Craftsman 580.325600, 580.326300 Owner's Manual

5600 Watt AC Generator
Model No.
580.325600
HOURS: Mon. - Fri. 8 a.m. to 5 p.m. (CT)
Part No. 191559GS Draft 10 (03/01/2005)
Owner’s Manual
Safety
Operation
Maintenance
Parts
Español
GENERATOR
CUSTOMER
HELPLINE
1-800-222-3136
PRECAUCIÓN
Antes de utilizar el producto, lea este
manual y siga todas las Reglas de Seguridad e Instrucciones de Uso.
CAUTION
Before using this product, read this
manual and follow all Safety Rules
and Operating Instructions.
Sears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.A.
Visit our Craftsman website: www.craftsman.com
2
TABLE OF CONTENTS
WARRANTY
LIMITED WARRANTY FOR DELUXE PORTABLE GENERATORS
SEARS warrants to the original purchaser that the alternator and engine for its portable generator will be free from defects in materials or workmanship for the items and period set forth below from the date of original purchase. This warranty is not transferable and applies only to portable generators driven by the Sears warranted engine.
CONSUMER* COMMERCIAL*
Alternator 2 years (2nd year parts only) 1 year Engine 2 years (2nd year parts only) 1 year
* NOTE: For the purpose of this warranty “Consumer Use” means personal residential household and emergency use by original purchaser, not to be used as a primary source of power. “Commercial Use” means all other uses, including rental, construction, commercial, and income producing purposes. Once a generator has experienced commercial use, it shall thereafter be considered a commercial use generator for the purpose of this warranty.
During said warranty period, SEARS will, at its option, repair or replace any part which, upon examination by SEARS, is found to be defective under normal use and service**. Starting batteries are not warranted by SEARS. All transportation costs under warranty, including return to the factory if necessary, are to be borne by the purchaser and prepaid by him. This warranty does not cover normal maintenance and service and does not apply to a generator set, alternator or engine, or parts which have been subjected to improper or unauthorized installation or alteration, misuse, negligence, accident, overloading, overspeeding, improper maintenance, repair or storage so as, in SEARS’s judgment, to adversely affect its performance and reliability.
** NORMAL WEAR: As with all mechanical devices, engines need periodic parts service and replacement to perform well. This warranty will not cover repair when normal use has exhausted the life of a part or engine.
THERE IS NO OTHER EXPRESS WARRANTY. SEARS HEREBY DISCLAIMS ANY AND ALL IMPLIED WARRANTIES, INCLUDING BUT NOT LIMITED TO THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO THE EXTENT PERMITTED BY LAW. THE DURATION OF ANY IMPLIED WARRANTIES WHICH CANNOT BE DISCLAIMED IS LIMITED TO THE TIME PERIOD AS SPECIFIED IN THE EXPRESS WARRANTY. LIABILITY FOR CONSEQUENTIAL, INCIDENTAL, OR SPECIAL DAMAGES UNDER ANY AND ALL WARRANTIES IS EXCLUDED.
Some states do not allow limitations on how long an implied warranty lasts, or the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other rights, which vary from state to state.
For service, see your nearest SEARS authorized warranty service facility. Warranty service can be performed only by a SEARS authorized service facility. This warranty will not apply to service at any other facility. At the time of requesting warranty service, evidence of original purchase date must be presented.
SEARS, ROEBUCK AND CO., Dept. D/817 WA, Hoffman Estates, IL 60179 U.S.A
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SAFETY RULES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
FEATURES AND CONTROLS . . . . . . . . . . . . . . . . . . . . . . 5
ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-11
SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-15
STORAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
SCHEMATIC DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . 18
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . . . 20-28
NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
EMISSION CONTROL WARRANTY . . . . . . . . . . . . . . 30-31
ESPAÑOL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-51
HOW TO ORDER PARTS . . . . . . . . . . . . . . . . BACK PAGE
© Sears, Roebuck and Co.
3
SAFETY RULES
Read this manual carefully and become familiar with your generator. Know its applications, its limitations, and any hazards involved.
The safety alert symbol ( ) is used with a signal word (DANGER, CAUTION, WARNING), a pictorial and/or a safety message to alert you to hazards. DANGER indicates a hazard which, if not avoided, will result in death or serious injury. WARNING indicates a hazard which, if not avoided, could result in death or serious injury. CAUTION indicates a hazard which, if not avoided, might result in minor or moderate injury. CAUTION, when used without the alert symbol, indicates a situation that could result in equipment damage. Follow safety messages to avoid or reduce the risk of injury or death.
Hazard Symbols and Meanings
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
The engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
WARNING
• This generator does not meet U. S. Coast Guard Regulation 33CFR-183 and should not be used on marine applications.
• Failure to use the appropriate U. S. Coast Guard approved generator could result in bodily injury and/or property damage.
WARNING
Fire
Explosion
Toxic Fumes
Hot Surface
Electrical Shock
Electrocution
Electrical Shock
Kickback
• Operate generator ONLY outdoors.
• Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes or other openings.
• DO NOT operate generator inside any building or enclosure, including the generator compartment of a recreational vehicle (RV).
Running generator gives off carbon monoxide, an odorless, colorless, poison gas.
Breathing carbon monoxide will cause nausea, fainting or death.
WARNING
• When using generator for backup power, notify utility company. Use approved transfer equipment to isolate generator from electric utility.
• Use a ground circuit fault interrupter (GFCI) in any damp or highly conductive area, such as metal decking or steel work.
• DO NOT touch bare wires or receptacles.
• DO NOT use generator with electrical cords which are worn, frayed, bare or otherwise damaged.
• DO NOT operate generator in the rain.
• DO NOT handle generator or electrical cords while standing in water, while barefoot, or while hands or feet are wet.
• DO NOT allow unqualified persons or children to operate or service generator.
Generator produces powerful voltage. Failure to isolate generator from power utility
can result in death or injury to electric utility workers due to backfeed of electrical energy.
WARNING
• When starting engine, pull cord slowly until resistance is felt and then pull rapidly to avoid kickback.
• NEVER start or stop engine with electrical devices plugged in and turned on.
Rapid retraction of starter cord (kickback) will pull hand and arm toward engine faster than you can let go.
Broken bones, fractures, bruises or sprains could result.
WARNING
4
• DO NOT tamper with governed speed. Generator supplies correct rated frequency and voltage when running at governed speed.
• DO NOT modify generator in any way.
Excessively high operating speeds increase risk of injury and damage to generator.
Excessively low speeds impose a heavy load.
CAUTION
• See “Don’t Overload Generator”.
• Start generator and let engine stabilize before connecting electrical loads.
• Connect electrical loads in OFF position, then turn ON for operation.
• Turn electrical loads OFF and disconnect from generator before stopping generator.
Exceeding generators wattage/amperage capacity can damage generator and/or electrical devices connected to it.
CAUTION
• Use generator only for intended uses.
• If you have questions about intended use, ask dealer or contact Sears.
• Operate generator only on level surfaces.
• DO NOT expose generator to excessive moisture, dust, dirt, or corrosive vapors.
• DO NOT insert any objects through cooling slots.
• If connected devices overheat, turn them off and disconnect them from generator.
• Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
Improper treatment of generator can damage it and shorten its life.
CAUTION
WHEN ADDING OR DRAINING FUEL
• Turn generator OFF and let it cool at least 2 minutes before removing fuel cap. Loosen cap slowly to relieve pressure in tank.
• Fill or drain fuel tank outdoors.
• DO NOT overfill tank. Allow space for fuel expansion.
• Keep fuel away from sparks, open flames, pilot lights, heat, and other ignition sources.
• DO NOT light a cigarette or smoke.
WHEN STARTING EQUIPMENT
• Ensure spark plug, muffler, fuel cap and air cleaner are in place.
• DO NOT crank engine with spark plug removed.
• If fuel spills, wait until it evaporates before starting engine.
WHEN OPERATING EQUIPMENT
• Do not tip engine or equipment at angle which causes fuel to spill.
• DO NOT choke carburetor to stop engine.
• This generator is not for use in mobile equipment or marine applications.
WHEN TRANSPORTING OR REPAIRING EQUIPMENT
• Transport/repair with fuel tank EMPTY or with fuel shutoff valve OFF.
• Disconnect spark plug wire.
WHEN STORING FUEL OR EQUIPMENT WITH FUEL IN TANK
• Store away from furnaces, stoves, water heaters, clothes dryers or other appliances that have pilot light or other ignition source because they can ignite fuel vapors.
Fuel and its vapors are extremely flammable and explosive.
Fire or explosion can cause severe burns or death.
WARNING
• DO NOT touch hot surfaces.
• Allow equipment to cool before touching.
• The generator must be at least 5 feet from structures having combustible walls and/or other combustible materials.
• Keep at least 3 feet of clearance on all sides of generator for adequate cooling, maintenance and servicing.
• In the State of California a spark arrester is required by law (Section 4442 of the California Public Resources Code). Other states may have similar laws. Federal laws apply on federal lands. If you equip the muffler with a spark arrester, it must be maintained in effective working order.You can order a spark arrester through your authorized Sears service dealer.
Running engines produce heat. Temperature of muffler and nearby areas can reach or exceed 150°F (65°C).
Severe burns can occur on contact. Combustible debris, such as leaves, grass,
brush, ect. can catch fire.
WARNING
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR GENERATOR
• Disconnect the spark plug wire from the spark plug and place the wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
• Use approved spark plug tester.
• DO NOT check for spark with spark plug removed.
Unintentional sparking can result in fire or electric shock.
WARNING
5
KNOW YOUR GENERATOR
Read the owner’s manual and safety rules before operating your generator.
Compare the illustrations with your generator to familiarize yourself with the locations of various controls and adjustments. Save this manual for future reference.
120 Volt AC, 20 Amp, Duplex Receptacles — May be used to supply electrical power for the operation of 120 Volt AC, 20 Amp, single phase, 60 Hz electrical, lighting, appliance, tool and motor loads.
120/240 Volt AC, 30 Amp Locking Receptacle — May be used to supply electrical power for the operation of 120 and/or 240 Volt AC, 30 Amp, single phase, 60 Hz electrical, lighting, appliance, tool and motor loads.
Air Cleaner — Protects engine by filtering dust and debris out of intake air.
Choke Lever — Used when starting a cold engine. Circuit Breakers (AC) — Push to reset circuit
breakers are provided to protect the generator against electrical overload.
Fuel Tank — Capacity of five (5) U.S. gallons. Fuel Valve — Used to turn fuel on and off to engine. Grounding Fastener — If required, please consult a
qualified electrician, electrical inspector, or local agency having jurisdiction.
Oil Fill — Add engine oil here. Recoil starter — Used to start the engine. Rocker Switch — Set this switch to "On" before using
recoil starter. Set switch to "Off" to switch off engine. Spark Arrester Muffler — Exhaust muffler lowers
engine noise and is equipped with a spark arrester screen.
(2) 120 Volt AC, 20 Amp Duplex Receptacles
Fuel Tank
Choke Lever
Recoil Handle Starter
Rocker Switch (on engine shroud)
Circuit Breakers (AC)
120/240 Volt AC, 30 Amp Receptacle
Spark Arrester Muffler (not shown)
Air Cleaner
Grounding Fastener
Oil Fill
Fuel Valve (not shown)
FEATURES AND CONTROLS
6
Your Craftsman generator requires some assembly and is ready for use only after it has been properly serviced with the recommended oil and fuel.
If you have any problems with the assembly of your generator, please call the generator helpline at 1-800-222-3136.
IMPORTANT: Any attempt to run the engine before it
has been serviced with the recommended oil will result in an engine failure.
REMOVE GENERATOR FROM CARTON
Set the carton on a rigid flat surface with “up” arrows pointing upward.
Carefully open the top flaps of the shipping carton.
Slice two corners at one end of carton from top to bottom and lay that side of carton down flat.
Remove all packing material, carton fillers, etc.
Remove the generator from the shipping carton.
CARTON CONTENTS
Check all contents. If any parts are missing or damaged, call the generator helpline at 1-800-222-3136.
The main unit
Owner’s manual
Engine oil
120/240 Volt, 30 Amp locking plug
Wheel Kit
ASSEMBLING THE WHEEL KIT
The wheel kit is designed to greatly improve the portability of your generator.
NOTE: Wheel kit is not intended for over-the-road use. You will need a socket wrench with 1/2" or 13mm
sockets and a needle-nose plier to install this kit.
Refer to illustration shown below and install the wheel kit as follows:
1. Place the bottom of the generator cradle on a flat, even surface. Temporarily place unit on blocks to ease assembly.
2. Slide axle through both axle mounting brackets on cradle frame, as shown.
3. Slide a wheel over the axle.
NOTE: Be sure to install both wheels with the air pressure valve on the outboard side.
4. Place the e-ring onto the groove in the axle. You may add the flat washer if desired.
5. Place one end of the needle nose pliers on the bottom of the axle and the other end of the pliers on top of the e-ring. Seat the e-ring by pressing the pliers closed.
6. Repeat step 3 through 5 to secure second wheel.
7. Remove the temporary blocks.
8. To aid support leg assembly, rest generator on cradle, engine end down. Attach the support leg with two M8 x 16mm cap screws and two locking hex nuts as shown.
9. Use two 13 mm wrenches to tighten leg hardware. Rest generator on wheels and support leg.
10. Center the handle bracket on generator frame at support leg end of cradle, as shown.
11. Attach handle bracket with two M8 x 45mm cap screws and two locking hex nuts.
12. Check that all fasteners are tight and the tires are inflated to the value marked on the tire or within 15 and 40 psi.
ASSEMBLY
Wheel Kit Assembly View
Support Leg
Hex Nut
Axle
Flat Washer
Cap Screw
Handle Assembly
Hex Nut
Wheel
E-Ring
Cap Screw
7
BEFORE STARTING THE GENERATOR
To operate the generator you will need to first add engine oil and gasoline, as follows:
Add Engine Oil
NOTE: When adding oil to the engine crankcase, use
only high quality detergent oil rated with API service classification SF, SG, SH, SJ or higher. DO NOT use special additives.
1. Choose a viscosity according to the table below:
NOTE: Synthetic oil meeting ILSAC GF-2, API certification mark and API service symbol with “SJ/CF ENERGY CONSERVING” or higher, is an acceptable oil at all temperatures. Use of synthetic oil does not alter required oil change intervals.
* The use of multi-viscosity oils (5W-30, 10W-30, etc.) in temperatures above 40°F (4°C) will result in higher than normal oil consumption. When using a multi­viscosity oil, check oil more frequently.
** If using SAE 30 oil in temperatures below 40°F (4°C), it will result in hard starting and possible engine bore damage due to inadequate lubrication.
2. Place generator on a level surface.
3. Clean area around yellow oil fill cap. Remove oil fill cap.
4. Slowly fill engine with oil through oil fill opening until oil level is to the point of overflowing.
5. Install yellow oil fill cap and finger tighten securely.
6. Check engine oil level before starting each time thereafter. If oil level is below the point of overflowing, fill to proper level.
NOTE: Check oil often during engine break–in.
Add Fuel
NOTE: This gasoline engine is certified to operate on
gasoline. Exhaust Emission Control System: EM (Engine Modifications).
1. Use clean, fresh, regular UNLEADED fuel with a minimum of 85 octane with equipment. DO NOT use fuel which contains Methanol. DO NOT mix oil with fuel.
2. Clean area around fuel fill cap, remove cap.
3. Slowly add regular unleaded fuel to fuel tank. Be careful not to overfill. Allow about 1.5" of tank space for fuel expansion, as shown here.
4. Install fuel cap and wipe up any spilled fuel.
CAUTION! Alcohol-blended fuels (called gasohol,
ethanol or methanol) can attract moisture, which leads to separation and formation of acids during storage. Acidic gas can damage the fuel system of an engine while in storage.
To avoid engine problems, the fuel system should be emptied before storage of 30 days or longer. Drain the fuel tank, start the engine and let it run until the fuel lines and carburetor are empty. Use fresh fuel next season. See “Storage” on page 16 for additional information.
NEVER use engine or carburetor cleaner products in the fuel tank as permanent damage may occur.
Fuel
Tank
1.5” Airspace
Synthetic 5W-30, 10W-30
5W-30, 10W-30
30
°F -20 0 20 32 40 60 80 100
°C -30 -20 -10 0 10 20 30 40
STARTING TEMPERATURE RANGE ANTICIPATED BEFORE NEXT OIL CHANGE
WHEN ADDING FUEL
• Turn generator OFF and let it cool at least 2 minutes before removing fuel cap. Loosen cap slowly to relieve pressure in tank.
• Fill fuel tank outdoors.
• DO NOT overfill tank. Allow space for fuel expansion.
• Keep fuel away from sparks, open flames, pilot lights, heat, and other ignition sources.
• DO NOT light a cigarette or smoke.
Fuel and its vapors are extremely flammable and explosive.
Fire or explosion can cause severe burns or death.
WARNING
8
HOW TO USE YOUR GENERATOR
If you have any problems operating your generator, please call the generator helpline at 1-800-222-3136.
System Ground
The generator has a system ground that connects the generator frame components to the ground terminals on the AC output receptacles. The system ground is connected to the AC neutral wire (the neutral is bonded to the generator frame).
Special Requirements
There may be Federal or State Occupational Safety and Health Administration (OSHA) regulations, local codes, or ordinances that apply to the intended use of the generator. Please consult a qualified electrician, electrical inspector, or the local agency having jurisdiction.
In some areas, generators are required to be registered with local utility companies.
If the generator is used at a construction site, there may be additional regulations which must be observed.
Connecting to a Building’s Electrical System
Connections for standby power to a building’s electrical system must be made by a qualified electrician. The connection must isolate the generator power from utility power, and must comply with all applicable laws and electrical codes.
Generator Location
Generator Clearance
The generator must be at least 5 ft. (152 cm) from structures having combustible walls and/or other combustible materials. Leave at least 3 ft. (92 cm) all around generator including overhead, for adequate cooling, maintenance and servicing.
Place generator in a well ventilated area, which will allow for removal of deadly exhaust gas. DO NOT place generator where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building. Ensure exhaust gas is kept away from any windows, doors, ventilation intakes or other openings that can allow exhaust gas to collect in a confined area. Prevailing winds and air currents should be taken into consideration when positioning generator.
OPERATION
• When using generator for backup power, notify utility company. Use approved transfer equipment to isolate generator from electric utility.
• Use a ground circuit fault interrupter (GFCI) in any damp or highly conductive area, such as metal decking or steel work.
• DO NOT touch bare wires or receptacles.
• DO NOT use generator with electrical cords which are worn, frayed, bare or otherwise damaged.
• DO NOT operate generator in the rain.
• DO NOT handle generator or electrical cords while standing in water, while barefoot, or while hands or feet are wet.
• DO NOT allow unqualified persons or children to operate or service generator.
Generator produces powerful voltage. Failure to isolate generator from power utility
can result in death or injury to electric utility workers due to backfeed of electrical energy.
WARNING
• Operate generator ONLY outdoors.
• Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes or other openings.
• DO NOT operate generator inside any building or enclosure, including the generator compartment of a recreational vehicle (RV).
Running generator gives off carbon monoxide, an odorless, colorless, poison gas.
Breathing carbon monoxide will cause nausea, fainting or death.
WARNING
Exhaust Port
Typical Generator Shown
TO START THE ENGINE
Disconnect all electrical loads from the generator. Use the following start instruction steps by numerical order:
1. Make sure unit is on a level surface. IMPORTANT: Failure to start and operate unit on a
level surface will cause the unit not to start or shut down during operation.
2. Turn the fuel valve to the “On” position.
3. Place the choke lever in the “Choke” position.
4. Set the rocker switch to “On” position.
5. Grasp the recoil handle and pull slowly until slight resistance is felt. Then pull rapidly to start engine.
IMPORTANT: If engine floods, place choke lever in “Run” position and crank until engine starts.
6. Move choke lever to “Run” position a short
distance at a time over several seconds in warm weather or minutes in cold weather. Let engine run smoothly before each change. Operate with choke in “Run” position.
NOTE: If engine starts after 3 pulls but fails to run, or if unit shuts down during operation, make sure unit is on a level surface and check for proper oil level in crankcase. This unit may be equipped with a low oil protection device.
To Stop the Engine
1. Unplug all electrical loads from generator panel receptacles. NEVER start or stop engine with electrical devices plugged in and turned on.
2. Let engine run at no-load for several minutes to stabilize internal temperatures of engine and generator.
3. Move rocker switch to “Off” position.
4. Move fuel valve to “Off” position.
Connecting Electrical Loads
DO NOT connect 240 Volt loads to 120 Volt
receptacles.
DO NOT connect 3–phase loads to generator.
DO NOT connect 50 Hz loads to generator.
Let engine stabilize and warm up for a few minutes
after starting.
Plug in and turn on desired 120 and/or 240 Volt
AC, single phase, 60 Hz electrical loads.
DO NOT OVERLOAD THE GENERATOR. See
“Don’t Overload Generator”.
9
“Off”
Position
“On”
Position
Rocker Switch
is shown in the
On position
• See “Don’t Overload Generator”.
• Start generator and let engine stabilize before connecting electrical loads.
• Connect electrical loads in OFF position, then turn ON for operation.
• Turn electrical loads OFF and disconnect from generator before stopping generator.
Exceeding generators wattage/amperage capacity can damage generator and/or electrical devices connected to it.
CAUTION
• DO NOT touch hot surfaces.
• Allow equipment to cool before touching.
• The generator must be at least 5 feet from structures having combustible walls and/or other combustible materials.
• Keep at least 3 feet of clearance on all sides of generator for adequate cooling, maintenance and servicing.
• In the State of California a spark arrester is required by law (Section 4442 of the California Public Resources Code). Other states may have similar laws. Federal laws apply on federal lands. If you equip the muffler with a spark arrester, it must be maintained in effective working order.You can order a spark arrester through your authorized Sears service dealer.
Running engines produce heat. Temperature of muffler and nearby areas can reach or exceed 150°F (65°C).
Severe burns can occur on contact. Combustible debris, such as leaves, grass,
brush, ect. can catch fire.
WARNING
• When starting engine, pull cord slowly until resistance is felt and then pull rapidly to avoid kickback.
• NEVER start or stop engine with electrical devices plugged in and turned on.
Rapid retraction of starter cord (kickback) will pull hand and arm toward engine faster than you can let go.
Broken bones, fractures, bruises or sprains could result.
WARNING
DO NOT stop engine by moving choke lever to “Choke” position. Backfire, fire or engine damage could occur.
CAUTION
10
CORD SETS AND RECEPTACLES
Use only high quality, well-insulated, extension cords with the generator’s 120 Volt electrical receptacles.
Check the ratings of all extension cords before you use them. Extension cord sets used should be rated for 125 Volt AC loads at 20 Amps or greater for most electrical devices. Some devices, however, may not require this type of extension cord. Check the owner’s manuals of those devices for the manufacturer’s recommendations.
Keep extension cords as short as possible, preferably less than 15 feet long, to prevent voltage drop and possible overheating of wires.
120 Volt AC, 20 Amp Duplex Receptacle
Each receptacle is protected against overload by a single 20 Amp push-to-reset circuit breaker. Use each receptacle to operate 120 Volt AC, single phase 60 Hz electrical loads requiring up to 2,400 watts (2.4 kW) at 20 Amps of current.
120/240 Volt AC, 30 Amp Receptacle
This is a full capacity receptacle; it can supply the generator’s full rated output from this sole outlet. The outlet is protected by two 20 Amp push–to–reset circuit breakers.
A NEMA L14-30 plug is used with this 240 Volt receptacle. Connect a suitable 4-wire cord set to the plug and to the desired load. The cord set should be rated for 250 Volt AC loads at 30 Amps (or greater).
4-Wire Cord Set
240V
120V
120V
W (Neutral)
X (Hot)
Y (Hot)
NEMA L14-30
Ground (Green)
• NEVER attempt to power a device requiring more amperage than generator or receptacle can supply.
• DO NOT overload the generator. See “Don’t Overload Generator”.
Receptacles may be marked with rating value greater than generator output capacity.
CAUTION
11
DON'T OVERLOAD GENERATOR
Capacity
You must make sure your generator can supply enough rated (running) and surge (starting) watts for the items you will power at the same time. Follow these simple steps:
1. Select the items you will power at the same time.
2. Total the rated (running) watts of these items. This is the amount of power your generator must produce to keep your items running. See the table on the right.
3. Estimate how many surge (starting) watts you will need. Surge wattage is the short burst of power needed to start electric motor-driven tools or appliances such as a circular saw or refrigerator. Because not all motors start at the same time, total surge watts can be estimated by adding only the item(s) with the highest additional surge watts to the total rated watts from step 2.
Example:
Total Rated (Running) Watts = 3075 Highest Additional Surge Watts = 1800 Total Generator Output Required = 4875
Power Management
To prolong the life of your generator and attached devices, it is important to take care when adding electrical loads to your generator. There should be nothing connected to the generator outlets before starting it's engine. The correct and safe way to manage generator power is to sequentially add loads as follows:
1. With nothing connected to the generator, start the engine as described in this manual.
2. Plug in and turn on the first load, preferably the largest load you have.
3. Permit the generator output to stabilize (engine runs smoothly and attached device operates properly.
4. Plug in and turn on the next load.
5. Again, permit the generator to stabilize.
6. Repeat steps 4 and 5 for each additional load. NEVER add more loads than the generator capacity.
Take special care to consider surge loads in generator capacity, as described above.
*Wattages listed are approximate only. Check tool or appliance for actual wattage.
Tool or Appliance
Rated
(Running) Watts
Additional Surge
(Starting) Watts Window Air Conditioner
1200
1800
Refrigerator
800
1600
Deep Freezer
500
500
Television
500
-
Light (75 Watts)
75
-
3075 Total
Running Watts
1800 Highest
Surge Watts
Tool or Appliance
Rated*
(Running)
Watts
Additional
Surge
(Starting)
Watts
Essentials
Light Bulb - 75 watt
75
-
Deep Freezer
500
500
Sump Pump
800
1200
Refrigerator/Freezer - 18 Cu. Ft.
800
1600
Water Well Pump - 1/3 HP
1000
2000
Heating/Cooling
Window AC - 10,000 BTU
1200
1800
Window Fan
300
600
Furnace Fan Blower - 1/2 HP
800
1300
Kitchen
Microwave Oven - 1000 Watt
1000
-
Coffee Maker
1500
-
Electric Stove - Single Element
1500
-
Hot Plate
2500
-
Family Room
DVD/CD Player
100
-
VCR
100
-
Stereo Receiver
450
-
Color Television - 27”
500
­Personal Computer w/17” monitor
800
-
Other
Security System
180
­AM/FM Clock Radio
300
­Garage Door Opener - 1/2 HP
480
520 Electric Water Heater - 40 Gallon
4000
-
DIY/Job Site
Quartz Halogen Work Light
1000
-
Airless Sprayer - 1/3 HP
600
1200
Reciprocating Saw
960
960 Electric Drill - 1/2 HP
1000
1000
Circular Saw - 7 1/4”
1500
1500
Miter Saw - 10”
1800
1800
Table Planer - 6”
1800
1800 Table Saw/Radial Arm Saw ­10”
2000
2000
Air Compressor - 1-1/2 HP
2500
2500
12
ENGINE TECHNICAL INFORMATION
This is a single cylinder, overhead valve(OHV), air cooled engine. It is a low emissions engine.
In the State of California, Model Series 200000 engines are certified by the California Air Resources Board to meet emissions standards for 250 hours. Such certification does not grant the purchaser, owner or operator of this engine any additional warranties with respect to the performance or operational life of this engine. The engine is warranted solely according to the product and emmisions warranties stated elsewhere in this manual.
Power Ratings
The power ratings for an individual engine model are initially developed by starting with SAE (Society of Automotive Engineers) code J1940 (Small Engine Power & Torque Rating Procedure) (Revision 2002-
05). Given both the wide array of products on which our engines are placed, and the variety of environmental issues applicable to operating the equipement, it may be that the engine you have purchased will not develop the rated horsepower when used in a peice of power equipment (actual “on-site” power). This difference is due to a variety of factors including, but not limited to, the following: differences in altitude, temperature, barometric pressure, humidity, fuel, engine lubrication, maximum governed engine speed, individual engine to engine variability, design of the particular peice of power equipment, the manner in which the engine is operated, engine run-in to reduce friction and clean out of combustion chambers, adjustments to the valves and carburetor, and other factors. The power ratings may also be adjusted based on comparisons to other similar engines utilizedin similar applications, and will thereforenot necessarily match the values derived using the foregoing codes.
PRODUCT SPECIFICATIONS
Generator Specifications
Rated Maximum Power . . . . . . . . . 5600 Watts (5.6 kW)
Surge Power . . . . . . . . . . . . . . . . . 8600 Watts (8.6 kW)
Rated AC Voltage . . . . . . . . . . . . . . . . . . . 120/240 Volts
Rated Maximum AC Current
at 240 Volts . . . . . . . . . . . . . . . . . . . . . 23.3 Amperes
at 120 Volts . . . . . . . . . . . . . . . . . . . . . 46.6 Amperes
Rated Frequency . . . . . . . . . . . . . . . 60 Hz at 3600 rpm
Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Single Phase
Unit Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170 lbs.
Engine Specifications
Rated Horsepower . . . . . . . . . . . . . . . . . 10 at 3600 rpm
Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.12 in. (79mm)
Stroke . . . . . . . . . . . . . . . . . . . . . . . . . . 2.44 in. (62mm)
Displacement . . . . . . . . . . . . . . . . . . . 18.64 in. (305 cc)
Spark Plug
Type: . . . . . . . . . . Champion RC12YC or Equivalent
Set Gap To: . . . . . . . . . . . . . . . . 0.030inch (0.76mm)
Armature Air Gap: . . . . . . . . . . . . . . . . . . 0.008-0.012 in.
(0.20-0.30mm) Valve clearance with valve springs installed and piston 1/4 in. (6 mm) past top dead center (check when engine is cold).
Intake . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.004-0.006 in.
(0.10-0.15 mm)
Exhaust . . . . . . . . . . . . . . . . . . . . . . . . . . 0.004-0.006 in.
(0.10-0.15 mm)
Fuel Capacity . . . . . . . . . . . . . . . . . . . . . . 5 U.S. gallons
Oil Capacity . . . . . . . . . . . . . . . .28 Ounces (.8 Liters)
Oil Type:
Above 40° F . . . . . . . . . . . . . . . . . . . . . . . .Sae 30
Below 40° F . . . . . . . . . . . .SAE 5W-30 or 10W-30
SPECIFICATIONS
13
GENERAL RECOMMENDATIONS
Regular maintenance will improve the performance and extend the life of the generator. See any authorized Sears dealer for service.
The generator’s warranty does not cover items that have been subjected to operator abuse or negligence. To receive full value from the warranty, the operator must maintain generator as instructed in this manual.
Some adjustments will need to be made periodically to properly maintain your generator.
All service and adjustments should be made at least once each season. Follow the requirements in the “Maintenance Schedule” chart above.
NOTE: Once a year you should clean or replace the spark plug and replace the air filter. A new spark plug and clean air filter assure proper fuel-air mixture and help your engine run better and last longer.
EMISSION CONTROL
Maintenance, replacement or repair of the emission control devices and systems may be performed by any non-road engine repair establishment or individual.
GENERATOR MAINTENANCE
Generator maintenance consists of keeping the unit clean and dry. Operate and store the unit in a clean dry environment where it will not be exposed to excessive dust, dirt, moisture or any corrosive vapors. Cooling air slots in the generator must not become clogged with snow, leaves, or any other foreign material.
Check the cleanliness of the generator frequently and clean when dust, dirt, oil, moisture or other foreign substances are visible on its exterior surface.
NOTE: DO NOT use a garden hose to clean generator. Water can enter the engine fuel system and cause problems. In addition, if water enters the generator through cooling air slots, some of the water will be retained in voids and cracks of the rotor and stator winding insulation. Water and dirt buildup on the generator internal windings will eventually decrease the insulation resistance of these windings.
Generator Cleaning
Daily or before use, clean accumulated debris from generator. Keep linkage, spring and controls clean. Keep area around and behind muffler free from any combustible debris.
Generator parts should be kept clean to reduce the risk of overheating and ignition of accumulated debris.
Use a damp cloth to wipe exterior surfaces clean.
Use a soft bristle brush to loosen caked on dirt, oil,
etc.
Use a vacuum cleaner to pick up loose dirt and debris.
Use low pressure air (not to exceed 25 psi) to blow
away dirt. Inspect cooling air slots and openings on the generator. These openings must be kept clean and unobstructed.
MAINTENANCE
OWNER’S RESPONSIBILITIES
Follow the hourly or calendar intervals, whichever occurs first. More frequent service is required when operating in adverse conditions noted below.
¹ Change oil after the first (5) operating hours and every 50 hours or every year, whichever occurs first, thereafter.
Change sooner when operating under dirty or dusty conditions.
² Clean or replace more often under dirty or dusty conditions.
• DO NOT expose generator to excessive moisture, dust, dirt, or corrosive vapors.
• DO NOT insert any objects through cooling slots.
Improper treatment of generator can damage it and shorten its life.
CAUTION
MAINTENANCE SCHEDULE
FILL IN DATES AS YOU
COMPLETE REGULAR SERVICE
SERVICE DATES
SERVICE DATES
MAINTENANCE TASK
Before
Each Use
Every 25 Hours
or Yearly
Every 50 Hours
or Yearly
Every 100
Hours or Yearly
Check oil level
X
Clean debris
X
Change engine oil
Service air cleaner
Service spark plug
X
Service spark arrester
X
Clean cooling system
Prepare for storage If unit is to remain idle for longer than 30 days.
14
ENGINE MAINTENANCE
Checking Oil Level
Oil level should be checked prior to each use or at least every 5 hours of operation. Keep oil level maintained.
Changing Engine Oil
Change the oil after the first 5 hours of operation. Change oil every 50 hours thereafter. If you are using your generator under extremely dirty or dusty conditions, or in extremely hot weather, change the oil more often.
KEEP OUT OF REACH OF CHILDREN. DON'T POLLUTE. CONSERVE RESOURCES. RETURN USED OIL TO COLLECTION CENTERS.
Change the oil while the engine is still warm from running, as follows:
1. Clean area around oil drain plug. The oil drain plug is located at base of engine, opposite carburetor.
2. Remove oil drain plug and oil fill cap and drain oil completely into a suitable container.
3. Install oil drain plug and tighten securely.
4. Fill oil sump with recommended oil to the point of overflowing. See page 7 for oil recommendations.
5. Install oil cap. Tighten cap securely.
6. Wipe up any spilled oil.
Clean/Replace Spark Plug
Change the spark plug every 100 hours of operation or once each year, whichever comes first. This will help your engine to start easier and run better.
1. Clean area around spark plug.
2. Remove and inspect spark plug.
3. Check electrode gap with wire feeler gauge and set spark plug gap to 0.030 inch (0.76mm) if necessary.
4. Replace spark plug if electrodes are pitted, burned or porcelain is cracked. Use a recommended replacement plug.
NOTE: You can purchase a new spark plug by calling 1-800-366-PART.
Service Air Cleaner
Your engine will not run properly and may be damaged if you run it using a dirty air cleaner. Clean or replace the air cleaner paper filter once every 25 hours of operation or once a year, whichever comes first. Clean or replace more often if operating under dusty or dirty conditions.
Service Air Filter
1. Loosen screws and remove air cleaner cover. Remove paper filter.
2. Install clean (or new) air cleaner assembly inside cover. Dispose of old filter properly.
3. Assemble air cleaner cover onto base and tighten screws.
NOTE: You can purchase new air cleaner elements by calling 1-800-366-PART.
Cartridge
Screw
Cover
Base
• Used motor oil has been shown to cause skin cancer in certain laboratory animals.
• Thoroughly wash exposed areas with soap and water.
Avoid prolonged or repeated skin contact with used motor oil.
CAUTION
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR GENERATOR
• Disconnect the spark plug wire from the spark plug and place the wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
• Use approved spark plug tester.
• DO NOT check for spark with spark plug removed.
Unintentional sparking can result in fire or electric shock.
WARNING
15
Carburetor
If you think your carburetor needs adjusting, see your nearest Sears service center. Engine performance may be affected at altitudes above 3000 feet. For operation at higher elevations, contact your nearest Sears service center.
Clean Spark Arrester Screen
The engine exhaust muffler has a spark arrester screen. Inspect and clean the screen every 100 hours of operation or once each year, whichever comes first.
NOTE: You can purchase a new spark arrester screen by calling 1-800-366-PART.
If you use your generator on any forest-covered, brush­covered, or grass-covered unimproved land, it must have a spark arrester. The spark arrester must be maintained in good condition by the owner/operator.
Clean and inspect the spark arrester as follows:
1. To remove muffler heat shield from muffler, remove four screws that connect guard to muffler bracket.
2. Remove four screws that attach spark arrester screen.
3. Inspect screen and replace if torn, perforated or otherwise damaged. DO NOT use a defective screen. If screen is not damaged, clean it with commercial solvent.
4. Reattach screen and muffler guard.
Air Cooling System
Over time debris may accumulate in cylinder cooling fins and cannot be observed without partial engine disassembly. For this reason, we recommend you have an authorized Sears service dealer clean the cooling system per recommended intervals (see “Maintenance Schedule” on page 13). Equally important is to keep top of engine free from debris. See “Generator Cleaning”.
Muffler
Spark Arrester Screen
Heat Shield
• DO NOT touch hot surfaces.
• Allow equipment to cool before touching.
• The generator must be at least 5 feet from structures having combustible walls and/or other combustible materials.
• Keep at least 3 feet of clearance on all sides of generator for adequate cooling, maintenance and servicing.
• In the State of California a spark arrester is required by law (Section 4442 of the California Public Resources Code). Other states may have similar laws. Federal laws apply on federal lands. If you equip the muffler with a spark arrester, it must be maintained in effective working order.
Running engines produce heat. Temperature of muffler and nearby areas can reach or exceed 150°F (65°C).
Severe burns can occur on contact. Combustible debris, such as leaves, grass,
brush, ect. can catch fire.
WARNING
16
STORAGE
GENERAL
The generator should be started at least once every seven days and allowed to run at least 30 minutes. If this cannot be done and you must store the unit for more than 30 days, use the following information as a guide to prepare it for storage.
Long Term Storage Instructions
It is important to prevent gum deposits from forming in essential fuel system parts, such as the carburetor, fuel filter, fuel hose or tank during storage. Also, experience indicates that alcohol-blended fuels (called gasohol, ethanol or methanol) can attract moisture, which leads to separation and formation of acids during storage. Acidic fuel can damage the fuel system of an engine while in storage.
To avoid engine problems, the fuel system should be emptied before storage of 30 days or longer. Follow these instructions:
Protect Fuel System
1. Remove all gasoline from fuel tank to prevent gum deposits from forming on these parts and causing possible malfunction of engine.
2. Run engine until engine stops from lack of fuel.
Change Oil
While engine is still warm, drain oil from crankcase. Refill with recommended grade.
Oil Cylinder Bore
Remove spark plug and pour about 1 ounce (30ml) of clean engine oil into the cylinder.
Install spark plug and crank slowly to distribute oil.
Generator
1. Clean generator as outlined in “Generator Cleaning”.
2. Check that cooling air slots and openings on
generator are open and unobstructed.
Other Storage Tips
1. DO NOT store fuel from one season to another.
2. Replace fuel can if it starts to rust. Contaminated
fuel will cause engine problems.
3. If possible, store unit indoors and cover it to give
protection from dust and dirt. BE SURE TO EMPTY FUEL TANK.
4. Cover unit with a suitable protective cover that
does not retain moisture.
5. Store generator in clean, dry area.
• DO NOT place a storage cover over a hot generator.
• Let equipment cool for a sufficient time before placing the cover on the equipment.
Storage covers can be flammable.
WARNING
WHEN STORING FUEL OR EQUIPMENT WITH FUEL IN TANK
• Store away from furnaces, stoves, water heaters, clothes dryers or other appliances that have pilot light or other ignition source because they can ignite fuel vapors.
WHEN DRAINING FUEL
• Turn generator OFF and let it cool at least 2 minutes before removing fuel cap. Loosen cap slowly to relieve pressure in tank.
• Drain fuel tank outdoors.
• Keep fuel away from sparks, open flames, pilot lights, heat, and other ignition sources.
• DO NOT light a cigarette or smoke.
Fuel and its vapors are extremely flammable and explosive.
Fire or explosion can cause severe burns or death.
WARNING
• NEVER crank engine with spark plug removed.
Unintentional sparking can result in fire or electric shock.
WARNING