Product Guide
EBDSM-PRM
Ceiling PIR presence/absence detector
The EBDSM-PRM PIR (passive infrared) presence detector
provides automatic control of lighting loads with optional
manual control.
The output channel comprises a mains voltage relay
capable of simple on/off switching.
Functioning as a presence detector, the unit can turn lights
on when a room is occupied and off when the room is
empty. Optional settings allow lights to be turned off in
response to ambient daylight.
All functionality is fully programmable using an IR handset.
Overview
Front features
Back features
Power Input
& Switched
Output
connections
Sensor Lens
which covers...
PIR Sensor
IR Receiver
Light Level Sensor
Status LEDs
Switch Input
Connector
Features
PIR Sensor
Detects movement within the unit’s detection range,
allowing load control in response to changes in occupancy.
IR Receiver
Receives control and programming commands from an
IR (infrared) handset.
Light Level Sensor
Measures the overall light level in the detection area
Status LEDs
The LED flashes Red to indicate the following:
Walk Test LED active
Valid setting received
Power Input & Switched Output Connector
Used to connect mains power to the unit and to connect a
switched load.
Switch Input Connector
Two input terminals can be used to manually override the
lights on or off.
when movement is detected
Power Input
& Switched
Output Connector
Detection diagram
Area of lower sensitivity Area of high sensitivity
Sensor functionality
Detection Mode
The Detection Mode can be set to behave in Presence or Absence mode:
Presence When movement is detected the load will automatically turn on. When the area is no longer occupied the
load will automatically switch off after an adjustable time period.
Absence The load is manually switched on. When the area is no longer occupied the load will automatically switch
off after the adjustable time period has elapsed.
In either case, sensitivity to movement of the PIR sensor can be adjusted using the Sensitivity parameter.
HINT: To assist in setting the Sensitivity, turn on the Walk Test LED which will flash red when movement is detected.
Switch Level On/Off
Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level
parameters.
2
Choosing a Suitable Location
The EBDSM-PRM is designed to be ceiling mounted and must satisfy the following criteria:
Avoid positioning the unit where direct sunlight may enter the sensor element.
Do not site the sensor within 1m of any lighting, forced air heating or ventilation.
Do not fix the sensor to an unstable or vibrating surface.
Installation
Absence detection
To use absence detection a retractive (momentary) switch must be connected between the 2 terminals on the
diagram. Note that this will be switching mains voltage.
The unit ships with presence detection as default. To change to absence detection, press and release the external
switch 5 times within the first minute of power up. The LED will turn on solid for 30 seconds to indicate absence
mode has been selected.
To change back to presence detection, repeat the above procedure—the LED will flash for 30 seconds to indicate
presence mode has been selected.
Note: the above adjustments can also be made using the UHS5 or UNLCDHS handsets. See Programming sections.
Power-up test procedure
When power is applied to the unit, the load will turn on immediately.
Set the timeout to 10 seconds, vacate the room or remain very still and wait for the load to switch off .
Check that the load switches on when movement is detected.
The unit is now ready for programming.
3