COSMOGAS AGUADENS Installation, Operating And Maintenance Manual

Page 1
62403581 - R00 07-01-2014_GB/IE
INSTALLATION, OPERATING AND MAINTENANCE MANUAL
AGUADENS
WALL-MOUNTED GAS CONDENSING WATER HEATERS
Page 2
2
AGUADENS
COSMOGAS
INDEX
1 - GENERAL SAFETY RECOMMENDATIONS ..................................................................................................4
1.1 - National laws and regulations .................................................................................................................................. 5
2 - GENERAL INFORMATION .............................................................................................................................6
2.1 - Presentation ............................................................................................................................................................. 6
2.2 - Model overview ........................................................................................................................................................ 6
2.3 - Manufacturer ............................................................................................................................................................ 7
2.4 - Symbols key ............................................................................................................................................................. 7
2.5 - Maintenance ............................................................................................................................................................. 7
2.6 - Warranty ................................................................................................................................................................... 7
3 - MAIN COMPONENTS .....................................................................................................................................8
4 - OPERATION .................................................................................................................................................10
4.1 - Operation and intended use of the appliance .........................................................................................................11
4.2 - D.H.W. circulation pump performance curves .........................................................................................................11
4.3 - Examples of installation ......................................................................................................................................... 12
5 - INSTALLATION .............................................................................................................................................14
5.1 - Opening the packaging .......................................................................................................................................... 14
5.2 - Dimensions and minimum safety clearances ......................................................................................................... 14
5.3 - Choosing suitable installation location ................................................................................................................... 14
5.4 - Mounting the appliance .......................................................................................................................................... 14
5.5 - Domestic hot and cold water .................................................................................................................................. 14
5.6 - Gas ......................................................................................................................................................................... 15
5.7 - Condensate drain ................................................................................................................................................... 16
5.8 - Safety valve ............................................................................................................................................................ 16
5.9 - Hydraulic and gas connections .............................................................................................................................. 17
5.10 - Water softener (on request) ................................................................................................................................. 17
5.11 - Electrical connections ........................................................................................................................................... 18
5.11.1 - Power supply cable connection ............................................................................................................... 19
5.12 - D.H.W. buffer tank hydraulic layout ...................................................................................................................... 19
5.12.1 - Anti- legionella precaution ....................................................................................................................... 19
5.12.2 - External secondary return conguration ................................................................................................. 19
5.13 - Flue systems ........................................................................................................................................................ 20
5.13.1 - Exhaust ue with indipendent combustion air grille type B23 ................................................................. 21
5.13.2 - “Split 80/80PP” System (polypropylene) (Type C43; C53; C83) AGUADENS 16-22-27 ......................... 22
5.13.3 - “Split 80/80PP” System (polypropylene) (Type C43; C53; C83) AGUADENS 37 ................................... 23
5.13.4 - “Split 80/80PP” System (Type C43; C53; C83): accessories available ................................................... 24
5.13.5 - “Split 80/80PP” System (Type C43; C53; C83): installation examples ................................................... 25
5.13.6 - “60/100PP vertical coaxial” System (polypropylene) (C13; C33 Type) ................................................... 26
5.13.7 - “60/100PP horizontal coaxial” System (polypropylene) (C13; C33 Type) ............................................... 27
5.13.8 - “60/100PP Coaxial” System: accessories available ................................................................................ 28
5.13.9 - “60/100PP Coaxial” System: installation examples ................................................................................ 29
5.13.10 - “80/125PP vertical coaxial” System (polypropylene) (C13; C33) .......................................................... 30
5.13.11 - “80/125PP Coaxial” System: accessories available .............................................................................. 31
5.13.12 - “80/125PP Coaxial” System: installation examples .............................................................................. 32
6 - OPERATING .................................................................................................................................................33
6.1 - Operating ............................................................................................................................................................... 33
6.1.1 - User instructions ....................................................................................................................................... 33
6.1.2 - Filling the condensate drain siphon .......................................................................................................... 33
6.2 - General recommendations regarding the supply of gas ........................................................................................ 33
6.3 - Type of gas for which the appliance is regulated. .................................................................................................. 33
6.4 - Conversion of the appliance from one type of gas to another ................................................................................ 34
6.5 - Ignition .................................................................................................................................................................... 36
6.6 - Measurement and adjustment of gas pressure adjustment ................................................................................... 37
6.7 - Measurement of combustion air pressure .............................................................................................................. 38
6.8 - Measurement and adjustment of CO2 levels ......................................................................................................... 39
6.9 - Adjusting the domestic hot water ow rate ............................................................................................................. 40
7 - USE ...............................................................................................................................................................41
7.1 - Valve positions ....................................................................................................................................................... 41
7.2 - Display ................................................................................................................................................................... 41
7.3 - Ignition procedure .................................................................................................................................................. 41
7.4 - “User menu” ........................................................................................................................................................... 42
7.5 - Adjustment of domestic hot water temperature ...................................................................................................... 42
7.6 - Pump control features ............................................................................................................................................ 42
Page 3
3
AGUADENS
COSMOGAS
INDEX
7.7 - Pumps anti-block .................................................................................................................................................... 42
7.8 - Display Energy Saving mode ................................................................................................................................. 42
7.9 - “User menu” Parameters ........................................................................................................................................ 43
7.10 - “Installer menu” & parameters .............................................................................................................................. 44
7.11 - Diagnostics ........................................................................................................................................................... 46
7.11.1 - Diagnostics “Loc” block fault codes and potential solution ...................................................................... 47
7.11.2 - Diagnostics “E” error fault codes and potential solutions ........................................................................ 49
7.11.3 - Diagnostics “AttE” alarm fault codes and potential solutions .................................................................. 50
8 - MAINTENANCE ............................................................................................................................................51
8.1 - General recommendations ..................................................................................................................................... 51
8.2 - Casing removal ...................................................................................................................................................... 52
8.3 - Burner and fan removal .......................................................................................................................................... 53
8.4 - Gas burner and heat exchanger outer surface cleaning procedure ....................................................................... 53
8.5 - Condensate siphon cleaning procedure ................................................................................................................. 54
8.6 - Ignition and ame isonising electrode position ....................................................................................................... 55
8.7 - Circulation pump replacement procedure .............................................................................................................. 55
8.8 - Domestic water ow meter replacement procedure ............................................................................................... 56
8.9 - Safety valve replacement procedure ...................................................................................................................... 56
8.10 - Procedure for draining the water heater ............................................................................................................... 57
8.11 - Fan test mode procedure ..................................................................................................................................... 57
8.12 - Gas burner minimum and maximum performance test mode procedure ............................................................. 57
8.13 - Checking the ionisation current ............................................................................................................................ 57
8.14 - Water temperature measurement sensor testing procedures .............................................................................. 57
8.15 - AGUADENS models 16, 22 and 27 electrical connections .................................................................................. 58
8.16 - AGUADENS models 16, 22 and 27 internal multi-core wiring diagram ................................................................ 60
8.17 - AGUADENS model 37 electrical connections ...................................................................................................... 62
8.18 - AGUADENS model 37 multi-core wiring diagram ................................................................................................ 64
9 - TECHNICAL DATA ........................................................................................................................................66
10 - COMMAND MENU DIAGRAM ....................................................................................................................68
11 - ENGINEERS TEST MODE..........................................................................................................................69
12 - CE DECLARATION OF CONFORMITY ......................................................................................................70
13 - WARRANTY ................................................................................................................................................71
13.1 - General warranty conditions ................................................................................................................................ 71
13.2 - Instructions for lling-in the warranty card ............................................................................................................ 71
13.3 - Warranty limitations .............................................................................................................................................. 71
Page 4
4
AGUADENS
COSMOGAS
If you smell gas
1. - Close the gas cock.
2. - Ventilate the room.
3. - Do not switch on any electric device, telephone included.
4. - From another room, call a professionally qualified technician immediately or the gas supply company. Call the Fire Service if the former are not available.
If you can smell combustion products
1. - Switch the appliance off.
2. - Ventilate the room.
3. - Call a professionally qualied technician.
Explosive or highly ammable products
Do not store or use explosive or highly ammable materials
such as paper, solvents, paints, etc...in the same room where the appliance is installed.
Installation, modications
The gas appliance must be installed, calibrated or modied
by professionally qualied staff, in compliance with National
and local Standards, as wells as the instructions in this manual.
Incorrect installation or poor maintenance can cause
injury/damage to persons, animals or objects, for which the manufacturer cannot be deemed liable.
The appliance must be connected to an approved ue
system. Failure to comply with this regulation can lead to serious risks for people and animals
A domestic hot water temperature level exceeding 51°C
can cause permanent injury/damage to people, animals and objects. Special care should be taken to protect children, the elderly and those with special needs using non-accessible
blending valves to limit the ow hot water temperature at
outlets.
The water heater ue system must not be modied by
unqualied person.
The ue system terminals should not be obstructed in any
way.
Do not leave parts of the packaging and any replaced parts
within the reach of children.
Seal the adjustment devices after every calibration.In agreement with the provisions for use, the user must
keep the installation in good working order and guarantee reliable and safe operation of the appliance.
We also highlight the importance of an annual scheduled
maintenance contract with a professionally qualified technician.
The end user must have maintenance performed on the
appliance only by professionally qualied technicians in
accordance with this manual and in full compliance with both local and national standards.
Before performing any cleaning or maintenance, disconnect
the appliance from the mains power supply.
After having performed any cleaning or maintenance works,
make sure that all internal etc.
This appliance is not intended for use by persons (including
children) with reduced physical and sensory conditions or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
This manual is an integral and essential part of the product
and must be kept carefully by the user, for possible future consultation. If the appliance must be transferred or if you should move and leave the unit to another user, always ensure that this manual remains with the new user and/ or installer.
Any accessories or kits which might be added must be
original Cosmogas products.
This appliance must be intended only for the use for which
it has been expressly declared: production of domestic hot water for civilian use.
Any contractual and extra contractual liability of the
manufacturer is excluded for damage caused by installation errors or errors in use and however due to failure to comply with the instructions given by the manufacturer or by failure to comply with applicable national and/or local laws.
For safety reasons and respect for the environment, the
packaging elements must be disposed of in the relevant separate waste collection centres.
In case of breakdown
In the case of appliance breakdown and/or malfunctioning, deactivate it and do not attempt any repairs. Contact a
professionally qualied technician only. If components must
be replaced for repair to be successful, only use original spare parts. Failure to comply with the above can jeopardise the safety of the appliance.
Professionally qualied technician.
Professionally qualied technicians with certied training
covering gas boilers and/or gas water heaters as envisioned by the law.
Technical drawings
All drawings in this manual relating to electrical wiring, hydraulic and gas layouts are purely indicative. The external services such as electrical cable types and sizes, water services pipes and gas services must always be checked
by a professionally qualied technician or engineer to verify
compliance with all relevant standards, Laws and codes of good practice.
Carbon Monoxide. Every year deaths and serious injuries occur due to carbon monoxide poisoning. This tragedies are avoidable if certain preventative measures such as the following are undertaken:
Ensure that all boilers, water heaters, room heaters, stoves
and hobs which burn oil, natural gas, LP gas, coal, peat, wood and wood pallets are serviced regularly. Servicing is needed at least once per year to ensure safety. the
service person should be qualied and trained to service the specic types of appliance
If an appliance is fitted in a dwelling, then a carbon
monoxide detector should always be tted. There are two types avaiable: a simple detector works like a re alarm to emit a loud noise and ashing light if carbon monoxide is
detected or a more sophisticated version which will also switch off the appliance to provide more safety.
1 - GENERAL SAFETY RECOMMENDATIONS
Page 5
5
AGUADENS
COSMOGAS
1 - GENERAL SAFETY RECOMMENDATIONS
1.1 - National laws and regulations
- M.D. n°37 dated 22/01/2008 (former Law n°46 dated 05/03/90)
- Law n°10 dated 09/01/91
- Presidential Decree n°412 dated 26/08/93
- Presidential Decree n°551 dated 21/12/99
- Legislative Decree n° 192 dated 19/08/05
- Legislative Decree n° 311 dated 29.12.06
- UNI 7129 Standard
- UNI 7131 Standard
- UNI 11071 Standard
- IEC 64-8 Standard
All the gas appliances must be installed by a competent
and qualied person, in accordance with relevant clauses of
applicable standards and raccomandations. These include but may not be limited to the following:
- I.S. 813 Domestic gas installations.
- I.S. 820 Non-Domestic gas installations.
- IEE Wiring Regulations.
- BS 5546:2010 - Specication for installation and maintenance
of gas-fired water-heating appliances of rated input not exceeding 70 kW net.
- BS 5440-2:2009 - Flueing and ventilation for gas appliances
of rated input not exceeding 70 kW net (1st, 2nd and 3rd family
gases) specication for the installation and maintenance of
ventilation provision for gas appliances.
- BS 6644:2011 - Specification for the installation and
maintenance of gas-red hot water boilers of rated inputs
between 70 kW (net) and 1.8 MW (net) (2nd and 3rd family gases).
- BS 6891:2005+A2:2008 - Installation of low pressure gas
pipework of up to 35 mm (R1 1/4) in domestic premises (2nd
family gas) specication.
- BS 5482-1:2005 - Code of practice for domestic butane and
propane gas burning installations. Installations at permanent dwellings, residential park homes and commercial premises, with installation pipework sizes not exceeding DN 25 for steel and DN 28 for corrugate stianless steel or copper.
- BS 5482-2:AMD 12046: June 2001 - Domestic butane and
propane gas burning installations. Installations in caravans and non-permanent dwellings.
- BS 5482-3:2005 - Domestic butane and propane gas burning
installations. Installations in boats yachts and other vessels.
- Building regulations issued by Department of the Environment
and Building Standards Regulations.
- Gas safety (Installation and Use) Regulations current issue.
- BS 6700 - Design, installation, testing and maintenance of
services supplying water for domestic use within buildings
and their cartilages - Specication.
- UK Health and safety at work Act.
- All relevant Building Regulations.
- Local Water Bye Laws.
- Water Regulations.
- Health & Safety legislation.
Failure to install this appliance correctly could lead to prosecution. It is your own interest and that of safety to ensure that the law is complied with. Manufacturer’s instructions must not be interpreted as over-riding statutory obligations under any circumstances.
Page 6
6
AGUADENS
COSMOGAS
2.1 - Presentation
Congratulations! You have purchased one of the best products on the market. Each individual part is proudly designed, produced, tested and assembled within the COSMOGAS establishment, thus guaranteeing the best quality control. This product has been developed thanks to the COSMOGAS who pay the highest
respect to the environment with class 5 classication
as being the last polluting as envisioned by EN297 (and EN 483) Technical Standards. COSMOGAS place great importance to the end-of-life cycle for their appliances with all of components being easily separated for recycling.
2.2 - Model overview
AGUADENS XX
16 = Water heater with maximum heat input of 25.5 kW 22 = Water heater with maximum heat input of 34.8 kW 27 = Water heater with maximum heat input of 43.0 kW 37 = Water heater with maximum heat input of 60.0 kW
Condensing, indoor, pre-mixed, ecological gas water heater.
2 - GENERAL INFORMATION
Page 7
7
AGUADENS
COSMOGAS
2.3 - Manufacturer
COSMOGAS srl Via L. da Vinci 16 47014 - Meldola (FC) Italia Tel. 0543 498383 Fax. 0543 498393 www.cosmogas.com info@cosmogas.com
2.4 - Symbols key
ATTENTION !!!
El ectric s hock haza rd. Failure to comply with these recommendations can jeopardise the good working order of the appliance or cause serious damage to persons, animals or objects.
ATTENTION !!!
General hazard. Failure to comply with these recommendations can jeopardise the good working order of the appliance or cause serious damage to persons, animals or objects.
Important indication symbol.
2.5 - Maintenance
It is recommended to perform regular yearly maintenance of the appliance for the following reasons:
- to maintain a high yield and manage the domestic hot water plant economically (with low fuel consumption);
- to achieve a high level of safety;
- to maintain the level of environmental compatibility of the combustion high;
Offer your customer a scheduled maintenance contract.
2.6 - Warranty
see chapter 13.
2 - GENERAL INFORMATION
Page 8
8
AGUADENS
COSMOGAS
1 - Command and control board 2 - Electric connections board 3 - Electric control board box 4 - Lower cover
5 - Recirculation tting cap 6 - Water ow rate measuring device
7 - Cold water inlet temperature sensor (1007) 8 - Fan 9 - Non-return valve 10 - Air/gas manifold
11 - Double D.H.W. output sensor (1001 and 1005)
12 - Cold water inlet tting 13 - D.H.W. outlet tting
14 - Recirculation Pump 15 - Detection electrode
16 - Wall xing brackets
17 - Secondary return manual control valve
18 - Conveying tting 19 - Combustion air and exhaust ue connection
20 - Combustion analysis points 21 - Double exhaust ue temperature sensor (1006 and
1014)
22 - Spark generator 23 - Ignition cables 24 - Combustion gases non-return valve. 25 - Air inlet manifold 26 - Gas valve 27 - Front casing 28 - Safety valve 29 - Display 30 - Control board 31 - Gas valve adjustment service access hatch
3 - MAIN COMPONENTS
Figure 3.1 - Water heater internal components
16
28
6
8
25
16
26
4
3
2
21
24
22
9
19
11
23
17
10
15
20
12
7
31
1
13
18
30
5
29
14
27
020003.01.042
Page 9
9
AGUADENS
COSMOGAS
32 - Pump air vent
33 - Front casing xing tabs
34 - Left ignition electrode 35 - Right ignition electrode 36 - Gas burner viewing port 37 - Flue condensate collection collar drain pipe (connected to siphon) 38 - Burner 39 - Air/gas mixing unit 40 - Condensate drain siphon 41 - Safety valve drain pipe 42 - Non-return valve 43 - Condensate collection tank
44 - Domestic hot water temperature sensor (1002)
3 - MAIN COMPONENTS
Figure 3.1 - Water heater internal components
44
38
32
35
33
41
34
43
37
39
40
42
36
020003.01.043
Page 10
10
AGUADENS
COSMOGAS
Key to gure 4.1:
1 = Water heater 2 = Combustion air intake spigot
3 = Exhaust ue spigot 4 = Exhaust ue temperature sensor 1 (Par. 1006) 5 = Exhaust ue temperature safety sensor 2 (Par. 1014)
6 = Sealed chamber 7 = Water collection tub
8 = D.H.W. outlet temperature sensor 1 (Par. 1001) 9 = D.H.W. outlet temperature safety sensor 2 (Par. 1005)
10 = Burner 11 = Titanium plated stainless steel VRC type heat exchanger 12 = Fan
13 = Cold water inlet temperature sensor (Par. 1007) 14 = Condensate collection siphon with sediment decanter 15 = Air/gas mixer 16 = Pneumatic gas valve 17 = Safety valve 18 = Secondary return manual control valve 19 = Recirculation pump 20 = Non-return valve
21 = Water ow rate measuring device
22 = Secondary return connection 23 = Secondary return blanked connection
24 = Domestic hot water sensor (Par. 1002) 25 = Gas isolation valve 26 = Gas inlet 27 = Domestic cold water inlet 28 = Safety valve condensate drain collector 29 = Domestic hot water outlet
4 - OPERATION
Figure 4.1 - Hydraulic layout
AGUADENS
Figure 4.2 - Secondary return manual control valve
020003.01.044
OPEN Secondary return not present
CLOSE Secondary return present
020003.01.045
Page 11
11
AGUADENS
COSMOGAS
4.1 - Operation and intended use of the appliance
This product is a condensing gas appliance, intended for the production of domestic hot water for use by people. Consider the D.H.W. circulation pump performance curves
as detailed in paragraph 4.2 and as illustrated in gure 4.3.
The temperature of the domestic hot water can be adjusted by following the relevant procedure in chapter 7.5.
This appliance must be connected to a domestic hot
water distribution system which has adequately sized pipes to convey the correct water volume and all pipes
should be tted with good quality insulation to optimise
the performance of the water heater.
Before installation of the domestic cold and hot water
services should be ushed thoroughly in order to remove
any residues or impurities which could compromise the good working order of the appliance.
4 - OPERATION
Figure 4.3 - Curve of the domestic water circuit losses
Head losses (bar)
Water ow rate (l/min)
This appliance is not suitable for installation outdoors.
It must not be exposed to temperature below zero or temperature above 50°C. Select a suitable sheltered location for the appliance.
This appliance must be installed in a location which will
not cause damage to objects or property in the event of water leaking from within the appliance or connections at the appliance.
Check gure 5.1 concerning the minimum safety
distances for installation and future maintenance.
4.2 - D.H.W. circulation pump
performance curves
The pump curves as shown in gure 4.3 outline the
performances which can be archived. It is the designer’s responsability to ensure that the available pump head pressure will achieve the desired results.
Key to gure 4.3
I = Aguadens 16 II = Aguadens 22 and Aguadens 27 III = Aguadens 37
Page 12
12
AGUADENS
COSMOGAS
Figure 4.4 - Example of installation basic
Figure 4.6 - Example of installation with storage tank
4.3 - Examples of installation
In gures 4.4, 4.5, 4.6, 4.7, 4.8 and 4.9 you can see some
examples of installation.
Figure 4.5 - Example of installation with recircolation and external pump
Figure 4.7 - Example of installation with storage tank with supply direct to the water heater
4 - OPERATION
Page 13
13
AGUADENS
COSMOGAS
4 - OPERATION
Figure 4.8 - Example of installation with solar panel and storage tank
Figure 4.9 - Example of installation with solar panel
Page 14
14
AGUADENS
COSMOGAS
5.1 - Opening the packaging
The appliance is supplied in cardboard packaging. Open
following the instructions given on the aps of the packaging
itself.
5.2 - Dimensions and minimum
safety clearances
It is necessary to leave free spaces around the appliance as
illustrated in gure 5.1 both for installation and maintenance.
5.3 - Choosing suitable
installation location
ATTENTION !!! The appliance must be installed
exclusively on a solid, vertical wall, which can support the weight.
The appliance must be installed in a suitable room taking into account the following factors:
- connection of the exhaust/air intake pipes;
- connection of the gas supply pipe;
- connection to the cold water supply;
- connection of the domestic hot water supply;
- electrical connection;
- connection of the siphon and safety valve to a suitable
drain;
5.4 - Mounting the appliance
Refer to gure 5.3:
1.- place the paper template, provided with the appliance, against the wall;
2.- check that the template is square;
3.- mark the holes for the plugs and hydraulic ttings on the
wall;
4.- remove the paper template;
5.- make the holes “A” and introduce the wall plugs “B”;
6.- hang the appliance on the plugs “C”
7.- make the appliance hydraulic and gas connections;
8.- make the hydraulic ttings.
5.5 - Domestic hot and cold water
ATTENTION !!! If water hardness exceeds 25°F (250 mg/l) a polyphosphates water softener must be installed on the incoming cold water supply (see paragraph 5.10).
ATTENTION !!! Install a lter with mesh no wider than 0.5 mm² in the domestic cold water inlet.
ATTENTION !!! The domestic hot water
piping materials and ttings must be capable of
withstanding temperatures of a least 95°C and 10 bar pressure. These circuits must be protected with suitable expansion together with both temperature and pressure relief safety devices in accordance with all relevant safety standards.
In gure 5.2 the service and maintenance valves are not shown. Hydraulic and gas connections should be tted with
isolation valves to accomadate service and maintenance works.
1 - 3/4” recirculation 2 - 3/4” D.H.W. outlet 3 - 3/4” gas inlet 4 - 3/4” cold water inlet 5 - Fumes exhaust/Air intake 6 - Support attachments 7 - Ø20 condensate drain
A = 305 mm (MODELS 16-22-27) - 484 mm (MODEL 37) B = 120 mm (MODELS 16-22-27) - 175 mm (MODEL 37) C = 125 mm (MODELS 16-22-27) - 304 mm (MODEL 37)
5 - INSTALLATION
Figure 5.1 - Minimum safety distances
Figure 5.2 - Dimensions and attachments centre to centre distances
Page 15
15
AGUADENS
COSMOGAS
5 - INSTALLATION
5.6 - Gas
ATTENTION !!! It is prohibited to operate the appliance with the incorrect gas type. Ceck the data label on the appliance for Natural gas (G20) or Propane gas (G31) to ensure that the correct appliance in being installed.
ATTENTION !!! Check that the gas and supply pressure are those for which the appliance has been adjusted.
Two situations are possible: A - the gas and supply pressure correspond to the
adjustment of the appliance. In this case, it can be connected;
B - the gas and supply pressure do not correspond to the
adjustment of the appliance. In this case, the appliance must be converted to the type of gas and supply pressure corresponding to those of the supply available.
The appliance is provided with the relevant gas conversion kit.
Before the gas pipes are purged it is essential to ensure
that the internal surfaces are clean and free of metal or
plastic lings or any other solid pieces or liquids;
An isolation valve must be installed on the gas supply
pipe adjacent to the appliance;
ATTENTION !!! Before supplying gas to the
appliance, it is essential that the gas pipes have been pressure tested in accordance with the most recent applicable gas standards.
to prevent damage to the appliance gas valve, the
supply pressure should not exceed 50 mbar under any circumstances;
if the gas pipe-work must be tested in excess of 50
mbar, ensure that the appliance is fully isolated.
Figure 5.2 shows the position and the diameter of the gas connection on the appliance. Ensure that the gas service pipe-
work is adequately sized to provide the maximum volume ow
rate at the required minimum pressure.
Figure 5.3 - Appliance wall xing detail
Page 16
16
AGUADENS
COSMOGAS
Figure 5.4 - Safety valve drain and condensate drain connection
B
C
A
020002.01.005
D
A
E
020002.01.006
5 - INSTALLATION
5.7 - Condensate drain
There is a siphon inside the appliance for the evacuation
of condensate (see gure 3.1 detail “40”) and to prevent
combustion products from escaping, whose end
corresponds to the pipe “B” in gure 5.4. This termination must be conveyed into an anti-odour siphon (gure
5.8 detail “G”) to prevent bad odours returning into the environment (the anti-odour siphon “G” is supplied on request). The tank “A” is mounted in the factory as indicated
in gure 5.4, the exhaust pipe “F” is mounted in the factory as indicated in gure 5.5. In particular, the condensate
discharge must comply with the following:
for room used for residential purposes and for ofce with
more than 10 users, it can be connected to the domestic waste disposal plant by means of appropriate siphon with disjunction capable of preventing the pressurisation of the system (siphon prepared within appliance) and to prevent the return of bad odours from the sewer (detail
“G” in gure 5.8). If the room used for ofce purposes
has less than 10 users, before connection with the domestic waste drain, a condensate neutraliser is good practice (see chapter 9 for the value of acidity of the condensate and the quantities).
be connected to a plastic (not copper) drain pipe with a
minimum internal pipe diameter equal to or greater than 13 mm;
be installed in a way to prevent the liquid from freezing;
therefore pay attention to any external passings. It is prohibited to drain into gutters or drainpipes;
to slope continuously towards the drain point, avoid high
points, which could pressurise the pipe;
5.8 - Safety valve
The appliance is protected against overpressures by a
safety valve calibrated to 10 bar (see gure 3.1 detail “28”). The safety valve drain (detail “C” in gure
5.4), along with the condensate drain (detail “B” in gure
5.4) must be conveyed to a pipe “F” (see gure 5.5) with
minimum internal diameter of 13 mm. The pipe “F” must be
then taken to the anti-odour siphon (detail “G” gure 5.8).
This drain with siphon is used to prevent overpressures if the valve is opened and makes it possible for the user to
check the eventual intervention. The pipe “F” in gure 5.5 is supplied by standard along with the tank “A” in gure
5.4. The anti-odour siphon “G” in gure 5.8 is provided on
request.
ATTENTION !!! If not connected to the drain,
whenever the safety valve should intervene, it could cause damage to persons, animals or objects.
Figure 5.5 - Condensate drain pipe
A
F
020002.01.017
Page 17
17
AGUADENS
COSMOGAS
Figure 5.6 - Water and gas connections
5 - INSTALLATION
E
A
F
B
C
D
G
020003.01.004
Figure 5.8 - Siphon funnel (on request)
F
G
020002.01.028
min10 mm max 30 mm
5.9 - Hydraulic and gas connections
The appliance is supplied as per standard with the ttings illustrated in gure 5.6, where:
A = Ø 18 recirculation
B = domestic hot water Ø 18
C = 3/4” gas isolation valve (EN 331 type-approved)
D = 1/2“ domestic cold water isolation valve
E = gas Ø 18
F = domestic cold water Ø 18
Once the hydraulic and gas connections have been made, proceed with assembly of the lower cover “G” as indicated
in gure 5.6.
5.10 - Water softener (on request)
If the appliance is installed in a geographical area where domestic water has hardness exceeding 25°F (250 mg/l), a polyphosphates softener must be installed on the cold water
supply (see gure 5.7 detail “B”), in order to safeguard the
appliance from any lime scale deposits.
Proceed as follows for installation (refer to gure 5.7):
1.- connect the softener “B” to the isolation valve “A”;
2.- mount the isolation valve “A” to the appliance tting;
3.- proceed with the installation of the cold water inlet pipe
into the tting behind the softener “B”;
4.- before re-mounting the lower cover, it is necessary
to cut out the plastic section between “C” and “D” to accomodate the softener “B”.
ATTENTION !!! Please note that if the water
hardness levels are likely to be extremely high, it would be essential to consult with a water softening specialist who may recommend a more sophisticated system. In this regard, we would recommend that the incoming water supply should be tested in advance of any decision to purchase the appliance.
Figure 5.7 - Polyphosphates softener (on request)
B
A
C
B
A
D
020003.01.008
Page 18
18
AGUADENS
COSMOGAS
5.11 - Electrical connections
ATTENTION !!! The appliance is only electrically
safe when it has been correctly connected to an
efcient earth circuit, performed as envisioned by the
current Safety Standards.
This fundamental safety requirement must be met. If in doubt, request a thorough control of the electric plant by a
professionally qualied technician.
Have a professionally qualied technician check that the
electric plant is suitable for the electric power required by the appliance, indicated on the plate.
The appliance must be connected to the mains electricity
using a cable coupler. The use of adapters, multiple sockets, extensions, etc. is not allowed.
The appliance must be connected to the mains electricity
using a three-polar electric cable, with double isolation, minimum section of 1.5 mm² and resistant to a minimum temperature of 70°C (characteristic T).
For connection to mains electricity, a bi-polar switch
must be envisioned in the vicinity of the appliance with a contacts opening distance of at least 3mm, as envisioned by the current regulations on the subject.
Respect the polarity between the neutral phase during
connection of the appliance.
Make sure that the water plant pipes are not used as
earth points for the electric or telephone plant. This piping is not suitable for this purpose, moreover, serious corrosion damage would occur in a very short time, on the appliance, piping and radiators.
ATTENTION !!! the appliance is not protected against the effects caused by lightening.
D
C
C
C
B
A
020003.01.009
5 - INSTALLATION
Figure 5.9 - Electric connections
Key for gure 5.9
A = Commands board box; B = Electric connections board lid;
C = Connections lid closing aps;
D = Electric connections board;
Key for electric contacts
PM = Not used CH = Not used BUS = Not used TA = Not used 0-10 = Not used SE = Not used SB = Storage tank sensor (if present) MF = Multi-function output PE = Boiler pump (if present) DN = Not used (2 = Neutral; 3 = Line) L1 = Appliance power supply line N = Appliance power supply neutral EARTH SYMBOL = Earth contacts
020002.01.010
Page 19
19
AGUADENS
COSMOGAS
5.11.1 - Power supply cable connection
Proceed as follows to connect the power supply cable (refer
to gure 5.9):
1.- use a three-polar cable with double isolation, with minimum section of 1.5 mm²
2.- remove the casing from the appliance following the relevant instructions in paragraph 8.2;
3.- rotate the panel “A” towards the front of the appliance;
4.- operate on the aps “C” and open the lid “B” as
indicated by the arrow;
5.- lay the power supply cable through the fairlead in proximity of the contacts “L1”, “N” and earth symbol;
6.- strip the cable, making sure to keep the earth cable (yellow green) 20 mm longer than the other two;
7.- connect the yellow-green cable to the earth terminals (see symbol)
8.- connect the brown cable (Phase) to the terminals L1
9.- connect the blue cable (Neutral) to the terminals N
5.12 - D.H.W. buffer tank
hydraulic layout
The hydraulic connection must be made as in gure 5.10.
Proceed as follows for the electric connection (refer to the
gure 5.9):
1.- disconnect the electric power supply from the appliance;
2.- disconnect and remove the temperature sensor (detail
“44” in gure 3.1) from the domestic hot water outlet pipe;
3.- lay a bi-polar electric cable with minimum section of 1.5 mm², which goes from the appliance to the storage tank temperature sensor and connect it to the appliance at terminalss “8” and “9” (SB);
5 - INSTALLATION
Figure 5.10 - water connection to the storage tank
KEY 1 AGUADENS water heater 2 Recirculation (if activated) * 3 Domestic hot water outlet 4 Gas inlet 5 Cold water 6 Storage tank 7 Storage tank load pump 8 Storage tank sensor 9 Domestic utilities 10 Hydraulic safety unit (by the installer) 11 Cold water inlet 12 So me state re quir e thi s safe ty pressure-temperature relief valve
* The recirculation line is not mandatory.
4.- connect the other end of the cable to the storage tank temperature sensor;
5.- introduce the temperature sensor inside the storage tank
sample point (see gure 5.10 detail “8”).
6.- Connect the electric power of the storage tank pump (see
gure 5.10 detail “7”) to “PE” terminals of the water heater.
The AGUADENS appliances can be connected to a storage tank even following installation. In this case,
the parameter 3012 must be set at the value of 1.
The temperature of the water stored inside the storage tank can be selected by the user in a range between 40 and 70°C.
ATTENTION !!! A domestic hot water
temperature level exceeding 51°C can cause permanent injury/damage to persons, animals and objects. Children, the elderly and disabled must be protected against the potential risks of scalding, by introducing devices that limit the temperature of use of domestic hot water to utilities.
5.12.1 - Anti- legionella precaution
If the appliance is connected to a storage tank for the preparation of domestic hot water, a disinfection cycle is envisioned against the legionella bacterium. This cycle envisions taking the storage tank to a temperature of 60°C (temperature at which the legionella bacteria dies) at least every week. It is for this reason that the water (at certain times) can reach the utilities at a higher temperature that than set with the relative command.
ATTENTION !!! A domestic hot water
temperature level exceeding 51°C can cause permanent injury/damage to persons, animals and objects. Children, the elderly and disabled must be protected against the potential risks of scalding, by introducing devices that limit the temperature of use of domestic hot water to utilities.
5.12.2 - External secondary return
conguration
If the appliance is envisioned with external recirculation
unit, the recirculation cut-off valve (detail of gure 4.2) must
be turned to the closed position.
Page 20
20
AGUADENS
COSMOGAS
5.13 - Flue systems
ATTENTION !!! The relevant national and local
regulations must be strictly adhered to when installing
the exhaust ue and combustion air pipes.
ATTENTION !!! The exhaust ue gases from
the appliance can reach 90°C in certain conditions.
Therefore, the plastic ue components must be capable
of withstanding high temperatures and they must be
approved for these specic appliance.
ATTENTION !!! This appliance is the
“condensing” type. The polypropylene materials used
in the manufacture of plastic exhaust ue system
which are approved for use are designed to prevent corrosion which would otherwise be caused to the acidity of the condensate. AISI316 stainless steel
exhaust ue system can also be designed for this
purpose.
Regarding this, remember that the appliances of this type must have exhaust and intake pipes supplied by the manufacturer of the appliance itself. Other types of pipes, if used, must however be type-approved for this intended use. The types of exhaust for which the appliance is approved are given in the features table at the end of the
manual under “type” and o the features plate afxed to the appliance, also under “type”. The symbols used to dene
exhaust is reported below:
- B23, separated with intake in room and exhaust through wall or roof.
ATTENTION !!! If the appliance is installed with the
B23 type exhaust, it will take in air for combustion from the surrounding environment. Therefore, all precautions must be taken regarding ventilation of the rooms, which are prescribed by the national and/or local Standards.
- C13, coaxial in vertical wall
- C33, coaxial at the roof
- C43, separated with exhaust in ue, combined with intake
in common channel.
ATTENTION !!! The appliances installed in type
C43 must only be connected to conventional ues.
- C53, separated with exhaust on roof and intake on wall or however, in two potentially different pressure points.
- C63, the appliance can be tted to type-approved exhaust
and intake pipes of other brands.
ATTENTION !!! With the C63 type exhaust,
the condensate coming from the chimney cannot be conveyed into the appliance.
- C83, separated with wall intake or another point independent from the intakes of other appliances and
ue exhaust.
Figure 5.11 - Exhaust/intake systems
5 - INSTALLATION
Page 21
21
AGUADENS
COSMOGAS
During operation, especially in winter, a plume will be visible as the water vapour in the exhaust gases come into contact with the outside air. This plume should not cause any concern however the installer should discuss the matter with the customer prior to commencement of the installation in case the aesthetical impact of this plume might cause a problem.
5.13.1 - Exhaust ue with indipendent
combustion air grille type B23
In the case of B23 type combustion agent air/fumes exhaust systems, it is indispensable that the rooms in which the appliances are installed have at least as much air as that required by combustion and ventilation of the room. It is therefore good practice to remember that the combustion of
1 m³ of gas requires 11 cm³ of air. The natural ow of air must
take place directly through permanent openings made in the outside walls of the room to be ventilated; however away from sources of pollution, such as: vents of dubious origin, airborne industrial exhaust etc.
The ventilation openings must meet the following requirements:
have sections with net passage of at least 6 cm² for
every kW of heat input installed, with minimum of 100 cm²;
be realised in a way that the opening inlets both inside
and outside the wall cannot be blocked;
be protected for example with grids, metal meshes, etc.
The net section of the passage must not be reduced by these elements;
be situated at a height more or less of the oor and such
not to disturb the correct operation of the combustion products exhaust devices. Where this position is not possible, the section of the ventilation openings must be increased by at least 50%.
The ow of air can also be obtained from an adjacent room
as long as:
it has direct ventilation, in compliance with the previous
points;
only this gas appliance is installed in the room to be
ventilated;
the adjacent room is not a bedroom;the adjacent room is not a common part of the building;the adjacent room is not an environment with re hazard,
such as a hangars, garages, combustible materials warehouse, etc.;
the adjacent room does not have a negative pressure with
respect to the room to be ventilated due to reverse draught (which can be caused by the presence in the room of
another appliance operating with any type of fuel, a replace
and any other intake device for which an adequate air intake has not been envisioned);
the ow of air from the adjacent room to that to be ventilated
can take place freely through permanent openings with total net section not less than that indicated at the start of this chapter.
In rooms where gas appliances are installed, it may become necessary, as well as the input of combustion agent air, also to evacuate the stale air, with resulting release of an additional equal amount of clean air.
If the stale air is evacuated with the aid of a mechanical tool (electric fan) the following conditions must be respected: a) If there is a common exhaust pipe in the room, it must be
capped;
b) The ventilation opening of the room in which the gas
appliance is installed must be increased depending on the
maximum air ow rate required at the electric fan.
c) The action of the electric fan must not affect the correct
evacuation of the combustion products. To this end, that
stated above must be veried by draft testing, running the
fan or extractor hood at its maximum power and the gas appliance at the maximum and minimum power.
5 - INSTALLATION
Flue terminal location
Page 22
22
AGUADENS
COSMOGAS
5.13.2 - “Split 80/80PP” System
(polypropylene) (Type C43; C53; C83) AGUADENS 16-22-27
The appliance is supplied as per standard without ttings
for the connection of the fumes exhaust/air intake. To connect it to a “80/80PP Split” system, the relevant kit must
be requested and must be installed as in gure 5.12.
Fitting “A” can rotate freely by 360°, guaranteeing optimum installation versatility.
On the exhaust ue side, it is mandatory to install
polypropylene plastic pipes or AISI 316L stainless steel which are resistant to damage from condensation.
Take particular care with the installation of pipes in
the part that passes through the wall to the outside. The normal maintenance operations must always be possible, therefore install the pipes in a sheath so that they can slide out.
The horizontal exhaust ue pipes must always have
an inclination of 2% with the fall back towards the appliances as opposed to the wall terminal.
The appliance is already set-up to collect the
condensate, which must be tted to a drain pipe (see
chapter 5.7).
ATTENTION !!! This condensate drain is
designed to make all liquid produced ow from a single
appliance. If several appliances are installed, each one must envision its own condensate drain.
The fumes exhaust/air intake system can be extended up to a maximum distance as indicated in chapter 9. Every 90° bend has a loss equivalent to 1 metre of linear pipe. Every 45° bend has a loss equivalent to 0.5 m of linear pipe.
ATTENTION !!! The exhaust ue terminal must
be appropriately protected against the effects of the wind (see also 7.11.1 error Loc 20).
ATTENTION !!! Mechanically secure the joints
between the various component elements of the
exhaust and intake pipe, through the use of xing systems or equivalent systems. See gure 5.14
ATTENTION !!! The temperature of the exhaust
pipe can reach 90°C during operations. If it must pass through a wall that is sensitive to these temperatures, insert a protective heat-isolation sheath.
ATTENTION !!! If the air intake and fumes
exhaust terminals are positioned in the same wall, they must remain at a minimum distance of 1 metre.
ATTENTION !!! The exhaust and intake pipes
must be appropriately sustained via rigid brackets positioned no more than 1 metre from each other. The
brackets must be xed to rigid walls that can support
the weight of the pipe itself.
Figure 5.14 - Fixing the exhaust and intake pipes
Figure 5.12 - Installation of the “80/80PP Split” System
Figure 5.13 - Clearance
5 - INSTALLATION
B
D
A
C
020002.01.011
Page 23
23
AGUADENS
COSMOGAS
5.13.3 - “Split 80/80PP” System
(polypropylene) (Type C43; C53; C83) AGUADENS 37
The appliance is supplied as per standard without ttings
for the connection of the fumes exhaust/air intake. To connect it to a “80/80PP Split” system, the relevant kit must
be requested and must be installed as in gure 5.15.
Fitting “A” can rotate freely by 360°, guaranteeing optimum installation versatility.
On the exhaust ue side, it is mandatory to install
polypropylene plastic pipes or AISI 316L stainless steel which are resistant to damage from condensation.
Take particular care with the installation of pipes in
the part that passes through the wall to the outside. The normal maintenance operations must always be possible, therefore install the pipes in a sheath so that they can be slid out.
The horizontal exhaust ue pipes must always have an
inclination of 2% with the fall back towards the appliance as opposed to the wall terminal.
The appliance is already set-up to collect the
condensate, which must be tted to a drain pipe (see
chapter 5.7).
ATTENTION !!! This condensate drain is
designed to make all liquid produced ow from a single
appliance. If several appliances are installed, each one must envision its own condensate drain.
The fumes exhaust/air intake system can be extended up to a maximum distance as indicated in chapter 9. Every 90° bend has a loss equivalent to 1 metre of linear pipe. Every 45° bend has a loss equivalent to 0.5 m of linear pipe.
ATTENTION !!! The exhaust ue terminal must
be appropriately protected against the effects of the wind (see also 7.11.1 error Loc 20).
ATTENTION !!! Mechanically secure the joints
between the various component elements of the
exhaust and intake pipe, through the use of xing systems or equivalent systems. See gure 5.17
ATTENTION !!! The temperature of the exhaust
pipe can reach 90°C during operations. If it must pass through a wall that is sensitive to these temperatures, insert a protective heat-isolation sheath.
ATTENTION !!! If the air intake and fumes
exhaust terminals are positioned in the same wall, they must remain at a minimum distance of 1 metre.
ATTENTION !!! The exhaust and intake pipes
must be appropriately sustained via rigid brackets positioned no more than 1 metre from each other. The
brackets must be xed to rigid walls that can support
the weight of the pipe itself.
Figure 5.17 - Fixing the exhaust and intake pipes
Figure 5.15 - Installation of the “80/80PP Split” System
Figure 5.16 - Clearance
5 - INSTALLATION
B
C
A
020008.01.011
Page 24
24
AGUADENS
COSMOGAS
5.13.4 - “Split 80/80PP” System (Type C43;
C53; C83): accessories available
To make the “80/80PP split” fumes exhaust/air intake system, we propose some of the most common accessories available; remember that a wide range can be consulted in the relevant catalogue: (the number after the code is used to recall the piece in the following drawings) 62617306 - N° 10 PP roof terminal 62617244 - N° 12 90° bend M/F PP 62617255 - N° 29 converts for pitched roofs from 15° up to 25° 62617236 - N° 11 extension M/F PP 62617249 - N°18 anti-slip bands for extensions PP
62617240 - N° 14 exible hose M.F. PP L=20m 62617241 - N°16 spacer for exible hose
62617238 - N° 17 telescopic joint PP
62617242 - N° 15 T-tting PP
62617246 - N° 13 45° bend M/F PP
COD. 62617306
5 - INSTALLATION
Page 25
25
AGUADENS
COSMOGAS
5.13.5 - “Split 80/80PP” System (Type C43;
C53; C83): installation examples
In gure 5.18 two examples of installation are given:
- exhaust into chimney with collection of condensate inside the appliance itself.
The horizontal part of the fumes exhaust must slope towards the appliance. The intake must slope towards the outside to prevent rain water entering.
- exhaust to the outside directly with the appliance pipes with condensate collection inside the appliance itself.
The intake must slope towards the outside to prevent rain water entering.
In gure 5.19 it is possible to see a separated type of fumes exhaust, where fumes exhaust was realised with exible hose
in polypropylene for piping of technical cells. The condensate produced in the vertical pipe must all be conveyed into the appliance. The intake must slope towards the outside to prevent rain water entering.
Figure 5.18 - Example of “80/80 PP System” installation
Figure 5.19 - Example of “80/80 PP System” installation
5 - INSTALLATION
Page 26
26
AGUADENS
COSMOGAS
B
D
A
C
020002.01.012
5.13.6 - “60/100PP vertical coaxial” System
(polypropylene) (C13; C33 Type) AGUADENS 16-22-27
The appliance is supplied as per standard without ttings
for the connection of the fumes exhaust/air intake. To connect it to a vertical 60/100 system, the relevant kit must
be requested and must be installed as in gure 5.20.
ATTENTION !!! Scrupulously follow the installation
phases of the coaxial pipe as illustrated in gure 5.22. In
particular:
1.- introduce the coaxial pipe “C” inside the bend “A”;
2.- x the external pipe using the stainless steel self-threading
screws “B”.
ATTENTION !!! The coaxial exhaust and
intake pipes must be appropriately sustained via rigid brackets positioned no more than 1 metre from each
other. The brackets must be xed to rigid walls that can
support the weight of the pipe itself.
ATTENTION !!! Once these operations have
been performed, check that the exhaust/intake terminal is exposed to the outdoors with the tolerances given in
gure 5.26
Take particular care with the installation of pipes in the part
that passes through the wall to the outside. The normal maintenance operations must always be possible, therefore install the pipes in a sheath so that they can slide out.
The horizontal exhaust ue pipes must always have an
inclination of 2% with the fall back towards the appliances as opposed to the wall terminal.
The combined exhaust/air intake pipe can be extended up
to a maximum distance as indicated in the table in chapter 9 at the end of the manual. Every 90° bend has a loss equivalent to 1 metre of linear pipe. Every 45° bend has a loss equivalent to 0.5 m of linear pipe.
Figure 5.20 - Installation of vertical coaxial system
Figure 5.21 - Quotes and hole centre to centre distances for coaxial drain pre-installation
Figure 5.22 - Positioning the coaxial pipe
5 - INSTALLATION
Page 27
27
AGUADENS
COSMOGAS
Figure 5.24 - Quotes and hole centre to centre distances for coaxial drain pre-installation
5 - INSTALLATION
Figure 5.25 - Positioning the coaxial pipe
5.13.7 - “60/100PP horizontal coaxial”
System (polypropylene) (C13; C33 Type) AGUADENS 16-22-27
The appliance is supplied as per standard without ttings
for the connection of the fumes exhaust/air intake. To connect the appliance to a 60/100 coaxial system, request
the relevant kit and install it as in gure 5.23.
ATTENTION !!! Scrupulously follow the installation
phases of the coaxial pipe as illustrated in gure 5.25. In
particular:
1. - introduce the coaxial pipe “C” inside the bend “A”;
2. - x the external pipe using the stainless steel self-threading
screws “B”.
ATTENTION !!!The coaxial exhaust and intake
pipes must be appropriately sustained via rigid brackets positioned no more than 1 metre from each
other. The brackets must be xed to rigid walls that can
support the weight of the pipe itself.
ATTENTION !!! Once these operations have
been performed, check that the exhaust/intake terminal is exposed to the outdoors with the tolerances given in
gure 5.26
Take particular care with the installation of pipes in the part
that passes through the wall to the outside. The normal maintenance operations must always be possible, therefore install the pipes in a sheath so that they can be slid out.
The horizontal exhaust ue pipes must always have an
inclination of 2% with the fall back towards the appliances as opposed to the wall terminal.
The combined exhaust/air intake pipe can be extended up
to a maximum distance as indicated in the table in chapter 9 at the end of the manual. Every 90° bend has a loss equivalent to 1 metre of linear pipe. Every 45° bend has a loss equivalent to 0.5 m of linear pipe.
B
D
A
C
020002.01.013
Figure 5.23 - Installation of horizontal coaxial system
Page 28
28
AGUADENS
COSMOGAS
5.13.8 - “60/100PP Coaxial” System:
accessories available
The following accessories are available on request to make the 60/100 coaxial fumes exhaust/air intake system: (the number after the code is used to recall the piece in the following drawings) 62617255 - N° 2 converts for pitched roofs from 5° to 25° extension L = 1000 mm 62617234 - N° 1 90° coaxial bend M/F PP 62617252 - N° 6 45° coaxial bend M/F PP 62617231 - N° 7 Coaxial extension L 1m PP 62617304 - N° 3 coaxial PP roof terminal 62617232 - N° 5 coaxial PP wall terminal
5 - INSTALLATION
Page 29
29
AGUADENS
COSMOGAS
5 - INSTALLATION
5.13.9 - “60/100PP Coaxial” System:
installation examples
When a coaxial exhaust is made (see gure 5.26), both vertical
and horizontal, the exhaust pipe slope upwards in a way to
make the condensate ow into the appliance.
ATTENTION !!! The horizontal terminal must be
protected against the accidental return of rain water. To do this, gables must be installed (or projections or balconies or relevant protections ) with the minimum
dimensions given in gure 5.26
Figure 5.26 - Examples of coaxial pipe installations
Page 30
30
AGUADENS
COSMOGAS
B
C
A
020008.01.013
5.13.10 - “80/125PP vertical coaxial”
System (polypropylene) (C13; C33) AGUADENS 37
The appliance is supplied as per standard without ttings
for the connection of the fumes exhaust/air intake. To connect it to a vertical 80/125 system, the relevant kit must
be requested and must be installed as in gure 5.27.
ATTENTION !!! Scrupulously follow the installation
phases of the coaxial pipe as illustrated in gure 5.29. In
particular:
1.- introduce the coaxial pipe “C” inside the bend “A”;
2.- x the external pipe using the stainless steel self-threading
screws “B”.
ATTENTION !!! The coaxial exhaust and
intake pipes must be appropriately sustained via rigid brackets positioned no more than 1 metre from each
other. The brackets must be xed to rigid walls that can
support the weight of the pipe itself.
ATTENTION !!! Once these operations have
been performed, check that the exhaust/intake terminal is exposed to the outdoors with the tolerances given in
gure 5.30
Take particular care with the installation of pipes in the
part that passes through the wall to the outside. Normal maintenance operations must always be possible, therefore install the pipes in a sheath so that they can slide out.
The horizontal exhaust ue pipes must always have an
inclination of 2% with the fall back towards the appliances as opposed to the wall terminal.
The combined exhaust/air intake pipe can be extended up
to a maximum distance as indicated in the table in chapter 9 at the end of the manual. Every 90° bend has a loss equivalent to 1 metre of linear pipe. Every 45° bend has a loss equivalent to 0.5 m of linear pipe.
Figure 5.27 - Installation of vertical coaxial system
Figure 5.28 - Quotes and hole centre to centre distances for coaxial drain pre-installation
Figure 5.29 - Positioning the coaxial pipe
5 - INSTALLATION
Page 31
31
AGUADENS
COSMOGAS
5.13.11 - “80/125PP Coaxial” System:
accessories available
The following accessories are available on request to make the 80/125 coaxial fumes exhaust/air intake system: (the number after the code is used to recall the piece in the following drawings) 62617255 - N° 2 converts for pitched roofs from 5° to 25° extension L = 1000 mm 62617321 - N° 1 90° coaxial bend M/F PP 62617322 - N° 6 45° coaxial bend M/F PP 62617323 - N° 7 Coaxial extension L 1m PP 62617325 - N° 3 coaxial PP roof terminal 62617324 - N° 5 coaxial PP wall terminal
5 - INSTALLATION
62617255
62617321
62617322
62617323
62617324
62617325
Page 32
32
AGUADENS
COSMOGAS
5.13.12 - “80/125PP Coaxial” System:
installation examples
When a coaxial exhaust is made (see gure 5.30), both vertical
and horizontal, the exhaust pipe slope upwards in a way to
make the condensate ow into the appliance.
ATTENTION !!! The horizontal terminal must be
protected against the accidental return of rain water. To do this, gables must be installed (or projections or balconies or relevant protections ) with the minimum
dimensions given in gure 5.30
Figure 5.30 - Examples of coaxial pipe installations
5 - INSTALLATION
Page 33
33
AGUADENS
COSMOGAS
6.1 - Operating
Before starting the appliance up, it is necessary to carry out the following.
6.1.1 - User instructions
Instruct the user regarding correct use of the appliance and the plant in general. In particular:
Give the installation and user manual and all
documentation contained in the packaging to the user.
Instruct the user concerning the special measures for the
exhaust of burned gases, informing them that they must
not be modied.
Inform the user regarding the correct adjustment of the
temperatures settings.
6.1.2 - Filling the condensate drain siphon
The siphon found inside the appliance (see gure 3.1 detail “40”), must be lled with water to create the water head able to prevent the fumes escaping from pipe “F” in gure 5.8.
Proceed as follows to do this:
(refer to gure 6.1)
1.- loosen the screw “E”;
2.- remove the lid “D” and the gaskets “C”;
3.- introduce a rubber hose into the opening “B” (do not confuse with “A”) and the other end of the hose into the funnel;
4.- use the funnel to slowly pour about 200 cm³ (a glass) of water;
5.- re-mount everything in reverse order.
6 - OPERATING
Figure 6.1 - Filling the condensate drain siphon
ATTENTION !!! If the appliance remains off for
more than 3 months, the siphon must be lled again as
explained above.
6.2 - General recommendations regarding the supply of gas
For commissioning of the appliance, have a professionally
qualied technician perform the following checks:
That the appliance is powered by the type of fuel for
which it is set-up.
That the gas supply pressure (with appliance operating
and at a standstill) is within the maximum and minimum values indicated in the table in chapter 9 at the end of the manual.
That the supply plant has all safety and control parts
envisioned by the current national and local Standards.
That the exhaust ue terminal discharge terminal and
the combustion agent air intake terminal are free from any obstruction.
That the exhaust ue terminal and combustion agent air
intake terminal are positioned outside the building.
That the condensate drain connection is connected.
ATTENTION !!! If you smell gas:
A - Do not switch on any electric device, telephone
included or any object that can cause sparks;
B - Immediately open doors and windows causing
a current of air that quickly cleans the gas from the room;
C - From another room, or from a neighbour’s,
immediately call a professionally qualied
technician or the gas supply company. Call the Fire Service if the former are not available.
6.3 - Type of gas for which the appliance is regulated.
There is a label on the front of the appliance certifying the gas supply type and pressure for which it is adjusted. The appliance may have the following 2 types of wording:
2H-G20-20mbar NATURAL GAS
means that the appliance is adjusted to operate with H type gas of the second family (natural gas) at a supply pressure of 20 mbar.
3P-G31-37mbar LP GAS
means that the appliance is adjusted to operate with type P gas (Propane, also called LP Gas) of the third family, at a supply pressure of 37 mbar.
Page 34
34
AGUADENS
COSMOGAS
6.4 - Conversion of the appliance from one type of gas to another
ATTENTION !!! Read these instructions carefully
before changing the gas:
- The gas appliance must be installed, calibrated or
modied by specialised staff in compliance with legal
terms;
- Check and be certain that the type of gas which is powering the appliance is compatible with the adjustment kit in your possession;
- Do not power the appliance with gases different from those envisioned.
Follow the instructions given below to change the gas: 1 - disconnect the electric power supply upstream from the
appliance;
2 - open the appliance casing as reported in chapter 8.2; 3 - access the control and command board as reported in
chapter 8.2;
4 - move the microswitch “B” from left to right to the “ON”
position (see gure 6.5);
5 - apply electric power to the appliance; 6 - the parameter 3001 will appear on the appliance’s
visual display, followed by its value;
7 - using the
and keys, access the
parameter 3002;
8. - press the RESET key to make the 3002 parameter
ash;
9. - using the
and keys, set the value of
the parameter 3002 to the new corresponding value
according to the table in gure 6.7.
10. - press the RESET key to conrm the modication.
11.- remove voltage from the appliance, re-position the
microswitch “B” from right to left in “OFF” position (see gure
6.5).
12. - close the gas supply;
13. - remove the air manifold making sure to turn it
externally and then slide it out of the fan inlet (see gure
6.2, detail “C”);
15. - remove the gas inlet pipe via the two ttings (see gure 6.2, details “H” and “L”);
16. - remove the clamping spring “M” from the seat “N”
releasing the valve “P”(See gure 6.3);
17. - slide the gas valve “P” out upwards;
18. - replace the gas nozzle “R” (see gure 6.4) with an appropriate one according to that stated in gure 6.7
under “Diameter of the gas nozzle”;
19. - remount the gas valve (see gure 6.3, detail “P”),
making sure to reposition the spring “M”.
20. - remove the gas supply pipe via the two ttings (see gure 6.2, details “H” and “L”);
21. - re-mount the air manifold (see gure 6.2, detail “C”);
22. - open the gas isolation valve;
23. - check for gas leaks an all joints.
ATTENTION !!! Perform the gas leak test according
to that established by the current Standard and only using
soapy water. The use of naked ames is prohibited.
G
L
E
A
D
B
H
F
C
020003.01.040
N
Q
O
P
M
020003.01.41
R
020002.01.042
Figure 6.4 - Replacing the gas nozzle
Figure 6.3 - Removing the gas valve
Figure 6.2 - Removing the air manifold
6 - OPERATING
Page 35
35
AGUADENS
COSMOGAS
ATTENTION !!! If you smell gas:
A - Do not switch on any electric device, telephone
included or any object that can cause sparks;
B - Immediately open doors and windows causing
a current of air that quickly cleans the gas from the room;
C - From another room, or from a neighbour’s,
immediately call a professionally qualied
technician or the gas supply company. Call the Fire Service if the former are not available.
24.- check the supply gas pressure, following the procedure in paragraph 6.6;
25.- open the CO2 adjustment screw completely (see gure
6.14 detail “A”);
26.- control and adjust the CO2, following the procedure in paragraph 6.8;
27.- instead of the label that identified the old state of adjustment, apply the sticker onto the front casing of
the appliance (see gure 6.6), certifying the appliance’s
new state of adjustment, as follows: apply label “B” if the appliance has been converted from NATURAL GAS to LP GAS; apply label “A” if the appliance has been converted from LP GAS to NATURAL GAS.
B – Microswitch
Figure 6.5 - Positioning the microswitch
A
B
020002.01.043
ON
OFF
6 - OPERATING
Model
Type
of gas
Setting
parameter
3002
Gas supply
minimum pressure
(mbar)
Gas supply
maximum
pressure
(mbar)
Gas nozzle
diameter
(mm)
CO2
Maximum
power
(%)
CO2
Minimum
power
(%)
O2
Maximum
power
(%)
O2
Minimum
power
(%)
16
NAT 50 15 27 4,9 9,0 ±
0,3 8,5 ± 0,2 4,8 ± 0,2 5,5 ± 0,2
LPG 51 25 45 3,7 10,5 ± 0,3 10,0 ± 0,2 4,8 ± 0,2 5,6 ± 0,2
22
NAT 52 15 27 6,7 9,0 ±
0,3 8,5 ± 0,2 4,8 ± 0,2 5,5 ± 0,2
LPG 53 25 45 5,2 10,5 ± 0,3 10,0 ± 0,2 4,8 ± 0,2 5,6 ± 0,2
27
NAT 54 15 27 8,0 8,7 ±
0,3 8,3 ± 0,2 4,7 ± 0,2 5,4 ± 0,2
LPG 55 25 45 6,0 10,1 ± 0,3 9,9 ± 0,2 4,7 ± 0,2 5,5 ± 0,2
37
NAT 54 15 27 10,0 8,7 ±
0,3 8,3 ± 0,2 4,7 ± 0,2 5,4 ± 0,2
LPG 55 25 45 6,5 10,1 ± 0,3 10,8 ± 0,2 4,7 ± 0,2 5,8 ± 0,2
Figure 6.6 - Labels certifying the new status of adjustment of the appliance
Figure 6.7 - Correspondence table for the parameter 3002 and the operating values
Page 36
36
AGUADENS
COSMOGAS
Figure 6.8 - Gas valve
A - Gas inlet pressure point.
6 - OPERATING
6.5 - Ignition
1.- open the gas isolation valve;
2.- power the appliance electrically;
3. - adjust the temperature desired for the domestic hot water
service using the
and keys. The icon , present on the display will inform regarding the operating state of the domestic hot water service:
a) xed
icon: domestic hot water inactive (no-one is withdrawing domestic hot water, or in the case of a storage tank, the delivery temperature as been reached)
b) ashing
icon: domestic hot water is being withdrawn.
A
020003.01.023
Page 37
37
AGUADENS
COSMOGAS
6 - OPERATING
6.6 - Measurement and adjustment of gas pressure adjustment
The gas supply pressure must correspond to that stated in the table in chapter 9 at the end of the manual.
For its verication, proceed as follows:
1.- close the gas isolation valve;
2.- access the components inside the appliance, following the procedure in paragraph 8.2;
3.- loosen the pressure point “A” (see gure 6.8);
4.- connect to a manometer with resolution of at least 0.1 mbar (1 mmH2O);
5.- open the gas isolation valve;
6.- check that the pressure does not exceed the value given in the table in chapter 9 under “gas supply maximum pressure”;
7.- open the domestic hot water tap to maximum;
8.- wait for the temperature of the water heater to stabilise;
9.- check that the pressure does not drop to a lower value than the “gas supply minimum pressure” given in the table in table 9. If the supply pressure does not respect the values described, operate upstream from the appliance in order to take it back within the minimum and
maximum eld;
10.- close the domestic hot water tap;
11.- close the pressure point “A” in gure 6.8;
12.- check for gas leaks an all joints.
ATTENTION !!! Perform the leak test using a soap
and water only. The use of naked ames is prohibited.
Page 38
38
AGUADENS
COSMOGAS
Figure 6.9 - Combustion agent air pressure point
Figure 6.11 - Controlling combustion air pressure
6.7 - Measurement of
combustion air pressure
As the appliance has an air/gas ratio xed in the factory, the
gas pressure at the burner is controlled indirectly by measuring the pressure of the combustion air inside the appliance and must correspond to that stated in the table in chapter 9, under “Combustion agent air pressure”. Proceed as follows for the check (refer to the Figures from
6.9 to 6.12):
1.- use a differential manometer with precision of at least 0.1 mbar (1 mmH2O);
2.- close the gas isolation valve;
3.- open the appliance casing following paragraph 8.2;
4.- remove the caps “A” (see gure 6.9);
5.- take the exible hose “D”, which is found inside the appliance and remove the cap “B” (see gure 6.9);
6.- insert the pipe “D” inside the hole indicated by the arrow
in gure 6.9;
7.- loosen the pressure point “H” in gure 6.10;
8.- take a silicone pipe with external diameter of 10 mm and
internal diameter of 7mm (detail “E” in gure 6.10) and
introduce it into pressure point “H”;
9.- insert pipe “E” into the hose as indicated in gure 6.11;
10.- connect the manometer to the two pipes “E” and “F” as
illustrated in gure 6.12, making sure to connect the pipe “E”
to the negative pressure point and tube “F” to the positive pressure point;
11.- close the casing “B” in gure 8.1. It is indispensable
to have a reliable measurement;
12.- switch the appliance on;
13.- press the
and RESET keys simultaneously for
more than 5 seconds to enter the “installer” menu
conrmed by the icon
appearing on the display.
14.- using the
and keys, access the
parameter 2010;
15.- press the RESET key to enter the parameter and use the
and keys, to modify the value to FAn;
16.- press the RESET key to conrm the modication. Now
just the fan will operate at maximum speed for 10 minutes.
17.- compare the pressure value read on the manometer with that given in the table in table 9, “Combustion air pressure”. If the pressure is at a lower value, check that there are no
obstructions in the combustion air/exhaust ue pipes or
that the combustion air/exhaust system does not exceed the parameters as detailed in table 9 entitled combustion air/exhaust pipe max. length for the relevant type;
18.- Once the control has ended, press the RESET key
again to enter parameter
2010 and via the
and
keys, change the value to OFF;
19.- press the RESET key to conrm the modication;
20.- hold the RESET key down for 5 seconds to exit the “installer” menu.
At the end of the control, remove the tube “E”, close the holes indicated by the arrow using the previously-removed caps “A”, close the pipe “D” using cap “B” and close the
pressure point “H” again as in gures 6.9 and 6.10.
6 - OPERATING
D
A
C B
020002.01.019
D
C
E
F
020002.01.020
Figure 6.10 - Combustion agent air pressure point
H
E
020002.01.022
Page 39
39
AGUADENS
COSMOGAS
Figure 6.13 - Combustion analysis points
6.8 - Measurement and
adjustment of CO2 levels
The appliance in normal operating mode and for altitudes within 1000 m, must have a CO2 (carbon dioxide) level in the exhaust
ue gases within the parameters as detailed in paragraph 9. A value
which is different to those detailed can cause malfunctions and is strictly prohibited. Combustion analysis must be performed to check and eventually adjust this value. Proceed as follows:
1.- check a combustion analyser to the appropriate point on
the fumes exhaust tting “B” in gure 6.13;
2.- open the domestic hot water tap fully;
3.- wait for the CO2 measurement to stabilise;
4.- compare the value measured with that given in the
table in gure 6.7, “CO2 maximum power”. If the value
measured is offset from the value read, it must be taken
back within the value given in the table in gure 6.7.
proceeding as follows:
a) turn screw “A” clockwise as in gure 6.14 to decrease
the level of CO2;
b) turn screw “A” anti-clockwise as in gure 6.14 to increase
the level of CO2;
5.- once the check has been completed, seal the screw “A” in
gure 6.14 with red pain or something similar;
6.- press the RESET key again to enter the parameter
2010 and use the and keys, to modify
the value to
LOu;
7.- press the RESET key to conrm the modication. Now
the burner will operate at minimum power for 10 minutes.
8.- wait for the CO2 measurement to stabilise;
9.- the value of CO2 at minimum power must correspond;
10.- once the check has been completed, seal the screw “B”
in gure 6.14 with red pain or something similar;
11.- press the RESET key again to enter the parameter
2010 and use the and keys, to modify
the value to
OFF;
12.- press the RESET key to conrm the modication.
13.- hold the RESET key down for 5 seconds to exit the “installer” menu.
14.- close the previously-opened domestic hot water tap.
6 - OPERATING
B
A
C
D
E
020002.01.015
Figure 6.14 - Gas valve
A - CO2 regulation screw
A
B
020002.01.045
E
F
G
020002.01.021
Figure 6.12 - Controlling combustion agent air pressure
Page 40
40
AGUADENS
COSMOGAS
6 - OPERATING
Figure 6.15 - domestic hot water ow rate selector
A
020003.01.016
6.9 - Adjusting the domestic
hot water ow rate
The appliance is tted with a domestic hot water maximum ow rate adjuster. However, if the appliance is installed in a
geographical area where the temperature of the cold water
is very low, the ow rate of domestic hot water that passes
inside the appliance may have to be reduced. It is therefore good practice to perform this adjustment:
1.- switch the appliance on;
2.- using the
and keys, adjust the
temperature of the domestic hot water to 48 - 50°C;
3.- open the domestic hot water tap fully. In the case of a single lever mixer, the position must be completely on “HOT”;
4.- wait 3 minutes for the temperature to stabilise;
5 - if the water temperatures too cold, the ow rate must
be reduced via the selector “A” in gure 6.15, until the
desired temperature is reached.
Page 41
41
AGUADENS
COSMOGAS
7 - USE
Figure 7.1 - Control board
Key for gure 7.1
A - On/off switch B - Reset Key C - Burner status (the burner is on when this icon is
present) D - State of the domestic water service: Icon off = domestic water off Icon on = domestic water active but not operating
Icon ashing
= domestic water active and operating E - Unit of measurement of the pressure displayed F - Heating plant pressure or indicator of the various
parameters inside the various menus G - Icon for entry into the “Installer” menu H - Domestic hot water temperature or indicator of the
values assumed by the various parameters L - Unit of measurement of the temperature displayed M - Appliance blocked (see paragraphs 7.11.1 and 7.11.2
for the diagnostics) N - Key for switching on and increasing the temperature of
the domestic hot water or for scrolling and changing the
value of the parameters P - Key for reducing the temperature of the domestic
hot water (below minimum, the domestic hot water is
switched OFF) or for scrolling and changing the value of
the parameters
7.1 - Valve positions
- The gas isolation valve must be open;
- Any service valves which are tted on the cold and hot water
supply pipes must be open.
7.2 - Display
During operation the display shows the appliance operating state as well as other information as indicated in chapter
7.11 (Diagnostics). Other parameters can be consulted through the “User menu” (see paragraph 7.9), which are useful for understanding operation of the appliance and to control the latest blocks or errors occurring.
After 5 minutes of normal operation, the display switches off completely to save energy. Just press any key to switch it back on. In the case of any anomaly, the display switches back on
automatically. This function can be modied by following
chapter 7.8 (Energy saving).
7.3 - Ignition procedure
1.- open the gas isolation valve;
2.- power the appliance electrically;
3.- adjust the temperature of the domestic hot water as per chapter 7.5.
The command and control equipment will switch the burner on. If ignition does not take place within 20 seconds, (the appliance automatically re-attempts ignition 3 times), it blocks and the
visual display will show Loc 1. Press the RESET key to restore the normal operating conditions. The appliance will automatically attempt a new ignition.
Page 42
42
AGUADENS
COSMOGAS
7 - USE
ATTENTION !!! If shutdown due to blocking is
repeated frequently, contact a qualied technician to reset
the normal operating conditions.
7.4 - “User menu”
Entry into the “User menu” is highlighted by the visual display
“F”, in gure 7.1, which indicates parameters that can assume
values from 1001 to 1999. To enter the “User menu”:
1.- hold the RESET key down for 2 seconds until the visual
display “F” shows 1001;
2.- press the
and keys to scroll the parameters
situated inside the user menu;
3.- hold down the RESET key for more than 2 seconds to exit the “User menu”;
If no key is pressed for more than 60 seconds, the menu is exited automatically. The parameters in paragraph 7.9 can be queried in this menu.
7.5 - Adjustment of domestic
hot water temperature
The temperature of the domestic hot water is adjusted by
operating on the
and keys. On pressing one
of the two keys, the visual display “H” in gure 7.1 will start to ash and show the temperature that is being set. The range
of adjustment for the temperature of the domestic hot water goes from 40°C to 60°C or from 40°C to 70°C if there is a storage tank present.
By holding the
key down also below 40°C, OFF will
appear to indicate switch-off of the domestic hot water service,
also highlighted by switch-off of the icon “D” in gure 7.1.
7.6 - Pump control features
To safeguard the lifespan of the appliance, improve the comfort generated and increase energy saving, timings have been introduced during operation. These timings are:
- Pump post-circulation: every time the domestic hot water service ends, the pump continues to operate for 2 minutes;
- Pumps anti-block: every 24 hours the recirculation pump and the storage tank loading additional pump (if present) are forced;
- Anti-legionella; if the appliance is connected to a storage tank for preparation of the D.H.W., every seven days the latter is forced to a temperature of 60°C to disinfect against the legionella bacteria. This function activates also two hours after the appliance has been powered electrically.
7.7 - Pumps anti-block
The pump switches on once every 24 hours for 15 seconds during the summer period in order to prevent any deposits that may block it. The storage tank loading pump (if present) is activated at the same time for the same reason.
7.8 - Display Energy Saving mode
To reduce the consumption of display energy, it will switch off automatically after 5 minutes from the last operation performed. This function can be deactivated or the time
modied via parameter 2100 present in the “Installer menu”
(see chapter 7.10). If the parameter is set at OFF, the display will remain on constantly.
Page 43
43
AGUADENS
COSMOGAS
7 - USE
Parameter Parameter Description M.U. 1001 Domestic hot water outlet temperature 1 °C 1002 Domestic hot water outlet temperature (or storage tank temperature, if present) °C 1003 No function / 1004 No function / 1005 Domestic hot water outlet temperature 2 (safety sensor) °C 1006 Exhaust ue temperature °C 1007 Cold water inlet temperature °C 1008 Ionisation current uA 1009 Status of the pump inside the appliance ON/OFF 1010 No function / 1011 No function / 1012 No function / 1013 No function / 1014 Exhaust ue temperature 2 (safety sensor) °C 1040 Current rotation speed of the fan rpm 1041 Fan rotation speed on ignition rpm 1042 Fan rotation speed in minimum power mode rpm 1043 Fan rotation speed in maximum power mode rpm 1051 Latest block condition recorded (Loc) (see chapter 7.11.1) / 1052 Latest error condition recorded (Err) (see chapter 7.11.2) / 1053 Number of times the burner has lost the ame n° 1055 Number of failed burner ignitions n° 1056 No function / 1057 Number of hours worked in domestic hot water mode h x 10 1058 Number of burner working days days 1059 Interval of time between the last two blocking errors (Err)
1 value in minutes; 2 value in hours;
3 value in days; 4 value in weeks;
1060 Interval of time between the last two blocks (Loc)
1061 Current rotation speed of the domestic hot water turbine rpm 1062 Current domestic hot water ow rate l/min
7.9 - “User menu” Parameters
To access the “User menu” follow that reported in paragraph 7.4. The following parameters can be queried in this menu:
Page 44
44
AGUADENS
COSMOGAS
7.10 - “Installer menu” & parameters
ATTENTION !!! The modication of these
parameters could cause the appliance, and therefore the plant, to malfunction. For this reason only a technician that has the awareness and in­depth knowledge of the appliances can modify them.
The appliance command and control board makes this parameter menu available to the technician for the analysis of operation and adaptation of the appliance to the plant. Proceed as follows to enter the “Installer menu”:
1.- hold the RESET and
keys down simultaneously
for 5 seconds until the 2001 parameter is displayed.
The symbol
appears on the display to indicate the
entry into the “Installer menu”.
2.- the
and keys can be used inside the
menu to scroll the parameters;
3.- once the parameter of interest has been displayed, it
can be modied as follows:
a.- press the RESET key to access the parameter (the
visual display “H” in gure 7.1 will start to ash);
b.- modify the value of the parameter using the
and
keys;
c.- press the RESET key to conrm the data modied
and go back to the list of parameters;
4.- To exit the “Installer menu”, hold down the RESET key
for 5 seconds until the symbol
disappears from the
display.
If no key is pressed for more than 5 minutes, the menu is
exited automatically. Any data variation that is not conrmed
with the RESET key will be lost.
ATTENTION !!! Any variation to the
parameters must be noted in the “Customised values” column present in the following table in order to facilitate the eventual replacement of the command and control board.
The following parameters can be changed or queried in this menu:
7 - USE
Parameter Parameter Description M.U. Setting range
Factory
value
Custo-
mised
values
2001 No function / / / /
2002 No function / / / /
2003 No function / / / /
2004 No function / / / /
2005 No function / / / /
2010 Forcing of fan and burner / OFF = No forcing
FAN = Forcing of fan only to max speed LOu = Forcing of burner to minimum power Ign = Forcing of burner to igni­tion power HIgH = Forcing of burner to maximum power rEg = Forcing of burner to maxi­mum power
OFF
2011 Forcing the pump / On = Pump on
OFF = Pump off
OFF
2012 No function / / / /
2013 No function / / / /
2014 Icons test on the display. By pressing the REST key, all of the
icons on the display light up. By pressing the RESET key again to display goes back to normal operation
/ / /
2020 No function / / / /
2021 No function / / / /
2022 No function / / / /
2023 No function / / / /
2024 No function / / / /
2027 No function / / / /
Page 45
45
AGUADENS
COSMOGAS
7 - USE
2040 No function / / / /
2041 No function / / / /
2042 No function / / / /
2043 No function / / / /
2060 Domestic hot water minimum power level % Da 1 a 50 1
2061 Domestic hot water maximum power level % Da 1 a 100 100
2062 Post-circulation in domestic hot water mode sec Da 10 a 900 120
2063 Maximum time for loading storage tank min Da 0 a 60 60 /
2064 Number of ow meter revs. for every litre of water rpm/lt Da 0 a 5 3,2
2066 Delay in the detection of the instantaneous domestic hot water sec Da 1 a 10 3
2067 Storage tank loading procedure / 0 = the storage tank is charged for
the time set in parameter 2063; 1 = OFF, the domestic hot water does not have priority over heating; 2 = ON, the domestic hot water always has priority over heating;
2
2080 Periodic maintenance meter
(after RESET, the meter automatically goes back to ON)
/ ON = Periodic maintenance
meter active; OFF = Periodic maintenance meter off; RESE = Meter reset
OFF
2081 Periodic maintenance meter: maintenance request time days From 0 to 1000 1000
2100 Energy saving display min OFF = display always on
From 1 to 30 = delay to switch­off in minutes.
5
Page 46
46
AGUADENS
COSMOGAS
7.11 - Diagnostics
During normal operation of the appliance, the visual display
in gure 7.1 continuously shows the state of work of the
appliance, via the following indications:
7 - USE
Parameter Parameter Description Display on visual display “H” in gure 7.1
AFro
Anti-freeze function active Appliance temperature (°C)
AttE
Appliance not in block but in attention mode Attention code (see chapter 7.11.3 for decoding)
Fixed on = Domestic hot water service on but not active
On ashing = Domestic hot water service on and active
Domestic hot water temperature (°C)
Loc
Appliance blocked. To reset, press RESET. If the block occurs
frequently, contact a professionally qualied technician
Block code (see chapter 7.11.1 for decode)
Err
Appliance in error mode. Functioning can only be restored by solving the cause of the anomaly. Contact a professionally
qualied technician
Error code (see chapter 7.11.2 for decode)
ALEg
Anti-legionella function running (see chapter 5.12.1). It will end on reaching the water temperature of 60°C inside the storage tank.
Storage tank temperature (°C)
SEr
Maintenance request for the appliance Appliance temperature (°C)
Page 47
47
AGUADENS
COSMOGAS
7.11.1 - Diagnostics “Loc” block fault codes and potential solution
Block Block Description Checks Solutions
Loc 0 Internal memory error
E2prom at command board
Replace the command and control board.
Loc 1 1 No ame detection after
three successive ignition attempts.
Control: Supply gas pressure (see chapter 6.6), sparks on the ignition electrodes (see chapter
8.5);correct combustion air pressure (see chapter
6.7); 220Vac electric power supply to the gas valve; electric resistance of the two gas valve coils of 0.88 Kohm and 6.59 Kohm
If the burner switches on and switches off at the end of the ignition attempt, check: that the ionisation current is at a value over 4 (follow the procedure in chapter 8.13)
the supply pressure is not correct, operate upstream from the appliance to restore it; if the pressure of the combustion air is not correct, operate on the air intake/fumes exhaust circuit to eliminate any obstructions. If the current at the gas valve is not 230Vac, the command and control board must be replaced. If the electric resistance of the gas valve is not 0.88 Kohm and 6.59 Kohm, the valve must be replaced.
If the ionisation current is not over 4, the CO2 must be checked (follow chapter 6.8) and restore its correct value, check the ionisation electrode and replace it if necessary. Check the integrity of the ionisation current electric circuit cables.
Loc 2 Gas valve command relay
broken
Replace the command and control board.
Loc 3 I n tern al saf e ty rel ay
failure at command board
Replace the command and control board.
Loc 4 Appliance in error mode
for more than 20 hours
Control the last error displayed in the board. Operate according to the last error displayed.
Loc 5 Fan out of speed for
more than 60 seconds
Ceck that it is powered at 300 Vdc. If the fan is powered, it must be replaced, alternatively
replace the command and control board.
Loc 6 Software error inside the
command board
Replace the command and control board.
Loc 7 Content of the memo-
ry E2prom inside the command board, not updated
Replace the command and control board.
Loc 8 Parameters inside
the E2prom memory, incorrect
Replace the command and control board.
Loc 9 Software error inside the
command board
Replace the command and control board.
Loc 10 Software error inside the
command board
Replace the command and control board.
Loc 11 Not applicable
Loc 12 Not applicable
Loc 13 The appliance has
reached 95°C
Ceck that the pump functions. Restore water circulation or replace the command
and control board.
Loc 14 Exhaust ue maximum
temperature. To unblock the error, contact a qua-
lied after-sales centre,
which must move switch
“B” in g. 6.5 and press
the RESET key. Therefo­re, put the switch back in the original position.
Check that the pump is operating correctly;
Measure that appliance performance; it must corre­spond to that declared in the technical features.
If the pump does not operate, it must be replaced.
If the appliance is under-performing, the primary heat exchanger might be dirty either on the exhaust
ue side or the domestic water side or both. Follow
instructions in paragraph 8.4 and ceck again.
Loc 15 Software error inside the
command board
Replace the command and control board.
Loc 16 Software error inside the
command board
Replace the command and control board.
7 - USE
Page 48
48
AGUADENS
COSMOGAS
Loc 17 Software error inside the
command board
Replace the command and control board.
Loc 18 Flame present 10
seconds after gas valve is closed
Replace the gas valve or the command and control board.
Loc 19 Flame present before
ignition
Replace the gas valve or the command and control board.
Loc 20 Flame lost three times Control: that the ionisation current is at a value over 4
(follow the procedure in chapter 8.13)
Control: that the exhaust ue system is not being
affected by high gusts of wind or nearby mechanically operated fans
If the ionisation current is not over 4, the CO2 must be checked (follow chapter 6.8) and restore the correct value. Check the ionisation electrode and replace it if necessary. Check the integrity of the ionisation current electric circuit cables.
If a horizontal exhaust ue terminal is exposed to
unusually high wind conditions or nearby mechanically
operated fans then a suitable deection shield or
protection should be considered or an alternative location should be considered. The same approch
should be taken for a vertical exhaust ue and in
addiction, ceck that downdraughts are not being
encountered due to the proximity of higher roof proles.
Loc 21 Not applicable
Loc 22 Not applicable
Loc 23 The D.H.W. outlet
sensors measure the dif­ferent temperatures for more than 60 seconds.
Check that the electrical resistance of the two sensors match the graphics in chapter 8.15;
If one of the two or both sensors do not have correct values, they must be replaced;
Loc 24 The exhaust ue
sensors measure the dif­ferent temperatures for more than 60 seconds.
Check that the electrical resistance of the two exhaust ue sensors match the graphics in paragra­ph 8.15
If one of the two sensors does not match the double
exhaust ue sensor must be replaced
Loc 25 Non applicable
Loc 26 Non applicable
Loc 27 Software error inside the
command board
Replace the command and control board.
Loc 28 Software error inside the
command board
Replace the command and control board.
7 - USE
Page 49
49
AGUADENS
COSMOGAS
7 - USE
7.11.2 - Diagnostics “E” error fault codes and potential solutions
Error Error Description Checks Solutions
Err 30 Software error inside the
command board
Replace the command and control board.
Err 31 Software error inside the
command board
Replace the command and control board.
Err 32 Software error inside the
command board
Replace the command and control board.
Err 33 Software error inside the
command board
Replace the command and control board.
Err 34 Software error inside the
command board
Replace the command and control board.
Err 35 The supply temperature
exceeds 110°C with the gas valve closed
Check that the electrical resistance of the two supply sensors match the graphics in chapter 8.15.
Check that the gas valve closes the gas correctly when the burner switches off.
If one of the two sensors does not match, the double supply sensor must be replaced.
The gas valve must be replaced if it does not close correctly.
Err 36 Software error inside the
command board
Replace the command and control board.
Err 37 Software error inside the
command board
Replace the command and control board.
Err 38 Software error inside the
command board
Replace the command and control board.
Err 39 Software error inside the
command board
Replace the command and control board.
Err 40 Software error inside the
command board
Replace the command and control board.
Err 41 Software error inside the
command board
Replace the command and control board.
Err 42 Software error inside the
command board
Replace the command and control board.
Err 43 Software error inside the
command board
Replace the command and control board.
Err 44 Flame detected in a
moment when it should not be present
Replace the gas valve.
Err 45 Not applicable
Err 46 Not applicable
Err 47 Not applicable
Err 48 Software error inside the
command board
Replace the command and control board.
Err 49 Cold water inlet sensor
circuit(1007) open
Check that the electric resistance of the sensor matches the graphics in chapter 8.15. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 50 Domestic hot water inlet
sensor 1 circuit (1001) open
Check that the electric resistance of the sensor matches the graphics in chapter 8.15. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 51 Domestic hot water inlet
sensor 2 circuit (1005) open
Check that the electric resistance of the sensor matches the graphics in chapter 8.15. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 52 Domestic hot water inlet
sensor 2 circuit (1002) open
Check that the electric resistance of the sensor matches the graphics in chapter 8.15. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Page 50
50
AGUADENS
COSMOGAS
7 - USE
Err 53 Fumes 1 sensor circuit
(1006) open
Check that the electrical resistance of the exhaust ue
sensor 1006 matches the graphics in chapter 8.22
Check that the wires between the board and the
double exhaust ue sensor are connected correctly
If the sensor does not match, the double exhaust sensor must be replaced.
If the wires are not connected correctly, the connec­tions must be restored.
Err 54 Fumes 2 sensor circuit
(1014) open
Check that the electrical resistance of the exhaust ue
sensor 1014 matches the graphics in paragraph 8.15
Check that the wires between the board and the
double exhaust ue sensor are connected correctly
If the sensor does not match, the double exhaust sensor must be replaced.
If the wires are not connected correctly, the connec­tions must be restored.
Err 55 Not applicable
Err 56 Cold water inlet sensor
circuit(1007) in short circuit condition
Check that the electric resistance of the sensor matches the graphics in chapter 8.15. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 57 Domestic hot water inlet
sensor 1 circuit (1001) in short circuit condition
Check that the electric resistance of the sensor matches the graphics in chapter 8.15. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 58 Domestic hot water inlet
sensor 2 circuit (1005) in short circuit condition
Check that the electric resistance of the sensor matches the graphics in chapter 8.15. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 59 Domestic hot water inlet
sensor 2 circuit (1002) in short circuit condition
Check that the electric resistance of the sensor matches the graphics in chapter 8.15. Check the electric cables for connection between the sensor and the command board.
If the electric resistance does not match, replace it. The electric circuit must be repaired if it is damaged. Without either of the two previous cases, replace the command and control board.
Err 60 Fumes 1 sensor circuit
(1006) in short circuit condition
Check that the electrical resistance of the exhaust ue
sensor 1006 matches the graphics in chapter 8.15
Check that the wires between the board and the
double exhaust ue sensor are connected correctly
If the sensor does not match, the double exhaust sensor must be replaced
If the wires are not connected correctly, the connec­tions must be restored
Err 61 Fumes 2 sensor circuit
(1014) in short circuit condition
Check that the electrical resistance of the exhaust ue
sensor 1014 matches the graphics in chapter 8.15
Check that the wires between the board and the
double exhaust ue sensor are connected correctly
If the sensor does not match, the double exhaust sensor must be replaced
If the wires are not connected correctly, the connec­tions must be restored
Err 62 Not applicable
Err 63 RESET key pressed too
many times in a very brief period
7.11.3 - Diagnostics “AttE” alarm fault codes and potential solutions
Alarm Description of the alarm Checks Solutions
AttE 65 Not applicable
Page 51
51
AGUADENS
COSMOGAS
8.1 - General recommendations
It is recommended to perform regular yearly maintenance of
the appliance for the following reasons:
- to maintain high yield and therefore save fuel;
- to maintain a high level of safety;
- to maintain the level of environmental compatibility of the combustion high;
In order to maintain maintenance frequency, the parameter
2080 is present in the installer menu (see chapter
7.10), which is used to activate the maintenance call
(Service) along with parameter 2081 which is used to set the operating days and which must pass between one
intervention and the next. The control system identies the
operating days, verifying the burner activity time. Proceed as follows to activate the call service:
1.- access the Installer menu (see chapter 7.10)and set parameter 2080 on 0n;
2.- access parameter 2081 and set the appliance operating days which must pass between one call and the next.
The call will be completed with SEr on the display. To remove the wording SEr and renew the call period,
operate as follows:
1.- access the “Installer menu”;
2.- access the parameter 2080, set it on rESE and press the RESET key.
3.- exit the Installer menu by pressing the RESET key for 5 seconds.
The call time is now renewed and SEr appears on the display.
ATTENTION !!! Appliance maintenance must
only be performed by a professionally qualied
technician.
ATTENTION !!! Before every maintenance
operation, disconnect the appliance from the electric power supply, using the relevant switch in the vicinity.
ATTENTION !!! Close the gas isolation valve
before any maintenance operation
8 - MAINTENANCE
Page 52
52
AGUADENS
COSMOGAS
Figure 8.1 - removing the casing and opening of command board
8.2 - Casing removal
Proceed as follows to remove the casing (refer to gure
8.1):
1.- pull the lower cover “A” towards the front for approx. 10mm
2.- push the lower cover “A” downwards;
3.- loosen the screws “H”;
4.- pull the lower part of the front-piece “B” towards the front and then slide it out upwards until it is released from the guides “C”;
To access the command and control board:
1.- turn the command board “D” towards the front;
2.- open the commands board “D” by operating on closure “G”;
To access the electric connections board:
1.- turn the command board “D” towards the front;
2.- slide lid “E” out by operating on the “F” closing aps;
C
E
D
G
H
F
A
B
020003.01.018
8 - MAINTENANCE
Page 53
53
AGUADENS
COSMOGAS
8 - MAINTENANCE
8.3 - Burner and fan removal
Proceed as follows to remove the burner fan unit (refer to
gure 8.2 when not differently specied):
1.- access the internal components following chapter 8.2;
2.- remove the air manifold (detail “C” in gure 6.2) rotating
it towards the outside of the appliance and then pulling it
towards the right (see gure 6.2);
3.- unscrew nut “C” from the valve “D”;
4.- disconnect the cables “B” and the detection cable from the ignition and detection electrodes (details “15”, “34”
and “35” of gure 3.1);
5.- unscrew the four nuts “E”;
6.- extract the group “F” as per gure;
Figure 8.2 - Removing the burner fan unit
B
A
C
F
D
E
020003.01.024
8.4 - Gas burner and heat exchanger outer surface cleaning procedure
To correctly clean the burner and body of the heat
exchanger (exhaust ue side), proceed as follows (refer to gure 8.2 when not differently specied):
1.- access the internal components following paragraph 8.2;
2.- remove the burner unit following chapter 8.3;
3.- pass a cylindrical brush with plastic bristles inside the combustion chamber
4.- use a suction device to remove the unburned residues present inside the combustion chamber;
5.- use the same suction device on the surfaces of the burner and around the electrodes;
6.- re-mount the components in reverse order;
7.- open the gas isolation valve;
8.- restore the electric power supply.
9.- check that there are no gas leaks on all internal joints;
ATTENTION!!! Perform the leak test using a soap
and water only. The use of naked ames is prohibited.
Page 54
54
AGUADENS
COSMOGAS
8.5 - Condensate siphon
cleaning procedure
For correct cleaning of the collection siphon and the conveying of the condensate produced by combustion,
operate as follows (refer to the gures 8.3, 8.4 and 8.5):
1.- with the appliance on, open a domestic hot water tap or taps fully to force the burner to its maximum power and the level of the liquid present inside the siphon tank “D”
lowers (see gure 8.4);
2.- access the internal components following paragraph 8.2;
3 - remove the burner fan unit following paragraph 8.3; 4 - cover the electric plant with a cloth to protect it from any
residues of water inside the siphon to be removed.
5.- slide the support “C” outwards from the holding support;
6.- slide the tank “D” downwards, paying attention to the fact that it is full of condensate water and this could escape;
7.- extract the siphon outwards (see gure 8.6) paying
attention to disconnect the collection pipes of the water coming from the upper part of the appliance and from the air vent valve.
8.- clean the decanting tank “D”;
9.- re-mount everything in reverse order, paying attention to the gasket “E”, which is put back in the relevant seat and that terminal “G” is introduced correctly in the seat “H”;
10.- restore the level of liquid inside the siphon following the procedure in chapter 6.1.2.
Figure 8.4 - Removing condensate collection siphon
Figure 8.5 - Condensate collection siphon
H
G
F
D
E
020002.01.030
8 - MAINTENANCE
Figure 8.3 - Removal of the condensate collection siphon
B
C
A
020003.01.027
D
020003.01.029
Page 55
55
AGUADENS
COSMOGAS
8.6 - Ignition and ame
isonising electrode position
For good working order of the appliance, it is indispensable
that the electrodes are positioned correctly (refer to gure
8.6):
- the distance between the ignition electrodes “A” and “B”, must be between 2.0 and 2.5 mm;
- the distance between the ignition electrodes from the burner surface must be between 5 and 5.5 mm;
- the distance of the ionisation electrode “C” from the surface of the burner must be between 5.5 and 6.5 mm.
Figure 8.7 - Replacing the pump motor
B
A
020003.01.026
8 - MAINTENANCE
Figure 8.6 - positioning the electrodes on the burner
8.7 - Circulation pump
replacement procedure
Operate as follows if the pump must be replaced (refer to
gure 8.7):
1.- empty the domestic hot water circuit, following the procedure in chapter 8.10;
2.- disconnect the electric power supply upstream from the appliance;
3.- access the components inside the appliance, following paragraph 8.2;
4.- disconnect the electric cables from the pump body.
5.- loosen the screws “A”;
6.- extract the pump “B” outwards and replace it.
Page 56
56
AGUADENS
COSMOGAS
Figure 8.8 - Removing the ow meter
A
B
020003.01.036
8.8 - Domestic water ow meter
replacement procedure
Proceed as follows, making reference to gure 8.8:
1.- empty the domestic hot water circuit, following the procedure in paragraph 8.10;
2.- disconnect the electric power supply upstream from the appliance;
3.- access the components inside the appliance, following paragraph 8.2;
4.- disconnect the cables from the ow meter (detail “B” in gure 8.8);
5.- unscrew the small disks “A”, paying attention that the residual water from the pipes does not reach the control board;
6.- slide the ow meter “B” upwards and replace it.
Figure 8.9 - Removing the safety valve
A
020003.01.034
8 - MAINTENANCE
8.9 - Safety valve
replacement procedure
The safety valve (detail “A” in gure 8.9) protects the
appliance from over pressures. If it has to be replaced,
proceed as follows (refer to gure 8.9):
1.- empty the domestic hot water circuit, following the procedure in paragraph 8.10;
2.- access the components inside the appliance, following paragraph 8.2;
3.- disconnect the drain pipe from the valve to be replaced “A”;
4.- unscrew the lower xing disk of valve “A”;
5.- extract the safety valve “A” upwards;
Page 57
57
AGUADENS
COSMOGAS
Figure 8.10 - Water sensors curve
8 - MAINTENANCE
8.10 - Procedure for draining the water heater
To empty the appliance from the domestic hot water side, proceed as follows:
1.- close the main cold water supply isolation valve;
2.- open all hot and cold water taps;
3.- make sure that at least one of these is at a height below the level of the appliance.
8.11 - Fan test mode procedure
Switch-on of the fan only can be generated, accessing the parameter 2010 situated inside the “Installer menu” (see chapter 7.10) and set it on FAn. To go back to normal operating conditions, set parameter 2010 again to 0FF.
8.12 - Gas burner minimum
and maximum performance test mode procedure
Appliance operation can be forced to its own minimum, maximum, adjusted or ignition power. Proceed as follows:
1.- access parameter 2010 found in the “installer menu” (see chapter 7.10);
2.- set the parameter 2010 at the following value: a) LOu to force the appliance to minimum power; b) Ign to force the appliance to ignition power; a) HIgH to force the appliance to maximum power; a) rEg to force the appliance to maximum power.
4.- to end forcing, take the parameter 2010 to the 0FF
value and press the RESET key.
8.13 - Checking the ionisation current
In any operating status, also during verications of minimum
and maximum power stated in paragraph 8.12, the ionisation current value can be consulted on parameter 1008 present
in the “User menu” (table 7.9). This value must be between
1.5 and 3 uA (microampere) at minimum power and between 5 and 8 uA at maximum power.
8.14 - Water temperature measurement sensor testing procedures
The temperature sensors are positioned on the appliances’ exchanger body. The electric resistance existing between the two contacts of the sensor, must correspond with that
stated in gure 8.10.
The temperature sensors are: 1001, 1002, 1003,
1005, 1006, 1007 and 1014, the positioning of
which can be veried in gure 3.1.
Page 58
58
AGUADENS
COSMOGAS
8.15 - AGUADENS models 16, 22 and 27 electrical connections
Figure 8.11 - Operational wiring diagram
ATTENTION !!! To consult
the wiring diagram correctly, references K are given followed by a number (see example above) to identify the correct follow­on of the cables in the next page.
8 - MAINTENANCE
1001 - D.H.W. outlet temperature sensor 1 1002 - D.H.W. outlet temperature sensor 1002 (SB) - Storage tank sensor (on request) 1005 - D.H.W. outlet temperature safety sensor 2
1006 - Exhaust ue sensor 1
1007 - Cold water inlet sensor
1014 - Exhaust ue safety sensor 2 CM - Appliance control unit and ame control
DSP - Display DSPX - Remote control (on request) EA - Ignition electrode ER - Detection electrode
Page 59
59
AGUADENS
COSMOGAS
8 - MAINTENANCE
F (Digital) - Digital fan F (BCU) - 5A fuse F1 (SDC) - 1.6A power supply fuse PB - Storage tank load aux. pump (on request) PR - Recirculation Pump GS - Spark generator IG - Master switch J1 - 8 pin Molex connector J12- 6 pin Molex connector J2 - 6 pin Molex connector J26- 4 pin Molex connector J3 - 10 pin Molex connector J4 - 6 pin Stelvio connector
J5 - 4 pin Molex connector J6 - 14 pin Molex connector J7- 10 pin Molex connector J9- 4 pin Molex connector PB - Storage tank pump (on request) PS - Pressure sensor (present only in mod. 27) SDC- Connection board
TU - Domestic hot water ow meter
VG1- Gas Valve
Page 60
60
AGUADENS
COSMOGAS
8.16 - AGUADENS models 16, 22 and 27 internal multi-core wiring diagram
Figure 8.12 - Multi-core colours wiring diagram
Key - see key gure 8.11
8 - MAINTENANCE
COLOR OF DIAGRAM CABLE ARANCIO = ORANGE BIANCO = WHITE BLU = BLUE GIALLO = YELLOW GIALLO/VERDE = YELLOW/GREEN GRIGIO = GREY MARRONE = BROWN NERO = BLACK ROSSO = RED VERDE = GREEN
Page 61
61
AGUADENS
COSMOGAS
8 - MAINTENANCE
Page 62
62
AGUADENS
COSMOGAS
8.17 - AGUADENS model 37 electrical connections
Figure 8.13 - Operational wiring diagram
8 - MAINTENANCE
ATTENTION !!! To consult
the wiring diagram correctly, references K are given followed by a number (see example above) to identify the correct follow­on of the cables in the next page.
1001 - D.H.W. outlet temperature sensor 1 1002 - D.H.W. outlet temperature sensor 1002 (SB) - Storage tank sensor (on request) 1005 - D.H.W. outlet temperature safety sensor 2
1006 - Exhaust ue sensor 1
1007 - Cold water inlet sensor
1014 - Exhaust ue safety sensor 2 CM - Appliance control unit and ame control
DSP - Display DSPX - Remote control (on request) EA - Ignition electrode ER - Detection electrode
Page 63
63
AGUADENS
COSMOGAS
8 - MAINTENANCE
F (PWM) - PWM Fan F (BCU) - 5A fuse F1 (SDC) - 1.6A power supply fuse PB - Storage tank load aux. pump (on request) PR - Recirculation Pump GS - Spark generator IG - Master switch J1 - 8 pin Molex connector J12- 6 pin Molex connector J2 - 6 pin Molex connector J26- 4 pin Molex connector J3 - 10 pin Molex connector J4 - 6 pin Stelvio connector
J5 - 4 pin Molex connector J6 - 14 pin Molex connector J7- 10 pin Molex connector J9- 4 pin Molex connector PB - Storage tank pump (on request) PS - Pressure sensor SDC- Connection board
TU - Domestic hot water ow meter
VG1- Gas Valve
Page 64
64
AGUADENS
COSMOGAS
8.18 - AGUADENS model 37 multi-core wiring diagram
Figure 8.14 - Multi-core wiring loom diagram
Key - see key gure 8.13
8 - MAINTENANCE
COLOR OF DIAGRAM CABLE ARANCIO = ORANGE BIANCO = WHITE BLU = BLUE GIALLO = YELLOW GIALLO/VERDE = YELLOW/GREEN GRIGIO = GREY MARRONE = BROWN NERO = BLACK ROSSO = RED VERDE = GREEN
Page 65
65
AGUADENS
COSMOGAS
8 - MAINTENANCE
Page 66
66
AGUADENS
COSMOGAS
TECHNICAL DATA UM AGUADENS 16 AGUADENS 22
Type (Type of exhaust ue/combustion air intake) B23;C13;C33;C43;C53;C63;C83
Category II2H3P II2H3P
CE type certicate (PIN) 0694CN6126 0694CN6126
Max. heat input kW 25,5 34,8
Min. heat input kW 3,2 4,4
Max. useful heat output kW 27,5 37,6
Efciency at max heat output % 108 108
Min. heat output kW 3,97 4,35
Efciency at min heat output % 109 109
Gas ow rate
Nat gas m
3
/h 2,70 3,68
LP gas Kg/h 1,98 2,70
Gas supply pressure
Nat gas mbar 20 20
LP gas mbar 37 37
Gas supply minimum pressure
Nat gas mbar 15 15
LP gas mbar 25 25
Gas supply maximum pressure
Nat gas mbar 27 27
LP gas mbar 45 45
Combustion air intake pressure
Nat gas mbar 13,2 12,3
LP gas mbar 13,8 11,2
Instantaneous D.H.W. adjustment range °C 40-60 40-60
D.H.W. with storage tank adjustment range °C 40-70 40-70
Domestic circuit maximum pressure bar 7 7
Rated power supply voltage V 230 230
Rated power supply frequency Hz 50 50
Absorbed electric power W 120 120
Electric protection rating IPX4D IPX4D
Exhaust ue pipe diameter (split) mm 80 o 60 80 o 60
Exhaust ue pipe max. length (split) (80) m 40 25
Exhaust ue pipe max. length (split) (60) m 15 10
Exhaust ue pipe diameter (coaxial) mm 60/100 60/100
Exhaust ue pipe max. length (coaxial) m 10 10
Equivalent length of a bend m 45° bend = 0.5m, 90° bend =1m
Weighted CO (0% O2 with natural gas) ppm 8 15
Weighted NOx (0% O2 with natural gas) (class 5 EN 483 and 297) ppm 13 17
CO2 (%) at minimum/maximum power
Nat gas % 8,5/9,0 8,5/9,0
LP gas % 10/10,5 10/10,5
Exhaust ue gas maximum temperature at appliance outlet °C 75 75
Mass ow rate of exhaust ue gases kg/h 25,4 42,3
Head available at exhaust ue outlet Pa 60 60
Exhaust ue gas maximum temperature for overheating °C 90 90
Max. negative pressure avaiable in combined exhaust ue/combustion air
intake system
Pa 60 60
Condensate maximum ow rate l/h 1,9 3,2
Condensate average acidity PH 4 4
Operating environment temperature °C 0 ; +50 0 ; +50
Weight of the appliance kg 36 36
9 - TECHNICAL DATA
Page 67
67
AGUADENS
COSMOGAS
9 - TECHNICAL DATA
TECHNICAL DATA UM AGUADENS 27 AGUADENS 37
Type (Type of exhaust ue/combustion air intake) B23;C13;C33;C43;C53;C63;C83
Category II2H3P II2H3P
CE type certicate (PIN) 0694CN6126 0694CN6126
Max. heat input kW 43,0 57,8
Min. heat input kW 8,5 12,0
Max. useful heat output kW 46,4 61,9
Efciency at max heat output % 107 107
Min. heat output kW 9,2 13,0
Efciency at min heat output % 108 108
Gas ow rate
Nat gas m
3
/h 4,50 6,10
LP gas Kg/h 3,30 4,50
Gas supply pressure
Nat gas mbar 20 20
LP gas mbar 37 37
Gas supply minimum pressure
Nat gas mbar 15 15
LP gas mbar 25 25
Gas supply maximum pressure
Nat gas mbar 27 27
LP gas mbar 45 45
Combustion air intake pressure
Nat gas mbar 9,6 10,9
LP gas mbar 8,5 10,6
Instantaneous D.H.W. adjustment range °C 40-60 40-60
D.H.W. with storage tank adjustment range °C 40-70 40-70
Domestic circuit maximum pressure bar 7 7
Rated power supply voltage V 230 230
Rated power supply frequency Hz 50 50
Absorbed electric power W 140 140
Electric protection rating IPX4D IPX4D
Exhaust ue pipe diameter (split) mm 80 80
Exhaust ue pipe max. length (split) (80) m 10 8
Exhaust ue pipe max. length (split) (60) m / /
Exhaust ue pipe diameter (coaxial) mm 60/100 80/125
Exhaust ue pipe max. length (coaxial) m 4 10
Equivalent length of a bend m 45° bend = 0.5m, 90° bend =1m
Weighted CO (0% O2 with natural gas) ppm 25 25
Weighted NOx (0% O2 with natural gas) (class 5 EN 483 and 297) ppm 30 30
CO2 (%) at minimum/maximum power
Nat gas % 8,5/9,0 8,5/9,0
LP gas % 10/10,5 10/10,5
Exhaust ue gas maximum temperature at appliance outlet °C 75 75
Mass ow rate of exhaust ue gases kg/h 58,9 99,0
Head available at exhaust ue outlet Pa 60 60
Exhaust ue gas maximum temperature for overheating °C 90 90
Max. negative pressure avaiable in combined exhaust ue/combustion air
intake system
Pa 60 60
Condensate maximum ow rate l/h 4,4 7,2
Condensate average acidity PH 4 4
Operating environment temperature °C 0 ; +50 0 ; +50
Weight of the appliance kg 37 40
Page 68
68
AGUADENS
COSMOGAS
10 - COMMAND MENU DIAGRAM
Symbol Description
Press and release the RESET key
Hold the reset key down for a time in seconds, indicated by the number (2)
Hold the reset key down for a time in seconds, indicated by the number (5)
Hold down the RESET and key simultaneously for a time in seconds, indicated by the number
Press and release the key
Press and release the key
Pa rameters th at can be displayed in normal operating conditions (see chapter 7.11)
Use menu parameters (see chapter 7.9)
Installer menu parameters (see chapter
7.10)
Installer menu parameters (see chapter
7.10)
Us e me nu acce ss (see chapter 7.9)
Installer menu access (see chapter 7.10)
Return to normal operation
Return to normal operation
Figure 10.1 - Command menu diagram
Key for gure 10.1
Page 69
69
AGUADENS
COSMOGAS
ATTENTION !!!
The modication of these parameters could cause the appliance, and therefore the plant, to malfunction.
For this reason only a technician that has the awareness and in-depth knowledge of the appliances can modify them.
To access this menu, move the microswitch as stated in gure 6.5 detail “B”.
11 - ENGINEERS TEST MODE
Parameter Parameter Description M.U. Setting range
Factory value
Customised
value
3002 Selection type From 50 to 55 See gure 6.7
3012
Domestic hot water operating mode
/
0 = DO NOT USE; 1 = Storage tank with temperature sensor; 2 = Storage tank with thermostat; 3 = DO NOT USE; 4 = DO NOT USE; 5 = Instantaneous with turbine;
5
3013 No function / / /
3014
Instantaneous domestic hot water pre-heat
/
OFF = No pre-heat ON = With pre-heat OFF
OFF
3015
No function
/ / / /
3016
No function
/ / / /
3020
Domestic hot water ow rate
sensor
/
0 = B; 1 = DN 8; (AGUADENS 16) 2 = DN 10; 3 = DN 15; (AGUADENS 22, 27 and 37) 4 = DN 20; 5 = DN 25;
0
3021 2nd Exhaust ue sensor (1014) /
0 = Disabled; 1 = Enabled;
2 = Enabled with exhaust ue anti-closure
pressure switch;
1
3022 No function / / / 3033
No function
/ / /
3034
No function
/ / /
3035
No function
/ / /
3036
No function
/ / /
3052
No function
/ / /
Page 70
70
AGUADENS
COSMOGAS
The undersigned COSMOGAS S.r.L., with Registered Ofce in via L. Da Vinci n° 16 - 47014 Meldola (FC) ITALY,
DECLARES
under its own responsibility that the project:
subject of this declaration, is in compliance with the model described in the
Type examination certicate , whose reference is given in the table in
chapter 9 under “CE type certicate (PIN)” and meeting that required by the
Directives: Gas Appliances, (2009/142/CE former 90/396/CEE), Low Voltage,
(2006/95/CE), Electromagnetic Compatibility,
(2004/108/CEE).
(the warranty number corresponds to the serial number)
This declaration is issued for that established by the above-mentioned Directives.
Meldola (FC) ITALY, (Date of manufacture).
DATE OF MANUFACTURE
WARRANTY N°
GAS APPLIANCE MODEL
12 - CE DECLARATION OF CONFORMITY
Page 71
71
AGUADENS
COSMOGAS
13 - WARRANTY
13.1 - General warranty conditions
All COSMOGAS products are guaranteed against material
aws and manufacturing defects for 24 months from the date of commissioning, COSMOGAS also extends the warranty to :
SHELL AND TUBE HEAT EXCHANGER BODIES, CRR and CRV guaranteed up to 5 years;
PRE-MIXED BURNERS guaranteed up to 10 years;
ATMOSPHERIC BURNERS guaranteed up to 15 years.
This warranty extension will only be valid if COSMOGAS
has received the warranty card, lled-in completely, which
will certify the date of commissioning. Within the above­mentioned term COSMOGAS commits to repairing or replacing the faulty construction parts and which will be acknowledged as such with exclusion of normal deterioration due to operations. The extension of the warranty exclusively covers the cost of the spare part. All other accessory costs are excluded, such as: labour, transfer costs and expenses for transporting material. The warranty does not extend to the recasting of the damage, of any nature, that has happened to persons or property. The faulty material replaced under warranty is the property of COSMOGAS and must be returned to our establishment, without further damage, within 30 days from replacement. All COSMOGAS products are encumbered by the title retention agreement, until the appliance sold have been paid in full.
13.2 - Instructions for lling-
in the warranty card
1. - Have your installer put his stamp on the warranty
certicate.
2. - Always request the intervention of our authorised technician for commissioning and to validate the warranty;
To validate the warranty, the technician must control:
1. - Gas pressure at the burner (or combustion agent air pressure for pre-mixed and condensing appliances);
2. - Water leaks;
3. - Gas leaks;
The list of authorised technicians is found attached to the instruction manual or can be found in the Yellow Pages under “Gas water heater”.
The technician will take the warranty certicate and
deliver it to COSMOGAS.
13.3 - Warranty limitations
The warranty is not valid:
- if the appliance is installed by non-qualied staff;
- if the appliance is installed in a way that is not in compliance with the COSMOGAS instructions and/or that established by the current national and/local regulations;
- whenever the plant is not run/services in compliance with the instructions and/or the current national and local regulations.
- whenever the product has damage caused by changes in voltage;
- whenever the product has damaged caused by the use of excessively hard water, or which is too acid or too oxygenated;
- whenever the product has failures caused by heat shocks, abnormalities of chimneys and/or exhaust and intake pipes;
- whenever the product has anomalies not depending on COSMOGAS;
- whenever the appliances have been tampered with for adaptation, repairs or replacement with non-original spare parts;
- whenever repairs are performed by unauthorised staff.
- Whenever the warranty certicate is not sent
to COSMOGAS within 15 days from the date commissioning.
COSMOGAS does not assume any responsibility for any accident that may occur or be caused by the user, precluding any compensation that does not concern appliance parts recognised as defective manufacturing.
Any dispute is the jurisdiction of the Forlì Law Court, ITALY.
Page 72
COSMOGAS s.r.l.
Via L. da Vinci 16 - 47014
MELDOLA (FC) ITALY
info@cosmogas.com
www.cosmogas.com
Loading...