Cotek CR Series, CR-21 User Manual

Page 1
CR Series User’s Manual
CR-21 Remote Control For SR-1600 / SRC-2500
Page 2
1-1. System
The remote is designed to easily and quickly connect Cotek SR-1600 /
SRC-2500. The LCD display is used for setting up the inverter/charger, as well
as displaying current status or fault messages. Pressing buttons allows you to
select a menu item or to save a setting, once it is displayed on the LCD screen.
Description
Function
A
UP
Scroll up
B
DOWN
Scroll down
C
ESC
Go back to previous page.
D
ENTER
Enter next page and save setting value
E
RJ-45 port
Connect to the Inverter
Front and rear Panel introduction
Page 3
1-2. Mechanical Drawings Unit: mm
1-3. Hardware Installation
Page 4
2. Display tree
Power Switch ON
INVERTER
Initialization..
GRID-->SR-->LOAD BAT-------^ Major
2-1
User Interface
2-3
LCD Contrast
2-3-1
LCD Auto-off
2-3-2
Baudrate
2-3-3
DRY C Setting
2-3-4
Bat Parameter
2-4
OVP Setting
2-4-1
OVP Recovery
2-4-2
UVP Setting
2-4-3
UVP Recovery
2-4-4
UV Alarm
2-4-5
Charge Voltage
(For SRC)
2-4-6
Charge Current
(For SRC)
2-4-7
AC Parameter
2-5
O/P Voltage
2-5-1
O/P Frequency
2-5-2
Sync Frequency
2-5-3
AC or DC Mode
2-5-4
AC Sharing
2-5-5
OUTPUTxxx.xV
xx.xHz xxx.xA
GRIDxxx.xV
xx.xHz xxx.xA
BATTERYxxx.xV
discharging xxx.xA
STATUS
2-2
Enter into System Setup by “press for 3 seconds”
Page 5
2-1 GRID-->SR-->LOAD BAT-------^ Major
The connection status and Alarm type. For the description of alarm type, (Major / Minor Alarm) please refer to Alarm List in the “SR-1600 User Manual.”
2-2 STATUS
It indicates Alarm Message. Please refer to LED Indicator in the SR-1600 User Manual.”
2-3 User Interface
2-3-1 LCD contrast : Sets the LCD screen contrast.
Default = 50% Setting range = 0% ~ 100%
Setting Menu
SETT<value>
LCD Contrast
0 ~ 100
2-3-2 LCD Auto-off : Sets the LCD screen backlight auto off timer Default = 120 seconds Setting range = 0 ~ 120 seconds
Setting Menu
SETT<value>
LCD Auto-off
0 ~ 120
2-3-3 Baud rate : Default setting4800
Setting Menu
SETT<value>
RS-485
Baud rate
0
1200
1
2400
2
4800
3
9600
4
19200
2-3-4 Dry contact C setting : Default =1, Setting range = 0~2, default=1.
Setting Menu
SETT<value>
Dry contact C setting
0
Disable
1
Follow dry contact A
(major alarm)
2
Follow dry contact B
(minor alarm)
Page 6
2-4 Bat Parameter
2-4-1 OVP Setting : Set the Over Voltage Protection (OVP) and shutdown. Default = 34 VDC @ 24V Model. 68 VDC @ 48V Model
Model
Setting value range
24V
30 VDC ~ 34 VDC
48V
60 VDC ~ 68 VDC
2-4-2 OVP Recovery : When the DC input voltage is higher than the OVP
setting, the SR series shuts down; once the input voltage falls below the set OVP value, the SR series will automatically restart. Default = 28 VDC @ 24V Model. 56 VDC @ 48V Model
Model
Setting value range
24V
26 VDC ~ 30 VDC
48V
52 VDC ~ 60 VDC
2-4-3 UVP Setting : Setting Under Voltage Protection (UVP) and shutdown on
the inverter operation. Default= 18 VDC @ 24V Model. 36VDC @ 48V Model
Model
Setting value range
24V
18 VDC ~ 25 VDC
48V
36 VDC ~ 50 VDC
2-4-4 UVP Recovery : When the DC input voltage is below the set UVP value,
the SR series shuts down; once the input voltage rises above the set UVP value, the SR series will automatically restart. Default= 25 VDC @ 24V Model. 50VDC @ 48V Model
Model
Setting value range
24V
23 VDC ~ 27 VDC
48V
46 VDC ~ 54 VDC
2-4-5 UV Alarm : Setting Under Voltage (UV) alarm. When the input voltage is
lower than the set value, the SR series will sound a “beep” to remind you
that the unit is going to shutdown. Default= 21 VDC @ 24 V Model. 42 VDC @ 48 V Model
Page 7
Model
Setting value range
24V
19 VDC ~ 26 VDC
48V
38 VDC ~ 52 VDC
2-4-6 Charging voltage (For SRC): Default =54 VDC
Model
Setting value range
48V
52 VDC ~ 58 VDC
2-4-7 Charging current (For SRC): Default =0 A
Model
Setting value range
48V
0A ~ 25A
2-5 AC Parameter
2-5-1 O/P Voltage : Setting the SR series output voltage on the inverter
operation. 1xx = 100, 110, 115 or 120V ; 2xx = 200V, 220V, 230V or 240V.
Model
Setting value range
1XX
97 VAC ~ 127 VAC
2XX
194 VAC ~ 254 VAC
2-5-2 O/P Frequency : Setting the SR series output frequency on the inverter operation. 1xx = 100, 110, 115 or 120V ; 2xx = 200V, 220V, 230V or 240V.
Model
Setting value range
1XX & 2XX
50 or 60 Hz
2-5-3 Sync Frequency : Setting SR series output frequency tolerance range on
the inverter operation. 1xx = 100, 110, 115, 120V ; 2xx = 200V, 220V,
230V or 240V.
Model
Setting value range
1XX & 2XX
0 Hz ~ 3 Hz
Page 8
2-5-4 AC or DC Mode : Default =1, AC Mode is the 1st priority source.
DC Mode:DC is the 1st priority source, and the AC power is the 2nd priority
source.
AC Mode:AC is the 1st priority source, and the DC power is the 2nd priority
source.
Mode Priority
SETT<value>
DC Mode
0
AC Mode
1
2-5-5 AC Sharing : Setting range = 10, 20, 30, 40, 50, 60, 70, 80, 90, 100
Default= 100 (Disable)
Setting Menu
SETT<value>
Description
AC Ratio
10
AC load 10%, DC load 90%
20
AC load 20%, DC load 80%
30
AC load 30%, DC load 70%
40
AC load 40%, DC load 60%
50
AC load 50%, DC load 50%
60
AC load 60%, DC load 40%
70
AC load 70%, DC load 30%
80
AC load 80%, DC load 20%
90
AC load 90%, DC load 10%
100
Disable