Cozy CDV336C, CDV335C, CDV256C, CDV155C, CDV156C, CDV255C User Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
DIRECT VENT
WALL FURNACE
INSTALLATION AND
OPERATING INSTRUCTIONS
P/N 70905
REV. 06/2015
MODEL NUMBERS
NA TURAL GASCDV155CCDV255CCDV335C
L.P . GASCDV156CCDV256CCDV336C
W ARNING: If the information in these instructions ar e
not followed exactly, a fir e or explosion may result
causing property damage, personal injury or death.
-Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
-WHA T TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor’ s
phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire
department.
-INST ALLATION AND SERVICE MUST BE
PERFORMED BY A QUALIFIED INST ALLER,
SERVICE AGENCY OR THE GAS SUPPLIER.
The appliance may be installed in an aftermarket permanently located, manufactured home (USA only)
or mobile home, where not prohibited by local codes. This appliance is only for use with the type of
gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a
certified kit is used.
WARNING: Operation of this furnace without the properly installed, furnished vent system and vent
cap could result in Carbon Monoxide (CO) poisoning and possible death. For your safety, this furnace
and the vent system should be inspected at least annually by a qualified service technician.
CDV25/
CDV33-C
INST ALLER: Leave this manual with the
appliance.
CONSUMER: Retain this manual for
future reference.
The coating selected to provide longer life to
the heat exchanger may smoke slightly upon
initial firing. Please provide adequate
ventilation if this occurs.
CDV15-C
This unit is for residential use only and is not approved for installation in greenhouses, or environments
involving dusty, wet, corrosive, or explosive conditions. Such conditions will invalidate the warranty and
may create unsafe conditions.
Installation, maintenance, service, trouble shooting and repairs must be performed by a qualified service agency .
Mr./Mrs. Homeowner , DO NOT attempt any of these procedures yourself as this could expose you to property
damage, personal injury , or loss of life and will invalidate all warranties.
The State of Massachusetts r equires that installation and service of a gas appliance be
performed by a plumber or gas fitter licensed in the Commonwealth of Massachusetts.
Trouble Shooting……………………….18
Parts Drawing………………………….. 14//16
Parts List……………………………….. 15 /17
Warranty………………………………..21
INTRODUCTION
THIS IS A GAS-FIRED, DIRECT VENT WALL FURNACE THAT WILL OPERATE SAFELY AND
PROVIDE AN EFFICIENT SOURCE OF HEAT WHEN INSTALLED, OPERATED AND
MAINTAINED AS RECOMMENDED IN THESE INSTALLATION AND OPERATING
INSTRUCTIONS. READ THESE INSTRUCTIONS THOROUGHLY BEFORE INSTALLING,
SERVICING, OR USING THE APPLIANCE. IF YOU DO NOT UNDERSTAND ANY PART OF
THESE INSTRUCTIONS CONSULT LOCAL AUTHORITIES, OTHER QUALIFIED INSTALLERS,
SER VICE TECHNICIAN, THE GAS SUPPLIER OR THE MANUF ACTURER.
SPECIFICATIONS AND DIMENSIONS
Your Direct Vent Wall Furnace is shipped complete in one carton. This carton contains the furnace, vent
cap, vent tube, air inlet tube, template with rough-in dimensions, installation and operating instructions, and
the thermostat with thermostat wire. NOTE: There will be two cartons if optional vent kit or blower is purchased.
1.Improper installation, adjustment, alteration, service, or maintenance can cause property damage, bodily injury, or death.
2.Use in other than a residential application may result in unsatisfactory performance and may void the warranty.
3 .This appliance must be installed in accordance with local codes, if any; if not, follow the National Fuel Gas Code ANSI
Z223.1/NFP A 54 or the National Gas and Propane Installation Code CSA-B149.1.
4 .Do not install this wall furnace in a recreational vehicle or trailer.
5.Do not operate wall furnace unless it is connected to the factory supplied vent system with vent cap in place.
6.Check the rating label attached to the wall furnace to be sure it is equipped for the type gas you intend to use.
7 .Never use a match, candle, flame or other source of ignition to check for gas leaks. Use only soapy water or liquid detergent.
8.Have your wall furnace and vent system inspected at least annually by a qualified service technician.
Page 2
SAFETY RULES - CONT’D.
9 .Before cleaning or servicing, turn off the gas and allow furnace to cool.
10.
Do not operate wall furnace without outer casing in place.
Due to high temperatures, the wall furnace should be located out of traffic and away from furniture and drapes.
11.
12.
Children and adults should be alerted to the hazard of high surface temperature and should be kept away to avoid burns or
clothing ignition.
13.
Young children should be carefully supervised when they are in the same room with the wall furnace.
Do not place clothing or other flammable material on or near the furnace.
14.
15.
Installation and repair should be done by a qualified service technician. The wall furnace should be inspected before use
and at least annually by a professional service technician. More frequent cleaning may be required due to excessive lint
from carpeting, bedding material, etc. It is imperative that control compartments, burner, and circulating air passageways of
the furnace be kept clean.
16. Do not install in a closet, alcove, or small hallway where the furnace could be isolated from the space to be heated by
closing a door.
17. Do not put anything around the furnace or vent cap that will obstruct the flow of combustion and ventilation air.
18. The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local
codes, with the latest edition of National Electrical Code, ANSI/NFPA 70. In Canada, use CSA C22.1 Canadian
Electrical Code.
19. Never operate this furnace without the sight glass in place or with the glass broken or missing.
20. If it is suspected that rising water may enter the furnace, turn off the gas immediately. Do not use this appliance if any part
has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the
control system and any gas control which has been under water.
21. It is necessary to replace damaged gaskets or sealing material within the vent or air intake system. Failure to do so may
result in property damage, personal injury or loss of life.
22.
Any safety screen or guard removed for servicing must be replaced prior to operating heater.
23. A gas appliance must not be connected to a chimney flue serving a separate solid-fuel burning appliance.
CLEARANCES
CDV15-CCDV25 / CDV33-C ALL VENT CAPS
CEILING
24”
1”
LEFT SIDE WALL
1/2”
FLOOR
FIGURE 1
1.
If the wall furnace is installed directly on carpeting, tile or any combustible material other than wood flooring,
1”
LEFT SIDE WALL
RIGHT SIDE WALL
FIGURE 2
CEILING
30”
1”0”
4”
FLOOR
RIGHT SIDE WALL
FIGURE 3
12”
Min.
18” Min.
9”
Min.
12” Min.
the wall furnace shall be installed on a metal plate or wood panel secured to the floor, extending the full width
and depth of the wall furnace.
2. RESIDENTIAL GARAGE INSTALLATION:Gas utilization equipment in residential garages shall
be installed so that all burners and burner ignition devices are located not less than 18 inches (46cm)
above the floor . Such equipment shall be located, or protected so it is not subject to damage by a
moving vehicle. Use care in selecting a good location within the garage. DO NOT locate the appliance
where heated air will be directed onto a nearby parked vehicle. Paint may discolor or rubber may
harden and crack. DO NOT allow heated discharge air to blow directly onto open or closed containers
of paint, gasoline or other liquids having flammable vapors.
Page 3
V ent T erminal
Air Supply Inlet
Area where terminal is not permitted
VENT TERMINAL CLEARANCES
REFERENCE LETTER TO DRA WINGCANADIAN INST ALLATIONSU.S. INSTALLA TIONS
1
2
A = Clearance above grade, veranda,12 Inches (30 cm)12 Inches (30 cm)
porch, deck, or balcony
B = Clearance to window or door that12 Inches (30 cm)9 Inches (23 cm)
may be opened
C = Clearance to permanently closed12 Inches (30 cm)9 Inches (23 cm)
window
D = V ertical clearance to ventilated sof fit1 8 Inches (46 cm)18 Inches (46 cm)
located above the terminal within a
horizontal distance of 2 Feet (61 cm)
from the center line of the terminal
E = Clearance to unventilated soffit18 Inches (46 cm)18 Inches (46 cm)
F = Clearance to outside corner12 Inches (30 cm)12 Inches (30 cm)
G = Clearance to inside corner12 Inches (30 cm)12 Inches (30 cm)
H = Clearance to each side of center line3 Feet (91 cm) within a heightClearance in accordance with
extended above meter/regulator15 Feet (4.5m) above the meter/local installation codes and the
assemblyregulator assemblyrequirements of the gas supplier
I = Clearance to service regulator3 Feet (91 cm)Clearance in accordance with
vent outletlocal installation codes and the
requirements of the gas supplier
J = Clearance to nonmechanical air supply 12 Inches (30 cm)12 Inches (30 cm)
inlet to building or the combustion
air inlet to any other appliance
K = Clearance to a mechanical air supply6 Feet (1.83 m)3 Feet (91 cm) above if within
inlet10 Feet (3 m) horizontally
L = Clearance above paved sidewalk or7 Feet (2.13m) A vent shall notClearance in accordance with
paved driveway located on publicterminate directly above a sidewalk orlocal installation codes and the
propertypaved driveway that is located betweenrequirements of the gas supplier
two single family dwellings and
serves both dwellings
M = Clearance under veranda, porch,12 Inches (30 cm) permitted only ifClearance in accordance with
deck, or balconyveranda, porch, deck, or balcony islocal installation codes and the
fully open on a minimum of two sidesrequirements of the gas supplier
1
In accordance with the current CSA-B149.1 Natural Gas and Propane Installation Code
2
In aaccordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code
Page 4
LOCATION
1)The wall furnace must be installed on an outside wall.
2)For optimal heat distribution, locate furnace as centrally as possible in the area to be heated and where occupants may move
about freely without coming into contact with the grille.
3)If the furnace is installed in a basement, a 12” clearance must be maintained between ground level and the bottom of the
vent cap. Do not install furnace where vent cap will terminate in a window well or any other opening below ground level.
INSTALLATION
Failure to follow these instructions carefully could result in poor performance, property damage, personal
injury or death.
STEP 1. LOCATE VENT OPENING.Locate wall studs and center 9” vent opening a minimum of 22”
for CDV15 or 24-1/8” for CDV25/33 above the floor. To locate furnace at minimum clearance from floor, remove template from
carton and set on floor at location desired. On model CDV15, position template no closer than 1” from either side wall. For
model CDV25/33, position template 1” minimum from a left side wall or 0” from a right side wall. Check outside wall to be sure
there is proper clearances around the vent cap. See Figure 3. Next, mark and cut out the vent openings on both the inside and
outside walls (be sure to keep the holes level). See Figure 5. If a higher location on the wall is desired, raise bottom of template
to desired height, make sure template is level and centered between studs, mark and cut out vent openings.
STEP 2. ROUGH-IN GAS SUPPLY . Install a ½” diameter gas supply line. This line can enter through the
floor, side, or rear wall. For location of gas connection to valve, see Fig. 4. The gas supply line must have an individual manual
shut off valve located outside the cabinet, accessible from the room where the heater is installed. Install a drip leg immediately
ahead of the gas valve and provide a 1/8” N.P.T. plugged tapping, accessible for test gauge connection, immediately upstream of
the gas supply connection. The furnace and the individual shut off valve must be disconnected from the gas supply piping system
during any pressure testing of that system at test pressures in excess of 1/2” psig (3.5kPa). The furnace must be isolated from the
gas supply piping system by closing the individual manual shut off valve during any pressure testing of the gas piping system at
test pressures equal to or less than 1/2” psig (3.5kPa).
STEP 3. INSTALLING FURNACE – 5” TO 9” WALLS. Use only the exhaust tube, air intake
tube, wall thimble extension, and vent terminal provided with furnace. Do not attempt to lengthen the exhaust or air intake tubes,
this could cause an imbalance in the furnace resulting in poor performance and pilot outage, see Figure 6. Extend the telescoping
wall thimble extension (surrounding the wall thimble assembly) to approximately 9 inches. Center the wall thimble assembly in
the 9 inch opening and attach to inside wall using eight (8) screws. The wall thimble extension should extend through the
opening and be adjusted so end of wall thimble extension is even with outside wall. Install furnace flush to wall by sliding
exhaust tube and air intake tube through the wall thimble assembly. Secure the furnace to the wall with screws through each of
the four holes in the mounting brackets located on the back of the furnace. These holes are spaced so as to allow the screws to
enter into studs that are on 16 inch centers. On certain types of wall, anchors (not provided) may be required. Slide the vent
terminal onto the exhaust tube and the air intake tube. Secure vent terminal and vent terminal spacer plate to wall providing a
slight downward slope to the vent tubes. This will prevent water from entering. Anchors (not provided) may be required. Caulk
around vent terminal spacer plate with putty provided. See Figure 7. NOTE: Some framing may be necessary to provide a flat
surface for the vent terminal spacer plate to butt against, so rain cannot enter through cut out.
Page 5
INSTALLING FURNACE – 9 TO 15” WALLS (CDV15/CDV25-C). For
9” to 15” wall use V ent Kit No. VK1525/9-15-B. Do not attempt to lengthen the exhaust tube, air intake tube, or wall thimble extension
provided with furnace or the VK1525/9-15-B Vent Kit. Disconnect the air intake tube, and the exhaust tube from the back of the
furnace and discard. See Figure 6. Replace with exhaust tube and air intake tube from Kit No. VK1525/9-15-B. Discard the 5”
telescoping wall thimble extension that surrounds the wall thimble assembly. Center the wall thimble assembly in the 9” openin g and
attach to inside wall using eight (8) screws. Install furnace flush to wall by sliding exhaust tube and air intake tube through the wall
thimble assembly. Secure the furnace to the wall with screws through each of the four holes in the mounting brackets located o n the
back of the furnace. These holes are spaced so as to allow the screws to enter into studs that are on 16-inch centers. On certain
types of wall, anchors (not provided) may be required. From outside the building install the thick wall thimble extension, Part No.
43835, supplied in V ent Kit No. VK1525/9-15-B by sliding it through the cut out and over the wall thimble assembly . The wall thimble
extension should be even with the outside wall (some trimming may be necessary). Slide the vent terminal onto the exhaust tube and
the air intake tube. Secure vent terminal and vent terminal spacer plate to wall providing a slight downward slope to the vent tubes.
This will prevent water from entering. Anchors (not provided) may be required. Caulk around the vent terminal spacer plate with
putty provided. See Figure 7. NOTE: Some framing may be necessary to provide a flat surface for the vent terminal spacer plate to
butt against, so rain cannot enter through cut out.
INSTALLING FURNACE – 15” TO 24” WALLS (CDV15/CDV25-C).
For 15” to 24” wall use only V ent Kit No. VK1525/15-24-B. Do not attempt to lengthen the exhaust tube, air intake tube, or wall thimble
extension provided with furnace. The VK1525/15-24-B Vent Kit has a one inch restrictor in the exhaust tube which is necessary for
proper and safe operation of this furnace. Do not use any other vent kit. Disconnect the air intake tube and the exhaust tube from
the back of the furnace and discard, see Figure 6. Install the exhaust tube and air intake tube from Vent Kit No. VK1525/15-24-B.
Discard the 5” telescoping wall thimble extension that surrounds the wall thimble assembly. Center the wall thimble assembly i n the
9” opening and attach to inside wall using eight (8) screws. Install furnace flush to wall by sliding exhaust tube and air intake tube
through the wall thimble assembly. Secure the furnace to the wall with screws through each of the four holes in the mounting
brackets located on the back of the furnace. These holes are spaced so as to allow the screws to enter into studs that are on 16-inch
centers. On certain types of walls, anchors (not provided) may be required. From outside the building install the wall thimble
extension, Part No. 43730, supplied in Vent Kit No. VK1525/15-24-B by sliding it through the cut out and over the wall thimble
extension. For walls 15” to 19” the wall thimble extension, air intake tube, and the exhaust tube must be trimmed even with the outside
wall. Slide the vent terminal onto the exhaust tube and into the air intake tube. Secure vent terminal and vent terminal spacer plate
to wall providing a slight downward slope to the vent tubes. This will prevent water from entering. Anchors (not provided) may be
required. Caulk around the vent terminal spacer plate with putty provided, see Figure 7. NOTE: Some framing may be necessary to
provide a flat surface for the vent terminal spacer plate to butt against, so rain cannot enter through the cut out.
INSTALLING FURNACE – 9 TO 15” WALLS (CDV33-C). For 9” to 15” wall use Vent
Kit No. VK33/9-15-B. Do not attempt to lengthen the exhaust tube, air intake tube, or wall thimble extension provided with furnace
or the VK33/9-15-B Vent Kit. Disconnect the air intake tube, and the exhaust tube from the back of the furnace and discard. See
Figure 6. Replace with exhaust tube and air intake tube from Kit No. VK33/9-15-B. Discard the 5” telescoping wall thimble extension
that surrounds the wall thimble assembly. Center the wall thimble assembly in the 9” opening and attach to inside wall using e ight
(8) screws. Install furnace flush to wall by sliding exhaust tube and air intake tube through the wall thimble assembly. Secure the
furnace to the wall with screws through each of the four holes in the mounting brackets located on the back of the furnace. These
holes are spaced so as to allow the screws to enter into studs that are on 16-inch centers. On certain types of wall, anchors (not
provided) may be required. From outside the building install the thick wall thimble extension, Part No. 43835, supplied in V en t Kit No.
VK33/9-15-B by sliding it through the cut out and over the wall thimble assembly. The wall thimble extension should be even with
the outside wall (some trimming may be necessary). Slide the vent terminal onto the exhaust tube and the air intake tube. Secure vent
terminal and vent terminal spacer plate to wall providing a slight downward slope to the vent tubes. This will prevent water from
entering. Anchors (not provided) may be required. Caulk around the vent terminal spacer plate with putty provided. See Figure 7.
NOTE: Some framing may be necessary to provide a flat surface for the vent terminal spacer plate to butt against, so rain cannot
enter through cut out.
Page 6
18”
CABINET
34-1/2”
CABINET
29-3/4”
22”
1/2”
Center Line Pipe Elbow
SHUT OFF
V ALVE
DRIP LEG
FIG. 4 / CDV15-C
1” MINIMUM SIDE WALL TYP.
WALL STUDS
16” O.C.
TEMPLATE
9” DIA.
OPENING
8”
1/8” N.P.T.
PRESSURE TAP
9”
GAS VALVE
INLET
1/2”
1/2” BLACK IRON PIPE
FLOOR
GAS
SUPPLY
9” DIA.
OPENING
4”
13-3/8”
FLOOR
31-3/4”
24-1/8”
FIG. 4 / CDV25/33-C
1” MINIMUM SIDE WALL TYP.
16-5/8”
SHUT OFF
VALVE
DRIP
LEG
WALL STUDS 16” O.C.
TEMPLATE
MOUNTING
HOLES
GAS V AL VE
INLET
1/8” N.P.T.
PRESSURE TAP
GAS SUPPLY
13”
1/2” BLACK
IRON PIPE
MOUNTING
HOLES
FIG. 5 / CDV15-C
FIG. 6 / CDV15-C
EXHAUST
TUBE
AIR
INTAKE TUBE
FIG. 5 / CDV25/33-C
EXHAUST
TUBE
AIR
INTAKE TUBE
FIG. 6 / CDV25/33-C
Page 7
Loading...
+ 15 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.