COSMOGAS NOVADENS 24, NOVADENS 24C, NOVADENS 34, NOVADENS 34C, NOVADENS 45A User Manual

Page 1
62417003 - R00 07-12-2007_GB-IE
MODELS:
NOV ADENS 24 - 24B NOV ADENS 24C - 24P NOV ADENS 34 - 34B NOV ADENS 34C - 34P NOV ADENS 45A - 45C
USERS’ MANUAL FOR GAS BOILERS
PLEASE READ THE MANUAL CAREFULLY: IT CONTAINS IMPORTANT INFORMATION
Page 2
2
T able of contents
1 - GENERAL SAFETY WARNINGS........................................................................... 3
2 - GENERAL INFORMATION ..................................................................................... 4
2.1 - Introduction ............................................................................................................................... 4
2.2 - Description of models ............................................................................................................... 4
2.3 - Manufacturer ............................................................................................................................. 4
2.4 - Key to symbols used ................................................................................................................. 4
2.5 - Warranty ................................................................................................................................... 4
3 - USE.......................................................................................................................... 5
3.1 - Check that the cocks are open .................................................................................................. 5
3.2 - Check heating system pressure ................................................................................................ 5
3.3 - Overview...................................................................................................................................5
3.4 - Displays.................................................................................................................................... 6
3.5 - St art-up procedure .................................................................................................................... 6
3.6 - “Users’ menu”............................................................................................................................ 6
3.7 - Summer mode .......................................................................................................................... 7
3.8 - Winter mode .............................................................................................................................7
3.9 - Adjusting the heating temperature .............................................................................................7
3.10 - Adjusting the heating temperature with climatic adjustment......................................................7
3.1 1 - Domestic hot water temperature adjustment ............................................................................ 8
3.12 - Room temperature adjustment ................................................................................................ 8
3.13 - Errors and alarms ................................................................................................................... 8
3.14 - Pressure gauge ......................................................................................................................8
3.15 - Shutdown procedure ............................................................................................................... 9
3.16 - Precautions against freezing ................................................................................................... 9
3.17 - Flue gas discharge ................................................................................................................. 9
3.18 - Operating anomalies............................................................................................................... 9
3.19 - Remote control (on request) .................................................................................................. 10
4 - Warranty................................................................................................................. 11
4.1 - General warranty conditions ....................................................................................................11
4.2 - Instructions for filling in the warranty card ................................................................................. 11
4.3 - Warranty limits......................................................................................................................... 11
Page 3
3
If you smell gas
l Close the gas cock. l Ventilate the room. l Do not use any electrical appliances, telephone
included.
l Immediately call a qualified technician or the gas
board from another room or building. If you cannot contact them, call the Fire Brigade.
If you smell product of the combustion
l Switch off the appliance. l Ventilate the room. l Call a qualified technician.
In the presence of water leaks
l Switch off the appliance. l Close the central water mains cock. l Call a qualified technician.
Explosive or easily inflammable products
Do not store or use explosive or easily inflammable materials such as paper, solvents, paints, etc..., in the same room as the boiler.
In the event of a breakdown
In the event of breakdown and/or malfunctioning of the appliance, disconnect it, do not attempt to repair it or intervene in any way whatsoever. Cont act a qualified technician.
Qualified technicians
Qualified technicians are personnel with specific, technical training in the heating system component sector and with regards to domestic hot water production for public use, fuel gas systems and electrical systems. These individuals must have the legally required qualifications.
1 - GENERAL SAFETY WARNINGS
FThis booklet forms an integral and essential
part of the product and must be carefully kept by the user, for any future consult ation. Ensure that this booklet is handed over to the new owners and/or installer if the appliance should change hands or be moved for any reason whatsoever.
FThe installation, setting and modification of
the gas appliance must be carried out by qualified technicians, in compliance with local and national norms and the instructions in the installation and maintenance manual.
FFlue pipes must not be modified in any way. FThe user, in accordance with these instructions,
must keep the appliance in satisfactory running order and ensure reliable, safe operating.
F The user is responsible for employing a
qualified technician to carry out maintenance work on the appliance in compliance with local and national norms and the matters stated in the installation and maintenance manual. We highly recommend arranging a regular maintenance contract with a qualified technician.
FThe manufacturer cannot be held responsible
for any damage to people, animals or property caused by inadequate maintenance.
FDo not obstruct the ends of the venting pipes . FThe technician will explain the functioning,
use of the appliance and use of the system to the user.
FThe user must be familiar with filling and
discharge procedures for the boiler, and the control and eventual adjustment of water pressure in the heating circuit.
FThe user must be familiar with the
procedures for fully optimizing the conservation of energy and avoiding waste of the entire heating system.
FRegularly check the system pressure using
the pressure gauge “13” (see figure 1) to ensure a reading between 1 and 1.5 bar.
FWait a few minutes after opening the gas
supply cock before starting the boiler up.
FDo not leave the boiler switched on
unnecessarily if it is not going to be used for long periods; in such situations, close the gas cock and disconnect from the electricity mains supply . Consult section 3.16 if there is a risk of freezing.
FDo not touch the flue gas discharge pipe,
during and for some time after operations, as it is very hot.
Page 4
4
2 - GENERAL INFORMATION
2.1 - Introduction
Congratulations! Y ou have ef fectively purchased one of the best products on the market. Each single part is built, tested and assembled, with pride, at the COSMOGAS factories, thereby guaranteeing optimum quality control. Thanks to on-going research carried out by COSMOGAS, this product has been conceived and is considered to be the best in its class with regards to respect for
the environment, since it falls within class 5 (less polluting) envisaged by technical norm EN 297 (and EN
483) and has an elevated efficiency , 4 stars as per EC Directive 92/42/ EEC. Great importance is also given to the end of the appliance’s useful life. All its components can easily be separated into similar and completely recyclable parts.
2.3 - Manufacturer
COSMOGAS srl Via L. da Vinci 16 47014 - Meldola (FC) IT AL Y T el. +39 0543 498383 Fax. +39 0543 498393 www.cosmogas.com info@cosmogas.com
2.4 - Key to symbols used
General danger!
Failure to observe this warning may compromise the smooth running of the appliance or cause serious damage to individuals, animals or property .
l Operation symbol
F Important indication symbol
2.5 - W arranty
See section 4
NOVADENS XXYYYY
“ “ =
Boiler with exchanger sanitary to partial accumulation; “A” = Boiler for only heating without integrated pump; “B” = Boiler which can be combined with BWR C series storage tank; “C” = Boiler for only heating with integrated pump; “P” = Boiler with exchanger secondary for D.H.W., to plates; “0834” = Boiler for low temperature central heating systems.
24 = Boiler with maximum input heat of 25 kW 34 = Boiler with maximum input heat of 34.8 kW
Gas-fired, condensing, hot water boiler, with sealed combustion chamber and pre-mix burner, for heating and domestic hot water production.
2.2 - Description of models
Page 5
5
3 - USE
Figure 1 - Instrument panel
3.1 - Check that the cocks are open
- The gas cock must be open;
- any supply and return valves must be open;
- any hot and cold water valves must be open.
3.2 - Check heating system pressure
If the pressure inside the heating circuit falls below 0.5 bar, the appliance switches off and the display 1 as per
figure 1, shows to indicate that it is necessary to restore the correct
pressure. Proceed as follows: l open the filling cock (see figure 5)
turning it in a counter-clockwise direction;
l check the pressure on the pressure
gauge “13” of figure 1, it must reach a pressure of 1.5 bar and the indication
must disappear;
l close the filling cock (see figure 5)
turning it in a clockwise direction.
CAUTION!!! During normal
operations, the filling cock (see figure 5) must always remain in the closed position.
If, with time, the pressure drops, restore the correct value. This operation may have to be repeated several times during the first month of operations to remove any gas bubbles present.
3.3 - Overview
The boiler is pre-set with standard parameters. However , it is possible to make a number of changes or consult the parameters by means of using the “Users’ Menu” (see section 3.6). During functioning display “1” of figure 1 displays the status of the boiler and display “2” (see figure 1) shows the
value of the parameter. The various operating statuses are shown in the table in figure 2. Within the “Users’ Menu” (see section
3.6) it is possible to check the last lock-outs or errors which have occurred. In addition to the operating modes, the instrument panel provides important information on the current functioning of the boiler, via the indicators “3”, “4”, “5” and “6” of figure 1. In particular:
- the indicator “3” displays whether the burner is functioning (on) or whether it is off (blinking);
- the indicator “4” displays whether the domestic hot water service is on or off;
- the indicator “6” displays whether a heating service request is active (on) or nor (off).
1 - Parameter display . 2 - Display of values adopted by parameters. 3 - Burner status indicator . On = burner on, flashing = burner off. 4 - Domestic hot water service status indicator. On = d.h.w. on, Off = d.h.w. off. 5 - Indicator of decimal of value displayed. 6 - Heating service status indicator. On = heating on, Of f = heating off. 7 - Heating temperature and start control. 8 - Key for decreasing parameter values. 9 - Key for resetting shutdowns and for scrolling the list of parameters. 10 - Key for increasing parameter values. 1 1 - Domestic hot water temperature and start control. 12 - On/off power switch. 13 - Heating circuit pressure gauge.
Page 6
6
3 - USE
Figura 2 - Parameters displayed during functioning
P ARAMETER DESCRIPTION ON DISPLA Y “2” (figure 1)
Boiler on stand-by or on hold (no heating or hot water request exists)
Anti-freeze function active Caution!!! Domestic hot water active for more than 120 minutes
(turn domestic hot water to OFF position in order to reinstate heating). Check that there are no leaking taps. If the problem persists, contact a professionally qualified technician
Caution!!! System pressure too low, fill system follow section
3.2. Domestic hot water service on
Heating service on
Boiler in lock-out mode. To reset it, press the
button. If
the lock-out occurs frequently, cont act a professionally qualified technician.
Boiler fault. Contact a professionally qualified technician
Auto-purging procedure in progress . It will end within 2 minutes
Boiler temperature (°C)
Boiler temperature (°C)
Boiler temperature (°C)
No display Domestic hot water temperature (°C)
Heating temperature (°C)
Lock-out code (see installation and maintenance manual)
Error code (see installation and maintenance manual)
Boiler temperature (°C)
POSSIBLE DISPLAYS
3.4 - Displays
During normal operations, the param­eters’ display “1” and the values’ display “2” (see figure 1) remain perma­nently on (if the ”Energy Saving” mode
has not be activated). The parameters which can be displayed
are shown with their meaning in the table shown in figure 2.
3.5 - Start-up procedure
l Open the gas cock; l switch on electric power to the boiler;
l If the display shows code 21, it
means that the polarity has not been observed between phase and neutral;
l on initial start-up, the appliance carries
out an auto-purging cycle lasting two minutes. This is indicated by the
appearance of on the display;
l wait two minutes until the end of the
auto-purging cycle;
l turn knob “7” of figure 1 until it reaches
the heating temperature desired. Turn knob “1 1” of figure 1 until it reaches the domestic water temperature desired.
The flame control appliance will start-up the burner. If the burner fails to ignite within 5 seconds, the boiler will automatically attempt ignition another three times, after which if it fails to start-up, it will shut down
and the display will show 01. Press the button in order to re-set
normal operating conditions. The boiler will automatically attempt another start-up.
CAUTION!!! If the appliance
frequently shuts down, contact a qualified technician to restore normal running conditions.
Now the boiler will continue to operate in relation to the service requested and will indicate the following on display “1”:
if a domestic water request is active; if a heating request is active;
if there is no domestic water or heating request active.
3.6 - “Users’ menu”
Entry into the “Users’ Menu” is shown by display “1” blinking. In order to access
the “Users’ menu” just: l press the button for 2 seconds
until the display starts to blink;
l press and release the button
several times until the parameter desired is displayed;
l by means of the or keys,
it is possible to change the value of the parameter;
l press in order to confirm the
amended data and pass onto the next parameter;
l Once you have reached the end of the
menu, on the last , the display “1” stops blinking indicating exit from
the “Users’ menu”.
If no key is pressed for more than 60 seconds, one automatically exists the menu. Any change in the p arameters not
confirmed using the button, will be lost.
In this menu it is possible to consult and/ or change the parameters indicated in figure 3.
Page 7
7
3 - USE
Figure 3 - Parameters within the “Users’ Menu”
“USERS’ MENU”
Adjustment of the gradient of the line as per figu­re 4. Visible only with climatic adjustment active. (See installation and instruction manual).
Adjustment of “Minimum heating temperature”. Visible only with climatic adjustment active. (See installation and instruction manual).
Adjustment of “Maximum heating temperature”. Visible only with climatic adjustment active. (See installation and instruction manual).
Adjustment of the parallelism “b” of the line as per figure 4. Visible only with climatic adjustment active. (See installation and instruction manual).
Display of calculated heating temperature (if climatic adjustment active) or display of tempera­ture set via the control “7” as per figure 1.
Display of domestic hot water temperature set via the control “11” as per figure 1.
Display of last error registered.
Display of last block which occurred.
Setting range: 0.1-5.0
Setting range: 20°C-60°C for radiant panels, 30°C - 60°C for radiators.
Setting range: 45°C for radiant panels, 80°C for radiators.
Only display . The regulation is carried out using the control “7” as per figure 1. It can adopt values ranging between ­10°C and +10°C
Only display. It can adopt values ranging between 20°C and 80°C
Only display. It can adopt values ranging between 40°C and 70°C
Only display. It can adopt the values indicated in the
installation and maintenance manual
Only display. It can adopt the values indicated in the
installation and maintenance manual
PARAMETER DESCRIPTION INFORMATION ON DISPLAY “2”
3.7 - Summer mode
To disable the heating functions for a prolonged period, leaving only the domestic hot water function, switch the heating temperature to minimum, until the wording OFF appears, by turning knob “7” of figure 1.
3.8 - Winter mode
In Winter mode, by means of the pump , the boiler sends the water to the system at the temperature set using knob “7” of figure 1. When the temperature inside the boiler reaches the temperature set, the burner starts to modulate the flame so as to reduce the output to a minimum. If the temperature rises further, the burner shut s down. Simultaneously, the pump which sends the water to the system is switched on and off by the room thermostat. This can be noted, because indicator “6” of figure 1 switches on and off in correspondence
with the on and off of the pump. At first the pump may make a noise. This is due to the presence of residual air in the hydraulic system which will soon disappear on its own. We recommend keeping the temperature set using knob “7” at the point shown by the symbols on the panel for a rational use of the boiler. If it is a p articularly cold Winter and it is difficult to maintain the desired temperature, turn knob “7” to gradually higher values.
3.9 - Adjusting the heating temperature
To set the heating temperature, turn control knob “7” of figure 1. As soon as
the knob is touched, will blink on display and the temperature being set will
appear on display “2”. As a rule, it is sufficient to turn control knob “7” to the half-way position. If it is a particularly cold Winter, progressively increase the temperature by rotating control “/”.
3.10 - Adjusting the heating temperature with climatic adjustment
The adjustment of the heating temperature, in the event that climatic adjustment has been set, is carried out by turning control “7” as per figure 1. As soon as the control is touched, display
“1” show a flashing and display “2” shows the value in °C of translation on a
parallel with the adjustment curve (see figure 4, detail “b”. As a rule, it is sufficient to adjust control “7” to the half-way position. If the Winter is particularly rigid, progressively increase the temperature using control “7” until the temperature inside the rooms is satisfactory. If the comfort produced by the climatic adjustment is not satisfactory (too hot, too cold, room temperature not constant)
Page 8
8
3 - USE
Outside temperature (°C)
Supply temperature (°C)
Figure 4 - Graphs of the climatic adjustment for high temperature
systems
Outside temperature (°C)
Supply temperature (°C)
OA = Inclination of the line Ob = Minimum heating temperature Oc = Maximum heating temperature br = “Fix point” of the angle fulcrum of the line b = parallel shift of the line (possible using control “7” of figure 1)
just enter the users’ menu and adjust the parameters corresponding to figure 4. It is necessary to consider that the thermal inertia of a dwelling is extremely high, therefore each time you make a change, wait at least 24 hours to see the result.
3.11 - Domestic hot water temperature adjustment
To adjust the domestic hot water, turn control knob “1 1” of figure 1. As soon as
the knob is touched, will blink on display “1” and the temperature being set
will appear on display “2”. It is advisable to set this value at 50°C-55°C; if a storage tank is present, the temperature can arrive at 60°C-65°C.
3.12 - Room temperature adjustment
It is necessary to install a time­programmable thermostat for an optimum setting of the room temperature and thus satisfactory energy saving; this is a device capable of switching on and off and/
or raising and lowering the room temperature, in relation to certain set times. Contact a qualified technician for the installation of this device. This boiler is suitable for being connected to devices of this type.
3.13 - Errors and alarms
The boiler control device carries out numerous checks. When it detects a malfunction, it shuts down the appliance and displays the reason for the shut down on the display . The boiler may stop as a result of two different series of shutdowns:
and followed by the number identifying the shutdown.
The shutdowns identified by can be re-set by pressing . If the boiler fails
to re-start, or if it shuts down frequently, contact a qualified technician.
The shutdowns identified by cannot be re-set unless the cause of the problem
is eliminated. In such cases, it is necessary to contact a qualified
technician. The alarms shown on the display by means of
, do not block the boiler, but
alert the user to the fact that a system anomaly is underway . E.g. domestic hot water cock leak. In this event, if you wish to reinstate the heating function, you must turn control knob “11” to zero and eliminate the water leak.
3.14 - Pressure gauge
The pressure gauge (detail “13” of figure
1) is a device which indicates the pressure of the water within the heating circuit.
Page 9
9
3 - USE
3.15 - Shutdown procedure
If the boiler is to be shutdown for a relatively short time and there is no risk of freezing, simply disconnect from the mains the switch “12” of figure 1. If there is a risk of freezing during your absence, leave the boiler connected to the mains and the gas open and carry out the procedure for the shutdown of the services, turning both knobs “7” and “11” of figure 1 to OFF . Now the two services of the boiler are switched off. On reaching a boiler temperature of 7°C, the heating pump automatically switches on. If the temperature falls further to under 2°C, the burner will also switch on, so as to protect the system and the boiler itself from the effects of freezing weather conditions. If the boiler is not used for a long period of time, we suggest emptying it. Contact a professionally qualified technician.
3.16 - Precautions against freezing
If you leave the dwelling, disconnect the gas and electricity supply, since the appliance is not protected against freezing. If it is switched off and runs the risk of being exposed to temperatures below zero, it is necessary to empty the appliance. Contact a professionally qualified technician.
CAUTION!!! It is absolutely
forbidden to introduce chemical additives, such as anti-freeze or others, into the domestic water circuit.
3.17 - Flue gas discharge
Due to its high efficiency and low pollution levels, this boiler is considered to be ecological. Therefore, white smoke may be discharged from the discharge pipe, under specific atmospheric and operating conditions. There is no cause for alarm as it is only steam which condenses on contact with the outside cold air .
3.18 - Operating anomalies
If the boiler fails to start, check that:
FThe gas supply is open; Fthe boiler power supply switch is on; Fthe heating temperature control knob
“7” is in the position suggested by the symbols;
Fthe boiler is not in lock-out mode.
Press the button to re-start it;
Fthe room thermostat is set to a higher
temperature than that of the room where it is installed and that it is programmed to call for heating at that time;
If during winter operations, there is hot water but no heating, check that:
FThe room thermostat is set to a higher
temperature than that of the room where it is installed and that it is programmed to call for heating at that time;
Fany valves installed on the supply and
return connections are open;
Fopen the radiator cocks to purge air;
CAUTION!!!
If after these checks, the system is still cold, do not attempt any repairs yourself but contact a qualified technician.
Figure 5 - Filling cock
OPEN CLOSE
Page 10
10
3 - USE
A - Heating adjustment knob B - RESET key C - Domestic hot water adjustment knob D - Green light (for indications, see section 3.19) E - Red light (for indications, see section 3.19)
Figure 6 - Remote control
3.19 - Remote control (on request)
If the boiler is connected to the remote control, the heating temperature adjust­ment and domestic hot water tempera­ture adjustment functions are performed directly on the remote control as indicated below:
- the adjustment of the heating is carried out directly using knob “A” as per figure 6;
- the adjustment of the domestic hot water is carried out directly using knob “C” as per figure 6. Furthermore, it is possible to reset any alarms by pressing the RESET key (see figure, 6 detail “B”). Two indication lights are present on the remote control, and have the following meaning:
- green light on: heating service on and correct communication between boiler and remote control;
- green light blinking every 7 seconds: correct communication between boiler and remote control;
- red light on: boiler in lock-out status. It is possible to re-activate it by pressing the RESET key (see figure 6, detail “B”). If the lock-out occurs frequently, contact a professionally qualified technician;
- red light blinking: boiler in lock-out for more than 5 minutes. It is possible to re-activate it by pressing the RESET key (see figure 6, detail “B”). If the lock­out occurs frequently, contact a professionally qualified technician;
- green light and red light blinking: heating pressure anomaly (see section 3.2).
In order to check the type of lock-out corresponding to the light illuminated, check the error type on the boiler and refer to the sections “LOCK-OUTS” and “ERRORS” in the installation manual.
Page 11
11
4.1 - General warranty conditions
COSMOGAS guarantees that all its
products are free from manufacturing and material defects for 24 months from the testing and inspection date of the first start-up. Within the afore­mentioned period, COSMOGAS will repair or replace any manufactured parts found to be defective, excluding any defects caused by normal wear and tear during operations. Any transport and handling costs for replaced parts are at the customer’s expense. The warranty does not cover compensation for any type of damage which may occur to people or property . The faulty materials replaced under warranty are the property of COSMOGAS and must be returned free of charge to our factory , within 30 days of their replacement, otherwise COSMOGAS will issue an invoice covering the cost of the replaced material. All COSMOGAS products are subject to reserved ownership agreement until the purchased appliance has been fully paid for .
4.2 - Instructions for filling in the warranty card
l The installer must stamp the
warranty certificate.
l Always request the intervention of
one of our authorized technicians for the initial start-up and testing of the appliance; a list is enclosed with the instruction manual or can be found in the Y ellow Pages under "Gas boilers".
l The technician will collect the
warranty certificate and forward it to
COSMOGAS.
4.3 - W arranty limits
The warranty is invalid:
- if the appliance is
not installed by
qualified technicians;
- if the appliance is not installed in
compliance with COSMOGAS instructions and/or those established by national and/or local standards in force;
- the running and/or maintenance of the
system is not carried out in compliance with these instructions and/or national and/or local standards in force;
- damage to the product has been
caused by voltage fluctuations;
- damage to the product has been
caused by the use of too hard, too acid or over oxygenated water;
- damage to the product has been
caused by thermal shock, defective chimneys and/or flue gas discharge and air intake piping;
- the product has anomalies not
dependent on COSMOGAS;
- the boiler has been tampered with due
to adaptation work, repair work and replacement work using non-original parts;
- the repair work has been carried out
by unauthorized personnel;
- the warranty certificate is not
forwarded to COSMOGAS within 15
days of the date of initial start-up. COSMOGAS cannot be held
responsible for any accident, including those caused by the user, any compensation which does not concern boiler parts with recognized manufacturing defects being excluded. Court of competent jurisdiction: Forlì, IT ALY.
4 - W arranty
Page 12
The appliance has been installed by qualified technicians in possession of the legally required qualifications, in compliance with the instructions contained in this manual, on the installation and maintenance manual and follow national and/or local standards in force.
Date______________________________
INSTALLER (Stamp)
The appliance has been tested and inspected for initial start-up purposes by qualified technicians in possession of the legally required qualifications, in compliance with the instructions contained in this manual, on the installation and maintenance manual and follow national and/or local standards in force, with the following results:
POSITIVE q NEGATIVE q
SERVICE CENTRE (Stamp)
Comments________________________________________________________________________
___________________________________________________________________________________
Service Centre signature
_________________________
User signature
_________________________
W ARRANTY CERTIFICATE
FOR “COSMOGAS” APPLIANCES
Warranty valid 24 months
Date______________________________
Comments________________________________________________________________________
___________________________________________________________________________________
TO BE COMPLETED BY THE INSTALLER
TO BE COMPLETED BY THE SERVICE CENTRE
Signature ________________
Page 13
Page 14
Page 15
Page 16
COSMOGAS s.r .l.
Via L. da Vinci 16 - 47014
MELDOLA (FC) ITAL Y
info@cosmogas.com
www .cosmogas.com
Loading...