COSMOGAS MYDENS 60 Installation, Use And Maintenance Manual

Page 1
62403579 - R00 28-11-2013_GB
INSTALLATION, USE AND MAINTENANCE MANUAL
MYDENS 60
GAS WALL-MOUNTED CONDENSING BOILER
Page 2
2
MYDENS 60
COSMOGAS
INDEX
1 - GENERAL SAFETY RECOMMENDATIONS ..................................................................................................4
1.1 - National installation laws and regulations ................................................................................................................ 4
2 - GENERAL INFORMATION .............................................................................................................................5
2.1 - Presentation ............................................................................................................................................................. 5
2.2 - Overview of the models ............................................................................................................................................ 5
2.3 - Manufacturer ............................................................................................................................................................ 5
2.4 - Key for the symbols used ......................................................................................................................................... 5
2.5 - Maintenance ............................................................................................................................................................. 5
2.6 - Warranty ................................................................................................................................................................... 5
3 - MAIN COMPONENTS .....................................................................................................................................6
4 - OPERATION ...................................................................................................................................................8
4.1 - Operation and intended use of the appliance .......................................................................................................... 9
4.1.1 - Modulating pump ........................................................................................................................................ 9
4.1.2 - Hydraulic separating device ........................................................................................................................ 9
4.1.3 - Production of domestic hot water ................................................................................................................ 9
4.1.4 - Plant types .................................................................................................................................................. 9
4.2 - Precautions during installation ................................................................................................................................. 9
4.3 - Characteristic curve of the residual head at the central heating plant ................................................................... 10
4.4 - Head losses characteristic curve ............................................................................................................................11
5 - INSTALLATION .............................................................................................................................................14
5.1 - Opening the packaging .......................................................................................................................................... 14
5.2 - Dimensions and minimum safety distances ........................................................................................................... 14
5.3 - Choosing the place of installation .......................................................................................................................... 14
5.4 - Mounting the appliance .......................................................................................................................................... 15
5.5 - Flow and Return ..................................................................................................................................................... 15
5.6 - Water supply .......................................................................................................................................................... 16
5.6.1 - Recommendations of the features of the water inside the plant ............................................................... 16
5.6.2 - For correct plant operation it is necessary to ascertain that: ................................................................... 16
5.6.3 Treatment of the water in the thermal plants for civil use ............................................................................ 17
5.7 - Draining the heating circuit ..................................................................................................................................... 17
5.8 - Expansion Tank ...................................................................................................................................................... 17
5.9 - Low temperature plants (or on the oor) ................................................................................................................ 17
5.10 - Gas ....................................................................................................................................................................... 17
5.11 - Condensate drain ................................................................................................................................................. 18
5.12 - Safety valve .......................................................................................................................................................... 18
5.13 - Water, gas connections ........................................................................................................................................ 18
5.14 - Electric connections: generalities ......................................................................................................................... 19
5.14.1 - Power supply cable connection .............................................................................................................. 20
5.14.2 - Choice of the room thermostat/chronothermostat ................................................................................... 20
5.14.3 - Connecting the room thermostat/chronothermostat ................................................................................ 20
5.14.4 - Installing the external temperature sensor (on request) ......................................................................... 21
5.15 - Connection of the boiler with Indirect Water Heater and coil ............................................................................... 22
5.15.1 - Anti- legionella ......................................................................................................................................... 22
5.16 - Burned gas exhaust and combustion agent air intake pipe ................................................................................. 23
5.16.1 - Type of intake/exhaust B23 ..................................................................................................................... 24
5.16.2 - “Split 80/80PP” System (polypropylene) (Type C43; C53; C83) ............................................................. 25
5.16.3 - “Split 80/80PP” System (Type C43; C53; C83): accessories available ................................................... 26
5.16.4 - “Split 80/80PP” System (Type C43; C53; C83): installation examples ................................................... 27
5.16.5 - “80/125PP vertical coaxial” System (polypropylene) (C13; C33) ............................................................ 28
5.16.6 - “80/125PP Coaxial” System: accessories available ................................................................................ 29
5.16.7 - “80/125PP Coaxial” System: installation examples ................................................................................ 30
6 - OPERATING .................................................................................................................................................31
6.1 - Operating ............................................................................................................................................................... 31
6.1.1 - User instructions ....................................................................................................................................... 31
6.1.2 - Filling the condensate drain siphon .......................................................................................................... 31
6.1.3 - Filling the central heating plant ................................................................................................................. 31
6.2 - General recommendations regarding the supply of gas ........................................................................................ 32
6.3 - Type of gas for which the appliance is adjusted ..................................................................................................... 32
6.4 - Conversion of the appliance from one type of gas to another ................................................................................ 33
6.5 - Ignition .................................................................................................................................................................... 35
6.6 - Controlling the supply gas pressure and any adjustment ...................................................................................... 35
6.7 - Controlling the combustion agent air pressure ....................................................................................................... 36
Page 3
3
MYDENS 60
COSMOGAS
INDEX
6.8 - Controlling the level of CO2 and any adjustment ................................................................................................... 37
6.9 - Adjustment of the power in central heating mode (Range Rated) .......................................................................... 38
7 - USE ...............................................................................................................................................................39
7.1 - Controlling cock opening ........................................................................................................................................ 39
7.2 - Checking central heating plant pressure ................................................................................................................ 39
7.3 - Generalities ............................................................................................................................................................ 40
7.4 - Ignition procedure .................................................................................................................................................. 40
7.5 - “User menu” ........................................................................................................................................................... 40
7.6 - Summer operating mode ........................................................................................................................................ 40
7.7 - Winter operating mode ........................................................................................................................................... 40
7.8 - Adjusting the domestic hot water (if a Indirect Water Heater is present) ................................................................ 40
7.9 - Central Heating ...................................................................................................................................................... 40
7.10 - Thermostatic adjustment ...................................................................................................................................... 41
7.11 - Climatic adjustment .............................................................................................................................................. 41
7.11.1 - Climatic adjustment: on which plants? .................................................................................................... 41
7.11.2 - Climatic adjustment: precautions during adjustment ............................................................................... 41
7.11.3 - Climatic adjustment: setting the parameters ........................................................................................... 41
7.11.4 - Climatic adjustment: adaptation to different climatic areas ..................................................................... 43
7.11.5 - Climatic adjustment: switching the central heating service on and off .................................................... 43
7.11.6 - Climatic adjustment with room compensation ......................................................................................... 43
7.12 - Timers of the various functions ............................................................................................................................ 43
7.13 - Pump anti-block ................................................................................................................................................... 43
7.14 - Anti-freeze protection ........................................................................................................................................... 43
7.15 - Automatic plant loading (not recommended) ........................................................................................................ 43
7.16 - Energy Saving ...................................................................................................................................................... 43
7.17 - “User menu” ......................................................................................................................................................... 44
7.18 - “Installer menu” .................................................................................................................................................... 45
7.19 - Diagnostics ........................................................................................................................................................... 47
7.19.1 - Diagnostics: blocks “Loc” ........................................................................................................................ 48
7.19.2 - Diagnostics: errors “E” ............................................................................................................................ 50
7.19.3 - Diagnostics: alarms“AttE” ....................................................................................................................... 51
8 - MAINTENANCE ............................................................................................................................................52
8.1 - General recommendations ..................................................................................................................................... 52
8.2 - Removing the casing and access to internal components ..................................................................................... 53
8.3 - Removing the burner fan unit ................................................................................................................................. 54
8.4 - Cleaning the burner and the fumes side primary heat exchanger ......................................................................... 54
8.5 - Correct positioning of the ignition and ionising electrodes ..................................................................................... 55
8.6 - Removing the ow meter ....................................................................................................................................... 55
8.7 - Removing the safety valve ..................................................................................................................................... 55
8.8 - Cleaning the condensate conveyor siphon ............................................................................................................ 56
8.9 - Removing the air vent valve ................................................................................................................................... 57
8.10 - Replacing the pump motor ................................................................................................................................... 57
8.11 - Removing the central heating circuit pressure sensor ......................................................................................... 57
8.12 - Emptying the appliance ........................................................................................................................................ 58
8.13 - Fan ....................................................................................................................................................................... 58
8.14 - Minimum and maximum power ............................................................................................................................ 58
8.15 - Checking the ionisation current ............................................................................................................................ 59
8.16 - Checking combustion performance ...................................................................................................................... 59
8.17 - Water temperature measurement sensors ........................................................................................................... 59
8.18 - External temperature sensor ................................................................................................................................ 59
8.19 - Operational wiring diagram .................................................................................................................................. 60
8.20 - Multi-wire wiring diagram ..................................................................................................................................... 62
9 - TECHNICAL DATA ........................................................................................................................................64
10 - COMMAND MENU DIAGRAM ....................................................................................................................66
11 - MENU FORCED BY INTERNAL ELECTRIC BRIDGE ................................................................................67
12 - CE DECLARATION OF CONFORMITY ......................................................................................................68
13 - HYDRAULIC TEST CERTIFICATE .............................................................................................................69
14 - WARRANTY ................................................................................................................................................70
14.1 - General warranty conditions ................................................................................................................................ 70
14.2 - Instructions for lling-in the warranty card ............................................................................................................ 70
14.3 - Limits of the warranty ........................................................................................................................................... 70
Page 4
4
MYDENS 60
COSMOGAS
If you smell gas
1. - Close the gas cock.
2. - Ventilate the room.
3. - Do not switch on any electric device, telephone included.
4. - From another room, call a professionally qualified technician immediately or the gas supply company. Call the Fire Service if the former are not available.
If you can smell combustion products
1. - Switch the appliance off.
2. - Ventilate the room.
3. - Call a professionally qualied technician.
Explosive or highly ammable products
Do not store or use explosive or highly ammable materials
such as paper, solvents, paints, etc...in the same room where the appliance is installed.
Installation, modications
The gas appliance must be installed, calibrated or modied
by professionally qualied staff, in compliance with National
and local Standards, as well as the instruction in this manual.
Incorrect installation or poor maintenance can cause
injury/damage to persons, animals or objects, for which the manufacturer cannot be deemed liable.
The appliance exhaust must be connected to a burned
gas evacuation pipe. Failure to comply with this regulation leads to serious risks for the safety of persons and animals.
A domestic hot water temperature level exceeding 51°C
can cause permanent injury/damage to persons, animals and objects. Children, the elderly and disabled must be protected against the potential risks of scalding, by introducing devices that limit the temperature of use of domestic hot water to utilities.
The parts conducting the fumes must not be modied.Do not obstruct the ends of the intake/exhaust pipes.Do not leave parts of the packaging and any replaced parts
within the reach of children.
Seal the adjustment devices after every calibration.In agreement with the provisions for use, the user must
keep the installation in good working order and guarantee reliable and safe operation of the appliance.
The user must have maintenance performed on the
appliance by a professionally qualified technician in agreement with national and local Standards and in compliance with that stated in this manual.
We also highlight the convenience of an annual scheduled
maintenance contract with a professionally qualified technician.
Before performing any cleaning or maintenance operation,
disconnect the appliance from the mains electricity and gas supplies and by acting on the cut-off devices.
After having performed any cleaning or maintenance
operation, make sure that all internal parts of the appliance are dry before re-connecting the electric power supply.
This appliance is not intended for use by persons (including
children) with reduced physical and sensory conditions or
lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
This manual is an integral and essential part of the product
and must be kept carefully by the user, for possible future consultation. If the appliance must be transferred or if you should move and leave the unit to another user, always ensure that this manual remains with the new user and/ or installer.
Any optional or kits added successfully must be original
Cosmogas products.
This appliance must be intended only for the use for which
it has been expressly declared: heating water for closed circuits intended for the central heating of rooms for civil and domestic use, production of domestic hot water for civil use.
Any contractual and extra contractual liability of the
manufacturer is excluded for damage caused by installation errors or errors in use and however due to failure to comply with the instructions given by the manufacturer or by failure to comply with applicable national and/or local laws.
For safety reasons and respect for the environment, the
packaging elements must be disposed of in the relevant separate waste collection centres.
In case of breakdown
In the case of appliance breakdown and/or malfunctioning,
deactivate it; do not attempt any repairs.
Cont act a professi onally qualifie d t echnician only. If components must be replaced for repair, only use original spare parts. Failure to comply with the above can jeopardise the safety of the appliance.
Professionally qualied technician.
Professionally qualied technician means, a person with specic technical skill in the sector regarding central heating
plants and the production of hot water for sanitary and domestic uses, for civil use, electric plants for the use of combustible gas. This staff must be authorised as envisioned by the law.
Technical drawings
All the drawings in this manual relating to electrical, hydraulic or gas installation plants, must be deemed purely indicative. All of the safety elements, auxiliary elements such as the diameters of the electric, hydraulic and gas pipes, must always
be checked by a professionally qualied technician to verify
compliance with applicable Standards and Laws.
1.1 - National installation laws and regulations
- Fire prevention rules issued by the Fire Service.
- D.M. dated 01/12/75
- D.M. dated 22/01/2008 n°37 (former Law n°46 dated 05/03/90)
- Law n°10 dated 09/01/91
- D.P.R. dated 26/08/93 n°412
- D.M. dated 12/04/96
- D.P.R. dated 21/12/99 n°551
- DLgs. dated 19/08/05 n° 192
- DLgs. dated 29/12/06 n° 311
- IEC 64-8 Standard
- INAIL (national insurance institute for accidents at work) certied “R” Collection (Former ISPESL “Higher Institute for Worker Security and Protection”)
1 - GENERAL SAFETY RECOMMENDATIONS
Page 5
5
MYDENS 60
COSMOGAS
2.1 - Presentation
Congratulations! You have purchased one of the best products on the market. Each individual part is proudly designed, realised, tested and assembled within the COSMOGAS establishment, thus guaranteeing the best quality control. This product has been developed thanks to the constant research by COSMOGAS, considered the “top”
regarding respect for the environment, as it lies within class 5 (the least polluting) envisioned by the EN 297 (and EN 483) Technical Standard and has high efciency; 4-star as per European Community Directive 92/42/
EEC. Great importance has also been given to the end of the appliance’s life. All of its components can be easily separated into homogeneous elements and completely re-cycled.
2.2 - Overview of the models
MYDENS XXY
“60C” = Boiler with maximum heat input of 57.8 kW with integrated pump; “60A” = Boiler with maximum heat input of 57.8 kW without integrated pump;
Indoor wall-mounted ecological condensing gas boiler with pre-mixed burner.
2.3 - Manufacturer
COSMOGAS srl Via L. da Vinci 16
47014 - Meldola (FC) Italia
Tel. 0543 498383 Fax. 0543 498393 www.cosmogas.com info@cosmogas.com
2.4 - Key for the symbols used
ATTENTION !!!
El ectric s hock haza rd. Failure to c omply wit h t hese recommendations can jeopardise the good working order of the appliance or cause serious damage to persons, animals or objects.
ATTENTION !!!
General hazard. Failure to comply with these recommendations can jeopardise the good working order of the appliance or cause serious damage to persons, animals or objects.
Important indication symbol
2.5 - Maintenance
It is recommended to perform regular yearly maintenance of the appliance for the following reasons:
- to maintain a high yield and manage the domestic hot water
plant economically (with low fuel consumption);
- to achieve a high level of safety;
- to maintain the level of environmental compatibility of the
combustion high;
Offer your customer a scheduled maintenance contract.
2.6 - Warranty
see chapter 14.
2 - GENERAL INFORMATION
Page 6
6
MYDENS 60
COSMOGAS
1 - Command and control board 2 - Electric connections board 3 - Electric control board box
4 - Water ow rate measuring device 5 - Flow tting
6 - Pump release screw
7 - Circulation pump (model “C” only)
8 - Detection electrode 9 - Primary heat exchanger
10 - Return tting
11 - Air vent valve 12 - Air intake and burned gas exhaust
13 - Support attachments 14 - Spark generator 15 - Ignition cables 16 - Fumes non-return valve 17 - Air inlet manifold 18 - Air/gas manifold 19 - Gas valve 20 - Access to the gas valve adjusters 21 - Front casing 22 - Display 23 - Control board
3 - MAIN COMPONENTS
Figure 3.1 - Boiler internal components
4
20
13
23
22
12
21
19
7
16
17
2
3
18
5
1
8
14
6
15
10
11
9
020005.01.002
Page 7
7
MYDENS 60
COSMOGAS
24 - Double fumes temperature sensor (Par. 10 0 6
and1014)
25 - Front casing couplings 26 - Double ow temperature sensor (Par. 1001 and
1005)
27 - Central heating circuit pressure sensor 28 - Return temperature sensor (Par. 1007)
29 - Condensate collection tank 30 - Safety valve 31 - Fan 32 - Air/gas mixing unit 33 - Condensate drain siphon 34 - Burner 35 - Burner window 36 - Left ignition electrode 37 - Right ignition electrode
3 - MAIN COMPONENTS
Figure 3.1 - Boiler internal components
25
29
24
36
37
32
31
27
28
35
26
30
33
34
02.0005.01.003
Page 8
8
MYDENS 60
COSMOGAS
Key gure 4.1:
1 = Boiler 2 = Combustion agent air inlet 3 = Fumes outlet
4 = Fumes temperature sensor (Par. 1006) 5 = Sealed chamber
6 = Fumes temperature safety sensor (Par. 1014) 7 = Water collection pipe coming from the combustion agent inlet pipe
8 = Flow temperature sensor (Par. 1001) 9 = Flow temperature safety sensor (Par. 1005)
10 = Burner 11 = Stainless steel VRC type heat exchanger 12 = Fan
13 = Return temperature sensor (Par. 1007) 14 = Condensate collection siphon with sediment decanter 15 = Air/gas mixer 16 = Pneumatic gas valve 17 = Central heating circuit pressure sensor 18 = Circulation pump *
19 = Central heating circuit ow
20 = Gas inlet 21 = Central heating circuit return 22 = Condensate drain collector and of the safety valve 23 = Central heating plant 24 = Air vent valve 25 = Safety valve
26 = Water ow rate measuring device
* Present only in model C
4 - OPERATION
Figure 4.1 - Hydraulic layout
MYDENS 60A MYDENS 60C
Page 9
9
MYDENS 60
COSMOGAS
4.1 - Operation and intended
use of the appliance
This product is a condensing gas appliance, intended for the production of central heating. It can also be interlocked to the production of domestic hot water for civil use, but
must be connected to a Indirect Water Heater (see g. 4.7.).
Make the adaptation between boiler and plant, selecting the characteristic residual head curve deemed most suitable
from those available (see g. 4.2).
4.1.1 - Modulating pump
The MYDENS 60A boiler is built especially without the internal pump, so that the installer can connect any pump, even the modulating type. The only precaution to take is that of introducing a by-pass
valve (see gure 4.5, detail “35”). This must be such, that the
boiler is guaranteed a minimum water circulation of 600 l/h in
any operating situation. The characteristic curve of the eld
of modulation of the modulating pump we supply on request,
is given in gure 4.3.
4.1.2 - Hydraulic separating device
If the plant must be served by a water ow rate higher than the
pump can supply, a hydraulic separator must be positioned
between the boiler and the plant (see gures 4.6 and 4.7, detail “20”).
4.1.3 - Production of domestic hot water
A Indirect Water Heater must be connected for the production
of domestic hot water, according to the layout in gure 4.7.
The temperature of the domestic hot water is adjusted following the relevant procedure in chapter 7.8.
4.1.4 - Plant types
The following types of plants can be realised depending on the model: This boiler can only be used to realise a central heating plant
(see gures 4.5 and 4.6) or a plant for central heating and the production of domestic hot water (see gure 4.7). In both
cases, the central heating plant can be high or low temperature
(see chapter 5.9 for adjustment of the boiler).
4.2 - Precautions during installation
Respect the following indications for good working order of the appliance:
It must be attached to a central heating plant and eventually
to a domestic hot water distribution network, compatible with the features, performance and powers of the appliance itself.
Check gure 5.1 concerning the minimum safety distances
for installation and future maintenance.
4 - OPERATION
Page 10
10
MYDENS 60
COSMOGAS
4.3 - Characteristic curve of the residual
head at the central heating plant
The residual head at the attachments of the MYDENS
boiler with standard pump is given as a graph in gure 4.2.
A modulating pump can be provided on request.
In this case, the eld of modulation (detail “x”) can be veried on the graphics in gure 4.3.
4 - OPERATION
Figure 4.2 - Residual head for MYDENS 60C with 8 metre pump (standard)
KEY for gures 4.2 and 4.3
I - II - III = Pump speed (see gure 4.2) X = Range of modulation (see gure 4.3)
Figure 4.3 - Residual head for MYDENS 60C with modulating pump (on request)
Page 11
11
MYDENS 60
COSMOGAS
Figure 4.4 - Flow resistance of the MYDENS “A” boiler
4 - OPERATION
4.4 - Head losses characteristic curve
The MYDENS 60A boiler does not have a circulation pump. To dimension this pump, the designer must consider
the ow resistances of the plant to be created and the ow resistances of the boiler itself. To do this, the ow
resistances of the boiler are given in a graphical form in
gure 4.4.
Page 12
12
MYDENS 60
COSMOGAS
4 - OPERATION
Figure 4.5 - Example of basic connection layout
KEY for gures 7 and 8
1 MYDENS 60 boiler range
2 INAIL certied Safety valve
3 INAIL certied manometer
4 INAIL certied thermometer
5 INAIL certied safety maximum pressure switch
6 INAIL certied safety thermostat
7 Gas cock
8 INAIL certied Gas Cut-off Valve
9 INAIL certied sample point
10 Gas inlet
11 Expansion tank
12 Microbubble separator
Figure 4.6 - Example of connection layout with
hydraulic separator device
13 External sensor (on request)
14 Filter
15 Electric power supply
16 Low or high temperature heat plant
17 Plant water supply
18 Domestic cold water
19 Central heating circuit pump
20 Water disconnector
21 Air vent valve
23 Condensate neutraliser
24 INAIL certied safety minimum pressure switch
35 By-pass valve
36 Circulation pump (to be envisioned for MYDENS 60A)
37 Room thermostat or equivalent system
Page 13
13
MYDENS 60
COSMOGAS
4 - OPERATION
1 MYDENS 60 boiler
2 INAIL certied Safety valve
3 INAIL certied manometer
4 INAIL certied thermometer
5 INAIL certied safety maximum
pressure switch
6 INAIL certied safety thermostat
7 Gas cock
8 INAIL certied Gas Cut-off Valve
9 INAIL certied sample point
10 Gas inlet
11 Expansion tank
12 Microbubble separator
13 External sensor (on request)
14 Filter
15 Electric power supply
16 Condensate neutraliser
17 Air vent valve
18 Domestic cold water
19 Central heating circuit pump
20 Water disconnector
21 Cut-off valve
22 Non-return valve
23 Central heating plant ow
24 Central heating plant return
25 Cap for sludge drain
26 Central heating plant mixing valve
27 Plant drain
28 Indirect Water Heater load pump
29 Plant load unit
30 Indirect Water Heater safety valve
31 Indirect Water Heater temperature sensor
32 Domestic hot water circuit expansion tank
33 Domestic hot water outlet
34 INAIL certied safety minimum pressure switch
36 Circulation pump (to be envisioned for MYDENS 60A)
37 Room thermostat or equivalent system
Figure 4.7 - Example of
connection layout with
hydraulic separator
device and Indirect
Water Heater
Page 14
14
MYDENS 60
COSMOGAS
5.1 - Opening the packaging
The appliance is supplied in cardboard packaging. Open
following the instructions given on the aps of the packaging
itself.
5.2 - Dimensions and minimum safety distances
It is necessary to leave free spaces around the boiler as
illustrated in gure 5.1 both for installation and maintenance.
5.3 - Choosing the place of installation
ATTENTION !!! The appliance must be installed
exclusively on a solid, vertical wall, which can support the weight.
Before installation, the central heating plant and, if
necessary, the domestic hot water plant must be washed thoroughly in order to remove any residues or impurities, which could compromise the good working order of the boiler itself.
This appliance is not envisioned for installation outdoors.
It must not be exposed to temperatures below zero and temperatures above 50°C. Selected a place sheltered from atmospheric agents and freezing.
This appliance must be installed in a location where any
loss of water from the same, the connections between the pipes or from the safety valve drain, cannot cause
damage to materials or objects below. The appliance must be installed within the home, or otherwise protected from atmospheric agents such as rain, wind, sun, and especially freezing.
Dene the room and suitable position for installation, taking
into account the following factors:
- connection of the fumes exhaust/air intake pipes;
- connection of the gas supply pipe;
- connection to the water supply;
- attachment of the central heating plant;
- attachment of the domestic hot water plant (if present);
- electric connection;
- connection to the drain for the condensate produced by
the boiler;
- electric connection of the room thermostat;
- eventual connection of the safety valve drain;
- eventual attachment of the external temperature sensor;
1 - 1” 1/2 central heating ow
2 - 1” gas inlet 3 - 1” 1/2 central heating return 4 - Fumes exhaust/Air intake 5 - Support attachments
5 - INSTALLATION
Figure 5.1 - Minimum safety distances
Figure 5.2 - Boiler dimensions and attachments centre to centre distances
Page 15
15
MYDENS 60
COSMOGAS
5 - INSTALLATION
5.4 - Mounting the appliance
Refer to gure 5.3:
1.- mark the holes for the plugs and hydraulic ttings on
the wall, checking that the template is square to the
environment;
2.- make the holes “A” and introduce the wall plugs “B”;
3.- make the boiler hydraulic and gas connections;
4.- hang the boiler on the plugs “C”;
5.- make the hydraulic ttings.
5.5 - Flow and Return
ATTENTION !!! COSMOGAS is not liable for any damage caused by incorrect use of additives in the central heating plant.
ATTENTION !!! The plant downstream from the appliance must be made with materials that resist temperatures up to 97°C and pressure of 3 bar.
Differently (e.g. plastic piping) the plant must be tted
with the relevant protection and safety devices.
Before connecting the central heating pipes, wash the plant thoroughly to eliminate any waste (hemp, radiators casting
sand, etc..), which could damage the appliance. This
washing operation must also be performed if the appliance is replaced.
Figure 5.2 shows the positioning of the ow and return ttings.
Install a metal mesh lter on the return pipe in order to stop
any plant residues before the return into the boiler.
Do not use the appliance for the introduction of any type
of additive into the plant.
Figure 5.3 - Support plugs
Page 16
16
MYDENS 60
COSMOGAS
5 - INSTALLATION
the winter the leaks on radiator valves are often not visible because they are dried by the heat produced by the radiator
or boiler). These micro leaks however allow air to enter the
plant. The main points that can give rise to micro leaks are in the joints and, in particular, from the intake side of the pump
(air vent valves, o-ring seals, loading valves). In these cases,
the plant must be protected with a suitable corrosion inhibitor in order to prevent damage.
5.6.2 - For correct plant operation it is necessary to ascertain that:
1) there are no leaks in the plant or the most evident ones have been eliminated;
2) if an automatic lling system is present, a litre meter must be installed on order to know the precise size of any leaks;
3) the plant must be lled and topped up with softened water
in order to reduce the total hardness. The water must also be conditioned in order to maintain the pH within the threshold
envisioned in order to prevent corrosion phenomena;
4) both in new plants and replacements, there must be efcient systems that eliminate air and impurities: lters, separators of micro impurities and separators of micro air bubbles;
5) do not drain plant water during routine maintenance, even if it appears to be an apparently insignicant amount: for example to clean lters, supply the plant with the relative cut-off valves upstream and downstream from the lter itself;
6) always analyse the plant water before opening the
communication between the new generator and plant, to establish whether the chemical and physical features of the water indicate the necessity to empty the plant completely, the use of the water already present in the plant or the chemical washing of the plant, using mains water with the addition of a detergent, when it is suspected that the plant may be dirty or particularly clogged and the successive new loading of treated water. If the analysis of a sample of water that will be used to load the plant shows the following factors:
- 9.6 < pH < 10.5 (if the plant is in contact with aluminium, the
pH must be lower than 8.5)
- Ca++ + Mg++ : <0.5°f
- OH + 1/2 C03 : from 5 to 15°f
- P205: from 10 to 30 mg/l
- Na 2S03: from 20 to 50 mg/l loading can be continued. A inhibitor must be used if the features are different.
5.6 - Water supply
Have the water network connection pressure checked. If necessary, have a suitable pressure reducer installed.
ATTENTION !!! The central heating plant (and
therefore the heat module) must be connected to the water mains with the interposition of a device that
prevents backow of drinking water towards the plant,
as requested by the current Anti-pollution Safety Standards.
5.6.1 - Recommendations of the features of the water inside the plant
Filling the central heating plant is an extremely delicate operation, not to be underestimated, regarding replacement of the heat generator or new installations. In certain cases, the incorrect assessment of the plant water features can lead to damage of the plant and heat module. A plant is almost never
sealed perfectly; sometimes water leaks as well as the entry of
oxygen can occur. Both of these phenomena are dangerous. The main parameters that can negatively affect the lifespan of the plant are:
- The simultaneous presence of different metals (copper,
brass, steel and aluminium) which, in aqueous environments,
give rise to galvanic corrosion.
- The presence of free oxygen, due to the inltrations of air that occur in proximity of ttings and gaskets, constitutes a
typical corrosive agent, particularly active at temperatures between 50 and 70° C.
- The loss of water, which leads to frequent top-ups, can act in a corrosive manner and as a deposit, depending on the type of water available to top-up the same.
In all cases, the size of the leaks (and relative top-ups) must be kept under control, especially when an automatic lling
system is installed. In this case, the installation of a meter is highly recommended, which indicates the amount of water reintegrated. Natural impurities or added in the water. Many drinking waters can contain high concentrations of chlorides and sulphates, which can increase the speed of corrosion on metal surfaces. Other undesired components could have been introduced into the plant before or during installation (construction materials,
metal shavings, sawdust, grease, deposits and dirt in general).
Welding residues can also cause corrosion, both in the case of
new plants and in the case of modications or repairs. In the
old plants designed to operate with radiators, characterised by a very large piping diameter, the water content in the plant is noteworthy and promotes the formation of sludge and deposits. Sludge and Deposits The presence of black deposits
(magnetite) indicate that corrosion is limited; however, the high specic weight of this oxide can cause difcult to remove
clogging, especially in the hottest areas. The deposits are due to the hardness of the water, i.e. the presence of calcium and magnesium salts. The calcium goes to the hottest areas of the plant in the form of carbonate. The magnetite often contributes to strengthening the deposit. The iron oxide (the
water is a reddish colour) is a sign of corrosion by oxygen.
Frequent leaks In the event of frequent leaks, hydrogen and/ or air accumulate on the top part of the heat exchanger and the radiators, preventing complete heat exchange. When the electrolytic corrosion process starts, the level of the water in the plant drops and gases accumulate on the top part of the heat exchanger and on the radiators. The presence of air is caused by the fact that the plant may not be perfectly sealed. A slow drop in plant pressure due to a leak is often
difcult to nd, especially when the aw is very small (in
Page 17
17
MYDENS 60
COSMOGAS
5 - INSTALLATION
5.6.3 Treatment of the water in the thermal plants for civil use
The water in the heating plants for civil use must always be treated on replacement of the generator and in the event of a new plant. On the basis of the features of the raw water, in the design phase all treatment plants and the chemical conditioners necessary to obtain water with the following features, must be envisioned:
- Aspect: possibly clear;
- pH: over 7 (with radiators with aluminium elements of light
alloys, the pH must be lower than 8.5);
- Conditioners: present within the concentrations prescribed by the supplier. If the features of the of the water are not known, the probability of the following typical drawbacks occurring is high:
1. LIME SCALE FOULING
1 °fr = 10mg/kg CaCO
3
30° fr = 300 mg/kg CaCO
3
In a plant that contains 1000 litres of water at 30°f, the content of CaC03 is equal to 300 gr, which if not treated suitably, will deposit on the surface of the heat exchanger as this is the hottest point of the plant. This creates concentrated temperature increases with consequent breakage of the heat exchanger.
2. CORROSION
Corrosion is normally promoted by the presence of oxygen, by the contact between different metals or the presence of chlorides.
3. DEPOSITS
They are insoluble organic and inorganic substances: SLUDGE, WORKING RESIDUES.
5.7 - Draining the heating circuit
To avoid continuous renewal of water and consequent input of oxygen and limestone, it is recommended to limit every heating circuit drainage as much as possible.
5.8 - Expansion Tank
ATTENTION !!! Provide the plant with an appropriately dimensioned expansion tank, as envisioned by the national and local Installation Standards.
5.9 - Low temperature
plants (or on the oor)
ATTENTION !!! The plant downstream from
the appliance must be made with materials that resist temperatures up to 97°C and pressure of 3 bar.
Differently (e.g. plastic piping) the plant must be tted
with the relevant protection and safety devices.
ATTENTION !!! when installing the boiler in
a low temperature plant, it is indispensable to set parameter 3015 at the value of 45°C and parameter
3016 at the value of 20°C (see chapter 11).
With this setting, the boiler will adjust the ow to a
temperature between 20°C and 45°C. No adjustment from
the command panel (also via climatic adjustment),can
supply water at a temperature over 45°C.
ATTENTION !!! If the boiler is installed in a oor
plant made with plastic piping, all of the precautions must be taken against corrosion due to oxygen in the water:
make sure that the plant is made with plastic pipes with permeability to oxygen not exceeding 0.1 g/m3 at 40°C. Whenever the pipe should not meet these features, the radiant panel circuit from the boiler must be isolated via a plate heat exchanger, suitable to resist the corrosion generated by the oxygen dissolved in the water.
5.10 - Gas
ATTENTION !!! It is prohibited to power the
appliance with gases different to that envisioned.
ATTENTION !!! Check that the gas and supply
pressure are those for which the boiler has been adjusted.
Two situations are possible: A - the gas and supply pressure correspond to the
adjustment of the boiler. In this case, it can be
connected;
B - the gas and supply pressure do not correspond to the
adjustment of the boiler. In this case, the boiler must be converted to the type of gas and supply pressure corresponding to the supply available.
The boiler is provided with the relevant gas conversion kit.
Before installation it is advised to clean the inside of the
gas supply pipe thoroughly;
A cut-off cock must always be installed on the gas
supply pipe;
To prevent damage to the appliance gas control unit,
perform the leak test at a pressure not exceeding 50
mbar;
If the gas plant must be inspected at pressures over
50 mbar, operate on the cock positioned immediately upstream from the boiler, to isolate the same from the plant.
Figure 5.2 veries the positioning of the appliance gas tting.
The sections of the pipes making up the gas supply plant
must always guarantee a gas supply sufcient to cover the
maximum requested.
Page 18
18
MYDENS 60
COSMOGAS
Figure 5.4 - Safety valve drain and condensate drain connection
5 - INSTALLATION
5.11 - Condensate drain
There is a siphon inside the boiler for the evacuation of
condensate (see gure 3.1 detail “33”) and to prevent
combustion products from escaping, whose end
corresponds to the pipe “B” in gure 5.4. This termination must be conveyed into an anti-odour siphon (gure
5.6 detail “G”) to prevent bad odours returning into the
environment (the anti-odour siphon “G” is supplied on
request).
The tank “A” is provided already mounted as indicated in
gure 5.4 and xed with the screw “D”. The drain pipe “F” is also installed as indicated in gure 5.4.
In particular, the condensate drain plant must be:
for room used for residential purposes and for ofce with
more than 10 users, it can be connected to the domestic waste disposal plant by means of appropriate siphon with disjunction capable of preventing the pressurisation of
the system (siphon prepared within boiler) and to prevent
the return of bad odours from the sewer (detail “G” in
gure 5.6). If the room used for ofce purposes has
less than 10 users, before connection with the domestic waste drain, a condensate neutraliser is good practice (see chapter 9 for the value of acidity of the condensate
and the quantities).
be performed with a pipe with internal diameter equal to
or greater than 13 mm;
be installed in a way to prevent the liquid from freezing;
therefore pay attention to any external passings. It is
prohibited to drain into gutters or drainpipes;
to slope continuously towards the drain point, avoid high
points, which could pressurise the pipe;
5.12 - Safety valve
The appliance is protected against overpressures by a
safety valve calibrated to 3 bar (see gure 3.1 detail “30”). The safety valve drain (detail “C” in gure 5.4), along with the condensate drain (detail “B” in gure 5.4) must be conveyed to a pipe “F” (see gure 5.4) with minimum
internal diameter of 13 mm. The pipe “F” must be then
taken to the anti-odour siphon (detail “G” gure 5.6). This
drain with siphon is used to prevent overpressures if the valve is opened and makes it possible for the user to check the eventual intervention.
The pipe “F” in gure 5.6 is supplied mounted as per standard along with tank “A” in gure 5.4. The anti-odour siphon “G” in gure 5.6 is provided on request.
ATTENTION !!! If not connected to the drain,
whenever the safety valve should intervene, it could cause damage to persons, animals or objects.
5.13 - Water, gas connections
The boiler is provided with the ttings illustrated in gure 5.5
as per standard, where:
A = central heating ow Ø 35 B = central heating return Ø 35 C = 1” 1/2 ow tting D = 1” 1/2 return tting
E = 1”1/2 Gasket
Figure 5.5 - Hydraulic connections
C
A
E
D
B
020005.01.005
Figure 5.6 - Siphon funnel (on request)
F
G
020002.01.028
min10 mm max 30 mm
C
B
A
D
G
F
E
020005.01.004
Page 19
19
MYDENS 60
COSMOGAS
5.14 - Electric connections: generalities
ATTENTION !!! The appliance is only electrically
safe when it has been correctly connected to an
efcient earth circuit, performed as envisioned by the
current Safety Standards.
This fundamental safety requirement must be met. If in doubt, request a thorough control of the electric plant by a
professionally qualied technician.
Have a professionally qualied technician check that the
electric plant is suitable for the electric power required by the appliance, indicated on the plate.
The appliance must be connected to the mains electricity
using a cable coupler. The use of adapters, multiple sockets, extensions, etc. is not allowed.
The appliance must be connected to the mains electricity
using a three-polar electric cable, with double isolation, minimum section of 1.5 mm² and resistant to a minimum
temperature of 70°C characteristic T).
For connection to mains electricity, a bi-polar switch
must be envisioned in the vicinity of the appliance with a contacts opening distance of at least 3 mm, as envisioned by the current regulations on the subject.
Respect the polarity between the neutral phase during
connection of the appliance.
Make sure that the water plant and heating pipes are not
used as earth points for the electric or telephone plant. This piping is not suitable for this purpose, moreover, serious corrosion damage would occur in a very short time, on the appliance, piping and radiators.
ATTENTION !!! the boiler is not protected
against the effects caused by lightening.
D
C
C
C
B
A
020002.01.009
5 - INSTALLATION
Figure 5.7 - Electric connections
Key for gure 5.7
A = commands board box; B = electric connections lid; C = connections lid closing aps;
D = electric connections
Key for electric contacts
PM = External modulating pump control (if present)
CH = Flow sensor BUS = Remote control TA = Room thermostat/chronothermostat 0-10 = 0-10 volt signal input
SE = External sensor (if present) SB = Indirect Water Heater sensor (if present)
MF = Multi-function output
PE = External pump (if present) DNC = External diverter valve (if present) (D = Domestic hot water line; N = Neutral; C = Heating line)
L1 = boiler power supply line N = Boiler power supply neutral EARTH SYMBOL = Earth contacts
020002.01.010
Page 20
20
MYDENS 60
COSMOGAS
Figure 5.8 - Correct positioning of the room thermostat/chronothermostat
5.14.1 - Power supply cable connection
Proceed as follows to connect the power supply cable (refer
to gure 5.7):
1.- use a three-polar cable with double isolation, with
minimum section of 1.5 mm²;
2.- remove the casing from the appliance following the
relevant instructions in chapter 8.2;
3.- rotate the panel “A” towards the front of the boiler;
4.- operate on the aps “C” and open the lid “B” as indicated by the arrow;
5.- lay the power supply cable through the fairlead in
proximity of the contacts “L1”, “N” and earth symbol;
6.- strip the cable making sure that the earth wire (yellow/
green) is kept 20 mm longer than the other two;
7.- connect the yellow-green cable to the earth clamp (see
symbol);
8.- connect the brown cable (Phase) to the clamp L1;
9.- connect the blue cable (Neutral) to the clamp N.
5.14.2 - Choice of the room thermostat/ chronothermostat
The boiler is set-up to operate with any room thermostat or chronothermostat, which has the contact to which the cables coming from the boiler are to be connected, with the following features:
- open/closed (ON/OFF);
- potential-free (not powered);
- closing when there is a request for heat;
- 24Vac, 1A electrical feature
5.14.3 - Connecting the room thermostat/ chronothermostat
Install the room thermostat in a place in the house where the temperature is the most characteristic of the home and however in an area that is not subjected to repeated temperature changes, away from windows or doors which
open directly to the outside (see gure 5.8).
Proceed as follows to connect the room thermostat cable
(refer to gure 5.7):
1.- use a bi-polar cable with minimum section of 1.5mm², which goes from the boiler to the room thermostat/ chronothermostat. The maximum length allowed is 20 metres. For lengths exceeding 100 metres, use a shielded
cable with shield earthing;
2.- remove the casing from the appliance following the
relevant instructions in chapter 8.2;
3.- lay the electric cable through the fairlead in proximity of
the “TA” contacts;
4.- use a free fairlead, not used by other wires;
5.- strip the cable;
6.- connect the two ends of the cable to the “TA” clamps
(see gure 5.7).
ATT ENTI O N !! ! As the room ther most a t/
chronothermostat cables are subjected to very low safety
voltage (25Vdc), they must ow in wires different from the
230 Vac power supplies.
5 - INSTALLATION
Page 21
21
MYDENS 60
COSMOGAS
5 - INSTALLATION
5.14.4 - Installing the external temperature sensor (on request)
IInstall the external temperature sensor outside the building in a wall facing NORTH or NORTH-EAST, at a height of 2 to
2.5 metres from the ground. In buildings with several oors, it must be installed at about half way up the second oor. Do not
install it above windows, doors or ventilation outlets or directly below balconies or gutters. Do not plaster over the external temperature sensor. Do not install the sensor on walls without eaves, i.e. not protected from rain. Whenever the sensor is installed on a wall that has yet to be plastered, it must be installed with a suitable thickness or be removed before plastering. Proceed as follows to connect the external temperature sensor cable:
1.- lay a bi-polar electric cable with minimum section of
1.5mm², which goes from the boiler to the external temperature sensor. The maximum length allowed is 20 metres. For other lengths up to 100 metres, use a shielded cable with shield earthing.
ATTENTION !!! As the cables are subjected to
very low safety voltage (24Vdc), they must ow in wires
different from the 230 Vac power supplies.
2.- connect the bipolar cable to the “SE” clamps in gure
5.7;
3.- connect the bi-polar cable to the ends of the external temperature sensor.
Set the boiler to learn of the external temperature sensor as
follows (refer to gure 7.1):
1.- press the RESET keys and
simultaneously for 5
seconds until the symbol
appears on the display to
indicate the entry to the “Installer” menu;
2.- press the
and keys to scroll the parameters
in the “Installer” menu until the parameter
2003 is
displayed;
3.- press the RESET key to enable the modication of the parameter (highlighted by the fact that it starts to ash);
4.- press the
and key to modify the value of
the parameter, taking it to the value of 1 or 2 depending on
the type of climatic adjustment desired (see chapter 7.11);
5.- press the RESET key to conrm the modication of the
parameter (highlighted by the fact that the value of the
parameter starts to ash);
6.- press the RESET key for 2 seconds to go back to normal
display;
The enabling of the external sensor is conrmed by the
appearance of the icon
on the display.
Proceed with the steps given in chapter 7.11.3 to set the
correct adjustment values of the ow temperature depending
on the external temperature.
Page 22
22
MYDENS 60
COSMOGAS
5.15 - Connection of the boiler with
Indirect Water Heater and coil
The MYDENS 60 model boiler can be connected to a Indirect Water Heater with coil.
The hydraulic connection must be made as in gure 4.7.
Proceed as follows for the electric connection (refer to the
gure 5.7):
1.- disconnect the electric power supply from the boiler;
2.- lay a bi-polar electric able with minimum section of 1.5
mm², which goes from the appliance to the Indirect Water Heater temperature sensor and connect it to the boiler at
clamps “8” and “9” (SB);
3.- connect the other end of the cable to the Indirect Water
Heater temperature sensor;
4.- introduce the temperature sensor sensor inside the
Indirect Water Heater sample point (see gure 4.7 detail “31”).
The MYDENS 60 model boiler can be connected to a Indirect Water Heater with coil also after installation. In this case, a diverter valve must be envisioned outside the boiler to load the Indirect Water Heater along with
setting the parameter 3012 at the value of 1.
The temperature of the water stored inside the Indirect Water Heater can be selected by the user in a range between 40 and 70°C.
ATTENTION !!! A hot water temperature level
exceeding 51°C can cause permanent injury/damage to persons, animals and objects. Children, the elderly and disabled must be protected against the potential risks of scalding, by introducing devices that limit the temperature of use of domestic hot water to utilities.
5.15.1 - Anti- legionella
If the boiler is connected to a Indirect Water Heater for the preparation of domestic hot water, a disinfection cycle is envisioned against the legionella bacterium. This cycle envisions taking the Indirect Water Heater to a temperature
of 60°C (temperature at which the legionella bacteria dies)
at least every week. It is for this reason that the water (at
certain times) can reach the utilities at a higher temperature
that than set with the relative command.
ATTENTION !!! A domestic hot water
temperature level exceeding 51°C can cause permanent injury/damage to persons, animals and objects. Children, the elderly and disabled must be protected against the potential risks of scalding, by introducing devices that limit the temperature of use of domestic hot water to utilities.
5 - INSTALLATION
Page 23
23
MYDENS 60
COSMOGAS
5.16 - Burned gas exhaust and
combustion agent air intake pipe
ATTENTION !!! To connect the burned gas
exhaust and combustion agent air intake, the relevant national and local regulations must be respected.
ATTENTION !!! The fumes of this appliance can
reach 90°C in determined conditions. Therefore, use pipes in plastic that can resist high temperatures.
ATTENTION !!! This appliance is the
“condensing” type. Use AISI 316 stainless steel materials to make the fumes exhaust. The polypropylene materials to prevent corrosions due to the acidity of the condensate.
Regarding this, remember that appliances of this type must have exhaust and intake pipes supplied by the manufacturer of the appliance itself. Other types of pipes, if used, must be type-approved for this intended use. The types of exhaust for which the appliance is approved are given on the technical features table at the end of the manual under the “type” heading and on the features plate
afxed to the boiler, also under the “type” heading. The symbols used to dene type of exhaust is given below:
- B23, separated with intake in room and exhaust through wall or roof.
ATTENTION !!! If the appliance is installed with the
B23 type exhaust, it will take in air for combustion from the surrounding environment. Therefore, all precautions must be taken regarding ventilation of the rooms, which are prescribed by the national and/or local Standards.
- C13, coaxial in vertical wall
- C33, coaxial at the roof
- C43, separated with exhaust in ue, combined with intake
in common channel.
ATTENTION !!! The boilers installed in type C43
must only be connected to conventional ues.
- C53, separated with exhaust on roof and intake on wall or however, in two potentially different pressure points.
- C63, the boiler can be tted to type-approved exhaust and
intake pipes of other brands.
ATTENTION !!! With the C63 type exhaust,
the condensate coming from the chimney cannot be conveyed into the boiler.
- C83, separated with wall intake or another point independent from the intakes of other appliances and
ue exhaust.
Figure 5.9 - Exhaust/intake systems
5 - INSTALLATION
Page 24
24
MYDENS 60
COSMOGAS
During operation, especially in the winter, due to high yield, white smoke may escape from the appliance exhaust. This is solely a natural phenomenon and must not be worried about in any case, because it is the water vapour present in the fumes which in contact with the outside air, condensates.
5.16.1 - Type of intake/exhaust B23
In the case of B23 type combustion agent air/fumes exhaust systems, it is indispensable that the rooms in which the appliances are installed have at least as much air as that required by combustion and ventilation of the room. It is therefore good practice to remember that the combustion of 1 m³ of gas requires 11 cm³ of air. The natural flow of air must take place directly through permanent openings made in the outside walls of the room to
be ventilated; however away from sources of pollution, such
as: vents of dubious origin, airborne industrial exhaust etc.
The ventilation openings must meet the following requirements:
have sections with net passage of at least 6 cm² for
every kW of heat input installed, with minimum of 100
cm²;
be realised in a way that the opening inlets both inside
and outside the wall cannot be blocked;
be protected, for example with grids, metal meshes, etc..
The net section of the passage must not be reduced by
these elements;
be situated at a height more or less of the oor and such
not to disturb the correct operation of the combustion products exhaust devices. Where this position is not possible, the section of the ventilation openings must be increased by at least 50%.
The ow of air can also be obtained from an adjacent room
as long as:
it has direct ventilation, in compliance with the previous
points;
in the room to be ventilated, only appliances tted to
exhaust pipes are installed;
the adjacent room is not a bedroom;the adjacent room is not a common part of the building;the adjacent room is not an environment with re hazard,
such as a hangars, garages, combustible materials
warehouse, etc.;
the adjacent room does not have a negative pressure with
respect to the room to be ventilated due to reverse draught (which can be caused by the presence in the room of
another appliance operating with any type of fuel, a replace
and any other intake device for which an adequate air intake
has not been envisioned);
the ow of air from the adjacent room to that to be ventilated
can take place freely through permanent openings with total net section not less than that indicated at the start of this chapter.
In rooms where gas appliances are installed, it may become necessary, as well as the input of combustion agent air, also to evacuate the stale air, with resulting release of an additional equal amount of clean air.
If the stale air is evacuated with the aid of a mechanical tool
(electric fan) the following conditions must be respected:
a) if there is a common exhaust pipe in the room, it must be
capped;
b) the ventilation opening of the room in which the gas
appliance is installed must be increased depending on the
maximum air ow rate required at the electric fan.
c) the action of the electric fan must not affect the correct
evacuation of the combustion products. To this end, that
stated above must be veried by draft testing, running the
fan or extractor hood at its maximum power and the gas appliance at the maximum and minimum power.
5 - INSTALLATION
Page 25
25
MYDENS 60
COSMOGAS
5 - INSTALLATION
5.16.2 - “Split 80/80PP” System
(polypropylene) (Type C43; C53; C83)
The appliance is supplied as per standard without ttings
for the connection of the fumes exhaust/air intake. To connect it to a “80/80PP Split” system, the relevant kit must
be requested and must be installed as in gure 5.10.
Fitting “A” can rotate freely by 360°, guaranteeing optimum installation versatility.
In the fumes exhaust side, it is mandatory to install AISI
316L stainless steel or polypropylene pipes, which are more resistant to the formation of condensate.
Take particular care with the installation of pipes in
the part that passes through the wall to the outside. The normal maintenance operations must always be possible, therefore install the pipes in a sheath so that they can slide out.
The horizontal tracts must always have an inclination of
at least 2% towards the condensate drain device.
The appliance is already set-up to collect the
condensate, which must be tted to a drain pipe (see chapter 5.11).
ATTENTION !!! This condensate drain is
designed to make all liquid produced ow from a single
appliance. If several appliances are installed, each one must envision its own condensate drain.
The fumes exhaust/air intake system can be extended up to a maximum distance as indicated in chapter 9. Every 90° bend has a loss equivalent to 1 metre of linear pipe. Every 45° bend has a loss equivalent to 0.5 m of linear pipe.
ATTENTION !!! The fumes exhaust terminal
must be appropriately protected against the effects of the wind (see also 7.19.1 chapitre error Loc 20).
ATTENTION !!! Mechanically secure the
joints between the various component elements of
the exhaust and intake pipe, through the use of xing systems or equivalent systems. See gure 5.12.
ATTENTION !!! The temperature of the exhaust
pipe can reach 90°C during operations. If it must pass through a wall that is sensitive to these temperatures, insert a protective heat-isolation sheath.
ATTENTION !!! If the air intake and fumes
exhaust terminals are positioned in the same wall, they must remain at a minimum distance of 1 metre.
ATTENTION !!! The exhaust and intake pipes
must be appropriately sustained via rigid brackets positioned no more than 1 metre from each other. The
brackets must be xed to rigid walls that can support
the weight of the pipe itself.
Figure 5.12 - Fixing the exhaust and intake pipes
Figure 5.10 - Installing the “80/80PP Split” system
Figure 5.11 - Clearance
B
C
A
020008.01.011
Page 26
26
MYDENS 60
COSMOGAS
5.16.3 - “Split 80/80PP” System (Type C43;
C53; C83): accessories available
To make the “80/80PP split” fumes exhaust/air intake system,
we propose some of the most common accessories available;
remember that a wide range can be consulted in the relevant catalogue: (the number after the code is used to recall the piece in the
following drawings)
62617306 - N° 10 PP coaxial roof terminal 62617244 - N° 12 90° bend M/F PP 62617255 - N° 29 converts for pitched roofs from 15 up to 25° 62617236 - N° 11 extension M/F PP 62617249 - N°18 anti-slip bands for extensions PP
62617240 - N° N° 14 exible hose M.F. PP L=20m 62617241 - N°16 spacer for exible hose
62617238 - N° 17 telescopic joint PP
62617242 - N° 15 T-tting PP
62617246 - N° 13 45° bend M/F PP
COD. 62617306
5 - INSTALLATION
Page 27
27
MYDENS 60
COSMOGAS
5.16.4 - “Split 80/80PP” System (Type C43;
C53; C83): installation examples
In gure 5.13 two examples of installation are given:
- exhaust into chimney with collection of condensate inside
the boiler itself. The horizontal part of the fumes exhaust side must be inclined towards the boiler. The intake must slope towards the outside to prevent rain water entering.
- exhaust to the outside directly with the boiler pipes with
condensate collection inside the boiler itself. The intake must slope towards the outside to prevent rain water entering.
In gure 5.14 it is possible to see a separated type of fumes exhaust, where fumes exhaust was realised with exible hose
in polypropylene for piping of technical cells. The condensate produced in the vertical pipe must all be conveyed into the boiler. The intake must slope towards the outside to prevent rain water entering.
Figure 5.13 - Example of “80/80 PP System” installation
Figure 5.14 - Example of “80/80 PP System” installation
5 - INSTALLATION
Page 28
28
MYDENS 60
COSMOGAS
5 - INSTALLATION
B
C
A
020008.01.013
5.16.5 - “80/125PP vertical coaxial” System
(polypropylene) (C13; C33)
The appliance is supplied as per standard without ttings
for the connection of the fumes exhaust/air intake. To connect it to a 80/125 vertical coaxial system, the relevant
kit must be requested and must be installed as in gure
5.15.
ATTENTION !!! Scrupulously follow the installation
phases of the coaxial pipe as illustrated in gure 5.17. In
particular:
1.- introduce the coaxial pipe “C” inside the bend “A”;
2.- x the external pipe using the stainless steel self-threading
screws “B”.
ATTENTION !!! The coaxial exhaust and
intake pipes must be appropriately sustained via rigid brackets positioned no more than 1 metre from each
other. The brackets must be xed to rigid walls that can
support the weight of the pipe itself.
ATTENTION !!! Once these operations have
been performed, check that the exhaust/intake terminal is exposed to the outdoors with the tolerances given in
gure 5.18
Take particular care with the installation of pipes in the part
that passes through the wall to the outside. The normal maintenance operations must always be possible, therefore install the pipes in a sheath so that they can slide out.
The horizontal tracts must always have an inclination of at
least 2% towards the appliance.
The fumes exhaust/air intake pipe can be extended up to
a maximum distance as indicated in the table in chapter 9 at the end of the manual. Every 90° bend has a loss equivalent to 1 metre of linear pipe. Every 45° bend has a loss equivalent to 0.5 m of pipe.
Figure 5.15 - Installation of vertical coaxial system
Figure 5.16 - Quotes and hole centre to centre distances for coaxial drain pre-installation
Figure 5.17 - Positioning the coaxial pipe
Page 29
29
MYDENS 60
COSMOGAS
5 - INSTALLATION
5.16.6 - “80/125PP Coaxial” System: accessories available
The following accessories are available on request to make the 80/125 coaxial fumes exhaust/air intake system: (the number after the code is used to recall the piece in the
following drawings)
62617255 - N° 2 converts for pitched roofs from 5° to 25° extension L = 1000 mm 62617321 - N° 1 90° coaxial bend M/F PP 62617322 - N° 6 45° coaxial bend M/F PP 62617323 - N° 7 Coaxial extension L 1m PP 62617325 - N° 3 coaxial PP roof terminal 62617324 - N° 5 coaxial PP wall terminal
62617255
62617321
62617322
62617323
62617324
62617325
Page 30
30
MYDENS 60
COSMOGAS
5.16.7 - “80/125PP Coaxial” System:
installation examples
When a coaxial exhaust is made (see gure 5.18), both vertical
and horizontal, the exhaust pipe slope upwards in a way to
make the condensate ow into the boiler.
Figure 5.18 - Examples of coaxial pipe installation
5 - INSTALLATION
Page 31
31
MYDENS 60
COSMOGAS
6.1 - Operating
Before starting the appliance up, it si necessary to carry out the following.
6.1.1 - User instructions
Instruct the user regarding correct use of the appliance and the plant in general. In particular:
Give the installation and use manual and all
documentation contained in the packaging to the user.
Instruct the user concerning the special measures for the
exhaust of burned gases, informing them that they must
not be modied.
Inform the user regarding the control of the pressure
of the water required in the plant and the measures
necessary to ll and bleed the air.
Inform the user regarding the correct adjustment of
the temperatures, control units/room thermostats and radiators for energy saving.
6.1.2 - Filling the condensate drain siphon
The siphon found inside the boiler (see gure 3.1 detail “33”), must be lled with water to create the water head able to prevent the fumes escaping from pipe “F” in gure 5.4. Proceed as follows to do this: (refer to gure 6.1)
1.- loosen and remove the cap “R”;
2.- introduce a rubber hose into the opening “S” and the
other end of the hose into the funnel;
3.- use the funnel to slowly pour about 200 cm3 (a glass) of water;
4.- re-mount everything in reverse order.
6 - OPERATING
Figure 6.1 - Filling the condensate drain siphon
ATTENTION !!! If the boiler remains off for
more than 3 months, the siphon must be lled again as
explained above.
6.1.3 - Filling the central heating plant
If the wording FILL, appears on the visual display when the boiler is powered electrically, it means that the central
heating plant must be lled. Proceed as follows:
only use clean water from the main supply.
ATTENTION !!! The addition of chemical
substances such as anti-freeze must be performed in compliance with the product instructions. In all cases, these substances must not be introduced directly inside the boiler.
1.- open the lling device envisioned by the installer upstream from the appliance and ll the bar to about 1.5
bar (FILL will appear on the visual display);
2.- make sure there are no water leaks from the ttings;
3.- close the lling device envisioned by the installer upstream from the appliance;
4.- bleed the heating elements;
5.- check the pressure on the boiler display again. If it has dropped, load up to 1.5 bar again.
S
R
S
R
020005.01.006
Page 32
32
MYDENS 60
COSMOGAS
6.2 - General recommendations
regarding the supply of gas
For commissioning of the boiler, have a professionally
qualied technician perform the following checks:
That the boiler is powered by the type of fuel for which it
is set-up.
That the gas supply pressure (with boiler operating
and at a standstill) is within the maximum and minimum
values indicated in the table in chapter 9 at the end of the manual.
That the supply plant has all safety and control parts
envisioned by the current national and local Standards.
That the fumes discharge terminal and the combustion
agent air intake terminal are free from any obstruction.
That the fumes exhaust and combustion agent air intake
terminal are positioned outside the building.
That the condensate drain connection is connected.
ATTENTION !!! If you smell gas:
A - Do not switch on any electric device, telephone
included or any object that can cause sparks;
B - Immediately open doors and windows causing
a current of air that quickly cleans the gas from the room;
C - From another room, or from a neighbour’s,
immediately call a professionally qualied
technician or the gas supply company. Call the Fire Service if the former are not available.
6.3 - Type of gas for which
the appliance is adjusted
There is a label on the front of the appliance certifying the gas supply type and pressure for which the boiler is adjusted. The boiler may have the following 2 types of wording:
2H-G20-20mbar NATURAL GAS
means that the appliance is adjusted to operate with H type
gas of the second family (natural gas) at a supply pressure
of 20 mbar.
3P-G31-37mbar L.P. GAS
means that the appliance is adjusted to operate with type P
gas (Propane, also called LP Gas) of the third family, at a
supply pressure of 37 mbar.
6 - OPERATING
Page 33
33
MYDENS 60
COSMOGAS
6.4 - Conversion of the appliance
from one type of gas to another
ATTENTION !!! Read these instructions carefully
before changing the gas:
- The gas appliance must be installed, calibrated or
modied by specialised staff in compliance with legal
terms;
- Check and be certain that the type of gas which is powering the appliance is compatible with the adjustment kit in your possession;
- Do not power the boiler with gases different from those envisioned.
Follow the instructions given below to change the gas: 1 - disconnect the electric power supply upstream from the
appliance;
2 - open the boiler casing as reported in chapter 8.2;
3 - access the control and command board as reported in
chapter 8.2;
4 - move the microswitch “B” of switch “A” from left to right
to the “ON” position (see gure 6.5);
5 - apply electric power to the boiler;
6 - the parameter 3001 will appear on the boiler’s visual
display, followed by its value;
7 - using the keys
and access the
parameter 3002.
8. - press the RESET key to make the 3002 parameter
ash;
9. - using the
and keys, set the value of
the parameter 3002 to the new corresponding value
according to the table in gure 6.7.
10. - press the RESET key to conrm the modication.
11.- remove voltage from the boiler, re-position the microswitch
“B” of switch “A” from right to left in “OFF” position (see gure
6.5).
12. - close the gas supply;
13. - remove the air manifold making sure to turn it
externally and then slide it out of the fan inlet (see gure
6.2, detail “C”);
15. - remove the gas inlet pipe via the two ttings (see gure 6.2, details “H” and “L”);
16. - remove the clamping spring “M” from the seat “N”
releasing the valve “P” (See gure 6.3);
17. - slide the gas valve “P” out upwards;
18. - replace the gas nozzle “R” (see gure 6.4) with an
appropriate one according to that stated in the table in
gure 6.7 under “Diameter of the gas nozzle”;
19. - remount the gas valve (see gure 6.3, detail “P”), making sure to reposition the spring “M”;
20. - remove the gas supply pipe via the two ttings (see gure 6.2, details “H” and “L”);
21. - re-mount the air manifold (see gure 6.2, detail “C”);
22. - open the gas cock;
23. - check for any gas leaks using the relevant means of control.
ATTENTION !!! Perform the leak test using a
soap and water only. The use of naked ames is
prohibited.
B
F
G
L
D
E
H
C
A
020005.01.014
N
P
M
Q
O
020002.01.041
R
020002.01.042
Figure 6.4 - Replacing the gas nozzle
Figure 6.3 - Removing the gas valve
Figure 6.2 - Removing the air manifold
6 - OPERATING
Page 34
34
MYDENS 60
COSMOGAS
ATTENTION !!! If you smell gas:
A - Do not switch on any electric device, telephone
included or any object that can cause sparks;
B - Immediately open doors and windows causing
a current of air that quickly cleans the gas from the room;
C - From another room, or from a neighbour’s,
immediately call a professionally qualied
technician or the gas supply company. Call the Fire Service if the former are not available.
24.- check the supply gas pressure, following the procedure
in chapter 6.6;
25.- open the CO2 adjustment screw completely (see gure
6.14 detail “A”);
26.- control and adjust the CO2, following the procedure in
chapter 6.8;
27.- instead of the label that identified the old state of adjustment, apply the sticker onto the front casing of the
boiler (see gure 6.6), certifying the appliance’s new state
of adjustment, as follows: apply label “B” if the boiler has
been converted from methane to LPG; apply label “A” if the
boiler has been converted from LPG to methane.
A – Microswitch B - Switch
Figure 6.5 - Positioning electric bridge
A
B
020002.01.043
ON
OFF
6 - OPERATING
Model
Type
of gas
Setting
parameter
3002
Minimum
gas supply
pressure
(mbar)
Maximum
Gas supply
pressure
(mbar)
Gas nozzle
diameter
(mm)
CO2
Maximum
power
(%)
CO2
Minimum
power
(%)
O2
Maximum
power
(%)
O2
Minimum
power
(%)
60
NAT
gas
54 15 27 10,0 9,0 ±
0,3 8,5 ± 0,2 4,9 ± 0,2 5,8 ± 0,2
LP gas 55 25 45 6,5 10,5 ± 0,3 10,0 ± 0,2 4,8 ± 0,2 5,6 ± 0,2
Figure 6.6 - Labels certifying the new status of adjustment of the boiler
Figure 6.7 - Correspondence table for the parameter 3002 and the operating values
Page 35
35
MYDENS 60
COSMOGAS
Figure 6.8 - Gas valve
A - Gas inlet pressure point.
6 - OPERATING
6.5 - Ignition
1.- open the gas cock;
2.- power the boiler electrically;
3.- adjust the temperature required from the heating service
using the
and keys. The icon , present on the display will inform regarding the operating state of the heating service:
a) xed icon
: central heating inactive (check that the room thermostat is in call mode or, in the case of external mode, that the external temperature is lower than the central heating switch-off external temperature
(par 2020);
b) ashing icon
: means that the central heating mode
is operating.
4. -adjust the temperature required for the domestic hot water
service using the
and keys. The icon , present on the display will inform regarding the operating state of the domestic hot water service:
a) xed icon
: domestic hot water inactive (no-one is withdrawing domestic hot water, or in the case of a Indirect Water Heater, the delivery temperature is
reached)
b) ashing icon
: domestic hot water is being withdrawn.
5.- if the icon
ashes, but the radiators do not heat-up,
it may mean that the pump (see gure 3.1 detail “7”) is
blocked. It must be unblocked by operating on the relevant
screws. TO do this remove screw “6” in gure 3.1 and turn the screw below to unblock the pump;
6.- if the icon
ashes but the radiator still does not heat
up, bleed the air from the radiators again.
6.6 - Controlling the supply gas pressure and any adjustment
The gas supply pressure must correspond to that stated in the table in chapter 9 at the end of the manual. Proceed as follows to verify:
1.- close the gas cock;
2.- access the components inside the boiler, following the
procedure in chapter 8.2;
3.- loosen the pressure point “A” (see gure 6.8);
4.- connect to a manometer with resolution of at least 0.1
mbar (1 mmH2O);
5.- open the gas cock;
6.- check that the pressure does not exceed the value given in the table in chapter 9 under “ gas supply maximum
pressure”;
7.- make sure that any cocks and thermostatic valves
downstream from the central heating circuit are open;
ATTENTION !!! During forcing of the delivery
temperature, it automatically goes to 93°C to give the possibility to dispose of as much of the heat generated by the boiler as possible. Check that the central heating plant can support this temperature.
8.- premere contemporaneamente per più di 5 secondi
press the
and RESET key simultaneously for
more than 5 seconds to enter the “installer” menu,
conrmed by the appearance of the icon
on the
display.
9.- using the
and keys access the
parameter 2010;
10.- press the RESET key to enter the parameter and use the
and keys, to modify the value to HIgH;
11.- press the RESET key to conrm the modication. Now
the burner will operate at maximum power for 10 minutes.
12.- check that the pressure does not drop to a value lower than the “gas supply minimum pressure” given in the table in chapter 9. If the supply pressure does not respect the values described, operate upstream from the appliance in order to take it back within the minimum and
maximum eld;
13.- Once the control has ended, press the RESET key
again to enter parameter
2010 and via the
and
keys, change the value to OFF;
14.- press the RESET key to conrm the modication;
15.- hold the RESET key down for 5 seconds to exit the
“installer” menu;
16.- close the pressure point “A” in gure 6.8;
17.- check for any gas leaks from the point with relevant control methods.
ATTENTION !!! Perform the leak test using a soap
and water only. The use of naked ames is prohibited.
A
020002.01.023
Page 36
36
MYDENS 60
COSMOGAS
Figure 6.9 - Combustion agent air pressure point
Figure 6.11 - Controlling combustion agent air pressure
6.7 - Controlling the combustion
agent air pressure
As the boiler has an air/gas ratio xed in the factory, the gas
pressure at the burner is controlled indirectly by measuring the pressure of the combustion agent air inside the boiler and must correspond to that stated in the table in chapter 9, under “Combustion agent air pressure”. Proceed as follows for the check (refer to the Figures from
6.9 to 6.12):
1.- use a differential manometer with precision of at least 0.1
mbar (1 mmH2O);
2.- close the gas cock;
3.- open the boiler casing following chapter 8.2;
4.- remove the caps “A” (see gure 6.9);
5.- take the exible hose “D”, which is found inside the appliance and remove the cap “B” (see gure 6.9);
6.- insert the pipe “D” inside the hole indicated by the arrow
in gure 6.9;
7.- loosen the pressure point “H” in gure 6.10;
8.- take a silicone pipe with external diameter of 10 mm and
internal diameter of 7mm (detail “E” in gure 6.10) and introduce it into pressure point “H”;
9.- insert pipe “E” into the hose as indicated in gure 6.11;
10.- connect the manometer to the two pipes “E” and “F” as
illustrated in gure 6.12, making sure to connect the pipe “E”
to the negative pressure point and tube “F” to the positive
pressure point;
11.- close the casing “B” in gure 8.1. It is indispensable
to have a reliable measurement;
12.- switch the boiler on;
13.- press the
and RESET keys simultaneously
for more than 5 seconds to enter the “installer” menu,
conrmed by the appearance of the icon
on the
display.
14.- using the
and keys, access the
parameter 2010;
15.- press the RESET key to enter the parameter and use the
and keys, to modify the value to FAn;
16.- press the RESET key to conrm the modication. Now
the fan will operate at maximum speed for 10 minutes.
17.- compare the pressure value read on the manometer with that given in the table in chapter 9, “Combustion agent air pressure”. If the pressure is at a lower value, check that there are no obstructions in the combustion agent air/fumes exhaust or that the air intake/fumes exhaust system is not longer than envisioned in chapter 9 under “Max. length of
fumes pipe”;
18.- once the control has ended, press the RESET key again
to enter parameter
2010 and via the and
keys, change the value to
OFF;
19.- press the RESET key to conrm the modication;
20.- hold the RESET key down for 5 seconds to exit the “installer” menu.
At the end of the control, remove the tube “E”, close the holes in the lower frame with the caps “A”, close the pipe “D” using cap “B” and close the pressure point “H” again as
in gures 6.9 and 6.10.
6 - OPERATING
D
A
C B
020002.01.019
D
C
E
F
020002.01.020
Figure 6.10 - Combustion agent air pressure point
H
E
020002.01.022
Page 37
37
MYDENS 60
COSMOGAS
Figure 6.13 - Combustion analysis points
6.8 - Controlling the level of
CO2 and any adjustment
The boiler in normal operating mode and for altitudes within 1000
m, has a level of CO2 (carbon dioxide) in the fumes which can be
detected in the table in chapter 9. A value different to those reported can cause malfunctions. Combustion analysis must be performed to check and eventually adjust this value. Proceed as follows:
1.- check a combustion analyser to the appropriate point on
the fumes exhaust tting “S” in gure 6.13;
2.- make sure that any cocks and thermostatic valves
downstream from the central heating circuit are open;
ATTENTION !!! During forcing of the delivery
temperature, it automatically goes to 93°C to give the possibility to dispose of as much of the heat generated by the boiler as possible. Check that the central heating plant can support this temperature.
3.- press the
and RESET keys simultaneously
for more than 5 seconds to enter the “installer” menu,
conrmed by the appearance of the icon
on the
display.
4.- using the
and keys access the
parameter 2010;
5.- press the RESET key to enter the parameter and use the
and keys, to modify the value to HIgH;
6.- press the RESET key to conrm the modication. Now
the burner will operate at maximum power for 10 minutes.
7.- wait for the CO2 measurement to stabilise;
8.- compare the value measured with that given in the
table in gure 6.7, “CO2 maximum power”. If the value
measured is offset from the value read, it must be taken
back within the value given in the table in gure 6.7.
proceeding as follows:
a) turn screw “A” clockwise as in gure 6.14 to decrease
the level of CO2;
b) turn screw “A” anti-clockwise as in gure 6.14 to increase
the level of CO2;
9.- Once the check has been completed, seal the screw “A”
in gure 6.14 with red pain or similar system;
10.- press the RESET key again to enter the parameter
2010 and use the and keys, to modify
the value to
LOu;
11.- press the RESET key to conrm the modication. Now
the burner will operate at minimum power for 10 minutes.
12.- wait for the CO2 measurement to stabilise;
13.- compare the value measured with that given in the
table in gure 6.7, “CO2 minimum power”.
If the value measured is offset from the value read, it must
be taken back within the value given in the table in gure
6.7. proceeding as follows:
a) turn screw “B” anti-clockwise as in gure 6.14 to decrease
the level of CO2;
b) turn screw “B” clockwise as in gure 6.14 to increase
the level of CO2;
14.- Once the check has been completed, seal the screw “B”
in gure 6.14 with red paint or similar system;
15.- press the RESET key again to enter the parameter
2010 and use the and keys, to modify
the value to
OFF;
16.- press the RESET key to conrm the modication.
17.- hold the RESET key down for 5 seconds to exit the “installer” menu.
6 - OPERATING
Figure 6.14 - Gas valve
A - CO2 adjustment screw at maximum power; B - CO2 adjustment screw at minimum power;
A
B
020002.01.045
E
F
G
020002.01.021
Figure 6.12 - Controlling combustion agent air pressure
S
R
S
R
020005.01.006
Page 38
38
MYDENS 60
COSMOGAS
Figure 6.15 - Corresponding values to introduce
into the parameter
2002 to obtain the desired
power necessary in central heating mode
6 - OPERATING
Power necessary
(kW)
Values for
parameter 2002
60 100 59 98 57 94 55 90 53 86 51 83 49 79 47 75 45 71 43 68 41 64 39 60 37 56 35 53 33 49 31 45 29 41 27 38 25 34 23 30 21 26 19 23 17 19 15 15 13 11 11 8
9 4
7,5 1
ATTENTION !!! If during forcing, the power
supplied by the boiler is much higher than the power absorbed by the plant, the boiler switches off continuously to reach the maximum temperature allowed (93°C). To remedy this problem the heating power must be set at the effective plant requirement, as laid down in chapter 6.9 and the CO2 analysis test or
combustion efciency test must be carried out, setting
parameter
2010 previously referred to at the rEg
value.
6.9 - Adjustment of the power in
central heating mode (Range Rated)
This appliance is designed and type-approved to adapt the maximum heating power to the effective necessity of the plant as per calculation. To do this and to use the boiler’s potentiality to its best, it is recommended to set the maximum power in central heating mode at the effective requirement of the plant. Operate as follows:
1.- press the
and RESET keys simultaneously
for more than 5 seconds to enter the “installer” menu,
conrmed by the appearance of the icon
on the
display.
4.- using the
and keys, access the
parameter 2002;
5.- press the RESET key to enter the parameter and using the
and keys modify the value corresponding to the power required by the plant, according to the table in Figure 6.15.
6.- Press the RESET key to conrm the modication.
7.- Hold the RESET key down for 5 seconds to exit the “installer” menu.
Page 39
39
MYDENS 60
COSMOGAS
7 - USE
Figure 7.1 - Control board
KEY FOR FIGURE 7.1
A - Key for reducing the central heating temperature (below
minimum the central heating is put in OFF)
B - Reset Key C - Key for switching-on and increasing the heating
temperature
D - Burner status (the burner is on when this icon is present)
E - Status of the heating service: Icon off = Central heating off Icon on = Central heating active but not operating
Icon ashing
= Central heating active and operating F - State of the domestic water service: Icon off = Domestic water off Icon on = Domestic hot water active but not operating
Icon ashing
= Domestic hot water active and operating G - Icon for entry into the “Installer” menu H - Unit of measurement of the pressure displayed L - Status of the cascade pump (if the icon is present, the
pump is on)
M - Central heating plant pressure or indicator of the
various parameters inside the various menus
N - Temperature of the central heating or domestic hot
water or indicator if the values assumed by the various
parameters O - Unit of measurement of the temperature displayed P - Central heating service adjusted by the external sensor Q - Boiler blocked (see chapters 7.19.1 and 7.19.2 for the
diagnostics)
R - Key for increasing the domestic hot water temperature
and to scroll and change the value of the parameters S - Key for reducing the domestic hot water temperature
and to scroll and change the value of the parameters T - On/Off switch
7.1 - Controlling cock opening
- The gas cock must be open;
- Any valves positioned on the ow and return must be open;
7.2 - Checking central heating plant pressure
If the pressure inside the central heating circuit drops below
0.5 bar, the visual display “N” in gure 7.1, shows
FILL
to indicate that the correct pressure must be restored. Proceed as follows:
1.- open the device envisioned by the installer upstream
from the appliance in order to load the plant;
2.- check the pressure on the visual display “M” in Figure
7.1; it must reach the pressure of 1.5 bar (the FILL indication must disappear);
3.- close the device envisioned by the installer upstream from the appliance.
ATTENTION !!! During normal operation, the device envisioned by the installer upstream from the appliance for loading the plant, must always remain in the closed position.
If the pressure drops through time, restore the correct value. This operation may have to be repeated several
times in the rst month of operation to remove any air
bubbles in the plant.
Page 40
40
MYDENS 60
COSMOGAS
7 - USE
7.3 - Generalities
During operation the display shows the boiler operating state as well as other information as indicated in chapter
7.19 (Diagnostics).
Other parameters can be consulted through the
“User menu” (see chapter 7.17), which are useful for
understanding operation of the appliance and to control the latest blocks or errors occurring. After 5 minutes of normal operation, the display switches off completely to save energy. Just press any key to switch it back on. In the case of any anomaly, the display switches back on automatically.
This function can be modied by following chapter 7.16 (Energy saving).
7.4 - Ignition procedure
1.- open the gas cock;
2.- power the boiler electrically;
3.- adjust the domestic hot water temperature, if present, and of the central heating respectively as per chapters 7.8 and 7.9.
The command and control equipment will switch the burner on. If ignition does not take place within 20 seconds, the boiler automatically re-attempts ignition 3 times, after which if it still
does not ignite, it blocks and the display will indicate Loc
1. Press the RESET key to restore the normal operating
conditions. The boiler will automatically attempt a new ignition.
ATTENTION !!! If shutdown due to blocking is
repeated frequently, contact a qualied technician to reset
the normal operating conditions.
Once the boiler has been ignited correctly, it will continue to operate for the service requested.
7.5 - “User menu”
Entry into the “User menu” is highlighted by the visual display
“M”, in gure 7.1, which indicates parameters that can assume
values from 1001 to 1999. To enter the “User menu”:
1.- hold the RESET key down for 2 seconds until the visual
display “M” shows 1001;
2.- press the
and keys to scroll the parameters
situated inside the user menu;
3.- hold down the RESET key for more than 2 seconds to
exit the “User menu”;
If no key is pressed for more than 60 seconds, the menu is exited automatically. The parameters in chapter 7.17 can be queried in this menu.
7.6 - Summer operating mode
Whenever the central heating function is to be interrupted for a long period of time, leaving only the domestic hot water function operating, adjust the central heating temperature to
minimum using the
or key until 0FF appears.
7.7 - Winter operating mode
In winter operating mode, using the pump, the boiler sends the water to the plant at the temperature set using the
or keys. When the temperature inside the
boiler approaches the temperature set, the burner starts to
modulate the ame until the power is reduced to the effective
requirement of the plant. If the temperature tends to rise further, the burner stops.
At the same time, the pump that sends water to the plant is switched on and off by the room thermostat. This can be
noted because the indicator
, ashes when the pump
is on, while it remains on with a xed light when the pump
is off. The pump may initially make a noise. This is due to the presence of residual air in the hydraulic plant, which will disappear quickly, without any intervention. For rational use of the boiler, it is recommended to keep the
central heating temperature, adjusted using the
or
keys, at the lowest value possible, compatibility with the temperature requested in the rooms. If the winter season is particularly cold, meaning the room temperature can no longer be maintained, raise the central heating temperature to higher values.
7.8 - Adjusting the domestic hot water (if a Indirect Water Heater is present)
The temperature of the domestic hot water is adjusted by
operating on the
and keys. On pressing one
of the two keys, the visual display “N” in gure 7.1 will start to ash and show the temperature that is being set. The range
of regulation within which the temperature of the domestic hot water can be adjusted goes from 40°C to 70°C. By holding
the key
down also below 40°C, the word OFF will
appear to indicate switch-off of the domestic hot water service,
highlighted by the switch-off of the “F” icon shown in gure 7.1.
7.9 - Central Heating
Using the parameter 2003 present in the “Installer menu”
(see chapter 7.18) it is possible to select different operating
modes of the central heating service:
-
2003 = 00; “Thermostatic adjustment”: the central heating
ow temperature is adjusted manually via the
or keys. The opening and closing of the room thermostat stops or starts the boiler pump correspondingly
in order to adjust the room temperature;
-
2003 = 01; “Climatic adjustment”: The icon , appears
on the display, the ow temperature to central heating is
adjusted automatically by the external temperature sensor according to the algorithm corresponding to Figure 7.2. The opening and closing of the room thermostat stops or starts the boiler pump correspondingly. When the external
temperature rises above the value set in parameter 2020
(Central heating switch-off external temperature), the
central heating service ends. It re-starts automatically when the external temperature drops below the temperature set
in the parameter 2020 again.
- 2003 = 02; “Climatic adjustment with room compensation”:
The icon
appears on the display, the ow temperature
to central heating is adjusted automatically by the external temperature sensor according to the algorithm corresponding to Figure 7.2. The opening of the room
thermostat reduces the temperature if the ow to central
heating by a value set in the parameter 2027. The boiler pump operates constantly. When the external temperature
rises above the value set in parameter 2020 (forced
central heating switch-off), the central heating service ends.
Page 41
41
MYDENS 60
COSMOGAS
7 - USE
It re-starts automatically when the external temperature drops below the temperature set in the parameter 2020
again (forced central heating switch-off).
7.10 - Thermostatic adjustment
In the factory the boiler is adjusted with the parameter 2003 to 00, i.e. the boiler supplies hot water to the central heating
plant at a temperature adjusted using the or
keys. Any room thermostat operates directly on the pump inside the boiler to adjust the heating of the rooms.
To make full use of boiler efciency, it is recommended to adjust the temperature to a value just sufcient to obtain
the temperature desired by the rooms. If the season gets colder, progressively increase the value of the central heating temperature. Proceed in reverse order when the season goes towards warmer temperatures. This very simple operating method is suitable for the following types of plants:
- small plants, with radiators, having a room whose temperature
is characteristic of all other rooms;
- large plants, with radiators, where each area is controlled by its own room thermostat and the boiler pump is stopped
only when all area thermostats are satised (envision the appropriate electric plant).
- large plants, with radiant panels (low temperature), where
each area is controlled by its own room thermostat and the boiler pump is stopped only when all area thermostats are
satised (envision the appropriate electric plant).
7.11 - Climatic adjustment
Using the “Installer menu” adjust the parameter 2003 to
01. The central heating ow temperature is reported to the
external temperature sensor according to the algorithm in
gure 7.2. To adapt the calculation line to the various hones/
climatic conditions, all adjustment parameters must be set according to the following chapters.
7.11.1 - Climatic adjustment: on which
plants?
The “Climatic adjustment” is a more sophisticated and precise adjustment than the “Thermostatic adjustment”. This can
make the most use of the boiler efciency and is suitable for
the following types of plant:
- small plants, with radiators, having a room whose temperature is characteristic of all other rooms.
The room thermostat makes the appropriate corrections to the
room temperature by switching the boiler pump on and off.
- large plants, with radiators, where each area is controlled by its own room thermostat and the boiler pump is stopped
only when all area thermostats are satised (envision the appropriate electric plant).
- small plants, with radiant panels (low temperature), having a
room whose temperature is characteristic of all other rooms. The room thermostat makes the appropriate corrections to the room temperature by switching the boiler pump on and off.
- large plants, with radiant panels (low temperature), where
each area is controlled by its own room thermostat and the boiler pump is stopped only when all area thermostats are
satised (envision the appropriate electric plant).
7.11.2 - Climatic adjustment: precautions during adjustment
To set the ow temperature correctly, it is good practice to immediately set the line setting values in gure 7.2. If these
values do not give a satisfactory result, proceed with the
relevant modications, keeping in mind that:
- every parameter must be adjusted in small degrees;
- after each change, wait at least 24 hours to see the result;
- the more the adjust ment line app roach es the real requirements of the building, the more building central heating will be comfortable and the greater the energy
saving will be;
- using the or key, it is possible to make the
small corrections highlighted in gure 7.2, i.e. move the
parallelism of the line, in steps of 1 °C more or less, up to 10°C.
7.11.3 - Climatic adjustment: setting the
parameters
Using the “Installer menu” (see chapter 7.18), set:
- 2020 = “External switch-off temperature of the central heating”, adjustable between 0 and 35°C. When the external temperature reaches the value set in this parameter, the central heating is switched-off automatically. The central heating switches back on automatically when the external temperature drops back below this value. The recommended start value is 22°C.
- 2021 = “Design external temperature (winter)”, adjustable between -20 and 5°C. It is the design external temperature
used to dene the heat output necessary at the plant. The value recommended for a typical home is -5°C;
- 2022 = “Flow temperature corresponding to the design
external temperature (winter)”, adjustable between 0 and 80°C. The ow temperature assumes the value set in this
parameter when the external temperature corresponds to that set in the parameter 2021. The recommended start
values are: 40°C for low temperature plants (oor heating); 67°C for high temperature plants (radiators);
- 2023 = “External spring-like temperature”, adjustable between 0 and 30°C. It is the external temperature at
which the central heating is to reach the minimum ow temperature. The recommended start value is 18°C;
- 2024 = “Flow temperature corresponding to the external spring-like temperature”, adjustable between 0 and 40°C.
The ow temperature assumes the values et, it corresponds
to that set in the parameter
2023. The recommended
start values are: 30°C for low temperature plants (oor heating); 42°C for high temperature plants (radiators);
- It is always possible to set the minimum and maximum central heating temperatures using the respective parameters
3016 and 3015 present in chapter 11.
Page 42
42
MYDENS 60
COSMOGAS
Figure 7.2 - Climatic adjustment graphics for “high temperature” plants (with radiators)
External temperature (°C)
Calculated temperature (°C)
Par. 2020 = External temperature for central heating switch-off Par. 2021 = Project external temperature (winter) Par. 2022 = Flow temperature corresponding to the project external temperature (winter) Par. 2023 = Spring-like external temperature Par. 2024 = Flow temperature corresponding to the spring-like external temperature Par. 3016 = Minimum ow temperature Par. 3015 = Maximum ow temperature
= Line parallelism increase key
= Line parallelism decrease key
7 - USE
Par. 2021
Par. 2023
Par. 2020
Par. 3016
Par. 2024
Par. 2022
Par. 3015
Page 43
43
MYDENS 60
COSMOGAS
7 - USE
7.11.4 - Climatic adjustment: adaptation to different climatic areas
The previously recommended values are for homes with average insulation and for climatic areas where the external temperature used for calculating heat requirement is
-5°C (with this data and a high temperature plant, there is
correspondence with the graphics in Figure 7.2). If the climatic
area is different, adjust parameter 2021 “Design external
temperature (winter)” in a way to obtain a ow temperature of 67°C (40°C in the case of “Low temperature” plants), when
the external temperature is that of the calculation base of the heat requirement.
7.11.5 - Climatic adjustment: switching the central heating service on and off
The climatic adjustment service is completely automatic, also regarding switch-off at the end of the season and successive switch-on at the start of the next season via the parameter
2020. When the external temperature rises above the value
set in this parameter, the heating switches off automatically. When the external temperature drops back below the value set in this parameter, the central heating service switches back on automatically.
7.11.6 - Climatic adjustment with room compensation
Using the “Installer menu” (see chapter 7.18) adjust the
parameter 2003 to 02. Everything operates exactly as in
the previous chapters relative to the “Climatic adjustment”, with the difference that now the boiler pump is always on. The opening of the room thermostat contact translates into a parallel downward movement of the line regarding the value
set on the parameter, 2027 as in gure 7.2 present in the “Installer menu” (see chapter 7.18). Parameter 2027
can assume values between 0°C and 50°C. The values recommended for this parameter are:
- 10°C for high temperature plants (radiators);
- 3°C for low temperature plants (oor).
Values of this parameter that are too high can translate into instability of the room temperature. Values that are too low can make the room thermostat ineffective.
The climatic adjustment with room compensation can be used in all cases envisioned in chapter 7.11.1, with the advantage that continuous operation of the pump manages to stabilise
and make the room temperatures uniform; especially in the case in which several heat plant loops have the ow
resistances that are much higher than others.
7.12 - Timers of the various functions
To safeguard the lifespan of the appliance, improve the comfort generated and increase energy saving, timings have been introduced during operation. These timings are:
- Pump post-circulation: every time that the room thermostat determines the end of the central heating service, the pump
continues to operate for 3 minutes;
- Central heating delay: every time that the domestic hot water
service nishes, before reactivation of the central heating service there is a stand-by period of 2 minutes;
- Pumps anti-block and diverter valve: every 24 hours, the central heating pump, the domestic hot water pump (if
present) and the diverter valve are forced;
- Anti-legionella; if the boiler is connected to a Indirect Water
Heater for preparation of the DHW., every seven days the latter is forced to a temperature of 60°C to disinfect against the legionella bacteria. This function activates also due hours after the boiler has been powered electrically.
- Ignition delay: In all operating modes, excluding domestic hot water mode, wait 3 minutes to ignite the burner again when it switches off.
7.13 - Pump anti-block
The pump switches on once every 24 hours for 15 seconds during the summer period in order to prevent any deposits that may block it. The diverter valve and the Indirect Water
Heater pump (if present) are activated at the same time for
the same reason.
7.14 - Anti-freeze protection
ATTENTION !!! For the anti-freeze protection
to be effective, the appliance must be left with electric power supply and gas supply present and the two services (domestic hot water and central heating) in the
OFF position.
ATTENTION !!! The anti-freeze protection
service offered by the boiler cannot guarantee the anti-freeze protection of the central heating plant, the domestic hot water plant or the building served or part of the same.
The central heating pump starts automatically when the boiler temperature reaches 10°C. If the temperature drops further below 5°C, the burner also ignites in a way to protect the boiler from the effects deriving from freezing.
If the boiler is not used for a long period of time (over a year),
it is recommended to empty it following the procedure in chapter 8.12.
7.15 - Automatic plant loading
(not recommended)
It strongly not recommended to use an automatic plant loading device for the reasons given in chapter 5.6.
7.16 - Energy Saving
To reduce the consumption of display energy, it will switch off automatically after 5 minutes from the last operation performed. This function can be deactivated or the time
modied via parameter 2100 in the “Installer menu”. If the parameter is set at OFF, the display will remain on constantly.
Page 44
44
MYDENS 60
COSMOGAS
7 - USE
7.17 - “User menu”
Press the RESET key for 2 seconds to access the “User
menu”. The visual display “M” in gure 7.1, starts to show
parameter 1001 to inform the use of the mode change.
Using the
and key, scroll the parameters contained in the menu. Just press the RESET key again for 2 seconds to exit the menu.
If no key is pressed for more than 60 seconds, the menu is exited automatically. The following parameters can be queried in this menu:
Parameter Description of the parameter M.U. 1001 Central heating ow temperature °C 1002 Domestic hot water temperature (or Indirect Water Heater temperature, if present) °C 1003 No function / 1004 External temperature (visible when an external temperature sensor is installed) °C 1005 Central heating ow temperature (safety sensor) °C 1006 Fumes temperature °C 1007 Return ow temperature °C 1008 Ionisation current uA 1009 Status of the pump inside the boiler ON/OFF 1010 Status of the central heating side diverter valve (ON = in central heating mode; OFF = in D.H.W. mode) ON/OFF 1011 Status of the D.H.W. side diverter valve (ON = in D.H.W. mode; OFF = in central heating mode) ON/OFF 1012 Central heating ow temperature calculated via the external sensor °C 1013 Status of the room thermostat contact
(OPEN = no central heating request; CLOSED = presence of central heating request)
OPEN/CLO-
SED 1014 Fumes temperature (safety sensor) °C 1040 Current rotation speed of the fan rpm 1041 Fan rotation speed on ignition rpm 1042 Fan rotation speed in minimum power mode rpm 1043 Fan rotation speed in maximum power mode rpm 1051 Latest block condition recorded (Loc) (see chapter 7.19.1) / 1052 Latest error condition recorded (Err) (see chapter 7.19.2) / 1053 Number of times the burner has lost the ame n° 1055 Number of failed burner ignitions n° 1056 Number of hours worked in central heating mode h x 10 1057 Number of hours worked in domestic hot water mode h x 10 1058 Number of burner working days day 1059 Interval of time between the last two blocking errors (Err)
1 value in minutes; 2 value in hours;
3 value in days; 4 value in weeks;
1060 Interval of time between the last two blocks (Loc)
1061 Current rotation speed of the domestic hot water turbine rpm 1062 Current domestic hot water ow rate l/min
Page 45
45
MYDENS 60
COSMOGAS
7.18 - “Installer menu”
ATTENTION !!! The modication of these
parameters could cause the boiler, and therefore the plant, to malfunction. For this reason only a technician that has the awareness and in-depth knowledge of the appliances can modify them.
The boiler command and control board makes this parameter menu available to the technician, for the analysis of operation and adaptation of the boiler to the plant. Proceed as follows to enter the “Installer menu”:
1.- hold the RESET and
keys down simultaneously
for 5 seconds until the 2001 parameter is displayed.
The symbol
appears on the display to indicate the
entry into the “Installer menu”.
2.- the
and keys can be used inside the
menu to scroll the parameters;
3.- once the parameter of interest has been displayed, it
can be modied as follows:
a.- press the RESET key to access the parameter (the
visual display “N” in gure 7.1 will start to ash);
b.- modify the value of the parameter using the
and
key;
c.- press the RESET key to conrm the data modied
and go back to the list of parameters;
4.- To exit the “Installer menu”, hold down the RESET key
for 5 seconds until the symbol
disappears from the
base of the display.
If no key is pressed for more than 5 minutes, the menu is
exited automatically.. Any data variation that is not conrmed
with the RESET key will be lost.
ATTENTION !!! Any variation to the parameters must be noted in the “Customised values” column present in the following table in order to facilitate the eventual replacement of the command and control board.
The following parameters can be changed or queried in this menu:
7 - USE
Parameter Description of the parameter M.U. Setting range
Factory value
Custo­mised values
2001 Central heating minimum power level % From 1 to 50 1
2002 Central heating maximum power level % From 1 to 100 100
2003 Central heating operating mode nn 00 = Central heating with room
thermostat 01 = Central heating with room thermostat and climatic adjustment 02 = Central heating with total climatic adjustment 03 = Permanent central heating
00
2004 Stand-by time after maximum differential sec From 0 to 30 10
2005 Post-circulation in central heating mode sec From 10 to 900 120
2010 Forcing of fan and burner / OFF = No forcing
FAN = Forcing of fan only to max speed LOu = Forcing of burner to minimum power Ign = Forcing of burner to igni­tion power HIgH = Forcing of burner to maximum power rEg = Forcing of burner to power (Par.2002)
OFF
2011 Forcing the pump / On = Pump on
OFF = Pump off
OFF
2012 Forcing of the central heating side diverter valve / ON = in central heating mode;
OFF = in D.H.W. mode
OFF
2013 Forcing of the domestic hot water side diverter valve / ON = in D.H.W. mode;
OFF = in central heating mode
OFF
Page 46
46
MYDENS 60
COSMOGAS
7 - USE
2014 Icons test on the display. By pressing the RESET key, all of the
icons on the display light up. By pressing the RESET key again to display goes back to normal operation
/ / /
2020 Climatic adjustment: external temperature for central heating
switch-off
°C From 0 to 35 22
2021 Climatic adjustment: project external temperature (winter) °C From -20 to 5 -5
2022 Climatic adjustment: ow temperature corresponding to the
project external temperature (winter)
°C From 0 to 80 80
2023 Climatic adjustment: external spring-like temperature °C From 0 to 30 20
2024 Climatic adjustment: ow temperature corresponding to the
external spring-like temperature
°C From 0 to 40 40
2027 Temperature reduction by room thermostat opening °C From 1 to 50 10
2040 Climatic adjustment: central heating boost temperature °C From 0 to 20 0
2041 Climatic adjustment: central heating boost time min From 0 to 30 20
2042 Protection against frequent switch-on in central heating mode:
time
sec From 10 to 900 180
2043 Protection against frequent switch-on in central heating mode:
temperature differential
°C From 0 to 20 16
2060 Domestic hot water minimum power level % From 1 to 50 1
2061 Domestic hot water maximum power level % From 1 to 100 100
2062 Post-circulation in domestic hot water mode sec From 10 to 900 120
2063 Maximum time for charging Indirect Water Heater min From 0 to 60 60 /
2064 Number of ow meter revs. for every litre of water rpm/lt From 0 to 5 3,2
2066 Delay in the detection of the instantaneous domestic hot water sec From 1 to 10 3
2067 Indirect Water Heater charging procedure / 0 = the Indirect Water Heater
charging for the time set in the parameter 2063; 1 = OFF, the domestic hot water does not have priority over heating; 2 = ON, the domestic hot water always has priority over heating;
2
2080 Periodic maintenance meter
(after RESET, the meter automatically goes back to ON)
/ ON = Periodic maintenance
meter active; OFF = Periodic maintenance meter off; RESE = Meter reset
OFF
2081 Periodic maintenance meter: maintenance request time days From 0 to 1000 1000
2100 Energy saving display min OFF = display always on
From 1 to 30 = delay to switch­off in minutes.
5
Page 47
47
MYDENS 60
COSMOGAS
7 - USE
7.19 - Diagnostics
During normal appliance operation, the visual display “N”
in gure 7.1, continuously shows the working status of the
appliance via the following indications:
Parameter Description of the parameter Display on visual display “N” in gure 7.1
AFro
Anti-freeze function active Appliance temperature (°C)
AttE
Boiler not in block but in attention mode Attention code (see chapter 7.19.3 for decoding)
FILL
Plant pressure too low, perform loading (see chapter 6.1.3) FILL
Fixed on = Domestic hot water service on but not active
On ashing = Domestic hot water service on and active
Domestic hot water temperature (°C)
Fixed on = Central heating service on but not active
On ashing = Central heating service on and active
Central heating temperature (°C)
Loc
Boiler blocked. To reset, press RESET. If the block occurs
frequently, contact a professionally qualied technician
Block code (see chapter 7.19.1 for decode)
Err
Boiler in error mode. Functioning can only be restored by solving the cause of the anomaly. Contact a professionally
qualied technician
Error code (see chapter 7.19.2 for decode)
ALEg
Anti-legionella function running (see chapter 5.15.1). It will end on reaching the water temperature of 60°C inside the Indirect Water Heater.
Indirect Water Heater temperature (°C)
SEr
Maintenance request for the boiler Appliance temperature (°C)
Page 48
48
MYDENS 60
COSMOGAS
7 - USE
7.19.1 - Diagnostics: blocks “Loc”
Block Description of block Checks Solutions
Loc 0 Internal memory error
E2prom at command board
Replace the command and control board.
Loc 1 No ame detection after
three successive ignition attempts.
Control: Supply gas pressure (see chapter 6.6), sparks on the ignition electrodes (see chapter
8.5);correct combustion agent air pressure (see chapter 6.7); 220 Vac electric power supply to the gas valve; electric resistance of the two gas valve coils of 0.88 Kohm and 6.59 Kohm
If the burner switches on and switches off at the end of the ignition attempt, check: that the ionisation current is at a value over 60 (follow the procedure in chapter 8.15)
If the supply pressure is not correct, operate upstream from the appliance to restore it; if the pressure of the combustion agent air is not correct, operate on the air intake/fumes exhaust circuit to eliminate any obstructions. If the current at the gas valve is not 230Vac, the command and control board must be replaced. If the electric resistance of the gas valve is not 0.88 Kohm and 6.59 Kohm, the valve must be replaced.
If the ionisation current is not over 60, the CO2 must be checked (follow chapter 6.8) and restore its correct value, check the ionisation electrode and replace it if necessary. Check the integrity of the ionisation current electric circuit cables.
Loc 2 Gas valve command relay
broken
Replace the command and control board.
Loc 3 Int e rnal s afet y rela y
failure at command board
Ceck the appliance main ground. Replace the command and control board.
Loc 4 Boiler in error mode for
more than 20 hours
Control the last error displayed in the board. Operate according to the last error displayed.
Loc 5 Fan out of speed for
more than 60 seconds
Control it is powered at 300 Vdc. If the fan is powered, it must be replaced, differently
replace the board.
Loc 6 Software error inside the
command board
Replace the command and control board.
Loc 7 Content of the memo-
ry E2prom inside the command board, not updated
Replace the command and control board.
Loc 8 Parameters inside
the E2prom memory, incorrect
Replace the command and control board.
Loc 9 Software error inside the
command board
Replace the command and control board.
Loc 10 Software error inside the
command board
Replace the command and control board.
Loc 11 Not applicable
Loc 12 Not applicable
Loc 13 The boiler has reached
95°C
Control that the pump functions. Restore water circulation or replace the command
and control board.
Loc 14 Fumes maximum tempe-
rature.
Check there is no air in the central heating circuit; bleed the highest radiators;
Check the circulation pump operates correctly;
Measure boiler efciency; it must correspond to that
declared in the technical features..
Bleed the air from the boiler and from the highest central heating elements with respect to the boiler.
If the pump does not operate, it must be replaced.
If the efciency does not correspond to the data at the
end of the manual, probably the primary heat exchan­ger is dirty from the fumes side or the water side.
Clean and check efciency again.
Loc 15 Software error inside the
command board
Replace the command and control board.
Loc 16 Software error inside the
command board
Replace the command and control board.
Page 49
49
MYDENS 60
COSMOGAS
7 - USE
Loc 17 Software error inside the
command board
Replace the command and control board.
Loc 18 Flame present 10
seconds after gas valve is closed
Replace the gas valve or the command and control board.
Loc 19 Flame present before
ignition
Replace the gas valve or the command and control board.
Loc 20 Flame lost three times Control: that the ionisation current is at a value over
60 (follow the procedure in chapter 8.15)
Control: that the fumes exhaust is suitably protected from obstructions caused by gusts of wind
If the ionisation current is not over 60, the CO2 must be checked (follow chapter 6.8) and restore the correct value. Check the ionisation electrode and replace it if necessary. Check the integrity of the ionisation current electric circuit cables.
If the fumes exhaust is placed in a vertical wall it must be protected with a wind-proof grid. If the fumes exhaust is positioned on the roof, make sure that it is
not in an area of reux and that any windproof chimney pot is really efcient.
Loc 21 Not applicable
Loc 22 Not applicable
Loc 23 The two ow sensors
measure the different temperatures for more than 60 seconds.
Check that the electrical resistance of the two sensors match the graphics in chapter 8.17;
Check that the central heating circuit ow rate is not
too low;
If one of the two or both sensors do not have correct values, they must be replaced;
If the temperature difference between U1 and U8 is
greater than 30°C at maximum power and the ow rate of the central heating circuit is low, the ow rate
must be increased;
Loc 24 The two fumes sensors
measure the different temperatures for more than 60 seconds.
Check that the electrical resistance of the two fumes sensors match the graphics in chapter 8.17
If one of the two sensors does not match the double fumes sensor must be replaced
Loc 25 Too many lling of the
heating circuit in one hour
Check the pressure switch calibration pressure. FILL must appear when the pressure drops below 0.6 bar and must disappear when the pressure rises above
1.5 bar; check that there are no water leaks from the central heating plant
If the pressure switch is not calibrated correctly, it must be replaced. If the plant has a leak it must be repaired.
Loc 26 Plant lling time too long Check the pressure switch calibration pressure. FILL
must appear when the pressure drops below 0.6 bar; check that there are no water leaks from the central heating plant
If the pressure switch is not calibrated correctly, it must be replaced. If the plant has a leak it must be repaired.
Loc 27 Software error inside the
command board
Replace the command and control board.
Loc 28 Software error inside the
command board
Replace the command and control board.
Page 50
50
MYDENS 60
COSMOGAS
7 - USE
7.19.2 - Diagnostics: errors “E”
Error Error Description Checks Solution
Err 30 Software error inside the
command board
Replace the command and control board.
Err 31 Software error inside the
command board
Replace the command and control board.
Err 32 Software error inside the
command board
Replace the command and control board.
Err 33 Software error inside the
command board
Replace the command and control board.
Err 34 Software error inside the
command board
Replace the command and control board.
Err 35 The ow temperature
exceeds 110°C with the gas valve closed
Check that the electrical resistance of the two ow
sensors match the graphics in chapter 8.17.
Check that the gas valve closes the gas correctly when the burner switches off.
If one of the two sensors does not match, the double
ow sensor must be replaced.
The gas valve must be replaced if it does not close correctly.
Err 36 Software error inside the
command board
Replace the command and control board.
Err 37 Software error inside the
command board
Replace the command and control board.
Err 38 Software error inside the
command board
Replace the command and control board.
Err 39 Software error inside the
command board
Replace the command and control board.
Err 40 Software error inside the
command board
Replace the command and control board.
Err 41 Software error inside the
command board
Replace the command and control board.
Err 42 Software error inside the
command board
Replace the command and control board.
Err 43 Software error inside the
command board
Replace the command and control board.
Err 44 Flame detected in a
moment when it should not be present
Replace the gas valve.
Err 45 Central heating water
low pressure
Check the pressure switch calibration pressure. FILL must appear when the pressure drops below 0.6 bar; check that there are no water leaks from the central heating plant.
If the pressure switch is not calibrated correctly, it must be replaced. If the plant has a leak it must be repaired.
Err 46 Central heating water
pressure sensor error
Check the pressure switch calibration pressure. FILL must appear when the pressure drops below 0.6 bar; check that there are no water leaks from the central heating plant.
If the pressure switch is not calibrated correctly, it must be replaced. If the plant has a leak it must be repaired.
Err 47 Not applicable
Err 48 Software error inside the
command board
Replace the command and control board.
Err 49 Return sensor circuit
(1007) open
Check that the electric resistance of the sensor matches the graphics in chapter 8.17. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 50 Flow sensor circuit 1
(1001) open
Check that the electric resistance of the sensor matches the graphics in chapter 8.17. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Page 51
51
MYDENS 60
COSMOGAS
7 - USE
Err 51 Flow sensor circuit 2
(1005) open
Check that the electric resistance of the sensor matches the graphics in chapter 8.17. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 52 Domestic hot water inlet
sensor 2 circuit (1002) open
Check that the electric resistance of the sensor matches the graphics in chapter 8.17. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 53 Fumes 1 sensor circuit
(1006) open
Check that the electrical resistance of the fumes sensor 1006 matches the graphics in chapter 8.17
Check that the wires between the board and the double fumes sensor are connected correctly
If the sensor does not match, the double fumes sensor must be replaced.
If the wires are not connected correctly, the connec­tions must be restored.
Err 54 Fumes 2 sensor circuit
(1014) open
Check that the electrical resistance of the fumes sensor 1014 matches the graphics in chapter 8.17
Check that the wires between the board and the double fumes sensor are connected correctly
If the sensor does not match, the double fumes sensor must be replaced.
If the wires are not connected correctly, the connec­tions must be restored.
Err 55 Not applicable
Err 56 Return sensor circuit
(1007) in short circuit condition
Check that the electric resistance of the sensor matches the graphics in chapter 8.17. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 57 Flow sensor circuit 1
(1001) in short circuit condition
Check that the electric resistance of the sensor matches the graphics in chapter 8.17. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 58 Flow sensor circuit 2
(1005) in short circuit condition
Check that the electric resistance of the sensor matches the graphics in chapter 8.17. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 59 Domestic hot water inlet
sensor 2 circuit (1002) in short circuit condition
Check that the electric resistance of the sensor matches the graphics in chapter 8.17. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 60 Fumes 1 sensor circuit
(1006) in short circuit condition
Check that the electrical resistance of the fumes sensor 1006 matches the graphics in chapter 8.17
Check that the wires between the board and the double fumes sensor are connected correctly
If the sensor does not match, the double fumes sensor must be replaced
If the wires are not connected correctly, the connec­tions must be restored
Err 61 Fumes 2 sensor circuit
(1014) in short circuit condition
Check that the electrical resistance of the fumes sensor 1014 matches the graphics in chapter 8.17
Check that the wires between the board and the double fumes sensor are connected correctly
If the sensor does not match, the double fumes sensor must be replaced
If the wires are not connected correctly, the connec­tions must be restored
Err 62 External temperature
sensor circuit (1004) in short circuit condition
Check that the electric resistance of the sensor matches the graphics in chapter 8.18. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 63 RESET key pressed too
many times in a very brief period
7.19.3 - Diagnostics: alarms“AttE”
Alarm Description of the
alarm
Checks Solutions
AttE 65 Central heating plant
pressure too low for more than 10 minutes
Check the pressure switch calibration pressure. FILL musty appear when the pressure drops below 0.6 bar; check that there are no water leaks from the central heating plant.
If the pressure switch is not calibrated correctly, it must be replaced. If the plant has a leak it must be repaired.
Page 52
52
MYDENS 60
COSMOGAS
8.1 - General recommendations
It is recommended to perform regular yearly maintenance of the central heating plant for the following reasons:
- to maintain high efciency of the appliance and therefore
save fuel;
- to maintain a high level of safety;
- to maintain the level of environmental compatibility of the
combustion high;
In order to maintain the frequency of maintenance, there is a parameter present 2080 in the installer menu (see
chapter 7.18), which is used to activate the maintenance call (Service) along with parameter 2081, which is used
to set the operating days that must pass between one call and the next.
NOTE: The day counter is based on the real operating days of the burner. Proceed as follows to activate the call service.
Per attivare il servizio di chiamata procedere come di seguito:
1.- access the Installer menu (see chapter 7.18) and set
parameter 2080 on 0n;
2.- access parameter 2081 and set the boiler operating
days which must pass between one call and the next.
The call will be completed with SEr on the display. To remove the wording SEr and renew the call period,
operate as follows:
1.- access the “Installer menu”;
2.- access the parameter 2080, set it on rESE and
press the RESET key.
3.- exit the Installer menu by pressing the RESET key for 5
seconds.
The call time is now renewed and SEr appears on the display.
ATTENTION !!! Appliance maintenance must
only be performed by a professionally qualied
technician.
ATTENTION !!! Before every maintenance operation, disconnect the appliance from the electric power supply, using the relevant switch in the vicinity.
ATTENTION !!! Close the gas cock before any maintenance operation
8 - MAINTENANCE
Page 53
53
MYDENS 60
G
A
C
E
D
F
B
020005.01.007
COSMOGAS
Figure 8.1 - removing the casing and opening of command board
8.2 - Removing the casing and access to internal components
Proceed as follows to remove the casing (refer to gure
8.1):
1.- loosen the screws “A”;
2.- pull the lower part of the front-piece “B” towards the front
and then slide it out upwards until it is released from the
guides “C”;
To access the command and control board:
1.- turn the command board “D” towards the front;
2.- open the commands board “D” by operating on closure
“G”;
To access the electric connections board:
1.- turn the command board “D” towards the front;
2.- slide lid “E” out by operating on the closing aps “F”;
8 - MAINTENANCE
Page 54
54
MYDENS 60
COSMOGAS
8 - MAINTENANCE
8.3 - Removing the burner fan unit
Proceed as follows to remove the burner fan unit (refer to
gure 8.2 when not differently specied):
1.- access the internal components following chapter 8.2;
2.- remove the air manifold (detail “C” in gure 6.2) rotating
it towards the outside of the boiler and then pulling it
towards the right (see gure 6.2);
3.- unscrew nut “C” from the valve “D”;
4.- disconnect the cables “B” and the detection cable from the ignition and detection electrodes (details “8”, “36” and
“37” in gure 3.1);
5.- unscrew the four nuts “E”;
6.- extract the group “F” as per gure;
Figure 8.2 - Removing the burner fan unit
G
C
B
E
A
F
D
020005.01.008
8.4 - Cleaning the burner and the fumes side primary heat exchanger
To correctly clean the burner and body of the heat
exchanger (fumes side), proceed as follows (refer to gure
8.2 when not differently specied):
1.- access the internal components following chapter 8.2;
2.- remove the burner unit following chapter 8.3;
3.- pass a cylindrical brush with plastic bristles inside the combustion chamber “G”
4.- use a suction device to remove the unburned residues
present inside the combustion chamber “G”;
5.- use the same suction device on the surfaces of the
burner and around the electrodes;
6.- re-mount the components in reverse order;
7.- open the gas cock;
8.- restore the electric power supply.
9.- check that there are no gas leaks between the joints
removed;
ATTENTION !!! Perform the leak test using a soap
and water only. The use of naked ames is prohibited.
Page 55
55
MYDENS 60
COSMOGAS
8 - MAINTENANCE
Figure 8.3 - positioning the electrodes on the burner
8.5 - Correct positioning of the
ignition and ionising electrodes
For good working order of the appliance, it is indispensable
that the electrodes are positioned correctly (refer to gure
8.3):
- the distance between the ignition electrodes “A” and “B”,
must be between 2.0 and 2.5 mm;
- the distance between the ignition electrodes from the burner
surface must be between 5 and 5.5 mm;
- the distance of the ionisation electrode from the surface of the burner must be between 5.5 and 6.5 mm.
8.6 - Removing the ow meter
The ow meter is used to measure the water ow rate
inside the boiler. If it has to be replaced, proceed as follows
(refer to gure 8.4):
1.- empty the appliance water, following the procedure in
chapter 8.12;
2.- access the internal components of the appliance
following chapter 8.2;
3.- remove the burner unit following chapter 8.3;
4.- loosen the ttings “B” and “C”;
5.- extract the ow meter “A” paying attention to the direction of the ow, as per arrow printed on the ow meter;
6.- replace the ow meter;
7.- during mounting, make sure the ow meter is positioned correctly (step highlighted in point 4).
8.7 - Removing the safety valve
The safety valve (detail “A” in gure 8.5) protects the boiler
from over pressures. If it has to be replaced, proceed as
follows (refer to gure 8.5):
1.- empty the appliance, following the procedure in chapter
8.12;
2.- access the internal components of the appliance
following chapter 8.2;
3.- remove the burner unit following chapter 8.3;
4.- disconnect the drain pipe from the safety valve,
loosening the sealing spring;
5.- unscrew the xing tting of the safety valve to the pipe;
6.- extract the safety valve “A” upwards and replace it by restoring the drain pipe of the same as it was previously mounted.
Figure 8.4 - Removing the ow meter
Figure 8.5 - Removing the safety valve
A
020005.01.009
B
C
A
020005.01.010
Page 56
56
MYDENS 60
COSMOGAS
8.8 - Cleaning the condensate
conveyor siphon
For correct cleaning of the collection siphon and the conveying of the condensate produced by combustion,
operate as follows (refer to the gures 8.6, 8.7 and 8.8):
1.- with the boiler on, force the central heating to maximum, following the procedure in chapter 8.14 in a way that the burner is at maximum power and the level of liquid
present inside the siphon tank “D” (see gure 8.6),
lowers. Now, switch the boiler off and disconnect it
electrically;
2.- access the internal components following chapter 8.2;
3 - remove the fan burner unit following chapter 8.3;
4 - cover the electric plant and pump unit with a cloth
to protect them from any residues of water inside the siphon to be removed.
5.- slide the support “C” outwards from the holding support;
6.- slide the tank “D” downwards, paying attention to the fact that it is full of condensate water and this could
escape;
7.- extract the siphon outwards (see gure 8.7) paying
attention to disconnect the collection pipes of the water coming from the upper part of the appliance and from the air vent valve.
8.- clean the decanting tank “D”;
9.- re-mount everything in reverse order, paying attention to the gasket “E”, which is put back in the relevant seat and
that terminal “G” is introduced correctly in the seat “H”;
10.- restore the level of liquid inside the siphon following the procedure in chapter 6.1.2.
Figure 8.7 - Removal of the condensate collection siphon
C
D
B
A
020002.01.027
D
E
02002.01.029
Figure 8.8 - Condensate collection siphon
H
G
F
D
E
020002.01.030
8 - MAINTENANCE
Figure 8.6 - Removal of the condensate collection siphon
Page 57
57
MYDENS 60
COSMOGAS
8.9 - Removing the air vent valve
Refer to Figure 8.9 and proceed as follows:
1.- close the plant load cock envisioned by the installer;
2. - take plant pressure to zero;
3.- access the internal components of the appliance
following chapter 8.2;
4.- unscrew and slide the air vent valve “A” upwards and
replace;
Figure 8.10 - Replacing the pump motor
8 - MAINTENANCE
Figure 8.9 - Removing the air vent valve
Figure 8.11 - Removing the central heating circuit pressure sensor
8.11 - Removing the central
heating circuit pressure sensor
Proceed as follows, making reference to gure 8.11:
1.- empty the central heating circuit, following the procedure
in chapter 8.12;
2.- access the internal components of the appliance
following chapter 8.2;
3.- disconnect the connection cable from sensor “A”;
4.- extract the drive bar “B” as indicated in the gure;
5.- slide out and extract the pressure sensor “A” from the
tting “C”, as indicated in the gure.
6.- replace the sensor, restoring the connections as previously.
8.10 - Replacing the pump motor
If the circulation pump must be replaced, operate as follows
(refer to gure 8.10)
1.- empty the central heating circuit, following the procedure
in chapter 8.12;
2.- access the internal components of the appliance
following chapter 8.2;
3.- disconnect the pump electric power supply cable;
4.- loosen the screws “B”;
5.- extract the pump “A” outwards;
6.- replace it, paying attention to the correct positioning of the internal gasket and re-connect the power supply cable.
A
020005.01.011
C
A
B
020005.01.012
C
B
A
020005.01.013
Page 58
58
MYDENS 60
COSMOGAS
8.12 - Emptying the appliance
Proceed as follows to empty the appliance:
1.- generate a central heating request;
2.- set the central heating temperature at the lowest value possible, with the purpose of cooling the water inside the
boiler;
3.- switch the boiler off;
4.- close the plant load cock envisioned by the installer;
5.- connect a exible hose to the drain cocks envisioned by
the installer and convey it onto the drain of a washbasin
or similar;
6.- open the drain cocks envisioned by the installer;
7.- open the central heating elements bleed valves. Start from the highest central heating elements and continue with the lowest
8.- once all of the water has been evacuated, close all of the heating element vent valves and the drain cocks envisioned by the installer.
ATTENTION !!! It is prohibited to recover and/
or re-use the water evacuated from the central heating circuit for any purpose; this could be polluted.
8.13 - Fan
Switch-on of the fan only can be generated, accessing the parameter 2010 situated inside the “Installer menu” (see chapter 7.18) and set it on FAn. To go back to normal operating conditions, set parameter 2010 again to 0FF.
8.14 - Minimum and maximum power
Appliance operation can be forced to its own minimum, maximum, adjusted or ignition power. Proceed as follows:
1.- make sure that any cocks and thermostatic valves
downstream from the central heating circuit are open;
ATTENTION !!! During forcing of the delivery
temperature, it automatically goes to 93°C to give the possibility to dispose of as much of the heat generated by the boiler as possible. Check that the central heating plant can support this temperature.
2.- access parameter 2010 found in the “installer menu”
(see chapter 7.18);
3.- set the parameter 2010 at the following value:
a) LOu to force the boiler to minimum power; b) Ign to force the boiler to ignition power; c) HIgH to force the boiler to maximum power; d) rEg to force the boiler to the maximum central heating
power, as adjusted (Range Rated) in chapter 6.9,
parameter 2002.
4.- To end forcing, take the parameter 2010 to the 0FF
value and press the RESET key.
ATTENTION !!! If during forcing, the power
supplied by the boiler is much higher than the power absorbed by the plant, the boiler switches off continuously to reach the maximum temperature allowed (93°C).
8 - MAINTENANCE
Page 59
59
MYDENS 60
COSMOGAS
8.15 - Checking the ionisation current
In any operating status, also during verications of minimum
and maximum power stated in chapter 8.14, the ionisation current value can be consulted on parameter 1008 present
in the “User menu” (chapter 7.17). This value must be between
1.5 and 3 uA (microampere) at minimum power and between
5 and 8 uA at maximum power.
8.16 - Checking combustion performance
On the basis of national laws regarding gas appliances, the
combustion performance must be checked periodically;
To do this, operate exactly as stated in chapter 6.8 and also
check, in addition to CO2, the combustion efciency, which
must be over 96%.
Figure 8.12 - Water sensors curve
Figure 8.13 - External temperature sensor curve
8 - MAINTENANCE
8.17 - Water temperature measurement sensors
The temperature sensors are positioned on the boiler’s exchanger body. The electric resistance existing between the two contacts of the sensor, must correspond with that
stated in gure 8.12.
The temperature sensors are: 1001, 1002, 1005,
1006, 1007 and 1014, the positioning of which can
be veried in gure 3.1.
8.18 - External temperature sensor
On request, the external temperature sensor can be connected to the boiler 1004 (see chapter 5.14.4). The
electric resistance existing between the two contacts of the
sensor, must correspond with that stated in gure 8.13.
Page 60
60
MYDENS 60
COSMOGAS
8.19 - Operational wiring diagram
Figure 8.14 - Operational wiring diagram
ATTENTION !!! To consult
the wiring diagram correctly, references K are given followed by a number (see example above) to identify the correct follow-on of the cables in the next page.
8 - MAINTENANCE
1001 - Boiler body sensor 1
1002 (SB) - Indirect water heater sensor
1004 - External temperature sensor 1005 - Boiler body sensor 2 1006 - Fumes sensor 1007 - Return sensor 1014 - Fumes safety sensor
CM - Boiler control unit and ame control
DSP - Display EA - Ignition electrode ER - Detection electrode
F (PWM) - Fan F (BCU) - 5A fuse
Page 61
61
MYDENS 60
COSMOGAS
8 - MAINTENANCE
F1 (SDC) - 1,6A power supply fuse
GP - Circulation pump GS - Spark generator IG - Master switch J1 - 6 pin Molex connector J12- 6 pin Molex connector J2 - 4 pin Molex connector J26- 4 pin Molex connector J3 - 12 pin Molex connector J4 - 4 pin Stelvio connector J5 - 16 pin Molex connector J6 - 14 pin Molex connector J7- 10 pin Molex connector
J9- 4 pin Molex connector PB - Indirect Water Heater pump PS - Central heating circuit pressure sensor SDC- Connection board TA- Room thermostat
TU - Flow meter (water ow rate measuring device)
VG1- Gas Valve
Page 62
62
MYDENS 60
COSMOGAS
8.20 - Multi-wire wiring diagram
Figure 8.15 - Multi-wire wiring diagram
Key - see key gure 8.14
8 - MAINTENANCE
Page 63
63
MYDENS 60
COSMOGAS
8 - MAINTENANCE
Page 64
64
MYDENS 60
COSMOGAS
TECHNICAL DATA MU MYDENS 60A MYDENS 60C
Type (Type of fumes exhaust/air intake) B23 ; C13 ; C33 ; C43 ; C53 ; C63 ; C83
Category II2H3P II2H3P
CE type certicate (PIN) 0694CN6126 0694CN6126
Central heating max. heat input “Q” kW 57,8 57,8
Domestic hot water max. heat input kW N.A. N.A.
Central heating min. heat input kW 12,0 12,0
Domestic hot water minimum heat input kW N.A. N.A.
Central heating max. useful heat output (80/60) “P” kW 56,1 56,1
Efciency at 100% load (80/60) % 97,1 97,1
Min. useful heat output (80/60) kW 11,6 11,6
Efciency at min. useful heat output (80/60) % 97 97
Central heating max. useful heat output (50/30) kW 60,7 60,7
Efciency at central heating max. useful heat output (50/30) % 105 105
Min. useful heat output (50/30) kW 12,8 12,8
Efciency at min. useful heat output (50/30) % 107 107
Central heating max. useful heat output (40/30) kW 61,9 61,9
Efciency at central heating max. useful heat output (40/30) % 107 107
Min. useful heat output (40/30) kW 12,8 12,8
Efciency at min. useful heat output (40/30) % 107 107
Efciency at 30% of the load % 107 107
Efciency certicate (92/42/EEC) stelle
Losses at the chimney burner on (80/60) % 1 1
Losses at the chimney burner on at minimum power % 0,5 0,5
Losses at the chimney burner off % 0,1 0,1
Losses at the casing burner on % 0,1 0,1
Losses at the casing burner off % 0,05 0,05
Losses at zero load % 0,05 0,05
Generator average test temperature (80/60) °C 70 70
Generator average test temperature (40/30) °C 35 35
Return temperature in test conditions (80/60) °C 60 60
Return temperature in test conditions (40/30) °C 30 30
Gas ow rate
Nat GAS m
3
/h 6,1 6,1
LP GAS Kg/h 4,5 4,5
Gas supply pressure
Nat GAS mbar 20 20
LP GAS mbar 37 37
Gas supply minimum pressure
Nat GAS mbar 15 15
LP GAS mbar 25 25
Gas supply maximum pressure
Nat GAS mbar 30 30
LP GAS mbar 45 45
Combustion agent air pressure
Nat GAS mbar 5 5
LP GAS mbar 4 4
Primary heat exchanger water content lt 3,2 3,2
Weight of the primary heat exchanger kg 18,2 18,2
Secondary heat exchanger water content lt N.A. N.A.
Domestic hot water useful heat output kW N.A. N.A.
D.H.W. minimum ow rate l/min N.A. N.A.
Instantaneous D.H.W. production (dt 30°C) l/min N.A. N.A.
Instantaneous D.H.W. adjustment range °C N.A. N.A.
D.H.W. with Indirect Water Heater adjustment range °C 40 - 70 40 - 70
Design temperature °C 95 95
Maximum central heating temperature °C 80 80
Minimum central heating temperature °C 20 20
9 - TECHNICAL DATA
Page 65
65
MYDENS 60
COSMOGAS
DATI TECNICI MU MYDENS 60A MYDENS 60C
Central heating maximum pressure “PMS” = bar 4 4
Central heating minimum pressure bar 0,5 0,5
D.H.W. circuit maximum pressure bar N.A. N.A.
D.H.W. minimum pressure bar N.A. N.A.
Expansion tank pre-load pressure bar N.A. N.A.
Expansion tank capacity lt N.A. N.A.
Rated power supply voltage V 230 230
Rated power supply frequency Hz 50 50
Absorbed electric power W 140 305
Electric protection rating IPX4D IPX4D
Elec. pow. of the generator aux. positioned before rebox W 140 140
Elec. pow. of the generator aux. at min.pow. positioned before rebox W 40 40
Elec. pow. of the generator aux. positioned after rebox W 0 165
Elec. pow. of the generator aux. at min.pow. positioned after rebox W 0 165
Power absorbed by the auxiliaries at rated power W 0 165
Power absorbed by the auxiliaries at intermediate load W 0 165
Power absorbed by the auxiliaries at zero load W 0 0
Electric power absorbed by the pump W 0 165
Fumes pipe diameter (split) mm 80 80
Fumes pipe max. length (split) (80) m 10 10
Fumes pipe max. length (split) (60) m N.A. N.A.
Fumes pipe diameter (coaxial) (80/125) mm 80/125 80/125
Fumes pipe max. length (coaxial) (80/125) m 10 10
Equivalent length of a bend m 1 1
Weighted CO (0% O2 with natural gas) ppm 15 15
Weighted NOx (0% O2 with natural gas) (class 5 EN 483 and 297) ppm 15 15
CO2 (%) at natural gas minimum/maximum power Metano % 8,5 / 9,0 8,5 / 9,0
CO2 (%) at LP gas minimum/maximum power GPL % 10,0 / 10,5 10,0 / 10,5
O2 (%) at natural gas minimum/maximum power Metano % 5,8 / 4,9 5,8 / 4,9
O2 (%) at LP gas minimum/maximum power GPL % 5,6 / 4,8 5,6 / 4,8
Maximum recirculation of fumes allowed in the event of wind % 10 10
Fumes maximum temperature at boiler outlet °C 90 90
Fumes minimum temperature at boiler outlet °C 30 30
Mass ow of the fumes kg/h 99 99
Head available at exhaust kg/h 20 20
Mass ow of the fumes at minimum power Pa 60 60
Maximum temperature of the combustion agent air °C 50 50
Maximum CO2 content in the combustion agent air % 0,9 0,9
Fumes maximum temperature for overheating °C 95 95
Max. negative pressure allowed in the fumes exhaust/intake system Pa 60 60
Condensate maximum ow rate l/h 7,2 7,2
Condensate average acidity PH 4 4
Operating environment temperature °C 0 ; + 50 0 ; + 50
Weight of the boiler kg 44 46
9 - TECHNICAL DATA
Page 66
66
MYDENS 60
COSMOGAS
10 - COMMAND MENU DIAGRAM
Symbol Description
Press and release the RESET key
Hold the reset key down for a time in seconds, indicated by the number (2)
Hold the reset key down for a time in seconds, indicated by the number (5)
Hold down the RESET and key simultaneously for a time in seconds, indicated by the number
Press and release the key
Press and release the key
Parameters that can be displayed in the normal operational conditions
(see chapter 7.19)
User menu parameters (see
chapter 7.17)
Installer menu parameters (see
chapter 7.18)
Installer menu parameters (see
chapter 7.18)
User menu access
(see chapter 7.17)
Installer menu access
(see chapter 7.18)
Return to normal operation
Return to normal operation
Figure 10.1 - Command menu diagram
Key of gure 10.1
Page 67
67
MYDENS 60
COSMOGAS
ATTENTION !!!
The modication of these parameters could cause the appliance, and therefore the plant, to malfunction.
For this reason only a technician that has the awareness and in-depth knowledge of the appliances can modify them.
To access this menu:
1.- Remove voltage to the appliance;
2.- Access the internal components as per chapter 8.2;
3.- Move the microswitch “A” in gure 6.5 to “ON” position;
4.- Apply voltage to the boiler;
5.- Parameter 3002 will be displayed;
6.- Navigate the menu using the
and keys. Once the parameter has been selected, press the RESET key
to make it modiable using the
and keys;
7.- Press the RESET key to save the modications;
8.- Remove voltage and move the microswitch “A” in gure 6.5 to “OFF” to go back to normal operating conditions.
11 - MENU FORCED BY INTERNAL ELECTRIC BRIDGE
Parameter Description of the parameter M.U. Setting range
Factory value
Customised values
3002 Selection type From 50 to 55 See gure 6.7
3012
Domestic hot water operating mode
/
0 = No domestic hot water; 1 = Indirect Water Heater with temperature sensor; 2 = Indirect Water Heater with thermostat;
3 = Instantaneous with ow switch;
4 = Microaccumulation with two sensors; 5 = Instantaneous with turbine;
model “P” = 5 model “B” = 1 model “C” = 0 model “A” = 0
3013 Plant load automatic valve /
0 = Valve disabled; 2 = Valve enabled;
0
3014
Instantaneous domestic hot water pre-heat
/
OFF = No pre-heat ON = with pre-heat
OFF
3015
Maximum central heating temperature
°C From 20 up to 90 80
3016
Minimum central heating temperature
°C From 20 up to 90 30
3020
Domestic hot water ow rate
sensor
/
0 = B; 1 = DN 8; 2 = DN 10; 3 = DN 15; 4 = DN 20; (MYDENS 60) 5 = DN 25;
0
3021 2nd Fumes sensor (1014) /
0 = Disabled; 1 = Enabled; 2 = Enabled with fumes exhaust anti­closure pressure switch;
1
3022
Central heating minimum pressure
bar OFF... 0,3 to 5,1; 0,5
3033
Modulating pump
/
0 = Disabled; 1 = Enabled;
2 = 20% x to 10 = 100% x;
0
3034
Modulating pump delta T target
°C From 5 to 40 15
3035
No function
/ / /
3036
No function
/ / /
3052
No function
/ / /
Page 68
68
MYDENS 60
COSMOGAS
The undersigned COSMOGAS S.r.L., with Registered Ofce in via L. Da
Vincin° 16 - 47014 Meldola (FC) ITALY,
DECLARES
under its own responsibility that the product:
subject of this declaration, is in compliance with the model described in the
Type examination certicate, whose reference is given in the table in
chapter 9 under “CE type certicate (PIN)” and meeting that required by the
Directives: Gas Appliances, (2009/142/CE former 90/396/CEE), Efciency,
(92/42/CEE), Low Voltage, (2006/95/CE), Electromagnetic Compatibility,
(2004/108/CEE).
(the warranty number corresponds to the serial number)
This declaration is issued for that established by the above-mentioned Directives.
Meldola (FC) ITALY, (Date of manufacture).
MANUFACTURE
WARRANTY N°
MODEL
12 - CE DECLARATION OF CONFORMITY
________________________
Alessandrini Arturo
General Menager
Page 69
69
MYDENS 60
COSMOGAS
HYDRAULIC TEST CERTIFICATE
Under the Ministerial Decree December 1st, 1975 art. 17, the company COSMOGAS srl
manufacturer of base and wall mounted boilers using gaseous fuels,
CERTIFIED
that this heat generator:
Refer to the identication data of the product
(WARRANTY N°, MODEL and MANUFACTURE)
listed in the CE declaration of conformity
was subjected to the hydraulic test of 6 bar with positive outcome.
Operating on gaseous fuel type**:
G20 G25 G30 G31
** (To be completed by the installer once found the type of gas appliance operating)
Thermal power refers to the PCI (heat input “Q”): 57,8 kW
Useful heat
“P”: 56,1 kW
Maximum pressure operating: 4 Bar
Test pressure: 6 Bar
Set pressure of the safety valve: 3,5 Bar
________________________
Alessandrini Arturo
General Menager
13 - HYDRAULIC TEST CERTIFICATE
Page 70
70
MYDENS 60
COSMOGAS
14 - WARRANTY
14.1 - General warranty conditions
All COSMOGAS products are guaranteed against material
aws and manufacturing defects for 24 months from the date of commissioning, COSMOGAS also extends the warranty to :
COPPER TUBE, CRR and CRV HEAT EXCHANGER guaranteed up to 5 years;
PRE-MIXED BURNERS guaranteed up to 10 years;
ATMOSPHERIC BURNER guaranteed up to 15 years.
This warranty extension will only be valid if COSMOGAS
ahas received the warranty card, lled-in completely,
which will certify the date of commissioning. Within the above-mentioned term COSMOGAS commits to repairing or replacing the faulty construction parts and which will be acknowledged as such with exclusion of normal deterioration due to operations. The extension of the warranty exclusively covers the cost of the spare part. All other accessory costs are excluded, such as: labour, transfer costs and expenses for transporting material. The warranty does not extend to the recasting of the damage, of any nature, that has happened to persons or property. The faulty material replaced under warranty is the property of COSMOGAS and must be returned to our establishment, without further damage, within 30 days from replacement. All COSMOGAS products are encumbered by the title retention agreement, until the appliance sold have been paid in full.
14.2 - Instructions for lling-
in the warranty card
1. - Have your installer put his stamp on the warranty
certicate.
2. - Always request the intervention of our authorised technician for commissioning and to validate the
warranty;
To validate the warranty it will be the technician perform all the controls of the appliance in accordance with instructions contained in this manual and the regulations in force national and / or local.
The list of authorised technicians is found attached to the instruction manual or can be found in the Yellow Pages under “Gas boiler”.
The technician will take the warranty certicate and
deliver it to COSMOGAS.
14.3 - Limits of the warranty
The warranty is not valid:
- if the appliance is installed by not-qualied staff;
- if the appliance is installed in a way that is not in compliance with the COSMOGAS instructions and/or that
established by the current national and/local regulations;
- whenever the plant is not run/services in compliance with the instructions and/or the current national and local
regulations;
- whenever the product has damage caused by changes in
voltage;
- whenever the product has damaged caused by the use of excessively hard water, or which is too acid or too
oxygenated;
- whenever the product has failures caused by heat shocks,
abnormalities of chimneys and/or exhaust and intake pipes;
- whenever the product has anomalies not depending on
COSMOGAS;
- whenever the appliances have been tampered with for adaptation, repairs or replacement with non-original spare
parts;
- whenever repairs are performed by unauthorised staff.
- Whenever the warranty certicate is not sent
to COSMOGAS within 15 days from the date of commisioning.
COSMOGAS does not assume any responsibility for
any accident that may occur or be caused by the user, precluding any compensation that does not concern boiler parts recognised as defective manufacturing. Any dispute is the jurisdiction of the Forlì Law Court, ITALY.
Page 71
Page 72
COSMOGAS s.r.l.
Via L. da Vinci 16 - 47014
MELDOLA (FC) ITALY
info@cosmogas.com
www.cosmogas.com
Loading...