COSMOGAS CR04 Instructions For The Installation And Use

REMOTE TIME CONTROL
“CR04”
INSTRUCTIONS FOR THE INSTALLATION AND USE OF
THE “CR04” REMOTE CONTROL
62403440 - R01 17-01-2008_GB-IE
PLEASE READ THE MANUAL CAREFULLY: IT CONTAINS IMPORTANT INFORMATION REGARDING
SAFETY, INSTALLATION, USE AND MAINTENANCE OF THE APPLIANCE
2
T able of contents
1 - Main features ........................................................................................................... 3
2 - Operating features................................................................................................... 3
2.1 - LCD Display ............................................................................................................................. 3
2.2 - Keys and associated functions.................................................................................................. 3
3 - Initial start-up............................................................................................................4
4 - Introduction .............................................................................................................. 4
5 - Users’ menu............................................................................................................. 4
5.1 - Selecting the operating modes.................................................................................................. 5
5.2 - Automatic or manual operation of the time programmable thermostat........................................ 5
5.3 - Adjusting the domestic hot water temperature............................................................................ 6
5.4 - Manual forcing of room temperature (overrun function)............................................................... 6
5.5 - Forcing of heating programme ..................................................................................................6
5.6 - Forcing of domestic hot water programme ................................................................................ 6
5.7 - System parameters’ consultation............................................................................................... 7
5.8 - Programming the heating times.................................................................................................8
5.8.1 - Calling up an existing programme for heating.................................................................8
5.8.2 - Programming of domestic hot water timing ..................................................................10
5.8.3 - Calling up an existing programme for domestic hot water.............................................10
5.9 - Adjusting the system operating parameters............................................................................. 11
5.10 - Date, hour and minute setting................................................................................................ 12
5.1 1 - Memorizing hour/minutes/date and operating mode...............................................................12
5.12 - Indication of boiler with burner on...........................................................................................1 2
5.13 - Indication of presence of anomalies ......................................................................................12
6 - Installers’ menu...................................................................................................... 13
6.1 - Displaying the system parameters........................................................................................... 13
6.2 - Displaying and changing the system parameters..................................................................... 14
6.2.1 - Thermoregulation - Setting the gradient........................................................................ 15
6.2.2 - Thermoregulation - Correction with room temperature.................................................. 16
6.2.3 - Thermoregulation - Choosing the operating modes...................................................... 18
6.2.4 - Hour type displayed .....................................................................................................19
6.2.5 - Domestic hot water programme type ........................................................................... 19
6.2.6 - Automatic pre-heating.................................................................................................. 19
6.2.7 - Minimum supply temperature .......................................................................................20
6.2.8 - Maximum supply temperature ...................................................................................... 20
6.2.9 - Pre-setting of room temperature .................................................................................. 20
6.2.10 - Pre-setting of domestic hot water temperature ........................................................... 20
6.2.1 1 - Pre-setting of system supply type ...............................................................................20
6.2.12 - Correcting the room temperature read ....................................................................... 20
6.2.13 - Factory settings ......................................................................................................... 21
6.3 - Diagnostics............................................................................................................................. 21
6.3.1 - models AXIA-Ei, BMS-Ei and BME-Ei ......................................................................... 21
6.3.2 - models AXIA-H, ECOPLUS, ECOBI, INKAS, NOV ADENS, INKADENS and
CIELODENS..........................................................................................................................22
6.4 - Setting the language ............................................................................................................... 22
6.5 - Operating parameters - P AR Menu ......................................................................................... 22
6.6 - Operating parameters - P ARC Menu.......................................................................................22
6.7 - Installation ............................................................................................................................... 23
3
2.2 - Keys and associated functions
The remote control envisages a user interface comprising 7 keys:
K1 depends on operating mode selected K2 depends on operating mode selected K3 depends on operating mode selected K4 depends on operating mode selected K+ increases value selected K- decreases value selected KM selection of the user and installer mode menus
Figure 1 - LCD Display
Figure 2 - Keys and associated functions
Safety instructions
Please read the manual carefully: it contains important information regarding installation and use.
This device must be installed by a professionally qualified technician, observing national and
local legislation, as well as the instructions contained in this manual.
1 - Main features
The CR04 series remote control acts as a time-programmable thermostat, a thermoregulator and a remote control. It can be used as an initial installation device or as an optional extra, connecting it to COSMOGAS boilers appropriately set up for such installation.
· Connection to boiler using 2 non-polarized wires
· Three different user languages supported (English, Italian and French)
2 - Operating features
- LCD Display
- Keys and associated functions
2.1 - LCD Display
The remote control uses an alphamumeric LCD display, whose symbols are shown in the following diagram:
4
3 - Initial start-up
On initial start-up or in any event each time the power supply fails for more than 5 hours, it is necessary to set the time and day of the week. This is done as follows:
- switch on the power supply to the boiler, the display will come on with the date field flashing; use the K+ and K­keys to set the correct day of the week;
- press key K2 so that the hour flashes; use the K+ e K- keys to set the correct hour of the day;
- press key K3 so that the minutes flash; use the K+ e K- keys to set the correct minutes;
- press key KM to save the data and return to user mode;
- consult section 5.10 to make further changes to the day and time data.
4 - Introduction
With the exclusion of the:
· “off”, “domestic hot water with heating”, “only domestic hot water”, “only heating” operating modes;
· PROG SAN (DHW programming) PROG RIS (heating programming) programming mode;
· OROL (date and time) programming mode; the remote control display shows a two-letter code (in the field used to indicate the current day) which identifies the menu displayed.
5 - Users’ menu
It is possible to carry out the following operations in “User” mode:
- selection of the operating mode: “off”, “domestic hot water with heating”, “only domestic hot water”, “only heating”
- automatic or manual operation of time programmable thermostat
- adjustment of domestic hot water temperature
- manual forcing of room temperature (overrun function)
- forcing of heating programme, RIS menu
- forcing of domestic hot water programme, SAN menu
- system parameters’ consultation
- programming of heating and domestic hot water times, PROG menu
- adjustment of system operating parameters, IMP menu
- setting of day, hour and minutes, OROL menu
Figure 3 - Display components
KEY (figure 3)
1 Heating on 2 Dom. hot water on 3 Day 4 Hours and minutes 5 Function keys 6 Activate and
deactivate menu mode
7 Room temperature 8 Decrease value
9 Increase value 10 Active key indictors 11 Time-programmable thermostat histogram
The display has the following aspect in “user” mode:
5
5.1 - Selecting the operating modes
Using key K1, with the remote control positioned in any operating mode, it is possible to select, by rotation, the possible operating modes of the boiler, such as:
· OFF
· domestic hot water and heating
· only domestic hot water
· only heating
OFF
Only the room anti-freeze function with temperature setting equal to 5°C is enabled in this mode. The display shows:
· current day, hour and minutes
· the value of the room temperature gauged
· the switched off symbol and the wording OFF
Domestic hot water and heating
The domestic hot water and heating functions are enabled in this mode. The display shows:
· current day, hour and minutes
· the value of the room temperature
· the tap symbol and the radiator symbol
· the timer bar (if related function enabled)
Only domestic hot water
The heating function is disabled and the functions relating to the domestic hot water are enabled in this operating mode. The display shows:
· current day, hour and minutes
· the value of the room temperature
· the tap symbol
· the timer bar (if related function enabled)
Only heating
The domestic hot water function is disabled and the functions relating to the heating are enabled in this operating mode. The display shows:
· current day, hour and minutes
· the value of the room temperature
· the radiator symbol
· the timer bar (if related function enabled)
5.2 - Automatic or manual operation of the time programmable thermostat
Using key K2, it is possible to enable or disable the time-programmable thermostat of the remote control in cyclical mode. This can be noted from the display of the histogram bar of the time-programmable thermostat (automatic position), alternatively from the display of the hand (manual position) The function only becomes available in the “heating with domestic hot water” and “only heating” modes. The function is not active in the “only domestic hot water” mode. Consult section 5.8 for the programming of the time-programmable thermostat . When the remote time control is in the MANUAL position (hand designed on the display), just use the K+ o K- keys for increasing or decreasing the temperature required.
6
5.3 - Adjusting the domestic hot water temperature
Using key K4, with the remote control positioned in any operating mode (excluding OFF mode), it is possible to select the menu for setting the domestic hot water temperature. The display shows the wording REG SAN and the domestic hot water temperature value; using keys K+ o K- it is possible to change these values between 40 and 65 °C. Use the KM key to save the data and return to the operating mode.
5.4 - Manual forcing of room temperature (overrun function)
This function only becomes available if the “heating mode” is enabled (see section 5.1) Having activated the automatic functioning of the time-programmable thermostat (see section 5.2) of the remote control (AUTO mode), using keys K+ o K-, the display will show TEMPER AMBIENTE and the room temperature value. By pressing K+ o K- once again, it is possible to temporarily change the room temperature required; in this way, the automatic functioning of the time-programmable thermostat is by-passed (overrun), forcing a manual setting value, until the following change of status requested of the timer of the time-programmable thermostat. Return to the operating mode takes place automatically, after 5 seconds, or manually using the KM key. If the temperature value has been changed, the display will show the hand symbol and the programming bar of the timer (see figure 3, detail 1 1) so as to indicate that the function in question is underway (the hand symbol disappears the next time the status of the time-programmable thermostat’s timer changes).
5.5 - Forcing of heating programme
Using the KM key , it is possible to access page 1 of the menus and from there, using key K1 (RIS), one accesses the heating forcing menu. Once this menu has been selected, it is possible to make the following choice:
· TIMER Return to the operating mode takes place automatically , af ter 2 minutes, or manually using the KM key. By pressing key K4 (TIMER), the TIMER heating mode function is enabled; effectively, the manual functioning of
the time-programmable thermostat is forced for a given period of time set on DURA TION using the K+ e K- keys, at a room temperature value set by pressing key K4 (TMP) and adjusted as always using the keys K+ e K-. Now the running of the boiler will depend on the room temperature selected and the duration of the time set on the timer. Return to the operating mode takes place automatically , af ter 2 minutes, or manually using the KM key. The display shows the wording TIMER RIS for the duration of the forced heating set on the TIMER, or , in the event that the domestic hot water timer function is active, the wording TIMERS. Once the time set on the TIMER has elapsed, the heating returns to that active before the setting. It is possible to interrupt the function in question at any given time; in order to do this, after having selected the RIS – TIMER heating mode (key KM followed by key K1), press key K1 (OFF). The remote control automatically returns to the operating mode.
5.6 - Forcing of domestic hot water programme
Using key KM, it is possible to access page 1 of the menus and from there, using key K2 (SAN), one accesses the domestic hot water forcing menu. This menu is enabled only if the selection parameter of the domestic hot water operating mode (PROG SAN) is set at 2 or 3 (see section 5.9). Once this menu has been selected, it is possible to make the following choice:
· AUTO
· TIMER By pressing key K1 (AUTO), the automatic functioning of the domestic hot water mode is obtained.
In relation to the PROGR SAN parameter set (see section 5.9), the AUTO domestic hot water mode can adopt 2 different operating features:
- follow an independent timing programme
7
- follow the setting of the timing programme of the heating service The activation of the AUTO domestic hot water mode is indicated on the display when the clock
symbol lights up. It is possible to interrupt the function in question at any given moment, re-setting the continual function (always ON) of the domestic hot water mode. In order to do so, after having selected the domestic hot water mode SAN – AUTO (key KM followed by key K2), press key K1 (ON); the remote control automatically returns to the operating mode.
By pressing key K4 (TIMER), the TIMER domestic hot water operating mode is enabled; in practice, the operating
of the domestic hot water mode is forced for a given period of time. The display shows the DURA TION p arameter which can be selected by using key K1 (DURATION); the flashing off said parameter indicates its selection and the possibility of changing it using the keys K+ o K-. The DURA TION parameter can adopt a value ranging between 30 minutes and 12 hours. Return to the operating mode takes place automatically, after 2 minutes, or manually using the KM key . The activation of the TIMER domestic hot water mode is indicated on the display when the TIMER SAN wording lights up, or, in the event that the heating timer function is also active, the TIMERS wording is shown. Once the timing has elapsed, the domestic hot water mode returns to that active before the setting of the TIMER domestic hot water mode. It is possible to interrupt the function in question at any given moment. In order to do so, after having selected the domestic hot water mode SAN – TIMER (key KM followed by key K2), press key K1 (OFF); the remote control automatically returns to the operating mode
5.7 - System parameters’ consultation
Using key K3, with the remote time control positioned in any operating mode (excluding OFF mode), it is possible to immediately access the user information. Having pressed key K3, the display will immediately show the external temperature; using keys K1 (<<) and K4 (>>), it is possible to display the subsequent information, listed below:
· TMP ESTERNA external temperature
· PRESSIONE data not available
· TMP MANDA TA
boiler unit temperature
· BRUCIATORE data not available
· TMP SAN domestic hot water temperature (only with water heater)
· PORT A T A SAN data not available
· STATO SAN domestic hot water mode status, 0 inactive 1 active
· TMP RITORNO data not available
· TMP AMBIENT room temperature
Return to the operating mode takes place automatically , after 2 minutes, or manually using the KM key.
8
5.8 - Programming the heating times
Using key KM and subsequently key K4 (>>), page 2 of the menus is accessed. Using key K1 (PROG), the programming menu is selected. Having selected this menu, it is possible to make one of the following choices:
· RIS (HEATING timer)
· SAN (DOMESTIC HOT WATER timer)
If the PROGR SAN parameter set (see section 5.9), does not anticipate the management of the SAN timer (different to 2), one directly accesses the programming of just the timer for the heating.
- press key K1 (RIS), one accesses the menu for programming the heating timer;
- press key K1 (GIO) in order to set the day one intends to programme (pressing it repeatedly , one will see that the two letters corresponding to the day of the week change continually , updating the day);
- press key K2 (IMP) to access the menu for selecting the temperature raising or lowering bands, comprising the levels T0, T1 and T2 plus the choice which makes it possible to leave the value unchanged ( - - );
- choose the T0, T1 or T2 temperature level which one intends to set, the display automatically returns to the previous status;
- using the keys K+ e K-, set the hour for that day during which one wishes it to function in the set timeband; (the timebands T0, T1 and T2 are displayed on the histogram bar, respectively by means of: nil, a small black square at the base of the histogram, two small black squares overlapping);
- press key K2 (IMP) once again to select the new temperature timeband and repeat the previous operation in order to set the operating timeband under T1;
- repeat the above procedure, so as to set the operating timeband under T2. So as to shift from one part of the timer to another over 24 hours, without changing the setting made previously,
proceed as follows:
- press key K2 (IMP), then press key K1 (- -); the display returns to the clock display, thus move between the hours using the keys K+ e K- until reaching the desired time;
- repeat the above procedure, selecting a new T0, T1 or T2 temperature level. Once the programming of the day has been carried out, just press key K3 (COP) in order to copy the same
programming to the next day , then press key K1 (GIO) in order to select the following day (whose time will have the same programming made above), then press K3 (COP) once again so as to copy the programming to the next day , and so on for all the days of the week which one wishes to programme as the same as the others. In order to programme one day of the week differently, it is sufficient to do so as per the above indications, without it being copied from a previous day .
In order to save the programme set, just press key KM. The display will return to normal view . If the display shows the histogram bar 11 as per figure 3, it means that the programme set above is already active. If this is not so, follow the instructions in section 5.2 to activate it.
5.8.1 - Calling up an existing programme for heating
The remote control makes 5 pre-compiled programmes available, in order to facilitate the user when programming the time. Proceed as follows to access them:
- press key KM and subsequently key K4 (>>), page 2 of the menus is accessed;
- press key K1 (PROG), the programming menu is selected; Once this menu has been selected, it is possible to make one of the following choices:
· RIS (HEATING timer)
· SAN (DOMESTIC HOT WATER timer)
If the PROGR SAN parameter set (see section 5.9) does not envisage the management of the SAN timer (different to 2), one directly accesses the programming of just the timer for the heating.
- press key K1 (RIS), one accesses the menu for programming the heating timer;
- press key K4 (PRE), one accesses the menu for selecting the pre-set operating programme;
- press keys K+ o K- to select the pre-set programme nearest to one’s requirements;
- press key K1 (OK) in order to load the programme in the memory or press key K2 (ANNULLA) to return to the previous menu without loading any pre-set programme.
Once the programme has been loaded, the display returns to show the menu of the heating programming mode.
9
Programme 2
Programme 3
Programme 4
Programme 5
By means of the procedure for programming the timebands, as per the previous section, it is possible to customize the pre-set programme loaded in the memory.
Having loaded and possibly customized the pre-set programme, just press key KM to save it and return to the main page. If the display shows the histogram bar 1 1 as per figure 3, it means that the programme set above is already active. If this is not so, follow the instructions in section 5.2 to activate it.
The pre-set programmes are as follows:
Programme 1
10
5.8.2 - Programming of domestic hot water timing
Using key KM and subsequently key K4 (>>), access is gained to page 2 of the menus. Using key K1 (PROG), the programming menu is selected. Once this menu has been selected, it is possible to make one of the following choices:
· RIS (HEATING timer)
· SAN (DOMESTIC HOT WATER timer) If the choice does not appear, it means that the domestic hot water programme is already active (PROG SAN
parameter as per section 5.9, at 1), or that it is linked to the programming of the heating (PROG SAN parameter as per section 5.9, at 3). So as to carry out programming of the domestic hot water independently from the programming of the heating, it is necessary to set the PROG SAN parameter as per section 5.9, at 2.
- press key K2 (SAN), one accesses the menu for programming the domestic hot water timer (the clock symbol which appears on the display acts as confirmation that the time programming of the heating is taking place);
- press key K1 (GIO) in order to set the day one intends to programme (by repeatedly pressing it, one will see that the two letters corresponding to the day of the week change continually , updating the day);
- press key K2 (IMP) in order to access the menu for selecting the on and off timebands for the domestic hot water service , comprising OFF and ON, plus the choice which makes it possible to leave the value unaltered ( -
- );
- choose the key corresponding to the function one intends to programme (OFF) or (ON), the display automatically returns to the previous setting;
- using keys K+ e K-, set the timeband, for that day , during which you wish it to operate in the chosen function; (the OFF and ON timebands are displayed on the histogram bar, respectively by means of: nil, a small black square at the base of the histogram);
- press key K2 (IMP) once again so as to select the new OFF or ON function timeband and repeat the operation carried out previously in order to set the new operating timeband.
So as to shift from one part of the timer to another over 24 hours, without changing the setting made previously, proceed as follows:
- press key K2 (IMP), then press key K1 (- -); the display returns to the clock display, thus move between the hours using the keys K+ e K- until reaching the desired time;
- repeat the above procedure, selecting a new ON or OFF operating timeband. Once the programming of the day has been carried out, just press key K3 (COP) in order to copy the same
programming to the next day , then press key K1 (GIO) in order to select the following day (whose time will have the same programming made above), then press K3 (COP) once again so as to copy the programming to the next day , and so on for all the days of the week which one wishes to programme as the same as the others. In order to programme one day of the week differently, it is sufficient to do so as per the above indications, without it being copied from a previous day .
In order to save the programme set, just press key KM. The display will return to normal view . If the display shows the histogram bar 11 as per figure 3, it means that the programme set above is already active. If this is not so, follow the instructions in section 5.2 to activate it.
5.8.3 - Calling up an existing programme for domestic hot water
The remote control makes 2 pre-compiled programmes available, in order to facilitate the user when programming the time. Proceed as follows to access them:
- press key KM and subsequently key K4 (>>), page 2 of the menus is accessed;
- press key K1 (PROG), the programming menu is selected; Once this menu has been selected, it is possible to make one of the following choices:
· RIS (HEATING timer)
· SAN (DOMESTIC HOT WATER timer)
If the PROGR SAN parameter set (see section 5.9) does not envisage the management of the SAN timer (different to 2), one directly accesses the programming of just the timer for the heating, therefore set PROGR SAN at 1 or
3.
- press key K2 (SAN), one accesses the menu for programming the domestic hot water timer;
- press key K4 (PRE), one accesses the menu for selecting the pre-set operating programme;
11
Programme 1
Programme 2
Having selected the pre-set programme, it is however possible to customize it as one likes, following the same indications in the previous paragraph “Domestic hot water programming”.
5.9 - Adjusting the system operating parameters
Using key KM and then key K4 (>>), access is gained to page 2 of the menus. Using key K2 (IMP), the menu for adjusting the operating parameters is selected. The menu makes it possible to display , and subsequently change, the parameters which can be accessed by the user. Using keys K1 (<<) and K4 (>>), it is possible to display the information listed below:
· TMP AMB T0 adjustment of room temperature value T0 (can adopt values ranging between 7 and 35°C)
· TMP AMB T1 adjustment of room temperature value T1 (can adopt values ranging between 7 and 35°C)
· TMP AMB T2 adjustment of room temperature value T2 (can adopt values ranging between 7 and 35°C)
· PROGR SAN adjustment of domestic hot water programme type (can adopt the values 1, 2 and 3)
· REG RISCALD adjustment of maximum heating supply temperature (can adopt values ranging between 20 and 45°C) Where:
- T0 is the room temperature level, considered to be saving status
- T1 is the room temperature level, considered to be reduction status
- T2 is the room temperature level, considered to be comfort status
- PROG SAN, if set at 1, means that the domestic hot water function is active continually throughout the entire day; if set at 2, it means that the operating time programme for the domestic hot water is independent from the heating time programme; if set at 3, it means that the operating time programme for the domestic hot water is linked to the heating time programme.
All the parameters can be changed using the keys K+ o K–. Return to the operating mode takes place automatically , af ter 2 minutes, or manually by using key KM.
If the MODO FUNZ parameter has been set at 4 (see section 6.2), the adjustment of TMP AMB T0, TMP AMB T1 and TMP AMB T2 is disabled.
All the afore-mentioned operating parameters are memorized within an Eeprom-type memory , which stores them even if the power to the remote control is cut.
- press keys K+ o K- to select the pre-set programme nearest to one’s requirements;
- press key K1 (OK) in order to load the programme in the memory or press key K2 (ANNULLA) to return to the previous menu without loading any pre-set programme. Once the programme has been loaded, the display returns to show the menu of the domestic hot water programming mode. By means of the procedure for programming the timebands, as per the previous section, it is possible to customize the pre-set programme, loaded in the memory. Having loaded and possibly customized the pre-set programme, just press key KM to save it and return to the main page. If the display shows the histogram bar 1 1 as per figure 3, it means that the programme set above is already active. If this is not so, follow the instructions in section 5.2 to activate it.
The pre-set programmes are as follows:
12
5.10 - Date, hour and minute setting
It is possible to adjust or set the date, hour and minutes of the remote control at any given time. Proceed as follows:
Using key KM and then key K4 (>>), access is gained to page 2 of the menus. Using key K3 (OROL), the programming menu is selected. Once this menu has been selected, it is possible to make one of the following choices:
· GIO
· ORA
· MINUTI Make the choice using keys K1, K2 or K3, then carry out the adjustment using keys K+ o K-. The parameter being adjusted is shown because it blinks.
The days are shown on the display, in two letters, according to the following scheme:
· DO = Sunday
· LU = Monday
· MA = Tuesday
· ME = Wednesday
· GI = Thursday
· VE = Friday
· SA = Saturday Return to the operating mode takes place automatically , af ter 2 minutes, or manually using the KM key. In relation to the TIPO ORA operating parameter selected (see section 6.2), the display of the hour is between 00
and 23, or, 00 and 12 AM/PM.
5.11 - Memorizing hour/minutes/date and operating mode
If the remote time control is electrically powered for an hour and subsequently there is a power cut, it is able to keep the clock (hour/minutes) and calendar (day) working and memorize all the data, before the power cut, for a period of time of up to 5 hours. If the remote control remains without power for more than 5 hours, on start-up said remote control positions itself automatically in day and hour programming mode; see section 3 for re-setting.
5.12 - Indication of boiler with burner on
The display shows the flame symbol indicating that the boiler’s burner is on.
5.13 - Indication of presence of anomalies
In the presence of anomalies, the display shows the flashing alarm symbol and the wording ANOMALY. If the anomaly requires re-set action to be taken by the user, the display shows a downwards arrow symbol, in correspondence with the key K1 (RESET). Using key K1 it is possible to reset normal running conditions, returning to operating mode, if the cause which generated the anomaly has been removed. Pressing key K4, it is possible to directly access the menu displaying the possible signals for the anomalous performance of the boiler and/or the remote time control. The type and number of anomalies which may be displayed, is shown in section 6.3, Diagnostics. In the event that the room temperature sensor of the remote time control is indicated as faulty , the supply temperature is automatically set at 40°C (in the absence of an external sensor). If an external sensor is present, the supply temperature is adjusted by means of the setting algorithm of the thermoregulation as per the diagram in figure 4. In the event that the external temperature sensor is indicated as faulty , the thermoregulation function changes and automatically becomes set at the room temperature (MODO FUNZ 2 as per section 6.2.3).
13
6 - Installers’ menu
Pressing down key KM for around 10 seconds it is possible to access the menus intended for the installer. Page 1 makes it possible to make one of the following choices:
· INFO display the system parameters
· IMP display and change the system parameters
· ERR display faults
·>> Pressing key K4 (>>), access is gained to page 2 of the menus, which makes it possible to make one of the
following choices:
· LING select the language of the remote time control
· P AR menu not available
· P ARC menu not available
·>> Using key K4 (>>), one passes from page 1 to page 2 and vice versa.
Return to the operating mode takes place automatically , after 2 minutes, or manually using the KM key for about 10 seconds
.
6.1 - Displaying the system parameters
Pressing down key KM for about 10 seconds and then using key K1 (INFO), the menu for the display of the operating parameters of the remote time control is selected. Using keys K1 (<<) and K4 (>>), it is possible to display the information listed below:
· TMP ESTERNA external temperature
· PRESSIONE data not available
· TMP MANDA TA
boiler temperature
· BRUCIATORE data not available
· TMP SAN domestic hot water temperature (only with water heater)
· PORT A T A SAN data not available
· STATO SAN domestic hot water mode status (0 inactive, 1 active)
· TMP RITORNO data not available
· TMP AMBIENT room temperature
· REG AMBIENT room temperature requested
· TEMP CALC supply temperature calculated
· CODICE ID identification number of the remote control version
· VERSIONE number of the version of the remote control’s firmware Return to the operating mode takes place automatically , after 2 minutes, or manually using the KM key for about
10 seconds
.
Possible values adopted by the afore-mentioned variables:
14
6.2 - Displaying and changing the system parameters
Pressing down key KM for 10 second and then key K2 (IMP), the menu which permits the display, and possible change, of the operating parameters of the remote time control, which can be accessed by the installer , is selected. Using keys K1 (<<) and K4 (>>), it is possible to display the information listed below:
· CURVA EST Thermoregulation - setting the gradient (see section 6.2.1)
· COMPENS AMB Thermoregulation - correction with room temperature (see section 6.2.2)
· MODO FUNZ Thermoregulation - choosing the operating modes (see section 6.2.3)
· TIPO ORA Hour type displayed (see section 6.2.4)
· PROGR SAN Domestic hot water programme type (see section 6.2.5)
· PRE RISCALD Automatic pre-heating (see section 6.2.6)
· TMP MIN RIS Minimum supply temperature (see section 6.2.7)
· REG RISCALD Maximum supply temperature (see section 6.2.8)
· TMP AMB T0 Pre-setting of T0 room temperature (see section 6.2.9)
· TMP AMB T1 Pre-setting of T1 room temperature (see section 6.2.9)
· TMP AMB T2 Pre-setting of T2 room temperature (see section 6.2.9)
· REG SAN Pre-setting of domestic hot water temperature (see section 6.2.10)
· RIEMPIMENTO Pre-setting of system supply type (see section 6.2.11)
· CORR TAMB Correcting the room temperature read (see section 6.2.12)
· IMP FABBRIC Factory settings (see section 6.2.13) The change of each parameter can be carried out by using the keys K+ o K– within the range permitted by said parameter (see table below) Return to the operating mode takes place automatically , af ter 2 minutes, or manually using the KM key for about 10 seconds
.
All the afore-mentioned operating parameters are memorized within an Eeprom-type memory , which stores them even if the power to the remote control is cut.
Possible values adopted by the afore-mentioned variables:
(1) It is not possible to set the maximum value of the TMP MIN RIS parameter greater than the minimum of the REG RISCALD parameter. V ice versa, it is not possible to set the minimum value of the REG RISCALD parameter lower than the maximum value of the TMP MIN RIS parameter. (2) The function is subject to the management of said parameter by means of the boiler control board to which the remote control is connected.
15
6.2.1 - Thermoregulation - Setting the gradient
Pressing key KM down for 10 seconds and then key K2 (IMP), the CURV A EST parameter is immediately displayed. Using the keys K+ o K- , it is possible to change the setting. The graph in figure 4, shows the ratio between the external temperature and the supply temperature calculated in relation to the value assigned to the CURV A EST parameter. The installer can use this graph in order to establish the exact CURVA EST to be set in relation to the geographic area where the installation will take place (typically , the curves chosen for Italian regions range between 0.6 and
1.1 for radiant panel systems). The adjustment of the supply temperature in relation to the external temperature is active only if the MODO FUNZ parameter is set at 3 (see section 6.2.3)
Figure 4 - Ratio between supply temperature and external temperature
Normally, the adjustment of just the CUR V A EST (gradient) as per the graph in figure 4, is not enough to adjust the supply temperature exactly, in relation to the external temperature. For this purpose, it is possible to adjust the parallelism of this line as well, taking action directly on the remote time control, requesting a room temperature other than 20°C. Figure 5 shows how the line (in this case with a CURVA EST gradient = 2.0) can move on a parallel in relation to the temperature set on the remote control. To set the temperature on the remote control, see section 5.2, or 5.8.
This type of setting is advisable above all else for radiant panel systems, where the remote control cannot be positioned as a sensor of a characteristic room temperature, or in situations where there are thermostats which regulate the temperature zone by zone.
EAST Curve 2.0
EAST Curve 0.8
EAST Curve 0.4
Calculated supply temperature (TEMP CALC) °C
External temperature (TMP ESTERN) °C
EAST Curve
EAST Curve 2.5
EAST Curve 1.6
EAST Curve 1.2
Room temperature requested = 20°C
16
6.2.2 - Thermoregulation - Correction with room temperature
Pressing key KM down for 10 seconds, then key K2 (IMP) and finally key K4 (>>) the COMPENS AMB parameter is displayed immediately. Using keys K+ o K-, it is possible to change the setting. When the value of the COMPENS AMB parameter differs from 0, the compensation of the room temperature is active. The effect of the room temperature compensation is the automatic parallel shift of the curve as per figure 4. In this way , the parallel translation of the line, which in the previous section was carried out manually , is now made automatically on the basis of the temperature registered by the remote control in the room. The shifting of the curve, defined as Delta, is calculated on the basis of the error between the value of the room temperature requested and that actually read by the remote control. The Delta is also influenced by the parameter defined as room compensation (COMPENS AMB) which can be selected from between 0 and 20 (as can be seen from the graph in figure 6). The rules for the correct setting of the room compensation value (COMPENS AMB) are:
· the compensation of the room temperature makes it possible to put the heating system in steady state much faster and automatically compensate the imperfect selection of the CURVA EST;
· the higher its value, the quicker the putting of the heating system in steady state is;
· too high a value may cause the system to react too quickly, involving the consequent sudden igniting and switching off of the boiler;
· generally, a large heating system, which requires a long period before it reaches steady state, requires a higher room compensation value with respect to a smaller heating system which requires a shorter period before it reaches steady state;
· the room compensation works correctly only if the CURVA EST has been correctly chosen. The room compensation is active only if the MODO FUNZ parameter is set at value 3 (see section 6.2.3)
This type of adjustment is advised for all radiant panel type systems where the remote time control can be installed in an area where the temperature is characteristic of the entire area to be heated.
Figure 5 - Parallel adjustment of the line as per figure 4.
Calculated supply temperature (TEMP CALC) °C
External temperature (TMP ESTERN) °C
EAST CURVE set at 2.0
17
Figure 6 - Automatic parallel translation of the line
Figure 7 - Room compensation curve
Compensation of the room temperature
·The curves, present in the following graph, show how the delta is calculated on the basis of the COMPENS AMB value set and the room temperature.
COMPENS AMB = 15
COMPENS AMB = 8
COMPENS AMB = 4
COMPENS AMB = 0
Delta calculated by the compensation of the room temperature
CURVA EST without influence of room compensation (COMPENS AMB = 0)
Calculated supply temperature (TEMP CALC) °C
External temperature (TMP ESTERN) °C
Delta on calculated supply temperature °C
Current room temperature °C
COMPENS AMB 20
COMPENS AMB 10
COMPENS AMB 6
COMPENS AMB 4
COMPENS AMB 2
Reference conditions:
- CURV A EST 2.0
- Room temperature required 20°C
- Room temperature read 18°C
Room temperature required = 20°C
18
6.2.3 - Thermoregulation - Choosing the operating modes
The MODO FUNZ parameter is one of the most important to be adjusted. On the basis of the setting of this parameter, the type of thermoregulation to be used in the system is chosen. Therefore, it is indispensable to choose the type of thermoregulation carefully , in relation to the type of system owned, in order to achieve the best degree of comfort envisaged. Pressing key KM down for more than 10 seconds, then key K2 (IMP), and subsequently key K4 (>>) until MODO FUNZ is displayed, it is possible to select, using keys K+ e K-, one of the 4 types of thermoregulation available: 1 · room thermoregulation with set supply temperature 2 · room thermoregulation in relation to the room temperature 3 · room thermoregulation in relation to the external temperature, with or without room temperature 4 · thermoregulation with exclusion of the room temperature and two-point adjustment
Room thermoregulation with set supply temperature (MODO FUNZ = 1)
The user sets the room temperature desired and the remote control generates a heat request to the boiler (pump comes on), every time the room temperature falls below the temperature requested. Vice versa, every time the room temperature rises above that set, the remote control interrupts the heat request to the boiler (pump switches off). In this operating mode, the supply temperature to the radiators is set at the value set on the REG RISCALD parameter (see section 6.2). This type of thermoregulation is recommended for a system with radiators or convector fans
Room thermoregulation in relation to the room temperature (MODO FUNZ = 2)
The heating supply temperature is calculated using a PID type algorithm so that the room temperature, read by the remote control, corresponds with that set by the user; the value calculated corresponds to the value of the heating supply temperature (TEMP CALC parameter , see section 6.1). This value however is always limited to the value set on the REG RISCALD parameter (see section 6.2.8). This type of thermoregulation is recommended for systems with radiators, convector fans or radiant panels where the temperature of the room where the remote time control is located is characteristic of all the rooms heated.
Room thermoregulation in relation to the external temperature, with or without room temperature (MODO FUNZ = 3)
The heating supply temperature is calculated using a formula which takes into account the CURV A EST selected (see section 6.2.1); the value calculated (TEMP CALC parameter , see section 6.1) corresponds with the setting of the heating supply temperature. This value however is always limited to the value of the REG RISCALD parameter set (see section 6.2.8). In this operating mode, if the COMPENS AMB parameter (see section 6.2.2) is set at zero, the adjustment of the supply temperature is made without considering the room temperature read by the remote control. Therefore, the installer will have to find the right angle of the line, adjusting the CURVA EST parameter as per section 6.2.1 and the right parallelism, adjusting the room temperature as per sections 5.2 and 5.8. This type of thermoregulation is recommended for a system with radiant panels where the rooms heated are served by room thermostats which act on the area valves, or in systems where it is not possible to install the remote control in a place where the room temperature registered is characteristic of the building. In such cases, the supply temperature is adjusted exclusively in relation to the external temperature according to the ratio shown in the graphs as per figures 4 and 5.
If the COMPENS AMB parameter (see section 6.2.2) is set at a value other than zero, the room temperature registered by the remote time control intervenes to correct the supply temperature on the basis of the matters already illustrated in section 6.2.2 and figures 6 and 7. This type of thermoregulation is recommended for a system with radiant panels where the temperature of the room in which the remote time control is located is characteristic of all the rooms heated.
In all the afore-mentioned cases, when the external temperature is greater than the calculated supply temperature (parameter TEMP CALC as per section 6.1), the heating is shutdown.
Thermoregulation with exclusion of the room temperature and two-point
19
adjustment (MODO FUNZ = 4)
The room temperature and the external temperature do not interact on the operating mode of the thermoregulation in question. The adjustment of the supply temperature to the radiators is carried out at two temperature levels, set respectively at TMP MIN RIS (minimum supply temperature, see section 6.2.7) and REG RISCALD (maximum supply temperature, see section 6.2.8). The meaning usually attributed to the parameters TMP AMB T0, TMP AMB T1 and TMP AMB T2 (room temperature levels which can be selected for the automatic operating mode of the room thermostat, see section 5.8), changes as indicated below:
TMP AMB T0 = heating request absent TMP AMB T1 = heating request present with supply adjustment at value of TMP MIN RIS parameter TMP AMB T2 = heating request present with supply adjustment at value of REG RISCALD parameter By means of the programming of the heating timer (see section 5.8), the user establishes when, over a period of
24 hours, to set the boiler going in heating mode (levels T1 or T2) or not (level T0) and what the setting of the supply temperature must be (TMP MIN RIS or REG RISCALD) for the water of the heating system.
When this thermoregulation operating mode is selected:
- the PRE RISCALD function (see chapter 6.2.6) is automatically disabled;
- the programming of the TMP AMB T0, TMP AMB T1 and TMP AMB T2 parameters as per section 5.9, is automatically disabled;
- during the manual adjustment of the room temperature, as per section 5.2, it permits the adjustment of the desired room temperature, at three levels corresponding to 0 = TMB AMB T0, 1 = TMP AMB T1 and 2 = TMP AMB T2.
6.2.4 - Hour type displayed
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until TIPO ORA is displayed, it is possible to select, using keys K+ e K-, the 12 hours or 24 hours timing display. Setting the parameter at 1, one obtains the 24 hour display, whilst setting it at 2 the 12 hour display is shown.
6.2.5 - Domestic hot water programme type
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until PROGR SAN is displayed, it is possible to select, using keys K+ e K-, the operating of the domestic hot water function, in the following manner: 1 = domestic hot water service always active; 2 = possibility of carrying out the time programming of the domestic hot water service independently from the
heating service (the function, when active, is shown on the display using the clock symbol). For the programming
of the domestic hot water service, refer to section 5.8; 3 = the domestic hot water service follows the time programming made for the heating service exactly. Due to how the boiler is conceived, it is advisable to keep the parameter at 1 or 3.
6.2.6 - Automatic pre-heating
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until PRE RISCALD is displayed, it is possible to select, using keys K+ e K-, the type of pre-heating one intends to carry out. The parameter can adopt the following values: 1 = pre-heating enabled in adaptive mode; 2 = pre-heating enabled with a ramp of 3°C/hour; 3 = pre-heating disabled.
If this parameter is set at 3, during the time programming of the heating function, the user must bear in mind to switch on the heating in advance with respect to the effective need, due to the thermal inertia of the plant (high in the case of radiant panels, low in the case of radiators, uninfluential in the case of convector fans). So as to avoid having to take these times into consideration, being among other things difficult to calculate and variable in relation to the season and type of plant, it is advisable to keep the parameter at the value of 1 or 2, where the remote time control carries out an automatic detection of the system’s features (with a frequency of 10 minutes), thus calculating the thermal inertia, or the time necessary for achieving a specific room temperature. In
20
this way , when the time programming is carried out it will be sufficient to introduce the switching on and switching off of the heating in correspondence with the time period of effective need; the remote time control will automatically take steps to bring forward the ignitions so as to obtain the desired room temperature, in the time period set.
6.2.7 - Minimum supply temperature
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until TMP MIN RIS is displayed, it is possible to select, using keys K+ e K-, the minimum supply temperature for the heating. It is recommended that it be left at 20°C. Only in the event that the MODO FUNZ parameter (see section 6.2.3) has been set at 4, the TMP MIN RIS must be adjusted to the supply temperature, corresponding to the energy saving timeband TMP AMB T1.
6.2.8 - Maximum supply temperature
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until REG RISCALD is displayed, it is possible to select, using keys K+ e K-, the maximum supply temperature for the heating. It is recommended that it be left at 45°C. In the event that the MODO FUNZ parameter has been set at 1 (see section 6.2.3), the REG RISCALD must be adjusted to the supply temperature, corresponding to the adjustment temperature. In the event that the MODO FUNZ parameter has been set at 4 (see section 6.2.3), the REG RISCALD must be adjusted to the supply temperature, corresponding to the comfort timeband TMP AMB T2.
6.2.9 - Pre-setting of room temperature
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until TMP AMB T0/T1/T2 is displayed, it is possible to select, using keys K+ e K-, the room temperature values, envisaged during the time programming of the heating function (see section 5.8). The operation for adjusting TMP AMB T0, TMP AMB T1 and TMP AMB T2, corresponds with the same regulation as per section 5.9. If the MODO FUNZ parameter has been set at 4 (see section 6.2.3) the adjustment of TMP AMB T0, TMP AMB T1 and TMP AMB T2 is disabled.
6.2.10 - Pre-setting of domestic hot water temperature
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until REG SAN is displayed, it is possible to select, using keys K+ e K-, the exit temperature of the domestic hot water between 40 and 65°C. The function corresponds with the adjustment of the domestic hot water as per section 5.3.
6.2.11 - Pre-setting of system supply type
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until RIEMPIMENTO is displayed, it is possible to select, using keys K+ e K-, the following values: 1 = manual 2 = automatic 3 = disabled
If the boiler comes with an automatic valve, for filling the heating circuit, with the RIEMPIMENTO parameter set at 2, the remote time control takes steps to carry out the filling of the boiler each time the water pressure drops below a pre-established value. In the event that the parameter is set at 1or 3, the filling of the system must always take place manually (follow the boiler instruction manual, so as to carry out the filling of the heating circuit’s system).
6.2.12 - Correcting the room temperature read
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until CORR TAMB is displayed, it is possible to select, using keys K+ e K-, the correction of the reading of the room sensor, with respect to the actual temperature. If the room temperature read by the remote time control is influenced by the installation position (e.g. installation on a wall which faces outside, installation on a thermal brigde, etc.) it is possible to correct the temperature of a value by more or less two degrees, using the CORR TAMB parameter.
21
6.2.13 - Factory settings
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until IMP FABBRIC is displayed, it is possible to select, using keys K+ e K-, whether to re-set the initial factoring settings. If during the programming of the remote time control, programmings or adjustments are carried out so that the system no longer correctly functions, it is possible to reset the initial factory settings, so as to re-start from a known programming basis. During the selection of the IMP F ABBRIC parameter , you will be requested to set the language, the day of the week and the current time once again.
Once the factory settings have been re-set, it is necessary to re-set the recommended settings as per the table in section 6.2.
6.3 - Diagnostics
6.3.1 - models AXIA-Ei, BMS-Ei and BME-Ei
Pressing the KM key down for more than 10 seconds and then key K3 (ERR), a menu of diagnostic faults is selected. The menu permits the display of the last functioning anomaly of the boiler and/or the remote control according to the following scheme:
Description of operating error Error number
Domestic hot water sensor or water heater sensor faulty 06 “Heating 1” system safety thermostat intervention 24 “Heating 1” boiler temperature sensor or supply sensor 05 Flame blocked 01 Safety thermostat against boiler overheating intervention 02 Flame control unit stalled (example: flue gas pipe obstructed) 14 H
2
O load not completed 16 attempts in one day (probable water loss) 21
H
2
O load underway 18
H
2
O load not completed in time requested (probable water loss) 19
Return to operating mode takes place automatically, after 2 minutes have elapsed, or by pressing key KM down for 10 seconds.
22
6.3.2 - models AXIA-H, ECOPLUS, ECOBI, INKAS, NOV ADENS, INKADENS and CIELODENS
ERRORS DISPLAYED BY CR04 ERRORS DISPLAYED BY BOILER ERROR 01 L01
ERROR 04 L46 ERROR 06 L05 ERROR 07 L07 ERROR 11 L03 ERROR 15 L45 ERROR 17 L17 ERROR 18 L25 ERROR 18 E01 ERROR 20 L19 ERROR 23 L32 ERROR 24 L02 ERROR 36 E50 ERROR 41 L20 ERROR 41 E20 ERROR 46 E21 ERROR 47 E22 ERROR 56 E07 ERROR 57 E02 ERROR 63 L33 ERROR 64 E17 ERROR 65 E12 ERROR 66 E11
ERROR 70 E51 For the correspondence of errors displayed in boiler to refer to the installation manual of the boiler to the chapter
Diagnostic
6.4 - Setting the language
Pressing down the KM key for more than 10 seconds and then key K4 (>>), it is possible to access page 2 of the menus. Using key K1 (LING), the menu for selecting the user language is selected. The wording corresponding to the set language (Italian, French or English) is shown on the display. Using keys K+ o K- it is possible to select the desired language from among those available:
· IT ALIANO (Italian)
· FRANCAIS (French)
· ENGLISH By pressing key K4 (OK), the choice is confirmed and the display returns to show page 1 of the menu.
Return to operating mode takes place automatically, after 2 minutes have elapsed, or by pressing key KM down for 10 seconds. The language selected is memorized within an Eeprom-type memory, which stores this information even if the power is cut to the remote control.
6.5 - Operating parameters - PAR Menu
Not available
6.6 - Operating parameters - PARC Menu
Not available
23
To open the remote control, once it has been fixed to the wall, remove the front as indicated in figure 12.
Figure 11 - Positioning within housing
Figure 12 - Opening of the control
Figure 9 - Passing the wires through
Figure 10 - Connecting the
connectors
Subsequently , using the fixing screws provided, fix the back of the remote control to the wall, t aking care to pass the two wires inside the central hole (see figure 9). Extract the terminal board from its housing and connect the two wires (see figure 10). Then replace the terminal board in its housing and close the remote control (see figure 11).
Figure 8 - Removal of front part
6.7 - Installation
The remote control is connected to the boiler by means of the connection of two unpolarized wires which must run in ducts other than those containing the 230 Vac power lines. The remote control is equipped with a specific screw terminal for this connection.
In order to gain access to the terminal board, remove the front part of the remote control using a screwdriver as lever at the point indicated (see figure 8):
COSMOGAS s.r.l.
Via L. da Vinci 16 - 47014
MELDOLA (FC) ITALY
info@cosmogas.com
www.cosmogas.com
Loading...