CR-21 Remote Control
For SR-1600 / SRC-2500

1. Introduction
1-1. System
The remote is designed to easily and quickly connect Cotek SR-1600 /
SRC-2500. The LCD display is used for setting up the inverter/charger, as well
as displaying current status or fault messages. Pressing buttons allows you to
select a menu item or to save a setting, once it is displayed on the LCD screen.
Go back to previous page.
Enter next page and save setting value
Front and rear Panel introduction

1-2. Mechanical Drawings
Unit: mm
1-3. Hardware Installation

2. Display tree
Power Switch ON
INVERTER
Initialization..
GRID-->SR-->LOAD
BAT-------^ Major
2-1
User Interface
2-3
LCD Contrast
2-3-1
LCD Auto-off
2-3-2
Baudrate
2-3-3
DRY C Setting
2-3-4
Bat Parameter
2-4
OVP Setting
2-4-1
OVP Recovery
2-4-2
UVP Setting
2-4-3
UVP Recovery
2-4-4
UV Alarm
2-4-5
Charge Voltage
(For SRC)
2-4-6
Charge Current
(For SRC)
2-4-7
AC Parameter
2-5
O/P Voltage
2-5-1
O/P Frequency
2-5-2
Sync Frequency
2-5-3
AC or DC Mode
2-5-4
AC Sharing
2-5-5
OUTPUT:xxx.xV
xx.xHz xxx.xA
GRID:xxx.xV
xx.xHz xxx.xA
BATTERY:xxx.xV
discharging xxx.xA
STATUS:
2-2
Enter into System Setup by “press for 3 seconds”

2-1 GRID-->SR-->LOAD BAT-------^ Major
The connection status and Alarm type. For the description of alarm type, (Major /
Minor Alarm) please refer to Alarm List in the “SR-1600 User Manual.”
2-2 STATUS:
It indicates Alarm Message. Please refer to LED Indicator in the SR-1600 User
Manual.”
2-3 User Interface
2-3-1 LCD contrast : Sets the LCD screen contrast.
Default = 50% Setting range = 0% ~ 100%
2-3-2 LCD Auto-off : Sets the LCD screen backlight auto off timer
Default = 120 seconds Setting range = 0 ~ 120 seconds
2-3-3 Baud rate : Default setting:4800
2-3-4 Dry contact C setting : Default =1, Setting range = 0~2, default=1.
Follow dry contact A
(major alarm)
Follow dry contact B
(minor alarm)

2-4 Bat Parameter
2-4-1 OVP Setting : Set the Over Voltage Protection (OVP) and shutdown.
Default = 34 VDC @ 24V Model. 68 VDC @ 48V Model
2-4-2 OVP Recovery : When the DC input voltage is higher than the OVP
setting, the SR series shuts down; once the input voltage falls below the set
OVP value, the SR series will automatically restart.
Default = 28 VDC @ 24V Model. 56 VDC @ 48V Model
2-4-3 UVP Setting : Setting Under Voltage Protection (UVP) and shutdown on
the inverter operation.
Default= 18 VDC @ 24V Model. 36VDC @ 48V Model
2-4-4 UVP Recovery : When the DC input voltage is below the set UVP value,
the SR series shuts down; once the input voltage rises above the set UVP
value, the SR series will automatically restart.
Default= 25 VDC @ 24V Model. 50VDC @ 48V Model
2-4-5 UV Alarm : Setting Under Voltage (UV) alarm. When the input voltage is
lower than the set value, the SR series will sound a “beep” to remind you
that the unit is going to shutdown.
Default= 21 VDC @ 24 V Model. 42 VDC @ 48 V Model

2-4-6 Charging voltage (For SRC): Default =54 VDC
2-4-7 Charging current (For SRC): Default =0 A
2-5 AC Parameter
2-5-1 O/P Voltage : Setting the SR series output voltage on the inverter
operation. 1xx = 100, 110, 115 or 120V ; 2xx = 200V, 220V, 230V or 240V.
2-5-2 O/P Frequency : Setting the SR series output frequency on the inverter
operation. 1xx = 100, 110, 115 or 120V ; 2xx = 200V, 220V, 230V or 240V.
2-5-3 Sync Frequency : Setting SR series output frequency tolerance range on
the inverter operation. 1xx = 100, 110, 115, 120V ; 2xx = 200V, 220V,
230V or 240V.

2-5-4 AC or DC Mode : Default =1, AC Mode is the 1st priority source.
DC Mode:DC is the 1st priority source, and the AC power is the 2nd priority
source.
AC Mode:AC is the 1st priority source, and the DC power is the 2nd priority
source.
2-5-5 AC Sharing : Setting range = 10, 20, 30, 40, 50, 60, 70, 80, 90, 100
Default= 100 (Disable)