
DANGER: Asphyxiation. Running engines produce carbon monoxide, a colorless, odorless,
poisonous gas. Carbon monoxide, if not
avoided, will result in death or serious injury.
(000103)
DANGER: Asphyxiation. The exhaust system
must be properly maintained. Do not alter or
modify the exhaust system as to render it
unsafe or make it noncompliant with local
codes and/or standards. Failure to do so will
result in death or serious injury. (000179b)
• If you start to feel sick, dizz y, or weak after the generator
has been running, move to fresh air IMMEDIATELY. See a
doctor, as you could have carbon monoxide poisoning.
DANGER: Electrocution. Water contact with a
power source, if not avoided, will result in
death or serious injury. (000104)
DANGER: Electrocution. Turn utility and emergency power supplies to OFF before connecting
power source and load lines. Failure to do so
will result in death or serious injur y. (000116)
WARNING: Equipment and property damage. Do
not alter construction of, installation, or block
ventilation for generator. Failure to do so could
result in unsafe operation or damage to the
generator. (000146)
WARNING: Asphyxiation. Always use a battery
operated carbon monoxide alarm indoors and
installed according to the manufacturer’s
instructions. Failure to do so could result in
death or serious injury. (000178a)
WARNING: Equipment and property damage. Do
not operate unit on uneven surfaces, or areas
of excessive moisture, dirt, dust or corrosive
vapors. Doing so could result in death, serious
injury, property and equipment damage.
(000250)
1
WARNING: Moving parts. Keep clothing, hair,
and appendages away from moving parts. Failure to do so could result in death or serious
injury. (000111)
WARNING: Hot surfaces. When operating
machine, do not touch hot surfaces. Keep
machine away from combustibles during use.
Hot surfaces could result in severe burns or fire.
(000108)
WARNING: Personal injury. Do not insert any
object through the air cooling slots. Generator
can start at any time and could result in death,
serious injury, and unit damage. (000142a)
WARNING: Risk of injury. Do not operate or service this machine if not fully alert. Fatigue can
impair the ability to service this equipment and
could result in death or serious injury. (000215)
WARNING: Injury and equipment damage. Do
not use generator as a step. Doing so could
result in falling, damaged parts, unsafe equipment operation and could result in death or
serious injury. (000216)
WARNING: Equipment damage. Do not attempt
to start or operate a unit in need of repair or
scheduled maintenance. Doing so could result
in serious injury, death or equipment failure or
damage. (000291)
• For safety reasons, it is recommended that the maintenance of this equipment be performed by a Service
Dealer. Inspect the generator regularly, and contact the
nearest Service Dealer for parts needing repair or
replacement.
Exhaust and Location Hazards
DANGER: Asphyxiation. Running engines produce carbon monoxide, a colorless, odorless,
poisonous gas. Carbon monoxide, if not
avoided, will result in death or serious injury.
(000103)
DANGER: Asphyxiation. The exhaust system
must be properly maintained. Do not alter or
modify the exhaust system as to render it
unsafe or make it noncompliant with local
codes and/or standards. Failure to do so will
result in death or serious injury. (000179b)
WARNING: Equipment and property damage. Do
not alter construction of, installation, or block
ventilation for generator. Failure to do so could
result in unsafe operation or damage to the
generator. (000146)
WARNING: Asphyxiation. Always use a battery
operated carbon monoxide alarm indoors and
installed according to the manufacturer’s
instructions. Failure to do so could result in
death or serious injury. (000178a)
• If you start to feel sick, dizzy, or weak after the generator
has been running, move to fresh air IMMEDIATELY. See a
doctor, as you could have carbon monoxide poisoning.
• NEVER run a generator indoors or in a partly enclosed
area such as garages.
• ONLY use outdoors and far away from windows, doors,
vents, crawl spaces and in an area where adequate ven-
tilation is available and will not accumulate deadly
exhaust gas.
• Using a fan or opening a door will not provide sufficient
ventilation.
• Point muffler exhaust away from people and occupied
buildings.
Electrical Hazards
DANGER: Electrocution. Contact with bare wire s,
terminals, and connections while generator is
running will result in death or serious injury.
(000144)
DANGER: Electrocution. Water contact with a
power source, if not avoided, will result in
death or serious injury. (000104)
DANGER: Electrocution. In the event of electrical
accident, immediately shut power OFF. Use
non-conductive implements to free victim from
live conductor. Apply first aid and get medical
help. Failure to do so will result in death or serious injury. (000145)
• The National Electric Code (NEC) requires the frame and
external electrically conductive parts of the generator be
properly connected to an approved earth ground. Local
electrical codes may also require proper grounding of
the generator. Consult with a local electrician for
grounding requirements in the area.
• Use a ground fault circuit interrupter in any damp or
highly conductive area (such as metal decking or steel
work).
• Once generator has been started outside, connect electrical loads to extension cord(s) inside.
Fire Hazards
DANGER: Explosion and Fire. Fuel and vapors
are extremely flammable and explosive. Add
fuel in a well ventilated area. Keep fire and
spark away. Failure to do so will result in death
or serious injury. (000105)
DANGER: Explosion and Fire. Do not overfill fuel
tank. Fill to 1/2 inch from top of tank to allow
for fuel expansion. Overfilling may cause fuel
to spill onto engine causing fire or explosion
which will result in death or serious injury.
(000166b)
WARNING: Personal injury. Do not insert any
object through the air cooling slots. Generator
can start at any time and could result in death,
serious injury, and unit damage. (000142a)
WARNING: Fire risk. Fuel and vapors are
extremely flammable. Do not operate indoors.
Doing so could result in death, serious injury, or
property or equipment damage. (000281)
WARNING: Explosion and fire risk. Do not smoke
near unit. Keep fire and spark away. Failure to
do so could result in death, serious injury, or
property or equipment damage. (000282)
WARNING: Explosion and Fire. Do not smoke
while refueling unit. Failure to do so could
result in death, serious injury, or property or
equipment damage. (000284a)
2
• Allow at least 5 feet of clearance on all sides of the generator when operating to prevent overheating and fire.
• Do not operate the generator if connected electrical
devices overheat, if electrical output is lost, if engine or
generator sparks, or if flames or smoke are observed
while unit is running.
• Keep a fire extinguisher near the generator at all times.
Standards Index
1. National Fire Protection Association (NFPA) 70: The
NATIONAL ELECTRIC CODE (NEC) available from
www.nfpa.org
2. National Fire Protection Association (NFPA) 5000:
BUILDING CONSTRUCTION AND SAFETY CODE
available from www.nfpa.org
5. ASAE EP-364.2 Installation and Maintenance of Farm
Standby Electric Power available from
www.asabe.org, American Society of Agricultural &
Biological Engineers 2950 Niles Road, St. Joseph, MI
49085
6. CSA C22.2 100-14 Electric motors and generators for
installation and use, in accordance with the Rules of
the Canadian Electrical Code
7. ANSI/PGMA G300 Safety and Performance of Porta-
ble Generators. Portable Generator Manufacturer’s
Association, www.pgmaonline.com
This list is not all inclusive. Check with the Authority Having Jurisdiction (AHJ) for any local codes or standards
which may be applicable to your jurisdiction.
3
GENERAL INFORMATION AND SETUP
006087
16
10
11
12
14
005678
17
18
19
15
12345678910111213
141516
17
18
19
20
006088
23 4
65
7
19
78
20
13
Fig. A
See Fig. A and Fig. B.
Generator Components
Low Oil Warning
Overload Warning
AC Power Light
Eco Mode Switch
1A/2.1A, 5 VDC USB Ports
AC Breaker
Parallel Ports
Grounding Location
120V, 20A Outlet
Handle
Fuel Tank Cap
Control Panel
Start Dial (Off/Run/Choke)
Recoil Starter
Muffler
Oil Fill/Drain
Air Cleaner
Carburetor
Spark Plug
120V, 30A Outlet (NEMA L5-30R)
4
Fig. B
Know Your Generator
WARNING: Consult Manual. Read and understand manual completely before using product. Failure to completely understand manual
and product could result in death or serious
injury. (000100a)
Replacement owner’s manuals are available at
WWW.CRAFTSMAN.COM.
Emissions
The United States Environmental Protection Agency (US
EPA) (and California Air Resources Board (CARB), for
engines/equipment certified to California standards)
requires that this engine/equipment complies with
exhaust and evaporative emissions standards. Locate the
emissions compliance decal on the engine to determine
applicable standards. For emissions warranty information, please reference the included emissions warranty. It
is important to follow the maintenance specifications in
the manual to ensure that the engine complies with the
applicable emissions standards for the duration of the
product’s life.
Product Specifications
Generator SpecificationsCMXGIAC3000
Rated Power2300 W
Starting Power3000 W
Rated AC Voltage120V
Rated AC Load at 120V19.1 Amps**
Rated Frequency60 Hz
Dimensions L x W x H (in/mm)22.25 x 13.35 x 18.4 (565 x 339 x 467)
Weight (dry)59.5 lb. (27 kg)
** Operating Temperature Range: -13 deg. C (8 deg. F) to 40 Deg. C (104 Deg. F). When operated above 25 deg. C
(77 deg. F) there may be a decrease in power.
** Maximum wattage and current are subject to, and limited by, such factors as fuel Btu content, ambient temperature, altitude, engine condition, etc.. Maximum power decreases about 3.5% for each 1,000 feet above sea level;
and will also decrease about 1% for each 6° C (10° F) above 16° C (60° F) ambient temperature.
Engine SpecificationsCMXGIAC3000
Engine TypeSingle Cylinder, 4-stroke
Displacement149 cc
Spark Plug Part Number0K95530157
Spark Plug TypeE6TC / E6RTC or equivalent
Spark Plug Gap (in/mm)0.024-0.028 (0.6-0.7)
Fuel Capacity / Type4.3 L (1.14 U.S. gallons) / Unleaded
Oil TypeSee Add Engine Oil
Oil Capacity0.6 L (0.6 qt.)
Run Time at 50% Load4.5 Hours
* Go to WWW.CRAFTSMAN.COM or call 1-888-331-4569 for replacement parts.
5
Outlets
001630
000844
1
2
3
OFF
ON
CHOKE
005482
3
2
1
213
OVERLOAD OUT
PU
T
1
2
3
005483
120 VAC, Duplex Outlet
The 120 Volt outlet is overload protected by the 20 Amp
push button circuit protector (Fig. C).
Fig. C
120 VAC, 30 Amp Outlet
Use a NEMA L5-30R plug with this outlet. Connect a suitable 3-wire cord set to the plug and to desired load. The
cord set should be rated for 125 Volts AC at 30 Amps (or
greater) (Fig. D).
Use this outlet to operate 120 Volt AC, 60Hz, single
phase loads requiring up to 3000 watts, 25 Amps starting power and 2300 watts of continuous power at 19.1
Amps. The outlet is protected by a 20 Amp push-to-reset
circuit breaker.
Fig. D
Start Dial (Off/Run/Choke)
This controls the ON/OFF functions, choke and fuel valve
operation (Fig. E ).
• The OFF position stops the engine and shuts off fuel
flow.
• The RUN position is for normal operation and to
gradually reduce the use of the choke.
• The CHOKE position switches the fuel valve on to
start the engine.
NOTE: The CHOKE is not required to start a warm engine.
Fig. E
USB Ports
The 1 Amp and 2.1 Amp USB outlets allow charging of
compatible electronic devices.
Eco Mode Switch
The economy switch has 2 modes of operation:
• On: The quietest mode and best when running appliances or equipment that are resistive loads (non-motor
starting), (example: TV, video game, light, radio).
• Off: Best when running a both inductive (motor-starting loads) and resistive (non-motor starting loads),
especially when these loads are turning on and off
(example: RV, air conditioner, hairdryer).
Generator Status Lights
See Fig. F.
• Overload LED (red): Indicates system overload .
During motor starting it is normal for the overload LED
to illuminate for a few seconds. If LED stays illuminated
and the ready LED turns off, the engine will continue to
run without output power. Remove all applied loads
and determine if attached devices exceed recommended output power. Check for faulty or shorted connections. To restore electrical output, turn dial OFF to
reset. Start engine. If condition was corrected, the red
LED will not illuminate and electrical output will be
restored. Loads can be applied once the green LED illuminates. If the orange LED returns, contact a Service
Dealer.
• Low Oil Level LED (yellow): Illuminates when oil level
is below safe operating level. Engine shuts down .
• Power LED (green): Indicates output from generator
(unless there is a low oil or overload condition).
Fig. F
6
Circuit Breakers
001792
The AC receptacles are protected by an AC circuit
breaker. The DC receptacles are protected by a DC circuit
breaker. If the generator is overloaded or an external
short circuit occurs, the circuit breaker will trip. If this
occurs, disconnect all electrical loads to determine the
cause of the problem before using the generator again.
Reduce the load if the circuit breaker is tripped.
NOTE: Continuous tripping of the circuit breaker may cause
damage to generator or equipment.
Push the button of the breaker to reset the circuit
breaker.
Remove Contents from Carton
1. Open carton completely by cutting each corner
from top to bottom.
2. Remove and verify carton contents prior to assembly. Carton contents should contain the following:
Accessories
ItemQty.
Inverter Generator1
Owner’s Manual1
Engine Oil1
Oil Funnel1
Tool Kit1
Service Warranty1
Emissions Warranty1
3. Call Customer Service at 1-888-331-4569 with the
unit model and serial number for any missing carton contents.
4. Record model, serial number, and date of purchase
on front cover of this manual.
Fig. G
000115
.
SAE 30
10W-30
Synthetic 5W-30
000399
5. To check oil level, remove funnel and insert dipstick
into oil filler neck.
Fig. H
Add Engine Oil
CAUTION: Engine damage. Verify proper type
and quantity of engine oil prior to starting
engine. Failure to do so could result in engine
damage. (000135)
NOTE: The generator is shipped without oil in the engine.
Add oil slowly and verify oil level often during filling process
to ensure overfilling does not occur.
See Fig. G and Fig. H.
1. Place generator on a level surface.
2. Clean area around oil fill and oil drain plug.
3. Remove oil fill cap and wipe dipstick clean.
4. Insert funnel into oil fill opening. Add recommended engine oil as necessary. Climate determines proper engine oil viscosity. See chart to select
correct viscosity.
NOTE: Use petroleum based oil (supplied) for engine breakin before using synthetic oil.
6. Remove dipstick and verify oil level is within safe
operating range.
NOTE: Verify oil level often during filling process to ensure
overfilling does not occur.
7. Install oil fill cap/dipstick and hand-tighten.
Fuel
DANGER: Explosion and Fire. Fuel and vapors
are extremely flammable and explosive. Add
fuel in a well ventilated area. Keep fire and
spark away. Failure to do so will result in death
or serious injury. (000105)
DANGER: Explosion and Fire. Do not overfill fuel
tank. Fill to 1/2 inch from top of tank to allow
for fuel expansion. Overfilling may cause fuel
to spill onto engine causing fire or explosion
which will result in death or serious injury.
(000166b)
7
Fuel requirements are as follows:
• Clean, fresh, unleaded gasoline.
• Minimum rating of 87 octane/87 AKI (91 RON).
• Up to 10% ethanol (gasohol) is acceptable.
• DO NOT use E85.
• DO NOT use a gas oil mix.
• DO NOT modify engine to run on alternate fuels. Stabilize fuel prior to storage.
1. Verify unit is OFF and cooled entirely prior to fueling.
2. Place unit on level ground in a well ventilated area.
3. Clean area around fuel cap.
WARNING: Explosion and Fire. Verify fuel cap
vent is set to ON for operation, and OFF for
transportation and storage. Failure to do so
could result in poor unit performance, death or
serious injury. (000362)
4. Turn cap slowly to remove.
5. Slowly add recommended fuel. Do not overfill.
6. Install fuel cap.
NOTE: Allow spilled fuel to evaporate before starting unit.
IMPORTANT NOTE: It is important to prevent gum
deposits from forming in fuel system parts such as
the carburetor, fuel hose or tank during storage. Alcohol-blended fuels (called gasohol, ethanol or methanol) can attract moisture, which leads to separation
and formation of acids during storage. Acidic gas can
damage the fuel system of an engine while in storage. To avoid engine problems, the fuel system
should be emptied before storage of 30 days or longer. See the Storage section. Never use engine or carburetor cleaner products in the fuel tank as
permanent damage may occur.
8
OPERATION
005485
Operation and Use Questions
Call Customer Service at 1-888-331-4569 with questions
or concerns about equipment operation and maintenance.
Before Starting Engine
1. Verify engine oil level is correct.
2. Verify fuel level is correct.
3. Verify unit is secure on level ground, with proper
clearance and is in a well ventilated area.
Prepare Generator for Use
DANGER: Asphyxiation. Running engines produce carbon monoxide, a colorless, odorless,
poisonous gas. Carbon monoxide, if not
avoided, will result in death or serious injury.
(000103)
DANGER: Asphyxiation. The exhaust system
must be properly maintained. Do not alter or
modify the exhaust system as to render it
unsafe or make it noncompliant with local
codes and/or standards. Failure to do so will
result in death or serious injury. (000179b)
WARNING: Risk of fire. Do not use generator
without spark arrestor installed. Failure to do
so could result in death or serious injury.
(000118a)
WARNING: Asphyxiation. Always use a battery
operated carbon monoxide alarm indoors and
installed according to the manufacturer’s
instructions. Failure to do so could result in
death or serious injury. (000178a)
WARNING: Risk of Fire. Hot surfaces could ignite
combustibles, resulting in fire. Fire could result
in death or serious injury. (000110)
WARNING: Hot surfaces. When operating
machine, do not touch hot surfaces. Keep
machine away from combustibles during use.
Hot surfaces could result in severe burns or fire.
(000108)
CAUTION: Equipment and property damage.
Disconnect electrical loads prior to starting or
stopping unit. Failure to do so could result in
equipment and property damage. (000136)
Grounding the Generator When In
Use
See Fig. I. The generator is equipped with an equipment
ground connecting the generator frame and the ground
terminals on the AC output outlets (see NEC 250.34 (A).
This allows the generator to be used as a portable without grounding the frame of the generator as specified in
NEC 250.34.
• Neutral Floating
Fig. I
The generator (stator winding) is isolated from the frame
and from the AC outlet ground pin. Electrical devices
that require a grounded outlet pin connection will not
function if the outlet ground pin is not functional.
Know Generator Limits
Overloading a generator can result in damage to the
generator and connected electrical devices. Observe the
following to prevent overload:
• Add up the total wattage of all electrical devices to be
connected at one time. This total should NOT be greater
than the generator's wattage capacity.
• The rated wattage of lights can be taken from light
bulbs. The rated wattage of tools, appliances, and
motors can be found on a data label or decal affixed to
the device.
• If the appliance, tool, or motor does not give wattage,
multiply volts times ampere rating to determine watts
(volts x amps = watts).
• Some electric motors, such as induction types, require
about three times more watts of power for starting th an
for running. This surge of power lasts only a few seconds
when starting such motors. Make sure to allow for high
starting wattage when selecting electrical devices to
connect to the generator:
1. Figure the watts needed to start the largest motor.
2. Add to that figure the running watts of all other
connected loads.
Wattage Reference Guide is provided to assist in deter-
mining how many items the generator can operate at
one time.
NOTE: All figures are approximate. See data label on appliance for wattage requirements.
9
Wattage Reference Guide
1
OFF
ON
CHOKE
1
2
3
005482
2
A
DeviceRunning
*Air Conditioner (12,000 Btu)1700
*Air Conditioner (24,000 Btu)3800
*Air Conditioner (40,000 Btu)6000
Battery Charger (20 Amp)500
Belt Sander (3")1000
Chain Saw1200
Circular Saw (6-1/2")800 to 1000
*Clothes Dryer (Electri c)5750
*Clothes Dryer (Gas)700
*Clothes Washer1150
Coffee Ma ker1750
*Compressor (1 HP)2000
*Compressor (3/4 HP)1800
*Compressor (1/2 HP)1400
Curling I ron700
*Dehumidifier650
Disc Sander (9")1200
Edge Trimmer500
Electric Blan ket40 0
Electric Nail Gun1200
Electric Range (per element)1500
Electric Skillet1250
*Freezer700
*Furnace Fan (3/5 HP)875
*Garage Door Opener500 to 750
Hair Dryer1200
Hand Drill250 to 1100
Hedge Trimmer450
Impact Wrench500
Iron1200
*Jet Pump800
Lawn Mower1200
Light Bulb100
Microwave Oven700 to 1000
*Milk Cooler1100
Oil Burner on Furnace300
Oil Fired Space Heater (140,000 Btu)400
Oil Fired Space Heater (85,000 Btu)225
Oil Fired Space Heater (30,000 Btu)150
*Paint Sprayer, Airless (1/3 HP)600
Paint Sprayer, Airless (hand-held)150
Radio50 to 200
Watts
*Refrigerator700
Slow Cooker200
*Submersible Pump (1-1/2 HP)2800
*Submersible Pump (1 HP)2000
*Submersible Pump (1/2 HP)1500
*Sump Pump800 to 1050
*Table Saw (10")1750 to 2000
Television200 to 500
Toaster1 000 to 1650
Weed Trimmer500
* Allow 3 times the listed watts for starting these de vices.
Transporting/Tipping of the Unit
Do not store or transport the unit at an angle greater
than 15 degrees.
Starting Pull Start Engines
WARNING: Recoil Hazard. Recoil could retract
unexpectedly. Kickback could result in death or
serious injury. (000183)
CAUTION: Equipment and property damage.
Disconnect electrical loads prior to starting or
stopping unit. Failure to do so could result in
equipment and property damage. (000136)
See Fig. J and Fig. K.
1. Rotate the Start Dial to CHOKE .
2. Switch Eco Mode Switch to OFF.
3. Firmly grasp recoil handle and pull slowly until
increased resistance is felt. Pull rapidly up and away.
Fig. J
4. When engine starts, rotate Start Dial to RUN .
Choke operation is reduced as Start Dial is rotated
towards RUN.
NOTE: If engine fires, but does not continue to run, rotate
the Start Dial to OFF and repeat starting inst ructions.
IMPORTANT: Do not overload generator or individual
panel outlets. If an overload occurs, the overload LED
will illuminate and AC output ceases. To correct,
see Generator Status Lights. Read Know Generator Limits
carefull y.
10
Fig. K
OVERLOAD OUT
PU
T
B
A
005483
3
B
Generator Shut Down
CAUTION: Equipment and property damage.
Disconnect electrical loads prior to starting or
stopping unit. Failure to do so could result in
equipment and property damage. (000136)
1. Shut off all loads and unplug electrical loads from
generator panel outlets.
2. Let engine run at no-load for several minutes to stabilize internal temperatures of engine and generator.
3. Rotate Start Dial to OFF . See Fig. J.
4. Turn fuel cap OFF.
Starting Hot Engines
CAUTION: Equipment and property damage.
Disconnect electrical loads prior to starting or
stopping unit. Failure to do so could result in
equipment and property damage. (000136)
1. Turn Start Dial from STOP to RUN. This will open the
fuel valve and permit starting. See Fig. J.
2. Firmly grasp recoil handle and pull slowly until
increased resistance is felt. Pull rapidly up and away.
NOTE: Do not disconnect any parallel kit connections once
the units are running.
3. Start both units per starting instructions. Once the
green output indicator illuminates, devices can be
connected and turned on using the parallel kit outlet.
4. Follow Generator Shut Down instructions.
NOTE: Only use approved parallel kit.
.
Low Oil Level Shutdown System
The engine is equipped with a low oil level sensor that
shuts down the engine automatically when the oil level
drops below a specified level to prevent engine damage
. The engine will not run until the oil has been filled
to the proper level. See Fi g. K.
If the engine shuts down and there is sufficient fuel,
check engine oil level.
Parallel Operation
For output power up to 4600 running Watts, two inverters can operate in parallel using Parallel Kit (optional).
See the Parallel Kit Operator’s Manual or contact Customer Service at 1-888-331-4569.
NOTE: All connections to the parallel kit should be made
while both inverters are turned off and all loads disconnected.
1. Make sure the Eco Mode Switch is in the same posi-
2. Make appropriate parallel connections to the out-
tion on both generators.
lets on each inverter as outlined in the owner’s
manual supplied with the kit.
11
MAINTENANCE AND TROUBLESHOOTING
Maintenance
Regular maintenance will improve performance and
extend engine/equipment life. Contact Customer Service at 1-888-331-4569, or WWW.CRAFTSMAN.COM to
find a dealer for maintenance work to be performed.
Regular maintenance, replacement or repair of the emissions control devices and systems may be performed by
any repair shop or person of the owner’s choosing. However, to obtain emissions control warranty service free of
charge, the work must be performed by a CRAFTSMAN
service dealer. See the emissions warranty.
NOTE: Call 1-888-331-4569 with questions about component replacement.
Maintenance Schedule
Follow maintenance schedule intervals, whichever
occurs first according to use.
NOTE: Adverse conditions will require more frequent service.
NOTE: All required service and adjustments should be each
season as detailed in the following chart.
Preventive Maintenance
Dirt or debris can cause improper operation and equipment damage. Clean generator daily or before each use.
Keep area around and behind muffler free from combustible debris. Inspect all cooling air openings on generator.
WARNING: Personal injury. Do not insert any
object through the air cooling slots. Generator
can start at any time and could result in death,
serious injury, and unit damage. (000142a)
• Use a damp cloth to wipe exterior surfaces clean.
• Use a soft bristle brush to loosen caked on dirt, oil, etc.
• Use a vacuum to pick up loose dirt and debris.
• Low pressure air (not to exceed 25 psi) may be used to
blow away dirt. Inspect cooling air slots and openings
on generator. These openings must be kept clean and
unobstructed.
NOTE: DO NOT use a garden hose to clean generator. Water
can enter engine fuel system and cause problems. If water
enters generator through cooling air slots, some water will
be retained in voids and crevices of rotor and stator winding insulation. Water and dirt buildup on generator internal
windings will decrease insulation resistance of windings.
At Each Use
Check engine oil level
Every 100 Hours or Every 6 Months
Clean/Replace Air Filter**
Change oil ¥
Muffler Screen
Clean/Replace Spark Arrestor
Every 300 Hours or Every Season*
Replace Spark Plug
Clean Spark Arrestor
Replace Fuel Filter +
Valve Clearance Adjustment
Clean/Replace Crankcase Breather Hose
Check Fittings/Fasteners +
¥ Change oil after first month or 20 hours of operation.
+ To be per formed by a Service Dealer.
* Change oil every month when operating under heavy
load or in high temperatures.
** Clean more often under dirty or dusty operating con-
ditions. Replace air filter parts if they cannot be adequately cleaned.
*** Check valve clearance and adjust if necessary after
first 50 hours of operation and every 300 hours
thereafter.
Engine Maintenance
WARNING: Personal injury. Do not insert any
object through the air cooling slots. Generator
can start at any time and could result in death,
serious injury, and unit damage. (000142a)
WARNING: Accidental start-up. Disconnect spark
plug wires when working on unit. Failure to do
so could result in death or serious injury.
(000141)
Engine Oil Recommendations
To maintain the product warranty, the engine oil should
be serviced in accordance with the recommendations of
this manual. For your convenience, maintenance kits
designed and intended for use on this product are available from the manufacturer that include engine oil, oil
filter, air filter, spark plug(s), a shop towel and funnel.
These kits can be obtained by contacting Customer Service at 1-888-331-4569.
SAE 30
10W-30
Synthetic 5W-30
000399
12
Inspect Engine Oil Level
000115
005484
002404
A
B
A
B
005486
WARNING: Risk of burns. Allow engine to cool
before draining oil or coolant. Failure to do so
could result in death or serious injury. (000139)
Inspect engine oil level prior to each use, or every 8
hours of operation.
1. Place generator on a level surface.
2. Clean area around oil fill, and oil drain plug.
3. Remove oil fill cap and wipe dipstick clean (Fig. L).
Fig. L
2. Disconnect the spark plug wire from the spark plug
and place the wire where it cannot contact spark
plug.
3. Clean area around oil fill and oil drain plug.
4. Remove oil fill cap and wipe dipstick clean.
5. Tip unit and drain oil completely into a suitable container.
6. Once oil is sufficiently drained from unit, tip unit
back to a level position.
7. Insert funnel into oil fill opening (Fig. N). Add recommended engine oil as necessary.
Fig. N
4. To check oil level, insert dipstick into oil filler neck
without screwing it in (Fig. M).
Fig. M
5. Remove dipstick and verify oil level is within safe
operating range.
6. Add recommended engine oil as necessary.
NOTE: Verify oil level often during filling process to ensure
overfilling does not occur.
7. Replace oil fill cap and hand-tighten.
NOTE: Some units have more than one oil fill location. It is
only necessary to use one oil fill point.
Change Engine Oil
WARNING: Accidental start-up. Disconnect spark
plug wires when working on unit. Failure to do
so could result in death or serious injury.
(000141)
When using generator under extreme, dirty, dusty conditions, or in extremely hot weather, change oil more frequently.
NOTE: Don’t pollute. Conserve resources. Return used oil to
collection centers.
Change oil while engine is still warm from running, as
follows:
1. Place generator on a level surface.
8. To check oil level, remove funnel and insert dipstick
into oil filler neck without screwing it in (Fig. M).
9. Remove dipstick and verify oil level is within safe
operating range.
NOTE: Verify oil level often during filling process to ensure
overfilling does not occur.
10. Replace oil fill cap and hand-tighten.
11. Wipe up any spilled oil.
12. Properly dispose of oil in accordance with all applicable regulations.
Air Filter
Engine will not run properly and may be damaged if run
with a dirty air filter. Service air filter more frequently in
dirty or dusty conditions.
To service air filter (Fig. O):
1. Unscrew bolt and remove air filter cover.
2. Wash filter in soapy water. Squeeze dry in clean
cloth (DO NOT TWIST).
3. Clean air filter cover before installation.
4. Replace side cover and screws.
NOTE: To order a new air filter, contact a Service Dealer at 1888-331-4569.
Fig. O
13
Service Spark Plug
000211
005487
To service spark plug:
1. Remove spark plug cover.
2. Clean area around spark plug.
3. Remove and inspect spark plug.
4. Inspect electrode gap with wire feeler gauge and
reset spark plug gap to 0.6 - 0.7mm (0.024 - 0.028
in) (Fig. P).
Fig. P
NOTE: Replace spark plug if electrodes are pitted, burned or
porcelain is cracked. Use ONLY recommended replacement
plug. See Product Specifications.
5. Install spark plug finger tight, and tighten an additional 3/8 to 1/2 turn using spark plug wrench.
Inspect Muffler and Spark Arrester
NOTE: It is a violation of California Public Resource Code,
Section 4442, to use or operate the engine on any forestcovered, brush-covered, or grass-covered land unless the
exhaust system is equipped with a spark arrester, as defined
in Section 4442, maintained in effective working order.
Other states or federal jurisdictions may have similar laws.
Contact original equipment manufacturer, retailer, or
dealer to obtain a spark arrester designed for exhaust
system installed on this engine.
NOTE: Use ONLY original equipment replacement parts.
Inspect muffler for cracks, corrosion, or other damage.
Remove spark arrester, if equipped, inspect for damage
or carbon blockage. Replace parts as required.
Inspect Spark Arrester Screen
WARNING: Hot surfaces. When operating
machine, do not touch hot surfaces. Keep
machine away from combustibles during use.
Hot surfaces could result in severe burns or fire.
(000108)
Clean Spark Arrestor Screen
The engine exhaust muffler has a spark arrestor screen.
Inspect and clean the screen every 100 hours of operation or every season, whichever comes first.
To service spark arrestor (Fig. Q):
1. Remove the clamp to remove retainer.
2. Slide spark arrestor screens out from the muffler
outlet tube.
3. Inspect screens and replace if torn, perforated or
otherwise damaged. Do NOT use a defective screen.
If screen is not damaged, clean with a commercial
solvent.
4. Replace the screens, and retainer, and secure with
clamp.
Fig. Q
Valve Clearance
IMPORTANT NOTE: If uncomfortable about doing this
procedure, or the proper tools are not available, take
generator to the nearest service center to have valve
clearance adjusted.
Check valve clearance after the first fifty-hours of operation. Adjust as necessary.
• Intake — 0.10 ± 0.02mm (cold), (0.004" ± 0.001"
inches)
• Exhaust — 0.10 ± 0.02mm (cold) (0.004" ± 0.001"
inches)
Storage
General
DANGER: Explosion and Fire. Fuel and vapors
are extremely flammable and explosive. Store
fuel in a well ventilated area. Keep fire and
spark away. Failure to do so will result in death
or serious injury. (000143)
WARNING: Risk of Fire. Verify machine has properly cooled before installing cover and storing
machine. Hot surfaces could result in fire.
(000109)
It is recommended to start and run the generator for 30
minutes, every 30 days. If this is not possible, refer to the
following list to prepare unit for storage.
• DO NOT place a storage cover on a hot generator. Allow
unit to cool to room temperature before storage.
• DO NOT store fuel from one season to another unless
properly treated.
• Replace fuel container if rust is present. Rust in fuel will
cause fuel system problems.
• Cover unit with a suitable protective, moisture resistant
cover.
• Store unit in a clean, dry area.
• Always store generator and fuel away from heat and
ignition sources.
14
Prepare Fuel System/Engine for Storage
Fuel stored over 30 days can go bad and damage fuel
system components. Keep fuel fresh, use fuel stabilizer.
If fuel stabilizer is added to fuel system, prepare and run
engine for long term storage. Run engine for 10-15 minutes to circulate stabilizer throughout fuel system. Adequately prepared fuel can be stored up to 24 months.
NOTE: If fuel has not been treated with fuel stabilizer, it
must be drained into an approved container. Run engine
until it stops from lack of fuel. Use of fuel stabilizer in fuel
storage container is recommended to keep fuel fresh.
1. Change engine oil.
2. Remove spark plug.
3. Pour tablespoon (5-10cc) of clean engine oil or
spray a suitable fogging agent into cylinder.
WARNING: Vision Loss. Eye protection is required
to avoid spray from spark plug hole when
cranking engine. Failure to do so could result in
vision loss. (000181)
4. Pull starter recoil several times to distribute oil in
cylinder.
5. Install spark plug.
6. Pull recoil slowly until resistance is felt. This will
close valves so moisture cannot enter engine cylinder. Gently release recoil.
Change Oil
Change engine oil before storage. See, Change Engine
Oil.
15
Troubleshooting
PROBLEMCAUSECORRECTION
Engine won't start.
1. Dial turned off.
2. Out of fuel.
3. Defective spark plug.
4. Plugged fuel filter.
5. Defective or stuck Dial assembly.
6. Incorrect engine oil level.
7. Defective ignition coil.
8. Fuel cap vent OFF.
9. Carb is flooded.
10. Throttle plate closed.
1. Turn on Dial.
2. Fill fuel tank.
3. Replace spark plug.
4. Replace fuel and fuel filter.
5. Contact Customer Service at 1-888331-4569.
6. Check/fill engine oil.
7. Contact Customer Service at 1-888331-4569.
8. Turn fuel cap vent ON.
9. Drain carb.
10. Open throttle plate (push toward
back of unit).
Engine starts, then shuts
down.
Engine will not start; or
starts and runs rough.*
No AC output.
Fuel leaks from drain hoses.
1. Out of fuel.
2. Incorrect engine oil level.
3. Contaminated fuel.
4. Defective low oil level switch.
1. Choke is stuck or left on.
2. Dirty or clogged air filter.
3. Defective or dirty spark plug.
4. Dirty fuel filter.
5. Dirty or gummed up carburettor.
6. Unit not warmed up.
7. Spark arrestor clogged.
1. Generator is overloaded.
2. Inverter module is overheated.
3. Short circuit in electrical device.
4. Defective inverter assembly.
1. Carburetor drain in bowl is not
closed.
1. Fill fuel tank.
2. Check engine oil level.
3. Contact Customer Service at 1-888331-4569.
4. Contact Customer Service at 1-888331-4569.
1. Turn choke off.
2. Clean or replace air filter.
3. Replace spark plug.
4. Replace fuel and fuel filter.
5. Clean carburetor.
6. Gradually adjust Dial and reduce
choke until engine runs smoothly in
RUN position.
7. Clean spark arrestor.
1. Disconnect all loads. Shut down generator to reset module. Reduce loads,
restart generator.
2. Verify service door is ON. Let cool 15
minutes by running engine without
AC output. Press and hold Reset button on control panel, restart generator.
3. Verify condition of extension cords
and items being powered. Press and
hold Reset button on control panel.
4. Contact Customer Service at 1-888331-4569.
1. Turn valve clockwise to close.
* Engine speed increases and decreases — This is normal as generator starts up and loads vary.
16
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.