COSMOGAS MYDENS Installation, Use And Maintenance Manual

Page 1
62403580 - R00 17-12-2013_IT
INSTALLATION, USE AND MAINTENANCE MANUAL
MYDENS
GAS WALL-MOUNTED CONDENSING BOILER
Page 2
2
MYDENS
COSMOGAS
INDEX
1 - GENERAL SAFETY RECOMMENDATIONS ..................................................................................................4
1.1 - National installation laws .......................................................................................................................................... 4
2 - GENERAL INFORMATION .............................................................................................................................5
2.1 - Presentation ............................................................................................................................................................. 5
2.2 - Overview of the models ............................................................................................................................................ 5
2.3 - Manufacturer ............................................................................................................................................................ 5
2.4 - Key for the symbols used ......................................................................................................................................... 5
2.5 - Maintenance ............................................................................................................................................................. 5
2.6 - Warranty ................................................................................................................................................................... 5
3 - MAIN COMPONENTS .....................................................................................................................................6
4 - OPERATION ...................................................................................................................................................8
4.1 - Operation and intended use of the appliance ........................................................................................................ 10
4.2 - Characteristic curves of the residual head at the central heating plant ...................................................................11
4.3 - Characteristic curve of the domestic hot water head losses .................................................................................. 13
5 - INSTALLATION .............................................................................................................................................14
5.1 - Opening the packaging .......................................................................................................................................... 14
5.2 - Dimensions and minimum safety distances ........................................................................................................... 14
5.3 - Choosing the place of installation .......................................................................................................................... 14
5.4 - Supply and return ................................................................................................................................................... 14
5.5 - Low temperature plants (or on the oor) ................................................................................................................ 15
5.6 - Domestic hot and cold water .................................................................................................................................. 15
5.7 - Gas ......................................................................................................................................................................... 15
5.8 - Mounting the appliance .......................................................................................................................................... 16
5.9 - Condensate drain ................................................................................................................................................... 16
5.10 - Safety valve .......................................................................................................................................................... 16
5.11 - Hydraulic and gas connections and mounting of the lower cover ........................................................................ 17
5.12 - Hydraulic connection for MYDENS -- B boiler ...................................................................................................... 18
5.13 - Polyphosphates softener (on request) ................................................................................................................. 18
5.14 - Electric connections: generalities ......................................................................................................................... 19
5.14.1 - Power supply cable connection .............................................................................................................. 20
5.14.2 - Choosing the room thermostat/chronothermostat ................................................................................... 20
5.14.3 - Connecting the room thermostat/chronothermostat ................................................................................ 20
5.14.4 - Installing the external temperature sensor (on request) ......................................................................... 21
5.15 - Connecting the boiler to indirect water heater with coil ........................................................................................ 22
5.15.1 - Anti- legionella ......................................................................................................................................... 22
5.16 - Burned gas exhaust and combustion agent air intake pipe ................................................................................. 23
5.16.1 - Type of intake/exhaust B23 ..................................................................................................................... 24
5.16.2 - “Split 80/80PP” System (polypropylene) (Type C43; C53; C83) ............................................................. 25
5.16.3 - “Split 80/80PP” System (Type C43; C53; C83): accessories available ................................................... 26
5.16.4 - “Split 80/80PP” System (Type C43; C53; C83): installation examples ................................................... 27
5.16.5 - “60/100PP vertical coaxial” System (polypropylene) (C13; C33) ............................................................ 28
5.16.6 - “60/100PP horizontal coaxial” System (polypropylene) (C13; C33) ........................................................ 29
5.16.7 - “60/100PP Coaxial” System: accessories available ............................................................................... 30
5.16.8 - “60/100PP Coaxial” System: installation examples ............................................................................... 31
6 - OPERATING .................................................................................................................................................32
6.1 - Operating ............................................................................................................................................................... 32
6.1.1 - User instruction ......................................................................................................................................... 32
6.1.2 - Filling the condensate drain siphon .......................................................................................................... 32
6.1.3 - Filling the central heating plant ................................................................................................................. 32
6.2 - General recommendations regarding the supply of gas ........................................................................................ 33
6.3 - Type of gas for which the appliance is regulated. .................................................................................................. 33
6.4 - Conversion of the appliance from one type of gas to another ................................................................................ 34
6.5 - Ignition .................................................................................................................................................................... 36
6.6 - Controlling the supply gas pressure and any adjustment ...................................................................................... 36
6.7 - Controlling the combustion agent air pressure ....................................................................................................... 37
6.8 - Controlling the level of CO2 and any adjustment ................................................................................................... 38
6.9 - Adjusting the power in central heating mode (Range Rated) ................................................................................. 39
6.10 - Adjusting the domestic hot water ow rate ........................................................................................................... 39
7 - USE ...............................................................................................................................................................40
7.1 - Controlling cock opening ........................................................................................................................................ 40
7.2 - Checking central heating plant pressure ................................................................................................................ 40
7.3 - Generalities ............................................................................................................................................................ 41
Page 3
3
MYDENS
COSMOGAS
INDEX
7.4 - Ignition procedure .................................................................................................................................................. 41
7.5 - “User menu” ........................................................................................................................................................... 41
7.6 - Summer operating mode ........................................................................................................................................ 41
7.7 - Winter operating mode ........................................................................................................................................... 41
7.8 - Adjusting the instantaneous domestic hot water .................................................................................................... 42
7.9 - Central Heating ...................................................................................................................................................... 42
7.10 - Thermostatic adjustment ...................................................................................................................................... 42
7.11 - Climatic adjustment .............................................................................................................................................. 42
7.11.1 - Climatic adjustment: on which plants? .................................................................................................... 42
7.11.2 - Climatic adjustment: precautions during adjustment ............................................................................... 43
7.11.3 - Climatic adjustment: setting the parameters ........................................................................................... 43
7.11.4 - Climatic adjustment: adaptation to different climatic areas ..................................................................... 43
7.11.5 - Climatic adjustment: switching the central heating service on and off .................................................... 43
7.11.6 - Climatic adjustment with room compensation ......................................................................................... 43
7.12 - Timers of the various functions ............................................................................................................................ 45
7.13 - Pumps anti-blocking and diverter valve ............................................................................................................... 45
7.14 - Anti-freeze protection ........................................................................................................................................... 45
7.15 - Automatic plant lling (on request) ....................................................................................................................... 45
7.16 - Energy Saving ...................................................................................................................................................... 45
7.17 - “User menu” ......................................................................................................................................................... 46
7.18 - “Installer menu” .................................................................................................................................................... 47
7.19 - Diagnostics ........................................................................................................................................................... 49
7.19.1 - Diagnostics: blocks “Loc” ........................................................................................................................ 50
7.19.2 - Diagnostics: errors “E” ............................................................................................................................ 52
7.19.3 - Diagnostics: alarms “AttE” ...................................................................................................................... 53
8 - MAINTENANCE ............................................................................................................................................54
8.1 - General recommendations ..................................................................................................................................... 54
8.2 - Removing the casing and access to internal components ..................................................................................... 55
8.3 - Removing the burner fan unit ................................................................................................................................. 56
8.4 - Cleaning the burner and the fumes side primary heat exchanger ......................................................................... 56
8.5 - Correct positioning of the ignition and ionising electrodes ..................................................................................... 57
8.6 - Controlling the expansion tank ............................................................................................................................... 57
8.7 - Cleaning the condensate conveyor siphon ............................................................................................................ 58
8.8 - Removing the air vent valve ................................................................................................................................... 59
8.9 - Replacing the pump motor ..................................................................................................................................... 59
8.10 - Removing the central heating circuit pressure sensor ......................................................................................... 59
8.11 - Removing the diverter valve servo-motor ............................................................................................................. 60
8.12 - Removing the diverter valve ................................................................................................................................. 60
8.13 - Removing the ow meter ..................................................................................................................................... 60
8.14 - Removing the safety valve ................................................................................................................................... 61
8.15 - Secondary heat exchanger for the production of d.h.w. ....................................................................................... 61
8.16 - Emptying the appliance on the domestic hot water side ...................................................................................... 62
8.17 - Emptying the appliance on the domestic hot water side ...................................................................................... 62
8.18 - Fan ....................................................................................................................................................................... 62
8.19 - Minimum and maximum power ............................................................................................................................ 62
8.20 - Checking the ionisation current ............................................................................................................................ 63
8.21 - Checking combustion efciency ........................................................................................................................... 63
8.22 - Water temperature measurement sensors ........................................................................................................... 63
8.23 - External temperature sensor ................................................................................................................................ 63
8.24 - Operational wiring diagram .................................................................................................................................. 64
8.25 - Multi-wire wiring diagram ..................................................................................................................................... 66
9 - TECHNICAL DATA ........................................................................................................................................68
10 - COMMAND MENU DIAGRAM ....................................................................................................................70
11 - MENU FORCED BY INTERNAL ELECTRIC BRIDGE ................................................................................71
12 - CE DECLARATION OF CONFORMITY ......................................................................................................72
13 - WARRANTY ................................................................................................................................................73
13.1 - General warranty conditions ................................................................................................................................ 73
13.2 - Instructions for lling-in the warranty card ............................................................................................................ 73
13.3 - Limits of the warranty ........................................................................................................................................... 73
Page 4
4
MYDENS
COSMOGAS
If you smell gas
1. - Close the gas cock.
2. - Ventilate the room.
3. - Do not switch on any electric device, telephone included.
4. - From another room, call a professionally qualified technician immediately or the gas supply company. Call the Fire Service if the former are not available.
If you can smell combustion products
1. - Switch the appliance off.
2. - Ventilate the room.
3. - Call a professionally qualied technician.
Explosive or highly ammable products
Do not store or use explosive or highly ammable materials
such as paper, solvents, paints, etc... in the same room where the appliance is installed.
Installation, modications
The gas appliance must be installed, calibrated or modied
by professionally qualied staff, in compliance with National
and local Standards, as well as the instruction in this manual.
Incorrect installation or poor maintenance can cause
injury/damage to persons, animals or objects, for which the manufacturer cannot be deemed liable.
The appliance exhaust must be connected to a burned
gas evacuation pipe. Failure to comply with this regulation leads to serious risks for the safety of persons and animals.
A domestic hot water temperature level exceeding 51°C
can cause permanent injury/damage to persons, animals and objects. Children, the elderly and disabled must be protected against the potential risks of scalding, by introducing devices that limit the temperature of use of domestic hot water to utilities.
The parts conducting the fumes must not be modied.Do not obstruct the ends of the intake/exhaust pipes.Do not leave parts of the packaging and any replaced parts
within the reach of children.
Seal the adjustment devices after every calibration.In agreement with the provisions for use, the user must
keep the installation in good working order and guarantee reliable and safe operation of the appliance.
The user must have maintenance performed on the
appliance by a professionally qualified technician in agreement with national and local Standards and in compliance with that stated in this manual.
We also highlight the convenience of an annual scheduled
maintenance contract with a professionally qualified technician.
Before performing any cleaning or maintenance operation,
disconnect the appliance from the mains power supply and/ or by acting on the cut-off devices.
After having performed any cleaning or maintenance
operation, make sure that all internal parts of the appliance are dry before re-connecting the electric power supply.
This appliance is not intended for use by persons (including
children) with reduced physical and sensory conditions or
lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
This manual is an integral and essential part of the product
and must be kept carefully by the user, for possible future consultation. If the appliance must be transferred or if you should move and leave the unit to another user, always ensure that this manual remains with the new user and/ or installer.
Any optional or kits added successfully must be original
Cosmogas products.
This appliance must be intended only for the use for which
it has been expressly declared: central heating water for closed circuits intended for central heating of rooms for civil and domestic use, production of domestic hot water for civil use.
Any contractual and extra contractual liability of the
manufacturer is excluded for damage caused by installation errors or errors in use and however due to failure to comply with the instructions given by the manufacturer or by failure to comply with applicable national and/or local laws.
For safety reasons and respect for the environment, the
packaging elements must be disposed of in the relevant separate waste collection centres.
In case of breakdown
In the case of appliance breakdown and/or malfunctioning, deactivate it, do not attempt any repairs. Cont act a professi onally qualifie d t echnician only. If components must be replaced for repair, only use original spare parts. Failure to comply with the above can jeopardise the safety of the appliance.
Professionally qualied technician.
Professionally qualied technician means, a person with specic technical skill in the sector regarding central heating
plants and the production of hot water for sanitary and domestic uses, for civil use, electric plants for the use of combustible gas. This staff must be authorised as envisioned by the law.
Technical drawings
All the drawings in this manual, relating to electrical, hydraulic or gas installation plants, must be deemed purely indicative. All of the safety elements, auxiliary elements such as the diameters of the electric, hydraulic and gas pipes, must always
be checked by a professionally qualied technician to verify
compliance with applicable Standards and Laws.
1.1 - National installation laws
- M.D. n°37 dated 22/01/2008 (former Law n°46 dated 05/03/90)
- Law n°10 dated 09/01/91
- Presidential Decree n°412 dated 26/08/93
- Presidential Decree n°551 dated 21/12/99
- Legislative Decree n° 192 dated 19/08/05
- Legislative Decree n° 311 dated 29.12.06
- UNI 7129 Standard
- UNI 7131 Standard
- UNI 11071 Standard
- IEC 64-8 Standard
1 - GENERAL SAFETY RECOMMENDATIONS
Page 5
5
MYDENS
COSMOGAS
2.1 - Presentation
Congratulations! You have purchased one of the best products on the market. Each individual part is proudly designed, realised, tested and assembled within the COSMOGAS establishment, thus guaranteeing the best quality control. This product has been developed thanks to the constant research by COSMOGAS, considered the “top”
regarding respect for the environment, as it lies within class 5 (the least polluting) envisioned by the EN 297 (and EN 483) Technical Standard and has high efciency; 4-star as per European Community Directive 92/42/
EEC. Great importance has also been given to the end of the appliance’s life. All of its components can be easily separated into homogeneous elements and completely re-cycled.
2.2 - Overview of the models
MYDENS XXY
“P” = Boiler for the instantaneous production of D.H.W. and central heating; “B” = Boiler set-up for coupling to a indirect water heater with coil; “C” = Central heating only boiler;
15 = Boiler with maximum heat input of 14 kW 24 = Boiler with maximum heat input of 25 kW 34 = Boiler with maximum heat input of 34.8 kW
Condensing, indoor, pre-mixed, ecological gas boiler.
2.3 - Manufacturer
COSMOGAS srl Via L. da Vinci 16
47014 - Meldola (FC) Italia
Tel. 0543 498383 Fax. 0543 498393 www.cosmogas.com info@cosmogas.com
2.4 - Key for the symbols used
ATTENTION !!!
El ectric s hock haza rd. Failure to c omply wit h t hese recommendations can jeopardise the good working order of the appliance or cause serious damage to persons, animals or objects.
ATTENTION !!!
Failure to comply with these recommendations can jeopardise the good working order of the appliance or cause serious damage to persons, animals or objects.
Important indication symbol
2.5 - Maintenance
It is recommended to perform regular yearly maintenance of the appliance for the following reasons:
- to maintain a high efciency and manage the domestic hot water plant economically (with low fuel consumption);
- to achieve a high level of safety;
- to maintain the level of environmental compatibility of the
combustion high;
Offer your customer a scheduled maintenance contract.
2.6 - Warranty
see chapter 13.
2 - GENERAL INFORMATION
Page 6
6
MYDENS
COSMOGAS
1 - Command and control board 2 - Electric connections board 3 - Electric control board box 4 - Lower cover 5 - Secondary heat exchanger for the domestic hot water 6 - Central heating circuit pressure sensor 7 - Safety valve 8 - Fan 9 - Air/gas manifold
10 - Return tting 11 - Supply tting
12 - Detection electrode 13 - Expansion tank 14 - Support attachments
15 - Conveying tting 16 - Air intake and burned gas exhaust ttings
17 - Combustion analysis points
18 - Double fumes temperature sensor (Par.
1006 and 1014)
19 - Spark generator 20 - Ignition cables 21 - Burner window 22 - Air inlet manifold
23 - Back ue preventer valve
24 - Gas valve 25 - Circulation pump 26 - Pump release screw 27 - Front casing
28 - Domestic hot water ow meter 29 - Domestic hot water ow meter sensor (Par.1061)
30 - Display 31 - Control board 32 - Access to the gas valve adjusters
3 - MAIN COMPONENTS
Figure 3.1 - Boiler internal components
14
28
29
14
26
21
5
25
24
20
22
4
3
8
2
16 18
7
23
19
6
12
17
9
10
11
15
13
1
323130
27
020002.01.002
Page 7
7
MYDENS
COSMOGAS
33 - Front casing couplings 34 - Titanium plated stainless steel primary heat exchanger
35 - Double supply temperature sensor (Par. 1001 and
1005)
36 - Return temperature sensor (Par. 1007) 37 - Supply hydraulic unit 38 - By-pass pipe 39 - Central heating circuit drain cock 40 - Central heating circuit drain cock
41 - Domestic hot water temperature sensor (Par. 1002)
42 - Plant ll cock
43 - Condensate collection tank 44 - Safety valve drain pipe 45 - Return hydraulic unit 46 - Air vent valve 47 - 3-way diverter valve 48 - Air vent valve drain pipe 49 - Condensate drain siphon 50 - Air/gas mixing unit 51 - Burner 52 - Drain pipe for any water coming from the combustion agent air pipe 53 - Left ignition electrode 54 - Right ignition electrode
3 - MAIN COMPONENTS
Figure 3.1 - Boiler internal components
53
39
36
34
4038
51
41
33
37
35
54
49
50
44
52
47
48
43
46
45
42
020002.01.003
Page 8
8
MYDENS
COSMOGAS
4 - OPERATION
Figure 4.1 - Hydraulic layout
MYDENS 24P MYDENS 34P
Figure 4.2 - Hydraulic layout
MYDENS 15B MYDENS 24B MYDENS 34B
Page 9
9
MYDENS
COSMOGAS
Key for gures 4.1, 4.2, 4.3:
1 = Boiler 2 = Combustion agent air inlet 3 = Fumes outlet
4 = Fumes temperature sensor (Par. 1006) 5 = Sealed chamber
6 = Fumes temperature safety sensor (Par. 1014) 7 = Water collection pipe coming from the combustion agent inlet pipe 8 = Expansion Tank
9 = Supply temperature sensor (Par. 1001) 10 = Supply temperature safety sensor (Par. 1005)
11 = Burner 12 = Titanium plated stainless steel VRC type heat exchanger 13 = Fan
14 = Return temperature sensor (Par. 1007) 15 = Condensate collection siphon with sediment decanter 16 = Air/gas mixer 17 = Pneumatic gas valve 18 = Safety valve 19 = Central heating circuit pressure sensor 20 = Circulation pump 21 = Air vent valve 22 = Diverter valve 23 = Plate heat exchanger for domestic hot water
24 = Domestic hot water sensor (Par. 1002) 25 = Central heating by-pass valve
26 = Domestic hot water ow meter 27 = Domestic hot water lter
28 = Supply circuit drain cock 29 = Return circuit drain cock
30 = Central heating plant ll cock
31 = Central heating circuit supply 32 = Domestic hot water outlet 33 = Gas inlet 34 = Domestic cold water inlet 35 = Central heating circuit return 36 = Condensate drain collector and of the safety valve 37 = Central heating plant 38 = Domestic hot water plant
39 = Water supply attachment for lling plant
40 = Supply to indirect water heater 41 = Return from indirect water heater 42 = Expansion tank for indirect water heater 43 = Hydraulic safety unit 44 = Cold water supply 45 = Safety valve 46 = Cold water 47 = Domestic hot water 48 = Indirect water heater
49 = Indirect water heater temperature sensor (Par. 1002)
Figure 4.3 - Hydraulic layout
MYDENS 15C MYDENS 24C MYDENS 34C
4 - OPERATION
Page 10
10
MYDENS
COSMOGAS
4.1 - Operation and intended use of the appliance
This product is a condensing, gas appliance, intended for the production of central heating and domestic hot water for civil use. Make the adaptation between boiler and plant, selecting the characteristic residual head curve deemed most suitable
from those available (see g. 4.4 and 4.5).
The max. useful power is always guaranteed at the production of domestic hot water as the central heating service switches off at every request for domestic hot water. The temperature of the domestic hot water is adjusted following the relevant procedure in chapter 7.8. The following types of plants can be realised depending on the model:
A) - MYDENS -- “P”. With this boiler it is possible to realise
a plant for the production of instantaneous domestic hot water and a central heating plant with the heating elements operating at a temperature between 30°C and 80°C. An
example of this type of plant is given in g. 4.1.
B) - MYDENS -- “B”. With this boiler it is possible to realise
a plant for the production of domestic hot water via a coil­type storage indirect water heater and a central heating plant with the heating elements operating at a temperature between 30°C and 80°C. An example of this type of plant is
given in g. 4.2.
C) - MYDENS -- “C”. With this boiler it is possible to realise
a plant for central heating only with the heating elements operating at a temperature between 30°C and 80°C. An
example of this type of plant is given in g. 4.3.
This model can be connected to a indirect water heater
with coil also after installation, lled via a diverter valve or a
pump outside the boiler.
In all of the boiler versions previously described, the connection of the domestic hot water service is not
indispensable; if the boiler is used for central heating only, just connect the cold water pipe to ll the central heating plant and close the d.h.w. outlet tting.
All boiler versions previously described, can be connected to a room thermostat for adjustment of the central heating. To perfect the quality of the heating service, an external
temperature sensor can be connected (climatic adjustment)
to automatically adjust the supply temperature depending on the external temperature. In this case, the room temperature can perform an ON /OFF type of compensation of the room temperature or in two steps. For further information regarding climatic adjustment, refer to chapter 7.11.
This appliance must be attached to a central heating
plant and eventually to a domestic hot water distribution network, compatible with the features, performance and powers of the appliance itself.
Before installation the central heating plant and the
domestic hot water plant must be washed thoroughly in order to remove any residues or impurities, which could compromise the good working order of the boiler.
This appliance is not envisioned for installation outdoors.
It must not be exposed to temperatures below zero and temperatures above 50°C. Selected a place sheltered from atmospheric agents and freezing.
This appliance must be installed in a location where any
loss of water from the same, the connections between the pipes or from the safety valve drain, cannot cause damage to materials or objects below.
Check gure 5.1 concerning the minimum safety
distances for installation and future maintenance.
4 - OPERATION
Page 11
11
MYDENS
COSMOGAS
4.2 - Characteristic curves of the residual head at the central heating plant
The residual head at the attachments of the MYDENS
boiler with standard pump is given as a graph in gures 4.4
and 4.5.
If the head is not sufcient, it is possible to request a 7
metre upgraded pump. In this case, the residual head can
be veried on the graphics in gures 4.6 and 4.7.
4 - OPERATION
Figure 4.4 - Residual head for MYDENS 24 with 6 metre pump (standard)
Figure 4.5 - Residual head for MYDENS 34 with 6 metre pump (standard)
You can request a modulating pump. In this case the
modulation range (particularly “x”) is veriable on the graph of gure 4.8.
ATTENTION !!! For MYDENS - “P” models it is prohibited to use the selector switch on the pump to modify its speed, as the domestic hot water production
efciency deteriorate.
0
50
100
150
200
250
300
350
400
450
500
0 200 400 600 800 1000 1200
1400
Q (l/h)
H (mbar)
RIC16-2012_b
0
50
100
150
200
250
300
350
400
450
500
0 200 400 600 800 1000 1200
1400
Q (l/h)
H (mbar)
RIC16-2012_a
Page 12
12
MYDENS
COSMOGAS
4 - OPERATION
Figure 4.6 - Residual head for MYDENS 24 with 7 metre pump (on request)
Figure 4.7 - Residual head for MYDENS 34 with 7 metre pump (on request)
RIC20-2012_b
0
50
100
150
200
250
300
350
400
450
500
550
0 200 400 600 800 1000 1200 1
400
Q (l/h)
H (mbar)
RIC20-2012_a
0
50
100
150
200
250
300
350
400
450
500
550
0 200 400 600 800 1000 1200
1400
Q (l/h)
H (mbar)
Page 13
13
MYDENS
COSMOGAS
Figure 4.9 - Domestic hot water losses curve
0
0,5
1
1,5
2
2,5
3
0 3,3 6,6 10 13,3 16,6
RIC17 - 2012
Head losses (bar)
Water ow rate (l/min)
4 - OPERATION
4.3 - Characteristic curve of the domestic hot water head losses
Each boiler offers certain resistance on the passage of
the domestic hot water (see ow rate/pressure graphics in gure 4.9). The installer or design technician must take this into consideration in order to guarantee the correct ow rate
of domestic hot water to the utility.
Figure 4.8 - Residual head for MYDENS with modulating pump (on request)
0
50
100
150
200
250
300
350
400
450
500
550
600
650
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300
X
RIC27-2013
H (mbar)
Q (l/h)
Page 14
14
MYDENS
COSMOGAS
5.1 - Opening the packaging
The appliance is supplied in cardboard packaging. Open
following the instructions given on the aps of the packaging
itself.
5.2 - Dimensions and minimum safety distances
It is necessary to leave free spaces around the boiler as
illustrated in gure 5.1 both for installation and maintenance.
5.3 - Choosing the place of installation
ATTENTION !!! The appliance must be installed exclusively on a solid, vertical wall, which can support the weight.
The appliance must be installed within the home, or otherwise protected from atmospheric agents such as rain, wind, sun, and especially freezing.
Dene the room and suitable position for installation, taking
into account the following factors:
- connection of the fumes exhaust/air intake pipes;
- connection of the gas supply pipe;
- connection to the water supply;
- attachment of the central heating plant;
- attachment of the domestic hot water plant;
- electric connection;
- connection to the drain for the condensate produced by
the boiler;
- electric connection of the room thermostat;
- eventual connection of the safety valve drain;
- eventual attachment of the external temperature sensor;
5.4 - Supply and return
ATTENTION !!! This boiler has a safety valve calibrated at 3 bar. A water head over 30 m must therefore not be installed.
ATTENTION !!! COSMOGAS is not liable for any damage caused by incorrect use of additives in the central heating plant.
ATTENTION !!! The plant downstream from the appliance must be made with materials that resist temperatures up to 95°C and pressure of 3 bar.
Differently (e.g. plastic piping) the plant must be tted
with the relevant protection and safety devices.
Before connecting the central heating pipes, wash the plant thoroughly to eliminate any waste (hemp, radiators casting
sand, etc..), which could damage the appliance. This
washing operation must also be performed if the appliance is replaced. Figure 5.2 shows the positioning of the supply and return
ttings.
Install a metal mesh lter on the return pipe in order to stop
any plant residues before the return into the boiler.
Do not use the appliance for the introduction of any type
of additive into the plant.
1 - Central heating supply 3/4” in the 15 and 24 models 1” in the 34 model
2 - 1/2” D.H.W. outlet (absent in “B” and “C” models) 3 - 3/4” indirect water heater return (present in “B” models only)
4 - 3/4” gas inlet 5 - 1/2” cold water inlet 6 - Central heating return 3/4” in the 15 and 24 models 1” in the 34 model 7 - Fumes exhaust 8 - Support attachments 9 - Ø20 condensate drain
5 - INSTALLATION
Figure 5.1 - Minimum safety distances
Figure 5.2 - Boiler dimensions and attachments centre to centre distances
Page 15
15
MYDENS
COSMOGAS
5 - INSTALLATION
A continuous intake of water into the central heating circuit increases the content of oxygen and lime scale with a risk of corrosion inside the heat exchanger body, with consequent reduction of the boiler’s lifespan. Any leaks from the central heating circuit must be repaired to prevent the problem.
5.5 - Low temperature
plants (or on the oor)
ATTENTION !!! The plant downstream from
the appliance must be made with materials that resist temperatures up to 95°C and pressure of 3 bar.
Differently (e.g. plastic piping) the plant must be tted
with the relevant protection and safety devices.
ATTENTION !!! when installing the boiler in
a low temperature plant, it is indispensable to set
the parameter
3015 at the value of 45°C and the
parameter 3016 at the value of 20°C (see chapter 11).
With this setting, the boiler will adjust the supply to a temperature between 20°C and 45°C. No adjustment from
the command panel (also via climatic adjustment), can
supply water at a temperature over 45°C.
ATTENTION !!! If the boiler is installed in a
oor-standing plant made with plastic piping, all of the
precautions must be taken against corrosion due to oxygen in the water:
make sure that the plant is made with plastic pipes with permeability to oxygen not exceeding 0.1 g/m3 at 40°C. Whenever the pipe should not meet these features, the radiant panel circuit from the boiler must be isolated, via a plate heat exchanger suitable to resist the corrosion generated by the oxygen dissolved in the water.
5.6 - Domestic hot and cold water
ATTENTION !!! If water hardness exceeds 25°F, we recommend the installation of a polyphosphates softener (see chapter 5.13).
ATTENTION !!! Install a lter with mesh no wider than 0.5 mm² in the domestic cold water inlet.
ATTENTION !!! The domestic hot water circuit must be realised with materials resistant to a temperature of at least 95°C and pressure of 10 bar.
Differently (e.g. plastic piping) the plant must be tted
with the relevant protection and safety devices.
In gure 5.2 it is possible to verify positioning of the domestic hot and cold water ttings.
Envision a closing cock upstream from the cold water inlet, useful for maintenance works. The connection of the domestic hot water service is not
indispensable; if the boiler is used for central heating only, just connect the cold water pipe to ll the central heating
plant and close the d.h.w. outlet.
5.7 - Gas
ATTENTION !!! It is prohibited to power the
appliance with gases different to that envisioned.
ATTENTION !!! Check that the gas and supply
pressure are those for which the boiler has been adjusted.
Two situations are possible: A - the gas and supply pressure correspond to the
adjustment of the boiler. In this case, it can be
connected;
B - the gas and supply pressure do not correspond to the
adjustment of the boiler. In this case, the boiler must be converted to the type of gas and supply pressure corresponding to those of the supply available.
The boiler is provided with the relevant gas conversion kit.
Before installation it is advised to clean the inside of the
gas supply pipe thoroughly;
A cut-off cock must always be installed on the gas
supply pipe;
To prevent damage to the appliance gas control unit, the
leak test at a pressure not exceeding 50 mbar;
If the gas plant must be inspected at pressures over
50 mbar, operate on the cock positioned immediately upstream from the boiler, to isolate the same from the plant.
Figure 5.2 veries the positioning of the appliance gas tting. The sections of the pipes making up the gas supply plant must always guarantee a gas supply sufcient to
cover the maximum requested.
Page 16
16
MYDENS
COSMOGAS
Figure 5.3 - Support plugs
Figure 5.4 - Safety valve drain and condensate drain connection
B
C
A
020002.01.005
D
A
E
020002.01.006
5 - INSTALLATION
5.8 - Mounting the appliance
Refer to gure 5.3:
1.- place the paper template, provided with the appliance,
against the wall;
2.- check that the template is square to the environment;
3.- mark the holes for the plugs and hydraulic ttings on the wall;
4.- remove the paper template;
5.- make the holes “A” and introduce the wall plugs “B”;
6.- make the boiler hydraulic and gas connections;
7.- hang the boiler on the plugs “C”;
8.- make the hydraulic ttings.
5.9 - Condensate drain
There is a siphon inside the boiler for the evacuation of
condensate (see gure 3.1 detail “49”) and to prevent
combustion products from escaping, whose end
corresponds to the pipe “B” in gure 5.4. This termination must be conveyed into an anti-odour siphon (gure
5.7 detail “G”) to prevent bad odours returning into the
environment (the anti-odour siphon “G” is supplied on
request). Open the tank “A” as indicated in gure 5.4 and x it using
the screw “D”, connect the drain pipe “F” as indicated in
gure 5.5.
In particular, the condensate drain plant must be:
for room used for residential purposes and for ofce with
more than 10 users, it can be connected to the domestic waste disposal plant by means of appropriate siphon with disjunction capable of preventing the pressurisation of
the system (siphon prepared within boiler) and to prevent
the return of bad odours from the sewer (detail “G” in
gure 5.7). If the room used for ofce purposes has
less than 10 users, before connection with the domestic waste drain, a condensate neutraliser is good practice (see chapter 9 for the value of acidity of the condensate
and the quantities).
be performed with a pipe with internal diameter equal to
or greater than 13 mm;
be installed in a way to prevent the liquid from freezing;
therefore pay attention to any external passings. It is
prohibited to drain into gutters or drainpipes;
to slope continuously towards the drain point, avoid high
points, which could pressurise the pipe;
5.10 - Safety valve
The appliance is protected against overpressures by a
safety valve calibrated to 3 bar (see gure 3.1 detail “7”). The safety valve drain (detail “C” in gure 5.4), along with the condensate drain (detail “B” in gure 5.4) must be conveyed to a pipe “F” (see gure 5.5) with minimum internal diameter of 13 mm; the pipe “F” must be then taken to the anti-odour siphon (detail “G” gure 5.7). This drain
with siphon is used to prevent overpressures if the valve is opened and makes it possible for the user to check the eventual intervention.
The pipe “F” in gure 5.5 is supplied as per standard along with tank “A” in gure 5.4. The anti-odour siphon “G” in gure 5.7 is provided on request.
ATTENTION !!! If not connected to the drain,
whenever the safety valve should intervene, it could cause damage to persons, animals or objects.
Page 17
17
MYDENS
COSMOGAS
Figure 5.6 - Water and gas connections
Figure 5.5 - Condensate drain pipe
5 - INSTALLATION
A
F
020002.01.017
EBA F
G
C DH
020002.01.004
Figure 5.7 - Siphon funnel (on request)
F
G
020002.01.028
min10 mm max 30 mm
5.11 - Hydraulic and gas connections
and mounting of the lower cover
The boiler is provided with the ttings illustrated in gure 5.6
as per standard, where:
A = central heating supply Ø 18 in the 15 and 24 models Ø 22 in the 34 model
B = domestic hot water Ø 14 (absent in the “B” and ”C” models) C = 3/4” gas inlet cock (EN 331 type-approved)
D = 1/2“ domestic cold water inlet cock
E = gas Ø 18
F = domestic cold water Ø 14
G = central heating return Ø 18 in the 15 and 24 models Ø 22 in the 34 model
Once the hydraulic and gas connections have been made, proceed with assembly of the lower cover “H” as indicated
in gure 5.6.
Page 18
18
MYDENS
COSMOGAS
5.12 - Hydraulic connection for MYDENS -- B boiler
The “B” version of the boiler must be connected to a indirect water heater with coil for the production of domestic
hot water (see also chapter 5.15). To do this, ttings have been set-up for connection to the
indirect water heater. Operate as follows to prepare (refer
to gure 5.8):
1.- mount the reducer “A”;
2.- mount the wires “B” and “C”;
Make sure that every coupling has its own gasket introduced
A = reducer tting
B = supply to indirect water heater coil C = return from indirect water heater coil
Figure 5.8 - Hydraulic connections for boiler with indirect water heater with coil
5.13 - Polyphosphates
softener (on request)
If the boiler is installed in a geographical area where
domestic water has hardness exceeding 25°F (250 mg/l), a
polyphosphates softener must be installed on the cold water
supply (see gure 5.9 detail “B”), in order to safeguard the
appliance from any lime scale deposits.
Proceed as follows for installation (refer to gure 5.9):
1.- connect the softener “B” to the cock “A”;
2.- mount the cock “A” to the boiler tting;
3.- proceed with the installation of the cold water inlet pipe
into the tting behind the softener “B”;
4.- before re-mounting the lower cover, it is necessary to
trim (only in the rear part), the entire part between walls
“C” and “D”, from the outer edge to the central slot, to allow the softener “B” to be housed.
Figure 5.9 - Polyphosphates softener (on request)
A
B
C
020002.01.007
B
A
C
B
A
D
020002.01.008
5 - INSTALLATION
Page 19
19
MYDENS
COSMOGAS
5.14 - Electric connections: generalities
ATTENTION !!! The appliance is only electrically
safe when it has been correctly connected to an
efcient earth circuit, performed as envisioned by the
current Safety Standards.
This fundamental safety requirement must be met. If in doubt, request a thorough control of the electric plant by a
professionally qualied technician.
Have a professionally qualied technician check that the
electric plant is suitable for the electric power required by the appliance, indicated on the plate.
The appliance must be connected to the mains electricity
using a cable coupler. The use of adapters, multiple sockets, extensions, etc. is not allowed.
The appliance must be connected to the mains electricity
using a three-polar electric cable, with double isolation, minimum section of 1.5 mm² and resistant to a minimum
temperature of 70°C characteristic T).
For connection to mains electricity, a bi-polar switch
must be envisioned in the vicinity of the appliance with a contacts opening distance of at least 3 mm, as envisioned by the current regulations on the subject.
Respect the polarity between the neutral phase during
connection of the appliance.
Make sure that the water plant and heating pipes are not
used as earth points for the electric or telephone plant. This piping is not suitable for this purpose, moreover, serious corrosion damage would occur in a very short time, on the appliance, piping and radiators.
ATTENTION !!! the boiler is not protected
against the effects caused by lightening.
D
C
C
C
B
A
020002.01.009
5 - INSTALLATION
Figure 5.10 - Electric connections
Key for gure 5.10
A = Commands board box; B = Electric connections board lid; C = Connections lid closing aps;
D = electric connections board
Key for electric contacts
PM = External modulating pump control (if present) CH = Supply sensor (for boilers in cascade mode)
BUS = Remote control TA = Room thermostat/chronothermostat 0-10 = 0-10 volt signal input
SE = External sensor (if present) SB = Indirect water heater sensor (if present)
MF = Multi-function output
PE = External pump (if present) DNC = External diverter valve (if present) (D = Domestic hot water line; N = Neutral; C = Heating line)
L1 = boiler power supply line N = Boiler power supply neutral EARTH SYMBOL = Earth contacts
020002.01.010
Page 20
20
MYDENS
COSMOGAS
Figure 5.11 - Correct positioning of the room thermostat/chronothermostat
5.14.1 - Power supply cable connection
Proceed as follows to connect the power supply cable (refer
to gure 5.10):
1.- use a three-polar cable with double isolation, with minimum section of 1.5 mm²
2.- remove the casing from the appliance following the
relevant instructions in chapter 8.2;
3.- rotate the panel “A” towards the front of the boiler;
4.- operate on the aps “C” and open the lid “B” as indicated by the arrow;
5.- lay the power supply cable through the fairlead in
proximity of the contacts “L1”, “N” and earth symbol;
6.- strip the cable making sure that the earth wire (yellow/
green) is kept 20 mm longer than the other two;
7.- connect the yellow-green cable to the earth clamp (see
symbol)
8.- connect the brown cable (Phase) to the clamp L1
9.- connect the blue cable (Neutral) to the clamp N
5.14.2 - Choosing the room thermostat/
chronothermostat
The boiler is set-up to operate with any room thermostat or chronothermostat, which has the contact to which the cables coming from the boiler are to be connected, with the following features:
- open/closed (ON/OFF);
- potential-free (not powered);
- closing when there is a request for heat;
- 24Vac, 1A electrical feature.
5.14.3 - Connecting the room thermostat/ chronothermostat
Install the room thermostat in a place in the house where the temperature is the most characteristic of the home and however in an area that is not subjected to repeated temperature changes, away from windows or doors which
open directly to the outside (see gure 5.11).
Proceed as follows to connect the room thermostat cable
(refer to gure 5.10):
1.- use a bi-polar cable with minimum section of 1.5.5mm², which goes from the boiler to the room thermostat/ chronothermostat. The maximum length allowed is 20 metres. For lengths exceeding 100 metres, use a
shielded cable with shield earthing;
2.- remove the casing from the appliance following the
relevant instructions in chapter 8.2;
3.- lay the electric cable through the fairlead in proximity of
the “TA” contacts;
4.- use a free fairlead, not used by other wires;
5.- strip the cable;
6.- connect the two ends of the cable to the “TA” clamps
(see gure 5.10).
ATT ENTI O N !! ! As the room ther most a t/
chronothermostat cables are subjected to very low safety
voltage (25Vdc), they must ow in wires different from the
230 Vac power supplies.
5 - INSTALLATION
Page 21
21
MYDENS
COSMOGAS
5 - INSTALLATION
5.14.4 - Installing the external temperature
sensor (on request)
Install the external temperature sensor outside the building in a wall facing NORTH or NORTH-EAST, at a height of 2 to
2.5 metres from the ground. In buildings with several oors, it
must be installed at about half way up the second oor. Do not
install it above windows, doors or ventilation outlets or directly below balconies or gutters. Do not plaster over the external temperature sensor. Do not install the sensor on walls without eaves, i.e. not protected from rain. Whenever the sensor is installed on a wall that has yet to be plastered, it must be installed with a suitable thickness or be removed before plastering. Proceed as follows to connect the external temperature sensor cable:
1.- lay a bi-polar electric cable with minimum section of
1.5mm², which goes from the boiler to the external temperature sensor. The maximum length allowed is 20 metres. For other lengths up to 100 metres, use a shielded cable with shield earthing.
ATTENTION !!! As the cables are subjected to
very low safety voltage (24Vdc), they must ow in wires
different from the 230 Vac power supplies.
2.- connect the bipolar cable to the “SE” clamps in gure
5.10;
3.- connect the bi-polar cable to the ends of the external temperature sensor.
Set the boiler to learn of the external temperature sensor as
follows (refer to gure 7.1):
1.- press the
and RESET keys simultaneously for 5
seconds and until the symbol
appears on the display
to indicate the entry to the “Installer” menu;
2.- press the
and keys to scroll the parameters
in the “Installer” menu until the parameter
2003 is
displayed;
3.- press the RESET key to enable the modication of the parameter (highlighted by the fact that it starts to ash);
4.- press the
and keys to modify the value of
the parameter, taking it to the value of 1 or 2 on the type
of climatic adjustment desired (see chapter 7.11);
5.- press the RESET key to conrm the modication of the
parameter (highlighted by the fact that the value of the
parameter starts to ash);
6.- press the RESET key for 2 seconds to go back to normal
display;
The enabling of the external sensor is conrmed by the
appearance of the icon
on the display. Proceed with the steps given in chapter 7.11.3 to set the correct adjustment values of the supply temperature depending on the external temperature.
Page 22
22
MYDENS
COSMOGAS
5.15 - Connecting the boiler to indirect water heater with coil
Only the MYDENS -- B model boiler can be connected to a indirect water heater with coil.
The hydraulic connection must be performed as per gure
5.12 (see also chapter 5.12).
Proceed as follows for the electric connection (refer to the
gure 5.10):
1.- disconnect the electric power supply from the boiler;
2.- lay a bi-polar electric able with minimum section of 1.5
mm², which goes from the appliance to the indirect water heater temperature sensor and connect it to the boiler at
clamps “8” and “9” (SB);
3.- connect the other end of the cable to the indirect water
heater temperature sensor;
4.- introduce the temperature sensor inside the indirect water
heater sample point (see gure 5.12 detail “14”).
The MYDENS -- C model boiler can be connected to a indirect water heater with coil also after installation. In this case, a diverter valve must be envisioned outside
the boiler to ll the indirect water heater along with
setting parameter 3012 at the value of 1.
The temperature of the water stored inside the indirect water heater can be selected by the user in a range between 40 and 70°C.
ATTENTION !!! A hot water temperature level
exceeding 51°C can cause permanent injury/damage to persons, animals and objects. Children, the elderly and disabled must be protected against the potential risks of scalding, by introducing devices that limit the temperature of use of domestic hot water to utilities.
5.15.1 - Anti- legionella
If the boiler is connected to a indirect water heater for the preparation of domestic hot water, a disinfection cycle is envisioned against the legionella bacterium. This cycle envisions taking the indirect water heater to a temperature
of 60°C (temperature at which the legionella bacteria dies)
at least every week. It is for this reason that the water (at
certain times) can reach the utilities at a higher temperature
that than set with the relative command.
ATTENTION !!! A hot water temperature level
exceeding 51°C can cause permanent injury/damage to persons, animals and objects. Children, the elderly and disabled must be protected against the potential risks of scalding, by introducing devices that limit the temperature of use of domestic hot water to utilities.
Figure 5.12 - hydraulic connection to BWR C type indirect water heater or general indirect water heater with coil
1 MYDENS -- B boiler 2 ­3 ­4 Gas supply
5 D.H.W. recirculation connection (optional) 6 Connection for lling central heating plant (by the installer)
7 BWR C indirect water heater or general indirect water heater with coil 8 Domestic hot water outlet 9 Cold water inlet
10 Supply and return for indirect water heater lling 11 Hydraulic safety unit (by the installer)
12 Supply to the central heating plant 13 Return from the central heating plant 14 Temperature sensor sample point
5 - INSTALLATION
Page 23
23
MYDENS
COSMOGAS
5.16 - Burned gas exhaust and combustion agent air intake pipe
ATTENTION !!! To connect the burned gas
exhaust and combustion agent air intake, the relevant national and local regulations must be respected.
ATTENTION !!! The fumes of this appliance can
reach 90°C in determined conditions. Therefore, use pipes in plastic that can resist high temperatures.
ATTENTION !!! This appliance is the
“condensing” type. Use AISI 316 stainless steel materials to make the fumes exhaust. The polypropylene materials to prevent corrosions due to the acidity of the condensate.
Regarding this, remember that appliances of this type must have exhaust and intake pipes supplied by the manufacturer of the appliance itself. Other types of pipes, if used, must be type-approved for this intended use. The types of exhaust for which the appliance is approved are given on the technical features table at the end of the manual under the “type” heading and on the features plate
afxed to the boiler, also under the “type” heading. The symbols used to dene type of exhaust is given below:
- B23, separated with intake in room and exhaust through
wall or roof.
ATTENTION !!! If the appliance is installed with the
B23 type exhaust, it will take in air for combustion from the surrounding environment. Therefore, all precautions must be taken regarding ventilation of the rooms, which are prescribed by the national and/or local Standards.
- C13, coaxial in vertical wall
- C33, coaxial at the roof
- C43, separated with exhaust in ue, combined with intake
in common channel.
ATTENTION !!! The boilers installed in type C43
must only be connected to conventional ues.
- C53, separated with exhaust on roof and intake on wall or
however, in two potentially different pressure points.
- C63, the boiler can be tted to type-approved exhaust and
intake pipes of other brands.
ATTENTION !!! With the C63 type exhaust,
the condensate coming from the chimney cannot be conveyed into the boiler.
- C83, separated with wall intake or another point
independent from the intakes of other appliances and
ue exhaust.
Figure 5.13 - Exhaust/intake systems
5 - INSTALLATION
Page 24
24
MYDENS
COSMOGAS
During operation, especially in the winter, due to high
efciency, white smoke may escape from the appliance
exhaust. This is solely a natural phenomenon and must not be worried about in any case, because it is the water vapour present in the fumes which in contact with the outside air, condensates.
5.16.1 - Type of intake/exhaust B23
In the case of B23 type combustion agent air/fumes exhaust systems, it is indispensable that the rooms in which the appliances are installed have at least as much air as that required by combustion and ventilation of the room. It is therefore good practice to remember that the combustion of 1 m³ of gas requires 11 cm³ of air. The natural flow of air must take place directly through permanent openings made in the outside walls of the room to
be ventilated; however away from sources of pollution, such
as: vents of dubious origin, airborne industrial exhaust etc.
The ventilation openings must meet the following requirements:
have sections with net passage of at least 6 cm² for
every kW of heat input installed, with minimum of 100
cm²;
be realised in a way that the opening inlets both inside
and outside the wall cannot be blocked;
be protected, for example with grids, metal meshes, etc..
The net section of the passage must not be reduced by
these elements;
ebe situated at a height more or less of the oor
and such not to disturb the correct operation of the combustion products exhaust devices. Where this position is not possible, the section of the ventilation openings must be increased by at least 50%.
The ow of air can also be obtained from an adjacent room
as long as:
it has direct ventilation, in compliance with the previous
points;
in the room to be ventilated, only appliances tted to
exhaust pipes are installed;
the adjacent room is not a bedroom;the adjacent room is not a common part of the building;the adjacent room is not an environment with re hazard,
such as a hangars, garages, combustible materials
warehouse, etc.;
the adjacent room does not have a negative pressure with
respect to the room to be ventilated due to reverse draught (which can be caused by the presence in the room of
another appliance operating with any type of fuel, a replace
and any other intake device for which an adequate air intake
has not been envisioned);
the ow of air from the adjacent room to that to be ventilated
can take place freely through permanent openings with total net section not less than that indicated at the start of this chapter.
In rooms where gas appliances are installed, it may become necessary, as well as the input of combustion agent air, also to evacuate the stale air, with resulting release of an additional equal amount of clean air.
If the stale air is evacuated with the aid of a mechanical tool
(electric fan) the following conditions must be respected: a) if there is a common exhaust pipe in the room, it must be
capped;
b) the ventilation opening of the room in which the gas
appliance is installed must be increased depending on the
maximum air ow rate required at the electric fan.
c) the action of the electric fan must not affect the correct
evacuation of the combustion products. To this end, that
stated above must be veried by draft testing, running the
fan or extractor hood at its maximum power and the gas appliance at the maximum and minimum power.
5 - INSTALLATION
Page 25
25
MYDENS
COSMOGAS
5.16.2 - “Split 80/80PP” System (polypropylene) (Type C43; C53; C83)
The appliance is supplied as per standard without ttings
for the connection of the fumes exhaust/air intake. To connect the boiler to a “80/80PP Split” system, the relevant
kit must be requested and must be installed as in gure
5.14. Fitting “A” can rotate freely by 360°, guaranteeing optimum installation versatility.
In the fumes exhaust side, it is recommended to install
AISI 316L stainless steel or polypropylene pipes, which are more resistant to the formation of condensate.
Take particular care with the installation of pipes in
the part that passes through the wall to the outside. The normal maintenance operations must always be possible, therefore install the pipes in a sheath so that they can be slid out.
The horizontal tracts must always have an inclination of
at least 2% towards the condensate drain device.
The boiler is already set-up to collect the condensate,
which must be tted to a drain pipe (see chapter 5.9).
ATTENTION !!! This condensate drain is
designed to make all liquid produced ow from a single
appliance. If several boilers are installed, each one must envision its own condensate drain.
The fumes exhaust/air intake system can be extended up to a maximum distance as indicated in chapter 9. Every 90° bend has a loss equivalent to 1 metre of linear pipe. Every 45° bend has a loss equivalent to 0.5 m of linear pipe.
ATTENTION !!! The fumes exhaust terminal
must be appropriately protected against the effects of the wind (see also 7.19.1 error Loc 20).
ATTENTION !!! Mechanically secure the joints
between the various component elements of the
exhaust and intake pipe, through the use of xing systems or equivalent systems. See gure 5.16
ATTENTION !!! The temperature of the exhaust
pipe can reach 90°C during operations. If it must pass through a wall that is sensitive to these temperatures, insert a protective heat-isolation sheath.
ATTENTION !!! If the air intake and fumes
exhaust terminals are positioned in the same wall, they must remain at a minimum distance of 1 metre.
ATTENTION !!! The exhaust and intake pipes
must be appropriately sustained via rigid brackets positioned non more than 1 metre from each other. The
brackets must be xed to rigid walls that can support
the weight of the pipe itself.
Figure 5.16 - Fixing the exhaust and intake pipes
Figure 5.14 - Installation of the “80/80PP Split” System
Figure 5.15 - Clearance
5 - INSTALLATION
B
D
A
C
020002.01.011
Page 26
26
MYDENS
COSMOGAS
5.16.3 - “Split 80/80PP” System (Type C43; C53; C83): accessories available
To make the “80/80PP split” fumes exhaust/air intake system,
we propose some of the most common accessories available;
remember that a wide range can be consulted in the relevant catalogue: (the number after the code is used to recall the
piece in the following drawings)
62617306 - N° 10 PP coaxial roof terminal 62617244 - N° 12 90° bend M/F PP 62617255 - N° 29 converts for pitched roofs from 15° up to 25° 62617236 - N° 11 extension M/F PP 62617249 - N°18 anti-slip bands for extensions PP
62617240 - N° 14 exible hose M.F. PP L=20m 62617241 - N°16 spacer for exible hose
62617238 - N° 17 telescopic joint PP
62617242 - N° 15 T-tting PP
62617246 - N° 13 45° bend M/F PP
COD. 62617306
5 - INSTALLATION
Page 27
27
MYDENS
COSMOGAS
5.16.4 - “Split 80/80PP” System (Type C43; C53; C83): installation examples
In gure 5.17 two examples of installation are given:
- exhaust into chimney with collection of condensate inside
the boiler itself. The horizontal part of the fumes exhaust side must be inclined towards the boiler. The intake must slope towards the outside to prevent rain water entering.
- exhaust to the outside directly with the boiler pipes with
condensate collection inside the boiler itself. The intake must slope towards the outside to prevent rain water entering.
in gure 5.18 it is possible to see a separated type of fumes exhaust, where fumes exhaust was realised with exible hose
in polypropylene for piping of technical cells. The condensate produced in the vertical pipe must all be conveyed into the boiler. The intake must slope towards the outside to prevent rain water entering.
Figure 5.17 - Example of “80/80 PP System” installation
Figure 5.18 - Example of “80/80 PP System” installation
5 - INSTALLATION
Page 28
28
MYDENS
COSMOGAS
B
D
A
C
020002.01.012
5.16.5 - “60/100PP vertical coaxial” System (polypropylene) (C13; C33)
The appliance is supplied as per standard without ttings
for the connection of the fumes exhaust/air intake. To connect the boiler to a 60/100 coaxial system, the relevant
kit must be requested and must be installed as in gure
5.19.
ATTENTION !!! Scrupulously follow the installation
phases of the coaxial pipe as illustrated in gure 5.21. In
particular:
1.- introduce the coaxial pipe “C” inside the bend “A”;
2.- x the external pipe using the stainless steel self-threading
screws “B”.
ATTENTION !!! The coaxial exhaust and
intake pipes must be appropriately sustained via rigid brackets positioned non more than 1 metre from each
other. The brackets must be xed to rigid walls that can
support the weight of the pipe itself.
ATTENTION !!! Once these operations have
been performed, check that the exhaust/intake terminal is exposed to the outdoors with the tolerances given in
gure 5.25
Take particular care with the installation of pipes in the part
that passes through the wall to the outside. The normal
maintenance operations must always be possible, therefore
install the pipes in a sheath so that they can be slid out.
The horizontal tracts must always have an inclination of at
least 2% towards the boiler.
The fumes exhaust/air intake pipe can be extended up to
a maximum distance as indicated in the table in chapter
9 at the end of the manual. Every 90° bend has a loss
equivalent to 1 metre of linear pipe. Every 45° bend has a
loss equivalent to 0.5 m of pipe.
Figure 5.19 - Installation of vertical coaxial system
Figure 5.20 - Quotes and hole centre to centre distances for coaxial drain pre-installation
Figure 5.21 - Positioning the coaxial pipe
5 - INSTALLATION
Page 29
29
MYDENS
COSMOGAS
Figure 5.23 - Quotes and hole centre to centre distances for coaxial drain pre-installation
5 - INSTALLATION
Figure 5.24 - Positioning the coaxial pipe
5.16.6 - “60/100PP horizontal coaxial” System (polypropylene) (C13; C33)
The appliance is supplied as per standard without ttings
for the connection of the fumes exhaust/air intake. To connect it to a 60/100 coaxial system, the relevant kit must
be requested and must be installed as in gure 5.22.
ATTENTION !!! Scrupulously follow the installation
phases of the coaxial pipe as illustrated in gure 5.24. In
particular:
1. - introduce the coaxial pipe “C” inside the bend “A”;
2. - x the external pipe using the stainless steel self-threading
screws “B”.
ATTENTION !!! The coaxial exhaust and
intake pipes must be appropriately sustained via rigid brackets positioned non more than 1 metre from each
other. The brackets must be xed to rigid walls that can
support the weight of the pipe itself.
ATTENTION !!! Once these operations have
been performed, check that the exhaust/intake terminal is exposed to the outdoors with the tolerances given in
gure 5.25
Take particular care with the installation of pipes in the part
that passes through the wall to the outside. The normal
maintenance operations must always be possible, therefore
install the pipes in a sheath so that they can be slid out.
The horizontal tracts must always have an inclination of at
least 2% towards the boiler.
The fumes exhaust/air intake pipe can be extended up to
a maximum distance as indicated in the table in chapter
9 at the end of the manual. Every 90° bend has a loss
equivalent to 1 metre of linear pipe. Every 45° bend has a
loss equivalent to 0.5 m of pipe.
B
D
A
C
020002.01.013
Figure 5.22 - Installation of horizontal coaxial system
Page 30
30
MYDENS
COSMOGAS
5.16.7 - “60/100PP Coaxial” System: accessories available
The following accessories are available on request to make the 60/100 coaxial fumes exhaust/air intake system: (the number after the code is used to recall the piece in the
following drawings)
62617255 - N° 2 converts for pitched roofs from 5° to 25° extension L = 1000 mm 62617234 - N° 1 90° coaxial bend M/F PP 62617252 - N° 6 45° coaxial bend M/F PP 62617231 - N° 7 Coaxial extension L 1m PP 62617304 - N° 3 coaxial PP roof terminal 62617232 - N° 5 coaxial PP wall terminal
5 - INSTALLATION
Page 31
31
MYDENS
COSMOGAS
5.16.8 - “60/100PP Coaxial” System: installation examples
When a coaxial exhaust is made (see gure 5.25), both vertical
and horizontal, the exhaust pipe slope upwards in a way to
make the condensate ow into the boiler.
Figure 5.25 - Examples of coaxial pipe installation
5 - INSTALLATION
Page 32
32
MYDENS
COSMOGAS
6.1 - Operating
Before starting the appliance up, it is necessary to carry out the following.
6.1.1 - User instruction
Instruct the user regarding correct use of the appliance and the plant in general. In particular:
Give the installation and use manual and all
documentation contained in the packaging to the user.
Instruct the user concerning the special measures for the
exhaust of burned gases, informing them that they must
not be modied.
Inform the user regarding the control of the pressure
of the water required in the plant and the measures
necessary to ll and bleed the air.
Inform the user regarding the correct adjustment of
the temperatures, control units/room thermostats and radiators for energy saving.
6.1.2 - Filling the condensate drain siphon
IThe siphon found inside the boiler (see gure 3.1 detail “49”), must be lled with water to create the water head able to prevent the fumes escaping from pipe “F” in gure 5.5. Proceed as follows to do this: (refer to gure 6.1)
1.- loosen the screw “E”;
2.- remove the lid “D” and the gaskets “C”;
3.- introduce a rubber hose into the opening “B” (do not confuse with “A”) and the other end of the hose into the
funnel;
6 - OPERATING
Figure 6.1 - Filling the condensate drain siphon
4.- use the funnel to slowly pour about 200 cm³ (a glass) of water;
5.- re-mount everything in reverse order.
ATTENTION !!! If the boiler remains off for
more than 3 months, the siphon must be lled again as
explained above.
6.1.3 - Filling the central heating plant
If the word FILLappears on the visual display when the boiler is powered electrically, it means that the central
heating plant must be lled. Proceed as follows:
only use clean water from the network.
ATTENTION !!! The addition of chemical
substances such as anti-freeze must be performed in compliance with the product instructions. In all cases, these substances must not be introduced directly inside the boiler.
1.- open the ll cock positioned under the boiler (see gure
7.2 detail “A”) and ll the plant to about 1.5 bar (the word
FILL) will disappear from the visual display;
2.- make sure there are no water leaks from the ttings;
3.- close the ll cock (see gure 7.2 detail “A”);
4.- bleed the heating elements;
5.- check the pressure on the boiler display again. If it has
dropped, ll up to 1.5 bar again.
Page 33
33
MYDENS
COSMOGAS
6.2 - General recommendations
regarding the supply of gas
For commissioning of the boiler, have a professionally
qualied technician perform the following checks:
That the boiler is powered by the type of fuel for which it
is set-up.
That the gas supply pressure (with boiler operating
and at a standstill) is within the maximum and minimum
values indicated in the table in chapter 9 at the end of the manual.
That the supply plant has all safety and control parts
envisioned by the current national and local Standards.
That the fumes discharge terminal and the combustion
agent air intake terminal are free from any obstruction.
That the fumes exhaust and combustion agent air intake
terminal are positioned outside the building.
That the condensate drain connection is connected.
ATTENTION !!! If you smell gas:
A - Do not switch on any electric device, telephone
included or any object that can cause sparks;
B - Immediately open doors and windows causing
a current of air that quickly cleans the gas from the room;
C - From another room, or from a neighbour’s,
immediately call a professionally qualied
technician or the gas supply company. Call the Fire Service if the former are not available.
6.3 - Type of gas for which the
appliance is regulated.
There is a label on the front of the appliance certifying the gas supply type and pressure for which the boiler is adjusted. The boiler may have the following 2 types of wording:
2H-G20-20mbar NATURAL GAS
means that the appliance is adjusted to operate with H type
gas of the second family (natural gas) at a supply pressure
of 20 mbar.
3P-G31-37mbar LP GAS
means that the appliance is adjusted to operate with type P
gas (Propane, also called LP Gas) of the third family, at a
supply pressure of 37 mbar.
6 - OPERATING
Page 34
34
MYDENS
COSMOGAS
6.4 - Conversion of the appliance
from one type of gas to another
- Read these instructions carefully before
changing the gas:
- The gas appliance must be installed, calibrated or
modied by specialised staff in compliance with legal
terms;
- Check and be certain that the type of gas which is powering the appliance is compatible with the adjustment kit in your possession;
- Do not power the boiler with gases different from those envisioned.
Follow the instructions given below to change the gas: 1 - disconnect the electric power supply upstream from the
appliance;
2 - open the boiler casing as reported in chapter 8.2;
3 - access the control and command board as reported in
chapter 8.2;
4 - move the microswitch “B” of switch “A” from left to right
to the “ON” position (see gure 6.5);
5 - apply electric power to the boiler;
6 - the parameter 3001 will appear on the boiler’s visual
display, followed by its value;
7 - using the
and keys, access the
parameter 3002.
8. - press the RESET key to make the 3002 parameter
ash
9. - using the
and keys, set the value of
parameter 3002 to the new corresponding value
according to the table in gure 6.7 (for 15 kW also modify
parameter
2002 taking it to 50 as indicated in the
INSTALLER MENU chapter).
10. - press the RESET key to conrm the modication.
11.- remove voltage from the boiler, re-position the microswitch
“B” of switch “A” from right to left in “OFF” position (see gure
6.5).
12. - close the gas supply;
13. - remove the air manifold making sure to turn it
externally and then slide it out of the fan inlet (see gure
6.2, detail “C”);
15. - remove the gas inlet pipe via the two ttings (see gure 6.2, details “H” and “L”)
16. - remove the clamping spring “M” from the seat “N”
releasing the valve “P” (See gure 6.3, detail “M”)
17. - slide the gas valve “P” out upwards;
18. - replace the gas nozzle “R” (see gure 6.4) with an appropriate one according to that stated in gure 6.7 under “Diameter of the gas nozzle”;
19. - remount the gas valve (see gure 6.3, detail “P”),
making sure to reposition the spring “M”.
20. - remove the gas supply pipe via the two ttings (see gure 6.2, details “H” and “L”);
21. - re-mount the air manifold (see gure 6.2, detail “C”);
22. - open the gas cock;
23. - check for any gas leaks using the relevant means of control.
L
E
H
F
A
G
C
D
B
020002.01.040
N
P
M
Q
O
020002.01.041
R
020002.01.042
Figure 6.4 - Replacing the gas nozzle
Figure 6.3 - Removing the gas valve
Figure 6.2 - Removing the air manifold
6 - OPERATING
Page 35
35
MYDENS
COSMOGAS
ATTENTION !!! Perform the leak test using a soap
and water only.The use of naked ames is prohibited.
ATTENTION !!! If you smell gas:
A - Do not switch on any electric device, telephone
included or any object that can cause sparks;
B - Immediately open doors and windows causing
a current of air that quickly cleans the gas from the room;
C - From another room, or from a neighbour’s,
immediately call a professionally qualied
technician or the gas supply company. Call the Fire Service if the former are not available.
24.- Check the supply gas pressure, following the procedure
in chapter 6.6;
25.- Open the CO2 adjustment screw completely (see gure
6.14 detail “A”);
26.- Control and adjust the CO2, following the procedure in
chapter 6.8;
27.- Instead of the label that identified the old state of adjustment, apply the sticker onto the front casing of the
boiler (see gure 6.6), certifying the appliance’s new state
of adjustment, as follows: apply label “B” if the boiler has
been converted from natural gas to LP gas; apply label “A”
if the boiler has been converted from LP gas to natural gas.
A – Microswitch B - Switch
Figure 6.5 - Positioning the switch
A
B
020002.01.043
ON
OFF
6 - OPERATING
Model
Type
of gas
Setting
parameter
3002
Gas supply
minimum pressure
(mbar)
Gas supply
maximum
pressure
(mbar)
Gas nozzle
diameter
(mm)
CO2
Maximum
power
(%)
CO2
Minimum
power
(%)
O2
Maximum
power
(%)
O2
Minimum
power
(%)
15
MET 50 15 27 4,9 9,0 ±
0,3 8,5 ± 0,2 4,8 ± 0,2 5,5 ± 0,2
GPL 51 25 45 3,7 10,5 ± 0,3 10,0 ± 0,2 4,8 ± 0,2 5,6 ± 0,2
24
MET 50 15 27 4,9 9,0 ±
0,3 8,5 ± 0,2 4,8 ± 0,2 5,5 ± 0,2
GPL 51 25 45 3,7 10,5 ± 0,3 10,0 ± 0,2 4,8 ± 0,2 5,6 ± 0,2
34
MET 52 15 27 6,7 9,0 ±
0,3 8,5 ± 0,2 4,8 ± 0,2 5,5 ± 0,2
GPL 53 25 45 5,2 10,5 ± 0,3 10,0 ± 0,2 4,8 ± 0,2 5,6 ± 0,2
Figure 6.6 - Labels certifying the new status of adjustment of the boiler
Figure 6.7 - Correspondence table for the parameter 3002 and the operating values
Page 36
36
MYDENS
COSMOGAS
Figure 6.8 - Gas valve
A - Gas inlet pressure point.
6 - OPERATING
6.5 - Ignition
1.- open the gas cock;
2.- power the boiler electrically;
3.- adjust the temperature required from the heating service
using the
and keys. The icon , present on the display will inform regarding the operating state of the heating service:
a) xed icon
: central heating inactive (check that the room thermostat is in call mode or, in the case of external mode, that the external temperature is lower than the central heating switch-off external temperature
(par 2020);
b) ashing icon
: means that the central heating mode
is operating.
4. - adjust the temperature required for the domestic hot water
service using the
and keys. The icon , present on the display will inform regarding the operating state of the domestic hot water service:
a) xed icon
: domestic hot water inactive (no-one is withdrawing domestic hot water, or in the case of a indirect water heater, the delivery temperature is
reached)
b) ashing icon
: domestic hot water is being withdrawn.
5.- if the icon
ashes, but the radiators do not heat-up,
it may mean that the pump (see gure 3.1 detail “25”) is
blocked. It must be unblocked by operating on the relevant
screws. To do this remove screw “26” in gure 3.1 and turn the screw below to unblock the pump;
6.- if the icon
ashes but the radiator still does not heat
up, bleed the air from the radiators again.
6.6 - Controlling the supply gas pressure and any adjustment
The gas supply pressure must correspond to that stated in the table in chapter 9 at the end of the manual. Proceed as follows to verify:
1.- close the gas cock;
2.- access the components inside the boiler, following the
procedure in chapter 8.2;
3.- loosen the pressure point “A” (see gure 6.8);
4.- connect to a manometer with resolution of at least 0,1
mbar (1 mmH2O);
5.- open the gas cock;
6.- check that the pressure does not exceed the value given in the table in chapter 9 under “gas supply maximum
pressure”;
7.- make sure that any cocks and thermostatic valves
downstream from the central heating circuit are open;
ATTENTION !!! During forcing of the delivery
temperature, it automatically goes to 93°C to give the possibility to dispose of as much of the heat generated by the boiler as possible. Check that the central heating plant can support this temperature.
8.- press the
and RESET keys simultaneously
for more than 5 seconds to enter the “installer” menu,
conrmed by the appearance of the icon
on the
display.
9.- using the
and keys, access the
parameter 2010;
10.- press the RESET key to enter the parameter and use the
and keys to modify the value to HIgH;
11.- press the RESET key to conrm the modication. Now
the burner will operate at maximum power for 10 minutes.
12.- check that the pressure does not drop to a value lower than the “gas supply minimum pressure” given in the table in chapter 9. If the supply pressure does not respect the values described, operate upstream from the appliance in order to take it back within the minimum and
maximum eld;
13.- once the control has ended, press the RESET key
again to enter parameter
2010 and via the
and
keys, change the value to OFF;
14.- press the RESET key to conrm the modication;
15.- hold the RESET key down for 5 seconds to exit the
“installer” menu;
16.- close the pressure point “A” in gure 6.8;
17.- check for any gas leaks from the point with relevant control methods.
ATTENTION !!! Perform the leak test using a soap
and water only. The use of naked ames is prohibited.
A
020002.01.023
Page 37
37
MYDENS
COSMOGAS
Figure 6.9 - Combustion agent air pressure point
Figure 6.11 - Controlling combustion agent air pressure
6.7 - Controlling the combustion
agent air pressure
As the boiler has an air/gas ratio xed in the factory, the gas
pressure at the burner is controlled indirectly by measuring the pressure of the combustion agent air inside the boiler and must correspond to that stated in the table in chapter 9, under “Combustion agent air pressure”. Proceed as follows for the check (refer to the Figures from
6.9 to 6.12):
1.- use a differential manometer with precision of at least 0.1
mbar (1 mmH2O);
2.- close the gas cock;
3.- open the boiler casing following chapter 8.2;
4.- remove the caps “A” (see gure 6.9);
5.- take the exible hose “D”, which is found inside the appliance and remove the cap “B” (see gure 6.9);
6.- insert the pipe “D” inside the hole indicated by the arrow
in gure 6.9;
7.- loosen the pressure point “H” in gure 6.10;
8.- take a silicone pipe with external diameter of 10 mm and
internal diameter of 7mm (detail “E” in gure 6.10) and introduce it into pressure point “H”;
9.- inserire il tubo “E” nel foro come indicato in gure 6.11;
10.- connect the manometer to the two pipes “E” and “F” as
illustrated in gure 6.12, making sure to connect the pipe “E”
to the negative pressure point and tube “F” to the positive
pressure point;
11.- close the casing “B” in gure 8.1. It is indispensable
to have a reliable measurement;
12.- switch the boiler on;
13.- press the
and RESET keys simultaneously
for more than 5 seconds to enter the “installer” menu,
conrmed by the appearance of the icon
on the
display.
14.- using the
and keys, access the
parameter 2010;
15.- press the RESET key to enter the parameter and use
the
and keys to modify the value to FAn;
16.- press the RESET key to conrm the modication. Now
the fan will operate at maximum speed for 10 minutes.
17.- compare the pressure value read on the manometer with that given in the table in chapter 9, “Combustion agent air pressure”. If the pressure is at a lower value, check that there are no obstructions in the combustion agent air/fumes exhaust or that the air intake/fumes exhaust system is not longer than envisioned in chapter 9 under “Max. length of
fumes pipe”;
18.- once the control has ended, press the RESET key
again to enter parameter
2010 and via the
and
keys, change the value to OFF;
19.- press the RESET key to conrm the modication;
20.- hold the RESET key down for 5 seconds to exit the “installer” menu.
At the end of the control, remove the tube “E”, close the holes “A”, close the pipe “D” using cap “B” and close the
pressure point “H” again as in gures 6.9 and 6.10.
6 - OPERATING
D
A
C B
020002.01.019
D
C
E
F
020002.01.020
Figure 6.10 - Combustion agent air pressure point
H
E
020002.01.022
Page 38
38
MYDENS
COSMOGAS
Figure 6.13 - Combustion analysis points
6.8 - Controlling the level of
CO2 and any adjustment
The boiler in normal operating mode and for altitudes within 1000
m, has a level of CO2 (carbon dioxide) in the fumes, which can be
detected in the table in chapter 9. A value different to those reported can cause malfunctions. Combustion analysis must be performed to check and eventually adjust this value. Proceed as follows:
1.- check a combustion analyser to the appropriate point on
the fumes exhaust tting “B” in gure 6.13;
2.- make sure that any cocks and thermostatic valves
downstream from the central heating circuit are open;
ATTENTION !!! During forcing of the delivery
temperature, it automatically goes to 93°C to give the possibility to dispose of as much of the heat generated by the boiler as possible. Check that the central heating plant can support this temperature.
3.- press the
and RESET keys simultaneously
for more than 5 seconds to enter the “installer” menu,
conrmed by the appearance of the icon
on the
display.
4.- using the
and keys, access the
parameter 2010;
5.- press the RESET key to enter the parameter and use the
and keys to modify the value to HIgH;
6.- press the RESET key to conrm the modication. Now
the burner will operate at maximum power for 10 minutes.
7.- wait for the CO2 measurement to stabilise;
8.- compare the value measured with that given in the
table in gure 6.7, “CO2 maximum power”. If the value
measured is offset from the value read, it must be taken
back within the value given in the table in gure 6.7.
Proceeding as follows:
a) turn screw “A” clockwise as in gure 6.14 to decrease
the level of CO2;
b) turn screw “A” anti-clockwise as in gure 6.14 to increase
the level of CO2;
9.- once the check has been completed, seal the screw “A” in
gure 6.14 with red paint or similar system;
10.- press the RESET key again to enter the parameter
2010 and use the and keys to modify
the value to
LOu;
11.- press the RESET key to conrm the modication. Now
the burner will operate at minimum power for 10 minutes.
12.- wait for the CO2 measurement to stabilise;
13.- compare the value measured with that given in the
table in gure 6.7, “CO2 minimum power”.
If the value measured is offset from the value read, it must
be taken back within the value given in the table in gure
6.7. proceeding as follows:
a) turn screw “B” anti-clockwise as in gure 6.14 to decrease
the level of CO2;
b) turn screw “B” clockwise as in gure 6.14 to increase
the level of CO2;
14.- Once the check has been completed, seal the screw “B”
in gure 6.14 with red paint or similar system;
15.- press the RESET key again to enter the parameter
2010 and use the and keys to modify
the value to
OFF;
16.- press the RESET key to conrm the modication.
17.- hold the RESET key down for 5 seconds to exit the “installer” menu.
6 - OPERATING
B
A
C
D
E
020002.01.015
Figure 6.14 - Gas valve
A - CO2 adjustment screw at maximum power; B - CO2 adjustment screw at minimum power;
A
B
020002.01.045
E
F
G
020002.01.021
Figure 6.12 - Controlling combustion agent air pressure
Page 39
39
MYDENS
COSMOGAS
Figure 6.15 - Corresponding values to introduce
into the parameter
2002 to obtain the desired
power necessary in central heating mode
6 - OPERATING
Figure 6.16 - domestic hot water ow rate selector
A
020002.01.016
BOILER MODEL
Power
necessary
(kW)
15 24 34
35 33 94 31 88 29 82 27 76 25 98 70 23 89 64 21 80 58 19 71 52 17 62 46 15 53 40 13 44 44 34 11 35 35 28
9 26 26 22 7 17 17 16 5 8 8 10
ATTENTION !!! If during forcing, the power
supplied by the boiler is much higher than the power absorbed by the plant, the boiler switches off continuously to reach the maximum temperature allowed (93°C). To remedy this problem the heating power must be set at the effective plant requirement, as laid down in chapter 6.9 and the CO2 analysis test or
combustion efciency test must be carried out, setting
parameter
2010 previously referred to at the rEg.
value
6.9 - Adjusting the power in central
heating mode (Range Rated)
This appliance is designed and type-approved to adapt the maximum heating power to the effective necessity of the plant as per calculation. To do this and to use the boiler’s potentiality to its best, it is recommended to set the maximum power in central heating mode at the effective requirement of the plant. Operate as follows:
1.- press the
and RESET keys simultaneously
for more than 5 seconds to enter the “installer” menu,
conrmed by the appearance of the icon
on the
display.
4.- using the
and keys, access the
parameter 2002;
5.- press the RESET key to enter the parameter and using the
and keys modify the value corresponding to the power required by the plant, according to the table in Figure 6.15.
6.- press the RESET key to conrm the modication.
7.- hold the RESET key down for 5 seconds to exit the “installer” menu.
6.10 - Adjusting the domestic
hot water ow rate
The boiler is supplied with a domestic hot water maximum
ow rate adjuster. However, if the boiler is installed in a
geographical area where the temperature of the cold water
is very low, the ow rate of domestic hot water that passes
inside the boiler may have to be reduced. It is therefore good practice to perform this adjustment:
1.- switch the boiler on;
2.- using the
and keys, adjust the
temperature of the domestic hot water to 48 - 50°C;
3.- open the hot water cock completely.
In the case of a single lever mixer, the position must be
completely on “HOT”;
4.- wait 3 minutes for the temperature to stabilise;
5 - if the water temperatures too cold, the ow rate must
be reduced via the selector “A” in gure 6.16, until the
desired temperature is reached.
Page 40
40
MYDENS
7.1 - Controlling cock opening
- The gas cock must be open;
- Any valves positioned on the supply and return must be open;
- Any valves positioned on hot and cold water, must be open.
7.2 - Checking central
heating plant pressure
If the pressure inside the central heating circuit drops below
0.5 bar, the visual display “N” in gure 7.1, shows FILL
to indicate that the correct pressure must be restored. Proceed as follows:
1.- pull the knob “A” in gure 7.2 downwards;
2.- open the ll cock turning the knob anti-clockwise to ll the plant;
3.- check the pressure on the visual display “M” in Figure
7.1, it must reach the pressure of 1 - 1.5 bar (the FILL
indication disappear on exceeding 0.8 bar);
4.- close the ll cock (see knob “A” in gure 7.2), turning it
clockwise.
In some boiler models the plant ll knob “A” in gure 7.2
may be absent. Therefore operate on the device envisioned by the installer upstream from the boiler itself.
ATTENTION !!! During normal operation, the
ll cock “A” (see gure 7.2) must always remain in the
closed position.
If the pressure drops through time, restore the correct value. This operation may have to be repeated several
times in the rst month of operation to remove any air
bubbles in the plant.
COSMOGAS
7 - USE
Figure 7.1 - Control board
Key for gure 7.1
A - Key for reducing the central heating temperature (below
minimum the central heating is put in OFF)
B - Reset Key C - Key for switching-on and increasing the heating
temperature
D - Burner status (the burner is on when this con is present)
E - Status of the heating service: Icon off = Central heating off Icon on = Central heating active but not operating
Icon ashing
= Central heating active and operating F - State of the domestic water service: Icon off = Domestic water off Icon on = Domestic hot water active but not operating
Icon ashing
= Domestic hot water active and operating G - Icon for entry into the “Installer” menu H - Unit of measurement of the pressure displayed L - Status of the cascade pump (if the icon is present, the
pump is on)
M - Central heating plant pressure or indicator of the
various parameters inside the various menus
N - Temperature of the central heating or domestic hot
water or indicator if the values assumed by the various
parameters O - Unit of measurement of the temperature displayed P - Central heating service adjusted by the external sensor Q - Boiler blocked (see chapters 7.19.1 and 7.19.2 for the
diagnostics)
R - Key for switching on and increasing the temperature of
the domestic hot water or for scrolling and changing the
value of the parameters S - Key for reducing the temperature of the domestic
hot water (below minimum, the domestic hot water is
switched OFF) or for scrolling and changing the value of
the parameters T - On/off switch
Page 41
41
MYDENS
7.3 - Generalities
During operation the display shows the boiler operating state as well as other information as indicated in chapter
7.19 (Diagnostics).
Other parameters can be consulted through the
“User menu” (see chapter 7.17), which are useful for
understanding operation of the appliance and to control the latest blocks or errors occurring. After 5 minutes of normal operation, the display switches off completely to save energy. Just press any key to switch it back on. In the case of any anomaly, the display switches back on
automatically. This function can be modied by following chapter 7.16 (Energy saving).
7.4 - Ignition procedure
1.- open the gas cock;
2.- power the boiler electrically;
3.- adjust the domestic hot water temperature and of the central heating respectively as per chapters 7.8 and 7.9.
The command and control equipment will switch the burner on. If ignition does not take place within 20 seconds, the boiler automatically re-attempts ignition 3 times, after which if it still
does not ignite, it blocks and the display will indicate Loc 1. Press the RESET key to restore the normal operating conditions. The boiler will automatically attempt a new ignition.
ATTENTION !!! If shutdown due to blocking is
repeated frequently, contact a qualied technician to reset
the normal operating conditions.
Once the boiler has been ignited correctly, it will continue to operate for the service requested.
7.5 - “User menu”
Entry into the “User menu” is highlighted by the visual display
“M”, in gure 7.1, which indicates parameters that can assume
values from 1001 to 1999. To enter the “User menu”:
1.- hold the RESET key down for 2 seconds until the visual
display “M” shows 1001;
2.- press the
and keys to scroll the parameters
situated inside the user menu;
3.- hold down the RESET key for more than 2 seconds to
exit the “User menu”;
If no key is pressed for more than 60 seconds, the menu is exited automatically. The parameters in chapter 7.17 can be queried in this menu.
7.6 - Summer operating mode
Whenever the central heating function is to be interrupted for a long period of time, leaving only the domestic hot water function operating, adjust the central heating temperature to
minimum using the
or keys until
the word
0FF appears.
7.7 - Winter operating mode
In winter operating mode, using the pump, the boiler sends
the water to the plant at the temperature set using the
or
keys.
When the temperature inside the boiler approaches the
temperature set, the burner starts to modulate the ame until
the power is reduced to the effective requirement of the plant. If the temperature tends to rise further, the burner stops. At the same time, the pump that sends water to the plant is switched on and off by the room thermostat. This can be
noted because the
indicator ashes when the pump is
on, while it remains on with a xed light when the pump is off.
The pump may initially make a noise. This is due to the presence of residual air in the hydraulic plant, which will disappear quickly, without any intervention. For rational use of the boiler, it is recommended to keep the
central heating temperature, adjusted using the
or
keys, at the lowest value possible, compatibility with the temperature requested in the rooms. If the winter season is particularly cold, meaning the room temperature can no longer be maintained, raise the central heating temperature to higher values.
Figure 7.2 - Plant ll cock
B A C
02002.01.044
Key for gure 7.2
A = Plant ll knob
B = Closing direction C = Opening direction
COSMOGAS
7 - USE
Page 42
42
MYDENS
COSMOGAS
7.8 - Adjusting the instantaneous domestic hot water
The temperature of the domestic hot water is adjusted by
operating on the
and keys. On pressing one
of the two keys, the visual display “N” in gure 7.1 will start to ash and show the temperature that is being set. The range
of adjustment for the temperature of the domestic hot water goes from 40°C to 60°C or from 40°C to 70°C if there is a indirect water heater present.
By holding the
key down also below 40°C, OFF will
appear to indicate switch-off of the domestic hot water service,
also highlighted by switch-off of the icon “F” in gure 7.1.
7.9 - Central Heating
Using the parameter 2003 present in the “Installer menu”
(see chapter 7.18) it is possible to select different operating
modes of the central heating service:
-
2003 = 00; “Thermostatic adjustment”: the central heating
supply temperature is adjusted manually via the
or keys . The opening and closing of the room thermostat stops or starts the boiler pump correspondingly
in order to adjust the room temperature;
-
2003 = 01; “Climatic adjustment”: The icon appears on
the display
, the supply temperature to central heating is adjusted automatically by the external temperature sensor according to the algorithm corresponding to Figure 7.3. The opening and closing of the room thermostat stops or starts the boiler pump correspondingly. When the external
temperature rises above the value set in parameter 2020
(Central heating switch-off external temperature), the
central heating service ends. It re-starts automatically when the external temperature drops below the temperature set
in the parameter 2020 again.
- 2003 = 02; “Climatic adjustment with room compensation”:
Th e icon
appears on th e dis pla y, the supply temperature to central heating is adjusted automatically by the external temperature sensor according to the algorithm corresponding to Figure 7.3. The opening of the room thermostat reduces the temperature if the supply to central
heating by a value set in the parameter 2027 The boiler pump operates constantly. When the external temperature
rises above the value set in parameter 2020 (forced
central heating switch-off), the central heating service ends.
It re-starts automatically when the external temperature drops below the temperature set in the parameter 2020
again (forced central heating switch-off).
7.10 - Thermostatic adjustment
In the factory the boiler is adjusted with the parameter 2003 to 00, i.e. the boiler supplies hot water to the central heating
plant at a temperature adjusted using the or
keys. Any room thermostat operates directly on the pump inside the boiler to adjust the heating of the rooms. To make full use of boiler performance, it is recommended
to adjust the temperature to a value just sufcient to obtain
the temperature desired by the rooms. If the season gets colder, progressively increase the value of the central heating temperature. Proceed in reverse order when the season goes towards warmer temperatures. This very simple operating method is suitable for the following types of plants:
- small plants, with radiators, having a room whose temperature
is characteristic of all other rooms;
- large plants, with radiators, where each area is controlled by its own room thermostat and the boiler pump is stopped
only when all area thermostats are satised (envision the appropriate electric plant).
- large plants, with radiant panels (low temperature), where
each area is controlled by its own room thermostat and the boiler pump is stopped only when all area thermostats are
satised (envision the appropriate electric plant).
7.11 - Climatic adjustment
Using the “Installer menu” adjust the parameter 2003 to
01. The central heating supply temperature is reported to
the external temperature sensor according to the algorithm in
gure 7.3. To adapt the calculation line to the various hones/
climatic conditions, all adjustment parameters must be set according to the following chapters.
7.11.1 - Climatic adjustment: on which
plants?
The “Climatic adjustment” is a more sophisticated and precise adjustment than the “Thermostatic adjustment”. This can make the most use of the boiler performance and is suitable for the following types of plant:
- small plants, with radiators, having a room whose temperature is characteristic of all other rooms. The room thermostat makes the appropriate corrections to the room temperature by switching the boiler pump on and off.
- large plants, with radiators, where each area is controlled by its own room thermostat and the boiler pump is stopped
only when all area thermostats are satised (envision the appropriate electric plant).
- small plants, with radiant panels (low temperature), having a
room whose temperature is characteristic of all other rooms. The room thermostat makes the appropriate corrections to the room temperature by switching the boiler pump on and off.
- large plants, with radiant panels (low temperature), where
each area is controlled by its own room thermostat and the boiler pump is stopped only when all area thermostats are
satised (envision the appropriate electric plant).
7 - USE
Page 43
43
MYDENS
COSMOGAS
7.11.4 - Climatic adjustment: adaptation to
different climatic areas
The previously recommended values are for homes with average insulation and for climatic areas where the external temperature used for calculating heat requirement is
-5°C (with this data and a high temperature plant, there is
correspondence with the graphics in Figure 7.3). If the climatic
area is different, adjust parameter 2021 “Design external
temperature (winter)” in a way to obtain a supply temperature of 67°C (40°C in the case of “Low temperature” plants), when
the external temperature is that of the calculation base of the heat requirement.
7.11.5 - Climatic adjustment: switching the
central heating service on and off
The climatic adjustment service is completely automatic, also regarding switch-off at the end of the season and successive switch-on at the start of the next season via the parameter
2020. When the external temperature rises above the value
set in this parameter, the heating switches off automatically. When the external temperature drops back below the value set in this parameter, the central heating service switches back on automatically.
7.11.6 - Climatic adjustment with room
compensation
Using the “Installer menu” (see chapter 7.18) adjust the
parameter 2003 to 02. Everything operates exactly as in the previous chapters relative to the “Climatic adjustment”, with the difference that now the boiler pump is always on. The opening of the room thermostat contact translates into a parallel downward movement of the line regarding the value
set on the parameter, as in gure 7.3 2027 ppresent in the “Installer menu” (see chapter 7.18). Parameter 2027
can assume values between 0°C and 50°C. The values recommended for this parameter are:
- 10°C for high temperature plants (radiators)
- 3°C for low temperature plants (oor).
Values of this parameter that are too high can translate into instability of the room temperature. Values that are too low can make the room thermostat ineffective.
The climatic adjustment with room compensation can be used in all cases envisioned in chapter 7.11.1, with the advantage that continuous operation of the pump manages to stabilise
and make the room temperatures uniform; especially in the case in which several heat plant loops have the ow
resistances that are much higher than others.
7.11.2 - Climatic adjustment: precautions during adjustment
To set the supply temperature correctly, it is good practice to
immediately set the line setting values in gure 7.3. If these
values do not give a satisfactory result, proceed with the
relevant modications, keeping in mind that:
- every parameter must be adjusted in small degrees;
- after each change, wait at least 24 hours to see the result;
- the more the adjustment line app roach es the real requirements of the building, the more building central heating will be comfortable and the greater the energy
saving will be;
- using the or keys, it is possible to make the
small corrections highlighted in gure 7.3, i.e. move the
parallelism of the line, in steps of 1 °C more or less, up to 10°C.
7.11.3 - Climatic adjustment: setting the
parameters
Using the “Installer menu” (see chapter 7.18), set:
- 2020 = “External switch-off temperature of the central heating”, adjustable between 0 and 35°C. When the external temperature reaches the value set in this parameter, the central heating is switched-off automatically. The central heating switches back on automatically when the external temperature drops back below this value. The recommended start value is 22°C.
- 2021 = “Design external temperature (winter)”, adjustable
between -20 and 5°C. It is the design external temperature
used to dene the heat output necessary at the plant. The value recommended for a typical home is -5°C;
- 2022 = “Supply temperature corresponding to the design
external temperature (winter)”, adjustable between 0 and
80°C. The supply temperature assumes the value set in this parameter when the external temperature corresponds
to that set in parameter 2021. The recommended start
values are: 40°C for low temperature plants (oor heating); 67°C for high temperature plants (radiators);
- 2023 = “External spring-like temperature”, adjustable between 0 and 30°C. It is the external temperature at which the central heating is to reach the minimum supply
temperature. The recommended start value is 18°C;
- 2024 = “Supply temperature corresponding to the external spring-like temperature”, adjustable between 0 and 40°C. The supply temperature assumes the values set in this parameter, when the external temperature corresponds to
that set in the parameter
2023. The recommended start
values are: 30°C for low temperature plants (oor heating); 42°C for high temperature plants (radiators);
- It is always possible to set the minimum and maximum central heating temperatures using the respective parameters
3016 and 3015 present in chapter 11.
7 - USE
Page 44
44
MYDENS
COSMOGAS
Figure 7.3 - Climatic adjustment graphics for “high temperature” plants (with radiators)
External temperature (°C)
Calculated temperature (°C)
Par. 2020 = External temperature for central heating switch-off Par. 2021 = Project external temperature (winter) Par. 2022 = Supply temperature corresponding to the project external temperature (winter) Par. 2023 = Spring-like external temperature Par. 2024 = Supply temperature corresponding to the spring-like external temperature Par. 3016 = Minimum supply temperature Par. 3015 = Maximum supply temperature
= Line parallelism increase key
= Line parallelism decrease key
7 - USE
Par. 2021
Par. 2023
Par. 2020
Par. 3016
Par. 2024
Par. 2022
Par. 3015
Page 45
45
MYDENS
COSMOGAS
7.12 - Timers of the various functions
To safeguard the lifespan of the appliance, improve the comfort generated and increase energy saving, timings have been introduced during operation. These timings are:
- Pump post-circulation: every time that the room thermostat determines the end of the central heating service, the pump
continues to operate for 3 minutes;
- Central heating delay: every time that the domestic hot water
service nishes, before reactivation of the central heating service there is a stand-by period of 2 minutes;
- Pumps anti-block and diverter valve: every 24 hours, the central heating pump, the domestic hot water pump (if
present) and the diverter valve are forced;
- Anti-legionella; if the boiler is connected to a indirect water
heater for preparation of the DHW., every seven days the latter is forced to a temperature of 60°C to disinfect against the legionella bacteria. This function activates also due hours after the boiler has been powered electrically.
- Ignition delay: In all operating modes, excluding domestic hot water mode, wait 3 minutes to ignite the burner again when it switches off.
7.13 - Pumps anti-blocking
and diverter valve
The pump switches on once every 24 hours for 15 seconds during the summer period in order to prevent any deposits that may block it. The diverter valve and the indirect water
heater pump (if present) are activated at the same time for
the same reason.
7.14 - Anti-freeze protection
ATTENTION !!! For the anti-freeze protection
to be effective, the appliance must be left with electric power supply and gas supply present and the two services (domestic hot water and central heating) in the
OFF position.
ATTENTION !!! The anti-freeze protection
service offered by the boiler cannot guarantee the anti-freeze protection of the central heating plant, the domestic hot water plant or the building served or part of the same.
The central heating pump starts automatically when the boiler temperature reaches 10°C. If the temperature drops further below 5°C, the burner also ignites in a way to protect the boiler from the effects deriving from freezing.
If the boiler is not used for a long period of time (over a year),
it is recommended to empty it following the procedures in chapters 8.16 and 8.17.
7 - USE
7.15 - Automatic plant
lling (on request)
Normally the appliance is supplied with a manual cock for
lling the central heating plant. On request, the boiler can be manufactured with the automatic plant ll.
7.16 - Energy Saving
To reduce the consumption of display energy, it will switch off automatically after 5 minutes from the last operation performed. This function can be deactivated or the time
modied via parameter 2100 present in the “Installer menu”.
If the parameter is set at OFF, the display will remain on constantly.
Page 46
46
MYDENS
COSMOGAS
7 - USE
Parameter Description of the parameter M.U. 1001 Central heating supply temperature °C 1002 Domestic hot water temperature (or indirect water heater temperature, if present) °C 1003 No function / 1004 External temperature (visible when an external temperature sensor is installed) °C 1005 Central heating supply temperature (safety sensor) °C 1006 Fumes temperature °C 1007 Central heating return temperature °C 1008 Ionisation current uA 1009 Status of the pump inside the boiler ON/OFF 1010 Status of the central heating side diverter valve
(ON = in central heating mode; OFF = in domestic hot water mode)
ON/OFF
1011 Status of the central heating side diverter valve (ON = in D.H.W. mode; OFF = in central heating mode) ON/OFF 1012 Central heating supply temperature calculated via the external sensor °C 1013 Status of the room thermostat contact
(OPEN = no central heating request; CLOSED = presence of central heating request)
OPEN/CLO-
SED 1014 Fumes temperature (safety sensor) °C 1040 Current rotation speed of the fan rpm 1041 Fan rotation speed on ignition rpm 1042 Fan rotation speed in minimum power mode rpm 1043 Fan rotation speed in maximum power mode rpm 1051 Latest block condition recorded (Loc) (see chapter 7.19.1) / 1052 Latest error condition recorded (Err) (see chapter 7.19.2) / 1053 Number of times the burner has lost the ame n° 1055 Number of failed burner ignitions n° 1056 Number of hours worked in central heating mode h x 10 1057 Number of hours worked in domestic hot water mode h x 10 1058 Numero di giorni di lavoro del bruciatore days 1059 Interval of time between the last two blocking errors (Err)
1 value in minutes; 2 value in hours;
3 value in days; 4 value in weeks;
1060 Interval of time between the last two blocks (Loc)
1061 Current rotation speed of the domestic hot water turbine rpm 1062 Current domestic hot water ow rate l/min
7.17 - “User menu”
Press the RESET key for 2 seconds to access the “User
menu”. The visual display “M” in gure 7.1, starts to show
parameter 1001 to inform the use of the mode change.
Using the
and keys, scroll the parameters contained in the menu. Just press the RESET key again for 2 seconds to exit the menu. The parameters in this menu are display only and cannot be
modied via the same.
If no key is pressed for more than 60 seconds, the menu is exited automatically. The following parameters can be queried in this menu:
Page 47
47
MYDENS
COSMOGAS
7.18 - “Installer menu”
ATTENTION !!! The modication of these
parameters could cause the boiler, and therefore the plant, to malfunction. For this reason only a technician that has the awareness and in-depth knowledge of the appliances can modify them.
The boiler command and control board makes this parameter menu available to the technician, for the analysis of operation and adaptation of the boiler to the plant. Proceed as follows to enter the “Installer menu”:
1.- hold the RESET and
keys down simultaneously
for 5 seconds until the
2001 parameter is displayed.
The symbol
appears on the display to indicate the
entry into the “Installer menu”.
2.- the
and keys can be used inside the
menu to scroll the parameters:
3.- once the parameter of interest has been displayed, it
can be modied as follows:
a.- press the RESET key to access the parameter (the
visual display “N” in gure 7.1 will start to ash);
b.- modify the value of the parameter using the
and
keys;
c.- press the RESET key to conrm the data modied
and go back to the list of parameters;
4.- To exit the “Installer menu”, hold down the RESET key
for 5 seconds until the symbol
disappears from the
base of the display.
If no key is pressed for more than 5 minutes, the menu is
exited automatically.. Any data variation that is not conrmed
with the RESET key will be lost.
ATTENTION !!! Any variation to the
parameters must be noted in the “Customised values” column present in the following table in order to facilitate the eventual replacement of the command and control board.
The following parameters can be changed or queried in this menu:
7 - USE
Parameter Description of the parameter U.M. Setting range
Factory
value
Custo­mised values
2001 Central heating minimum power level % From 1 to 50 1
2002 Central heating maximum power level % From 1 to 100 100
2003 Central heating operating mode nn 00 = Central heating with room
thermostat 01 = Central heating with room thermostat and climatic adjustment 02 = Central heating with total climatic adjustment 03 = Permanent central heating
00
2004 Stand-by time after maximum differential sec From 0 to 30 10
2005 Post-circulation in central heating mode sec From 10 to 900 120
2010 Forcing of fan and burner / OFF = No forcing
FAN = Forcing of fan only to max speed LOu = Forcing of burner to minimum power Ign = Forcing of burner to igni­tion power HIgH = Forcing of burner to maximum power rEg = Forcing of the burner to the power adjusted in central heating mode (Par.2002)
OFF
2011 Forcing the pump / On = Pomp on
OFF = Pomp off
OFF
2012 Forcing of the domestic central heating side diverter valve / ON = in central heating mode;
OFF = in domestic hot water mode
OFF
2013 Forcing of the domestic hot water side diverter valve / ON = in domestic hot water mode;
OFF = in central heating mode
OFF
Page 48
48
MYDENS
COSMOGAS
7 - USE
2014 Icons test on the display. By pressing the RESET key, all of the
icons on the display light up. By pressing the RESET key again to display goes back to normal operation
/ / /
2020 Climatic adjustment: external temperature for central heating
switch-off
°C From 0 to 35 22
2021 Climatic adjustment: design external temperature (winter) °C From -20 to 5 -5
2022 Climatic adjustment: supply temperature corresponding to the
design external temperature (winter)
°C From 0 to 80 80
2023 Climatic adjustment: external spring-like temperature °C From 0 to 30 20
2024 Climatic adjustment: supply temperature corresponding to the
external spring-like temperature
°C From 0 to 40 40
2027 Temperature reduction by room thermostat opening °C From 1 to 50 10
2040 Climatic adjustment: central heating boost temperature °C From 0 to 20 0
2041 Climatic adjustment: central heating boost time min From 0 to 30 20
2042 Protection against frequent switch-on in central heating mode:
time
sec From 10 to 900 180
2043 Protection against frequent switch-on in central heating mode:
temperature differential
°C From 0 to 20 16
2060 Domestic hot water minimum power level % From 1 to 50 1
2061 Domestic hot water maximum power level % From 1 to 100 100
2062 Post-circulation in domestic hot water mode sec From 10 to 900 120
2063 Maximum time for lling indirect water heater min From 0 to 60 60 /
2064 Number of ow meter revs. for every litre of water rpm/lt From 0 to 5 3,2
2066 Delay in the detection of the instantaneous domestic hot water sec From 1 to 10 3
2067 Indirect water heater lling procedure / 0 = The indirect water heater
is lled for the time set in the
parameter 2063; 1 = OFF, the domestic hot water does not have priority over heating; 2 = ON, the domestic hot water always has priority over heating;
2
2080 Periodic maintenance meter
(after RESET, the meter automatically goes back to ON)
/ ON = Periodic maintenance
meter active; OFF = Periodic maintenance meter off; RESE = Meter reset
OFF
2081 Periodic maintenance meter: maintenance request time days From 0 to 1000 1000
2100 Energy saving display min OFF = display always on
From 1 to 30 = delay to switch­off in minutes.
5
Page 49
49
MYDENS
COSMOGAS
7.19 - Diagnostics
During normal appliance operation, the visual display “N”
in gure 7.1, continuously shows the working status of the
appliance via the following indications:
7 - USE
Parameter Description of the parameter Display on visual display “N” in gure 7.1
AFro
Anti-freeze function active Boiler temperature (°C)
AttE
Boiler not in block but in attention mode Attention code (see chapter 7.19.3 for decoding)
FILL
Plant pressure too low, perform lling (see chapter 6.1.3) FILL
Fixed on = Domestic hot water service on but not active
On ashing = Domestic hot water service on and active
Domestic hot water temperature (°C)
Fixed on = =Central heating service on but not active
On ashing = =Central heating service on and active
Central heating temperature (°C)
Loc
Boiler blocked. To reset, press RESET. If the block occurs
frequently, contact a professionally qualied technician.
Block code (see chapter 7.19.1 for decode)
Err
Boiler in error mode. Functioning can only be restored by solving the cause of the anomaly. Contact a professionally
qualied technician
Error code (see chapter 7.19.2 for decode)
ALEg
Anti-legionella function running (see chapter 7.12). It will end on reaching the water temperature of 60°C inside the indirect water heater.
Indirect water heater temperature (°C)
SEr
Maintenance request for the boiler Appliance temperature (°C)
Page 50
50
MYDENS
COSMOGAS
7.19.1 - Diagnostics: blocks “Loc”
Block Description of block Checks Solutions
Loc 0 Internal memory error
E2prom at command board
Replace the command and control board.
Loc 1 No ame detection after
three successive ignition attempts.
Control: Supply gas pressure (see chapter 6.6), sparks on the ignition electrodes (see chapter
8.5);correct combustion agent air pressure (see chapter 6.7); 220 Vac electric power supply to the gas valve; electric resistance of the two gas valve coils of 0.88 Kohm and 6.59 Kohm
If the burner switches on and switches off at the end of the ignition attempt, check: that the ionisation current is at a value over 60 (follow the procedure in chapter 8.20)
If the supply pressure is not correct, operate upstream from the appliance to restore it; if the pressure of the combustion agent air is not correct, operate on the air intake/fumes exhaust circuit to eliminate any obstructions. If the current at the gas valve is not 230Vac, the command and control board must be replaced. If the electric resistance of the gas valve is not 0.88 Kohm and 6.59 Kohm, the valve must be replaced.
If the ionisation current is not over 60, the CO2 must be checked (follow chapter 6.8) and restore its correct value, check the ionisation electrode and replace it if necessary. Check the integrity of the ionisation current electric circuit cables.
Loc 2 Gas valve command relay
broken
Replace the command and control board.
Loc 3 I nter n al saf ety rel a y
failure at command board
Check the appliance earth. If the earth is good, replace the command and control
board.
Loc 4 Boiler in error mode for
more than 20 hours
Control the last error displayed in the board. Operate according to the last error displayed.
Loc 5 Fan out of speed for
more than 60 seconds
Control it is powered at 300 Vdc. If the fan is powered, it must be replaced, differently
replace the board.
Loc 6 Software error inside the
command board
Replace the command and control board.
Loc 7 Content of the memo-
ry E2prom inside the command board, not updated
Replace the command and control board.
Loc 8 Parameters inside
the E2prom memory, incorrect
Replace the command and control board.
Loc 9 Software error inside the
command board
Replace the command and control board.
Loc 10 Software error inside the
command board
Replace the command and control board.
Loc 11 Not applicable
Loc 12 Not applicable
Loc 13 The boiler has reached
95°C
Control that the pump functions. Restore water circulation or replace the command
and control board.
Loc 14 Fumes maximum tempe-
rature. To release the error,
contact a qualied after-
sales centre, which must move the switch “B” in
g. 6.5 and press the
RESET key. Then put the switch back in the original position.
Check there is no air in the central heating circuit; bleed the highest radiators;
Check the circulation pump operates correctly;
Measure the boiler efciency; it must correspond to
that declared in the technical features.
Bleed the air from the boiler and from the highest central heating elements with respect to the boiler.
If the pump does not operate, it must be replaced.
If the efciency does not correspond to the data at the
end of the manual, probably the primary heat exchan­ger is dirty from the fumes side or the water side.
Clean and check efciency again.
Loc 15 Software error inside the
command board
Replace the command and control board.
Loc 16 Software error inside the
command board
Replace the command and control board.
7 - USE
Page 51
51
MYDENS
COSMOGAS
Loc 17 Software error inside the
command board
Replace the command and control board.
Loc 18 Flame present 10
seconds after gas valve is closed
Replace the gas valve or the command and control board.
Loc 19 Flame present before
ignition
Replace the gas valve or the command and control board.
Loc 20 Flame lost three times Control: that the ionisation current is at a value over
60 (follow the procedure in chapter 8.20)
Controllare: che lo scarico dei fumi sia opportunamente protetto da ostruzioni causate da folate di vento
If the ionisation current is not over 60, the CO2 must be checked (follow chapter 6.8) and restore the correct value. Check the ionisation electrode and replace it if necessary. Check the integrity of the ionisation current electric circuit cables.
If the fumes exhaust is placed in a vertical wall it must be protected with a wind-proof grid. If the fumes exhaust is positioned on the roof, make sure that it is
not in an area of reux and that any windproof chimney pot is really efcient.
Loc 21 Not applicable
Loc 22 Not applicable
Loc 23 The two supply sensors
measure the different temperatures for more than 60 seconds.
Check that the electrical resistance of the two sensors match the graphics in chapter 8.22;
Check that the central heating circuit ow rate is not
too low;
If one of the two or both sensors do not have correct values, they must be replaced;
If the temperature difference between U1 and U8 is
greater than 30°C at maximum power and the ow rate of the central heating circuit is low, the ow rate
must be increased;
Loc 24 The two fumes sensors
measure the different temperatures for more than 60 seconds.
Check that the electrical resistance of the two fumes sensors match the graphics in chapter 8.22
If one of the two sensors does not match the double fumes sensor must be replaced
Loc 25 Too many plant lls in
one hour
Check the pressure switch calibration pressure. FILL must appear when the pressure drops below 0.6 bar and must disappear when the pressure rises above
1.5 bar; check that there are no water leaks from the central heating plant
If the pressure switch is not calibrated correctly, it must be replaced. If the plant has a leak it must be repaired.
Loc 26 Plant lling time too long Check the pressure switch calibration pressure. FILL
must appear when the pressure drops below 0.6 bar; check that there are no water leaks from the central heating plant
If the pressure switch is not calibrated correctly, it must be replaced. If the plant has a leak it must be repaired.
Loc 27 Software error inside the
command board
Replace the command and control board.
Loc 28 Software error inside the
command board
Replace the command and control board.
7 - USE
Page 52
52
MYDENS
COSMOGAS
7 - USE
7.19.2 - Diagnostics: errors “E”
Error Error Description Checks Solution
Err 30 Software error inside the
command board
Replace the command and control board.
Err 31 Software error inside the
command board
Replace the command and control board.
Err 32 Software error inside the
command board
Replace the command and control board.
Err 33 Software error inside the
command board
Replace the command and control board.
Err 34 Software error inside the
command board
Replace the command and control board.
Err 35 The supply temperature
exceeds 110°C with the gas valve closed
Check that the electrical resistance of the two supply sensors match the graphics in chapter 8.22.
Check that the gas valve closes the gas correctly when the burner switches off.
If one of the two sensors does not match, the double supply sensor must be replaced.
The gas valve must be replaced if it does not close correctly.
Err 36 Software error inside the
command board
Replace the command and control board.
Err 37 Software error inside the
command board
Replace the command and control board.
Err 38 Software error inside the
command board
Replace the command and control board.
Err 39 Software error inside the
command board
Replace the command and control board.
Err 40 Software error inside the
command board
Replace the command and control board.
Err 41 Software error inside the
command board
Replace the command and control board.
Err 42 Software error inside the
command board
Replace the command and control board.
Err 43 Software error inside the
command board
Replace the command and control board.
Err 44 Flame detected in a
moment when it should not be present
Replace the gas valve
Err 45 Central heating water
low pressure
Check the pressure switch calibration pressure. FILL must appear when the pressure drops below 0.6 bar; check that there are no water leaks from the central heating plant.
If the pressure switch is not calibrated correctly, it must be replaced. If the plant has a leak it must be repaired.
Err 46 Central heating water
pressure sensor error
Check the pressure switch calibration pressure. FILL must appear when the pressure drops below 0.6 bar; check that there are no water leaks from the central heating plant.
If the pressure switch is not calibrated correctly, it must be replaced. If the plant has a leak it must be repaired.
Err 47 Not applicable
Err 48 Software error inside the
command board
Replace the command and control board.
Err 49 Return sensor circuit
(1007) open
Check that the electric resistance of the sensor matches the graphics in chapter 8.22. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 50 Supply sensor circuit 1
(1001) open
Check that the electric resistance of the sensor matches the graphics in chapter 8.22. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Page 53
53
MYDENS
COSMOGAS
7 - USE
Err 51 Supply sensor circuit 2
(1005) open
Check that the electric resistance of the sensor matches the graphics in chapter 8.22. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 52 Domestic hot water inlet
sensor 2 circuit (1002) open
Check that the electric resistance of the sensor matches the graphics in chapter 8.22. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 53 Fumes 1 sensor circuit
(1006) open
Check that the electrical resistance of the fumes sensor 1006 matches the graphics in chapter 8.22
Check that the wires between the board and the double fumes sensor are connected correctly
If the sensor does not match, the double fumes sensor must be replaced.
If the wires are not connected correctly, the connec­tions must be restored.
Err 54 Fumes 2 sensor circuit
(1014) open
Check that the electrical resistance of the fumes sensor 1014 matches the graphics in chapter 8.22
Check that the wires between the board and the double fumes sensor are connected correctly
If the sensor does not match, the double fumes sensor must be replaced.
If the wires are not connected correctly, the connec­tions must be restored
Err 55 Not applicable
Err 56 Return sensor circuit
(1007) in short circuit condition
Check that the electric resistance of the sensor matches the graphics in chapter 8.22. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 57 Supply sensor circuit 1
(1001) in short circuit condition
Check that the electric resistance of the sensor matches the graphics in chapter 8.22. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 58 Supply sensor circuit 2
(1005) in short circuit condition
Check that the electric resistance of the sensor matches the graphics in chapter 8.22. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board..
Err 59 Domestic hot water inlet
sensor circuit (1002) in short circuit condition
Check that the electric resistance of the sensor matches the graphics in chapter 8.22. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 60 Fumes 1 sensor circuit
(1006) in short circuit condition
Check that the electrical resistance of the fumes sensor 1006 matches the graphics in chapter 8.22
Check that the wires between the board and the double fumes sensor are connected correctly
If the sensor does not match, the double fumes sensor must be replaced
If the wires are not connected correctly, the connec­tions must be restored
Err 61 Fumes 2 sensor circuit
(1014) in short circuit condition
Check that the electrical resistance of the fumes sensor 1014 matches the graphics in chapter 8.22
Check that the wires between the board and the double fumes sensor are connected correctly
If the sensor does not match, the double fumes sensor must be replaced
If the wires are not connected correctly, the connec­tions must be restored
Err 62 External temperature
sensor circuit (1004) in short circuit condition
Check that the electric resistance of the sensor matches the graphics in chapter 8.23. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 63 RESET key pressed too
many times in a very brief period
7.19.3 - Diagnostics: alarms “AttE”
Alarm Description of the alarm Checks Solutions
AttE 65 Central heating plant
pressure too low for more than 10 minutes
Check the pressure switch calibration pressure. FILL musty appear when the pressure drops below 0.6 bar; check that there are no water leaks from the central heating plant.
If the pressure switch is not calibrated correctly, it must be replaced. If the plant has a leak it must be repaired.
Page 54
54
MYDENS
COSMOGAS
8.1 - General recommendations
It is recommended to perform regular yearly maintenance of the central heating plant for the following reasons:
- to maintain high efciency of the appliance and therefore save fuel;
- to maintain a high level of safety;
- to maintain the level of environmental compatibility of the
combustion high;
In order to maintain the frequency of maintenance, there is a parameter present 2080 in the installer menu (see
chapter 7.18), which is used to activate the maintenance call (Service) along with the parameter 2081 which is
used to set the operating days that must pass between one call and the next.
The control system identies the operating days, checking
the burner activity time. Proceed as follows to activate the call service:
1.- access the Installer menu (see chapter 7.18) and set
parameter 2080 at 0n;
2.- access parameter 2081 and set the boiler operating days which must pass between one call and the next.
The call will be completed with SEr on the display. To remove the wording SEr and renew the call period,
operate as follows:
1.- access the “Installer menu”;
2.- access the parameter 2080, set it on rESE and press the RESET key.
3.- exit the Installer menu by pressing the RESET key for 5 seconds.
The call time is now renewed and SEr appears on the display.
ATTENTION !!! Appliance maintenance must
only be performed by a professionally qualied
technician.
ATTENTION !!! Before every maintenance
operation, disconnect the appliance from the electric power supply, using the relevant switch in the vicinity.
ATTENTION !!! Close the gas cock before any
maintenance operation
8 - MAINTENANCE
Page 55
55
MYDENS
COSMOGAS
Figure 8.1 - removing the casing and opening of command board
8.2 - Removing the casing and
access to internal components
Proceed as follows to remove the casing (refer to gure
8.1):
1.- pull the lower cover “A” towards the front for approx. 10mm
2.- push the lower cover “A” downwards;
3.- loosen the screws “H”;
4.- pull the lower part of the front-piece “B” towards the front and then slide it out upwards until it is released from the
guides “C”;
To access the command and control board:
1.- turn the command board “D” towards the front;
2.- open the commands board “D” by operating on closure
“G”;
To access the electric connections board:
1.- turn the command board “D” towards the front;
2.- slide lid “E” out by operating on the “F” closing aps;
C
E
D
G
H
F
A
B
020002.01.018
8 - MAINTENANCE
Page 56
56
MYDENS
COSMOGAS
8 - MAINTENANCE
8.3 - Removing the burner fan unit
Proceed as follows to remove the burner fan unit (refer to
gure 8.2 when not differently specied):
1.- access the internal components following chapter 8.2;
2.- remove the air manifold (detail “C” in gure 6.2) rotating
it towards the outside of the boiler and then pulling it
towards the right (see gure 6.2);
3.- unscrew nut “C” from the valve “D”;
4.- disconnect the cables “B” and the detection cable from the ignition and detection electrodes (details “12”, “53”
and “54” of gure 3.1);
5.- unscrew the four nuts “E”;
6.- extract the group “F” as per gure;
Figure 8.2 - Removing the burner fan unit
A
C
B
F
D
E
020002.01.024
8.4 - Cleaning the burner and the fumes side primary heat exchanger
To correctly clean the burner and body of the heat
exchanger (fumes side), proceed as follows (refer to gure
8.2 when not differently specied):
1.- access the internal components following chapter 8.2;
2.- remove the burner unit following chapter 8.3;
4.- pass a cylindrical brush with plastic bristles inside the combustion chamber
5.- use a suction device to remove the unburned residues
present inside the combustion chamber;
6.- use the same suction device on the surfaces of the
burner and around the electrodes;
7.- re-mount the components in reverse order;
8.- open the gas cock;
9.- restore the electric power supply.
10.- check that there are no gas leaks between the joints
removed;
ATTENTION !!! Perform the leak test using a soap
and water only. The use of naked ames is prohibited.
Page 57
57
MYDENS
COSMOGAS
8 - MAINTENANCE
Figure 8.3 - positioning the electrodes on the burner
Figure 8.4 - Access to the expansion tank
C
B
A
E
D
020002.01.025
8.5 - Correct positioning of the
ignition and ionising electrodes
For good working order of the appliance, it is indispensable
that the electrodes are positioned correctly (refer to gure
8.3):
- the distance between the ignition electrodes “A” and “B”,
must be between 2.0 and 2.5 mm;
- the distance between the ignition electrodes from the burner
surface must be between 5 and 5.5 mm;
- the distance of the ionisation electrode from the surface of the burner must be between 5.5 and 6.5 mm.
8.6 - Controlling the expansion tank
The expansion tank is positioned in the left side of the boiler.
Check the pre-ll pressure of the expansion vessel. It must
be at 1 bar. If the pressure is lower, restore it, allowing the water to evacuate from one of the two central heating drain
cocks (details “A” and “B” in gure 8.16).
If the replacement of the tan becomes indispensable,
proceed as follows to remove it (refer to gure 8.4 when not differently specied):
1.- access the boiler internal components following chapter
8.2;
2.- empty the central heating circuit, following the procedure
in chapter 8.16;
3.- remove the screw “B”;
4.- loosen the tting “C”;
5.- extract the expansion tank “D” towards the front.
6 - Replace the tank.
Page 58
58
MYDENS
COSMOGAS
8.7 - Cleaning the condensate
conveyor siphon
For correct cleaning of the collection siphon and the conveying of the condensate produced by combustion,
operate as follows (refer to the gures 8.5, 8.6 and 8.7):
1.- with the boiler on, open a domestic hot water cock to maximum in a way that the burner is at maximum power and the level of liquid present inside the siphon tank “D”
lowers (see gure 8.6);
2.- access the internal components following chapter 8.2;
3 - remove the fan burner unit following chapter 8.3;
4 - cover the electric plant and pump unit with a cloth
to protect them from any residues of water inside the siphon to be removed.
5.- slide the support “C” outwards from the holding support;
6.- slide the tank “D” downwards, paying attention to the fact that it is full of condensate water and this could
escape;
7.- extract the siphon outwards (see gure 8.6) paying
attention to disconnect the collection pipes of the water coming from the upper part of the appliance and from the air vent valve.
8.- clean the decanting tank “D”;
9.- re-mount everything in reverse order, paying attention to the gasket “E”, which is put back in the relevant seat and
that terminal “G” is introduced correctly in the seat “H”;
10.- restore the level of liquid inside the siphon following the procedure in chapter 6.1.2.
Figure 8.6 - Removal of the condensate collection siphon
C
D
B
A
020002.01.027
D
E
02002.01.029
Figure 8.7 - Condensate collection siphon
H
G
F
D
E
020002.01.030
8 - MAINTENANCE
Figure 8.5 - Removal of the condensate collection siphon
Page 59
59
MYDENS
COSMOGAS
8.8 - Removing the air vent valve
Refer to Figure 8.8 and proceed as follows:
1.- empty the central heating circuit, following the procedure
in chapter 8.16;
2.- access the internal components of the appliance
following chapter 8.2;
3.- remove the pipe “A” from the air vent valve “B”;
4.- slide the drive bar “C” towards the front;
5.- slide the air vent valve “B” upwards and extract it
8.9 - Replacing the pump motor
If the circulation pump must be replaced, operate as follows
(refer to gure 8.9)
1.- empty the central heating circuit, following the procedure
in chapter 8.16;
2.- access the internal components of the appliance
following chapter 8.2;
3.- disconnect the electric wires from the pump body.
4.- remove the screws “B”;
5.- extract the pump “C” outwards;
8.10 - Removing the central
heating circuit pressure sensor
Proceed as follows, making reference to gure 8.10:
1.- empty the central heating circuit, following the procedure
in chapter 8.16;
2.- access the internal components of the appliance
following chapter 8.2;
3.- extract the drive bar “A” towards the front;
4.- slide the pressure sensor “B” upwards and extract it.
Figure 8.9 - Replacing the pump motor
C
A
B
020002.01.026
8 - MAINTENANCE
A
B
C
020002.01.035
Figure 8.8 - Removing the air vent valve
Figure 8.10 - Removing the central heating circuit pressure sensor
A
B
020002.01.036
Page 60
60
MYDENS
COSMOGAS
8 - MAINTENANCE
8.11 - Removing the diverter
valve servo-motor
Proceed as follows, making reference to gure 8.11:
1.- access the internal components of the appliance
following chapter 8.2;
2.- remove the air manifold (detail “C” in gure 6.2) rotating
it towards the outside of the boiler and then pulling it
towards the right (see gure 6.2);
3.- slide the drive bar “A” in 8.11 out;
4.- extract the servo-motor “B” in gure 8.11 upwards.
8.12 - Removing the diverter valve
The diverter valve (detail “47” in gure 3.1) switches over the ow of water produced from the primary heat
exchanger to the central heating circuit or to the secondary heat exchanger for the production of d.h.w. If it has to be
replaced, proceed as follows (refer to gure 8.12):
1.- remove the diverter valve servo-motor following chapter
8.11;
2.- empty the central heating circuit, following the procedure
in chapter 8.16;
3.- slide the drive bar “D” out;
4.- slide the diverter valve “E” upwards.
8.13 - Removing the ow meter
The ow meter is used to measure the water ow rate of
the domestic hot water. If it has to be replaced, proceed as
follows (refer to gure 8.13):
1.- empty the domestic hot water circuit, following the
procedure in chapter 8.17;
2.- access the internal components of the appliance
following chapter 8.2;
3.- remove the spring “A”;
4.- extract the ow meter “B”, paying attention to direction for the correct re-positioning at the end of maintenance;
5.- clean the lter “C” making sure to extract it from the body of the ow meter “B” as indicated in the gure;
6.- wash the lter and re-mount everything in reverse order;
7.- during remounting, make sure the ow meter is positioned correctly (step highlighted in point 4).
ATTENTION ! !! This filter is inten de d as a
precaution only. A lter with greater capacity must be
installed outside the boiler, on the cold water inlet, as
specied in chapter 5.6.
Figure 8.11 - Removing the servo-motor
Figure 8.12 - Removing supply and return ttings
Figure 8.13 - Removing the ow meter
B
A
020002.01.031
E
D
020002.01.032
A
C
B
020002.01.033
Page 61
61
MYDENS
COSMOGAS
8.14 - Removing the safety valve
The safety valve (detail “D” in gure 8.14) protects the
boiler from over pressures. If it has to be replaced, proceed
as follows (refer to gure 8.14):
1.- empty the central heating circuit, following the procedure
in chapter 8.16;
2.- access the internal components of the appliance
following chapter 8.2;
3.- disconnect the drain pipe “A”, loosening the sealing
spring “B”;
4.- slide the drive bar “C” towards the front;
5.- extract the safety valve “D” upwards;
8.15 - Secondary heat exchanger
for the production of d.h.w.
The production of d.h.w. is delegated to the secondary heat
exchanger (detail “5” in gure 3.1). If this heat exchanger is no longer efcient with the passing of time, it may require cleaning
or replacement. To remove the secondary heat exchanger,
proceed as follows (refer to gure 8.15):
1.- empty the central heating circuit and the domestic hot water circuit, respectively following chapters 8.16 and
8.17;
2.- access the internal components as per chapter 8.2;
3.- remove the burner fan unit following chapter 8.3;
4.- loosen the bolts “A”;
5.- move the secondary heat exchanger “B” backwards and
turn it as per gure;
6.- extract the heat exchanger “B” towards the front of the boiler.
Figure 8.14 - Removing the safety valve
A
B
C
D
020002.01.034
Figure 8.15 - Removing the secondary heat exchanger
8 - MAINTENANCE
B
A
020002.01.037
Page 62
62
MYDENS
COSMOGAS
Figure 8.16 - Central heating circuit drain cocks
8.16 - Emptying the appliance on the domestic hot water side
To empty the appliance from the central heating side, proceed as follows:
1.- generate a central heating request;
2.- set the central heating temperature at the lowest value possible, with the purpose of cooling the water inside the
boiler;
3.- switch the boiler off;
4.- access the internal components following chapter 8.2;
5.- connect a exible hose to the drain cocks “A” and “B”(see gure 8.16) and convey it onto the drain of a washbasin or similar;
6.- open the drain cocks “A” and “B” (see direction of
rotation in gure 8.17);
7.- open the central heating elements bleed valves. Start from the highest central heating elements and continue with the lowest.
8.- once all of the water has been evacuated, close all of the heating element vent valves and the drain cocks “A”
and “B” in gure 8.16.
ATTENTION !!! It is prohibited to recover and/
or re-use the water evacuated from the central heating circuit for any purpose; this could be polluted.
8.17 - Emptying the appliance on
the domestic hot water side
To empty the appliance from the domestic hot water side, proceed as follows:
1.- close the main cold water supply cock in the house;
2.- open all hot and cold water taps around the home;
3.- make sure that at least one of these is at a height below the level of the boiler.
8.18 - Fan
Switch-on of the fan only can be generated, accessing the parameter 2010 situated inside the “Installer menu” (see chapter 7.18) and set it on FAn. To go back to normal operating conditions, set parameter 2010 again to 0FF.
8.19 - Minimum and maximum power
Appliance operation can be forced to its own minimum, maximum, adjusted or ignition power. Proceed as follows:
1.- make sure that any cocks and thermostatic valves
downstream from the central heating circuit are open;
ATTENTION !!! During forcing of the delivery
temperature, it automatically goes to 93°C to give the possibility to dispose of as much of the heat generated by the boiler as possible. Check that the central heating plant can support this temperature.
2.- access parameter 2010 found in the “installer menu”
(see chapter 7.18);
3.- set the parameter 2010 at the following value:
a) LOu to force the boiler to minimum power; b) Ign to force the boiler to ignition power; c) HIgH to force the boiler to maximum power; d) rEg to force the boiler to the maximum central heating
power, as adjusted (Range Rated) in chapter 6.9,
parameter 2002.
4.- To end forcing, take the parameter 2010 to the0FF e
premere il tasto RESET.
ATTENTION !!! If during forcing, the power
supplied by the boiler is much higher than the power absorbed by the plant, the boiler switches off continuously to reach the maximum temperature allowed (93°C).
8 - MAINTENANCE
BA
020002.01.038
BA
Figure 8.17 - Cocks opening and closing direction A = Open B = Closed
Page 63
63
MYDENS
COSMOGAS
8.20 - Checking the ionisation current
In any operating status, also during verications of minimum
and maximum power stated in chapter 8.19, the ionisation current value can be consulted on parameter 1008 present
in the “User menu” (chapter 7.17). This value must be between
1.5 and 3 uA (microampere) at minimum power and between
5 and 8 uA at maximum power.
8.21 - Checking combustion efciency
On the basis of national laws regarding gas appliances, the
combustion efciency must be checked periodically;
To do this, operate exactly as stated in chapter 6.8 and
check, along with the CO2, also the combustion efciency,
which must be over 96%.
Figure 8.18 - Water sensors curve
Figure 8.19 - External temperature sensor curve
8 - MAINTENANCE
8.22 - Water temperature measurement sensors
The temperature sensors are positioned on the boiler’s exchanger body. The electric resistance existing between the two contacts of the sensor, must correspond with that
stated in gure 8.18.
The temperature sensors are: 1001, 1002, 1003,
1005, 1006, 1007 and 1014, the positioning of
which can be veried in gure 3.1.
8.23 - External temperature sensor
On request, the external temperature sensor can be connected to the boiler 1004 (see chapter 5.14.4). The
electric resistance existing between the two contacts of the
sensor, must correspond with that stated in gure 8.19.
Page 64
64
MYDENS
COSMOGAS
8.24 - Operational wiring diagram
Figure 8.20 - Operational wiring diagram
ATTENTION !!! To consult
the wiring diagram correctly, references K are given followed by a number (see example above) to identify the correct follow-on of the cables in the next page.
8 - MAINTENANCE
1001 - Boiler body sensor 1 1002 - DHW outlet sensor
1002 (SB) - Indirect water heater sensor
1004 - External temperature sensor 1005 - Boiler body sensor 2 1006 - Fumes sensor 1007 - Return sensor
1014 - Flue gas sensor (redundant) CM - Boiler control unit and ame control
DSP - Display
DSPX - Remote control (on request)
EA - Ignition electrode ER - Detection electrode
F (Digital) - Digital fan F (BCU) - 5A fuse F1 (SDC) - 1.6A power supply fuse
GP - Circulation pump GS - Spark generator
Page 65
65
MYDENS
COSMOGAS
8 - MAINTENANCE
IG - Master switch J1 - 6 pin Molex connector J12- 6 pin Molex connector J2 - 4 pin Molex connector J26- 4 pin Molex connector J3 - 12 pin Molex connector J4 - 4 pin Stelvio connector J5 - 16 pin Molex connector J6 - 14 pin Molex connector J7- 10 pin Molex connector J9- 4 pin Molex connector PB - Indirect water heater pump PS - Central heating circuit pressure sensor SDC- Connection board TA- Room thermostat
TU - Domestic hot water ow meter
V3V- domestic hot water/central heating diverter valve VG1- Sit Gas Valve
Page 66
66
MYDENS
COSMOGAS
8.25 - Multi-wire wiring diagram
Figure 8.21 - Multi-wire wiring diagram
Key - see key gure 8.20
8 - MAINTENANCE
Page 67
67
MYDENS
COSMOGAS
8 - MAINTENANCE
Page 68
68
MYDENS
COSMOGAS
MYDENS TECHNICAL DATA M.U. 15 24 34
Type (Type of fumes exhaust/air intake) B23;C13;C33;C43;C53;C63;C83
Category II2H3P II2H3P II2H3P
CE type certicate (PIN) 0694CN6126 0694CN6126 0694CN6126
Central heating max. heat input “Q” kW 14,0 25,5 34,8
Domestic hot water max. heat input kW / 25,5 34,8
Central heating min. heat input kW 3,2 3,2 4,4
Domestic hot water minimum heat input kW / 3,2 4,4
Central heating max. useful heat output (80/60) “P” kW 13,8 25,0 34,1
Efciency at 100% load (80/60) % 98 98 98
Min. useful heat output (80/60) kW 3,17 3,17 4,35
Efciency at min. useful heat output (80/60) % 99 99 99
Central heating max. useful heat output (50/30) kW 15,1 27,5 37,6
Efciency at central heating max. useful heat output (50/30) % 108 108 108
Min. useful heat output (50/30) kW 3,49 3,49 4,8
Efciency at min. useful heat output (50/30) % 109 109 109
Central heating max. useful heat output (40/30) kW 15,9 27,8 37,9
Efciency at central heating max. useful heat output (40/30) % 109 109 109
Min. useful heat output (40/30) kW 3,5 3,5 4,84
Efciency at min. useful heat output (40/30) % 110 110 110
Efciency at 30% of the load % 110 110 110
Efciency certicate (92/42/EEC) stelle
Losses at the chimney burner on (80/60) % 1,5 1,5 1,5
Losses at the chimney burner on at minimum power % 0,5 0,5 0,5
Losses at the chimney burner off % 0,1 0,1 0,1
Losses at the casing burner on % 0,5 0,5 0,5
Losses at the casing burner off % 0,1 0,1 0,1
Losses at zero load % 0,3 0,3 0,3
Generator average test temperature (80/60) °C 70 70 70
Generator average test temperature (40/30) °C 35 35 35
Return temperature in test conditions (80/60) °C 60 60 60
Return temperature in test conditions (40/30) °C 30 30 30
Gas ow rate
Nat Gas m
3
/h 1,48 2,70 3,68
LP Gas Kg/h 1,09 1,98 2,70
Gas supply pressure
Nat Gas mbar 20 20 20
LP Gas mbar 37 37 37
Gas supply minimum pressure
Nat Gas mbar 15 15 15
LP Gas mbar 25 25 25
Gas supply maximum pressure
Nat Gas mbar 27 27 27
LP Gas mbar 45 45 45
Combustion agent air pressure
Nat Gas mbar 8,2 13,2 12,3
LP Gas mbar 8,6 13,8 11,2
Primary heat exchanger with shared water circulation pipes lt 1,5 1,5 1,7
Weight of the heat exchanger with stainless steel water pipes kg 8 8 9,2
Secondary heat exchanger water content lt / 0,5 0,5
Domestic hot water useful heat output kW / 27,5 37,6
D.h.w. minimum ow rate l/min / 2 2
Instantaneous d.h.w. production (dt 30°C) l/min / 13,1 18
Instantaneous d.h.w. adjustment range °C / 40-60 40-60
D.h.w. with indirect water heater adjustment range °C 40-70 40-70 40-70
Design temperature °C 95 95 95
Maximum central heating temperature °C 80 80 80
Minimum central heating temperature °C 20 20 20
9 - TECHNICAL DATA
Page 69
69
MYDENS
COSMOGAS
MYDENS TECHNICAL DATA M.U. 15 24 34
Central heating maximum pressure “PMS” bar 3 3 3
Central heating minimum pressure bar 0,5 0,5 0,5
D.h.w. circuit maximum pressure bar / 7 7
D.h.w. minimum pressure bar / 0,3 0,3
Expansion tank pre-load pressure bar 1 1 1
Expansion tank capacity lt 10 10 10
Rated power supply voltage V 230 230 230
Rated power supply frequency Hz 50 50 50
Absorbed electric power W 120 120 120
Electric protection rating IPX4D IPX4D IPX4D
Elec. pow. of the generator aux. positioned before rebox W 70 70 70
Elec. pow. of the generator aux. at min.pow. positioned before rebox W 30 30 30
Elec. pow. of the generator aux. positioned after rebox W 50 50 50
Elec. pow. of the generator aux. at min.pow. positioned after rebox W 50 50 50
Power absorbed by the auxiliaries at rated power W 50 50 50
Power absorbed by the auxiliaries at intermediate load W 20 20 20
Power absorbed by the auxiliaries at zero load W 1 1 1
Electric power absorbed by the pump W 50 50 50
Fumes pipe diameter (split) mm 80 o 60 80 o 60 80 o 60
Fumes pipe max. length (split) (80) m 40 40 25
Fumes pipe max. length (split) (60) m 15 15 10
Fumes pipe diameter (coaxial) mm 60/100 60/100 60/100
Fumes pipe max. length (coaxial) m 10 10 10
Equivalent length of a bend m Curva a 45° = 0.5m, curva a 90° =1m
Weighted CO (0% O2 with nat Gas) ppm 1 8 15
Weighted NOx (0% O2 with nat Gas) (class 5 EN 483 and 297) ppm 11 13 17
CO2 (%) at minimum/maximum power Nat Gas % 8,5/9,0 8,5/9,0 8,5/9,0
CO2 (%) at minimum/maximum power LP Gas % 10/10,5 10/10,5 10/10,5
O2 (%) at minimum/maximum power Nat Gas % 5,5/4,8 5,5/4,8 5,5/4,8
O2 (%) at minimum/maximum power LP Gas % 5,6/4,8 5,6/4,8 5,6/4,8
Maximum recirculation of fumes allowed in the event of wind % 10 10 10
Fumes maximum temperature at boiler outlet °C 75 75 75
Fumes minimum temperature at boiler outlet °C 30 30 30
Mass ow of the fumes kg/h 25,4 42,3 59
Mass ow of the fumes at minimum power kg/h 5,3 5,3 7,2
Head available at exhaust Pa 60 60 60
Maximum temperature of the combustion agent air °C 50 50 50
Maximum CO2 content in the combustion agent air % 0,9 0,9 0,9
Fumes maximum temperature for overheating °C 90 90 90
Max. negative pressure allowed in the fumes exhaust/intake system Pa 60 60 60
Condensate maximum ow rate l/h 1,9 3,2 4,3
Condensate average acidity PH 4 4 4
Operating environment temperature °C 0 ; +50 0 ; +50 0 ; +50
Weight of the boiler
B kg 36 36 38
C kg 34 34 36
P kg / 36 38
9 - TECHNICAL DATA
Page 70
70
MYDENS
COSMOGAS
10 - COMMAND MENU DIAGRAM
Symbol Description
Press and release the RESET key
Hold the reset key down for a time in seconds, indicated by the number (2)
Hold the reset key down for a time in seconds, indicated by the number (5)
Hold down the RESET and key simultaneously for a time in seconds, indicated by the number
Press and release the key
Press and release the key
Parameters that can be displayed in the normal conditions
(see chapter 7.19)
User menu parameters
(see chapter 7.17)
Installer menu parameters
(see chapter 7.18)
Installer menu parameters
(see chapter 7.18)
User menu access
(see chapter 7.17)
Installer menu access
(see chapter 7.18)
Return to normal operation
Return to normal operation
Figure 10.1 - Command menu diagram
Key of gure 10.1
Page 71
71
MYDENS
COSMOGAS
ATTENTION !!!
The modication of these parameters could cause the appliance, and therefore the plant, to malfunction.
For this reason only a technician that has the awareness and in-depth knowledge of the appliances can modify them.
To access this menu, introduce the bridge in the board as stated in gure 6.5 detail “A”.
11 - MENU FORCED BY INTERNAL ELECTRIC BRIDGE
Parameter Description of the parameter M.U. Setting range
Factory value
Customised
value
3002 Selection type From 50 to 55 See Figure 6.7
3012
Domestic hot water operating mode
/
0 = No domestic hot water; 1 = Indirect water heater with temperature sensor; 2 = Indirect water heater with thermostat;
3 = Instantaneous with ow switch;
4 = Microaccumulation with two sensors; 5 = Instantaneous with turbine;
model “P” = 5 model “B” = 1 model “C” = 0
3013 Plant ll automatic valve /
0 = Valve disabled; 2 = Valvola abilitata;
0
3014
Instantaneous domestic hot water pre-heat
/
OFF = No pre-heat ON = with pre-heat
OFF
3015
Maximum central heating temperature
°C From 20 to 90 80
3016
Minimum central heating temperature
°C From 20 to 90 30
3020
Domestic hot water ow rate
sensor
/
0 = B; (MYDENS 15, 24 e 34) 1 = DN 8; 2 = DN 10; 3 = DN 15; 4 = DN 20; 5 = DN 25;
0
3021 2nd Fumes sensor (1014) /
0 = Disabled; 1 = Enabled; 2 = Enabled with fumes exhaust anti­closure pressure switch;
1
3022
Central heating minimum pressure
bar OFF... 0,3 to 5,1; 0,5
3033 Modulating pump /
0 = Disabled; 1 = Enabled; From 4 to 10 = Fixed speeds from 40% to 100%;
0
3034 Modulating pump delta T target °C From 5 to 40 15 3035 No function / / / 3036 No function / / / 3052 No function / / /
Page 72
72
MYDENS
COSMOGAS
The undersigned COSMOGAS S.r.L., with Registered Ofce in via L. Da Vincin° 16 - 47014 Meldola (FC) ITALY,
DECLARES
under its own responsibility that the product:
subject of this declaration, is in compliance with the model described in the
Type examination certicate , whose reference is given in the table in
chapter 9 under “CE type certicate (PIN)” and meeting that required by the
Directives: Gas Appliances, (2009/142/CE former 90/396/CEE), Efciencys,
(92/42/CEE), Low Voltage, (2006/95/CE), Electromagnetic Compatibility,
(2004/108/CEE).
(the warranty number corresponds to the serial number)
This declaration is issued for that established by the above-mentioned Directives.
Meldola (FC) ITALY, (Date of manufacture).
DATE OF MANUFACTURE
WARRANTY N°
GAS BOILER MODEL
12 - CE DECLARATION OF CONFORMITY
Page 73
73
MYDENS
COSMOGAS
13 - WARRANTY
13.1 - General warranty conditions
All COSMOGAS products are guaranteed against material
aws and manufacturing defects for 24 months from the date of commissioning, COSMOGAS also extends the warranty to:
COPPER TUBE, CRR e CRV Heat exchanger guaranteed up to 5 years;
PRE-MIXED BURNERS guaranteed up to 10 years;
BRUCIATORI ATMOSFERICI guaranteed up to 15 years.
This warranty extension will only be valid if COSMOGAS
has received the warranty card, lled-in completely, which
will certify the date of commissioning. Within the above­mentioned term COSMOGAS commits to repairing or replacing the faulty construction parts and which will be acknowledged as such with exclusion of normal deterioration due to operations. The extension of the warranty exclusively covers the cost of the spare part. All other accessory costs are excluded, such as: labour, transfer costs and expenses for transporting material. The warranty does not extend to the recasting of the damage, of any nature, that has happened to persons or property. The faulty material replaced under warranty is the property of COSMOGAS and must be returned to our establishment, without further damage, within 30 days from replacement. All COSMOGAS products are encumbered by the title retention agreement, until the appliance sold have been paid in full.
13.2 - Instructions for lling-
in the warranty card
1. - Have your installer put his stamp on the warranty
certicate.
2. - Always request the intervention of our authorised technician for commissioning and to validate the
warranty;
To validate the warranty it will be the technician perform all the controls of the appliance in accordance with instructions contained in this manual and the regulations in force national and / or local.
The list authorised technicians is found attached to the instructions manual or can be found in the yellow pages under .
ATTENZIONE !!! - The authorized technician, performed
the rst ignition as mentioned above, must ll out the warranty card in all elds. In the top side, that will be sent to
COSMOGAS for the validation of the warranty, and in the
bottom side (to be cut) that will be given to the nal user as a validation test (the coupon below shows the identication data of the product and the date of rst ignition which is the beginning of warranty period). We recommend you to keep
the coupon along with the user manual for easy reference.
13.3 - Limits of the warranty
The warranty is not valid:
- if the appliance is installed by non-qualied staff;
- if the appliance is installed in a way that is not in compliance with the COSMOGAS instructions and/or that
established by the current national and/local regulations;
- whenever the plant is not run/services in compliance with the instructions and/or the current national and local
regulations;
- whenever the product has damage caused by changes in
voltage;
- whenever the product has damaged caused by the use of excessively hard water, or which is too acid or too
oxygenated;
- whenever the product has failures caused by heat shocks,
abnormalities of chimneys and/or exhaust and intake pipes;
- whenever the product has anomalies not depending on
COSMOGAS;
- whenever the appliances have been tampered with for adaptation, repairs or replacement with non-original spare
parts;
- whenever repairs are performed by unauthorised staff;
- Whenever the warranty certicate is not sent to
COSMOGAS within 15 gg from the date of commissioning.
COSMOGAS does not assume any responsibility for
any accident that may occur or be caused by the user, precluding any compensation that does not concern boiler parts recognised as defective manufacturing.
Any dispute is the jurisdiction of the Forlì Law Court, ITALY.
Page 74
Page 75
Page 76
COSMOGAS s.r.l.
Via L. da Vinci 16 - 47014
MELDOLA (FC) ITALY
info@cosmogas.com
www.cosmogas.com
Loading...