Correlate SmartSERVER Installation Manual

Page 1
SmartSERVER
Physical Installation Guide
SmartSERVER building 001-10134 Rev. 1 automation products
PHYSICAL INSTALLATION GUIDE
Section Contents
Physical Installation Guide........................................................................................................................................................1
1.2.1 Before you start...........................................................................................................................................................................................................1
1.2.2 Mounting Preparation (Step 1)....................................................................................................................................................................................2
1.2.3 C-Bus Cable Termination (Step 2)...............................................................................................................................................................................2
1.2.4 Physical Installation (Step 3).......................................................................................................................................................................................3
1.3.1 Electrical......................................................................................................................................................................................................................3
1.3.2 Physical.......................................................................................................................................................................................................................3
1.4.1 General Disclaimer......................................................................................................................................................................................................3
1.4.2 Limitations of Usage....................................................................................................................................................................................................3
1.4.3 Copyright and Trademarks..........................................................................................................................................................................................4
1.4.4 Contact Correlate........................................................................................................................................................................................................4
1.1 Scope
The following instructions apply to the electrician who is responsible for the physical installation activities (only) of a
SmartSERVER.
Information on other aspects of the installation including C-Bus and Network integration can be found within the SmartSERVER Instruction manual, document 001-10036.
1.2 Physical Installation
1.2.1 Before you start
Prior to commencing a SmartSERVER installation ensure that your intended approach will satisfy all of the following considerations detailed in this section:
• C-Bus connection
• Ethernet Connection
• Power Source
• Location, Access and Security
C-Bus connection
The SmartSERVER requires access to a wired C-Bus system in a manner similar to that required by a Clipsal C-Bus wall switch – two terminations are required at a pluggable connection provided at the rear.
Ethernet Connection
A connection to a local wired ethernet or fast ethernet network is required. This is provided at the front of the unit by a standard RJ style connector (as is typically present on Cat 5e and Cat 6 patch cables).
SmartSERVER includes an auto MDIX feature so cross over cables are never required (but can be used at any time).
Power Source
SmartSERVER requires a 5V DC input for operation. This can be provided to the front facing barrel style connector by:
• Suitably rated 5V plug pack or similar supply
• USB to barrel connector cable. USB3 sources will,
and most USB2.0 interfaces, can provide sufficient current (The later meaning it may be possible to power SmartSERVER off an unused router USB port)
NOT E: Consider the total curr ent dra w of oth er devices (if pres ent ) f rom a USB router or power ed hub to con fir m s ufficie nt capacity r ema ins.
Correlate carries a range of accessories that can help you professionally complete any installation. Please visit our website
www.correlate.com.au for further details.
IMP ORTANT: Is is li kely a genera l powe r o utl et (GPO) will also nee d to b e provi ded i n the vic ini ty of the Smar tSE RVER to pro vide inpu t to a DC plug pac k/s upply and for oth er custom er IT equipme nt.
Location, Access and Security
SmartSERVER is designed for indoor use only. It does not in itself generate any appreciable heat nor require convection for cooling. The selected location must afford occasional front panel access ..
Common suitable locations include:
© Copyright Correlate Pty Ltd 2015
Page 1 of 4
A
Page 2
SmartSERVER
Physical Installation Guide
SmartSERVER building 001-10134 Rev. 1 automation products
• wall mounting near a wired ethernet connection and GPO
• within a communications cabinet
Unsuitable locations include:
• areas of high electromagnetic radiation
• corrosive, explosive or highly dusty environments
• close proximity to medical apparatus or similarly
sensitive equipment
• anywhere where the SmartSERVERs rated parameters (Section 1.3) will be exceeded
WARNING : Always selec t a location which complie s with local bui ldi ng codes and reg ula tio ns, a nd ensure cabling sepa rat ion req uirements are m et. Typi cally equ ipment of th is typ e, as we ll as other I T equipmen t s hould n ot be i nst alled with in a mains swi tchboar d.
1.2.2 Mounting Preparation (Step 1)
The method of fixing the SmartSERVER is via two mounting screws spaced at 84mm centres. This is compatible with the standard spacing used by Australian and New Zealand switch plates and other mounting accessories.
Orientation of the SmartSERVER can be determined to best suit the installation position, however note that front panel artwork runs horizontally.
The two screws provided have sufficient reach for a mounting bracket present at the rear of a gyprock cavity wall (Illustration
1).
C-Bus cable entry is from the rear, meaning that on solid walls a suitable wall box cavity must be present, or a mounting block affixed to the wall. Non-standard configurations will need to be addressed by the installation professional on a case by base basis.
1.2.3 C-Bus Cable Termination (Step 2)
It is recommended the C-Bus cable termination and fitting of the connector be completed immediately prior to installation of the SmartSERVER, and after application of all finishes to the mounting surface.
Untwist the 2 cable pairs identified in Table 1. The other twisted pairs present are not used for the SmartSERVER installation and should remain unterminated.
C-Bus Connection Colour
C-Bus positive (+) blue
C-Bus negative (-) blue & white
C-Bus positive (+) orange
C-Bus negative (-) orange & white
Table 1: C-Bus cable colour code
Now strip approximately 7mm of insulation off each of the four wires of interest being careful not to nick the centre conductor. Combine the positive and negative C-Bus cables are shown in Illustration 2. A crimp ferule as used by other C-Bus products can be optionally applied to the cable ends, but is not required.
WARNING : Cable out er j acket not to be strippe d back f urther tha n shown in Il lus tration 2 (requir ed for SELV complianc e).
Sufficiently loosen the two connector screws to allow the cable (with or without crimp ferule) to be inserted. Insert the cables maintaining the polarity as shown in Illustration 3 and securely tighten.
IMP ORTANT: Ensure the C-Bus wires are cor rec tly paired tog ether and te rmi nated to the correct locatio ns o n th e pro vided conn ect or.
© Copyright Correlate Pty Ltd 2015
Page 2 of 4
Illustration 3: C-Bus connector termination
A
Illustration 2: C-Bus cable connection
Illustration 1: Example cavity installation
Page 3
SmartSERVER
Physical Installation Guide
SmartSERVER building 001-10134 Rev. 1 automation products
Optionally, electrical insulating tape can be applied over the connectors screw terminals and onto the cable to provide additional mechanical support.
1.2.4 Physical Installation (Step 3)
Plug the connector into the mating socket on the rear of SmartSERVER. The connector is keyed and will easily engage when inserted with the correct orientation.
NOT E: Ful ly engage t he con nec tor wi th correc t ori enta tio n – Do not force.
Carefully move the SmartSERVER back against the mounting surface ensuring the C-Bus cable generally feeds away from the unit at right angles, and does not kink or sharply bend any of the individual conductors.
Loosely inserting both of the provided retention screws prior to final tightening may assist in initially aligning the unit.
Do not over tighten the screws, also taking care to avoid cosmetic damage to both the screw head and SmartSERVER front panel.
1.3 Technical Specifications
An abbreviated set of specifications are given here to support site selection and other aspects of the installation. Please refer to the SmartSERVER Instruction Manual for a complete set.
1.3.1 Electrical
Parameter Value Note
min nom max units
DC Supply IN 4.5 5 7.5 V Reverse, under, over voltage
protected.
200 mA
Ethernet Fast Ethernet with auto MDIX
(crossover).
C-Bus system clock
none yes Software selectable via C-
Bus toolkit.
C-Bus network burden
none yes Software selectable via C-
Bus toolkit.
Operating Temperature
0 21 45 C
Operating Humidity
0 95 % RH Non-condensing.
Table 2: Abbreviated Electrical Specifications
1.3.2 Physical
Parameter Value Note
Controls Restart Front panel. Momentary press will
restart SmartSERVER reloading currently saved parameters.
Reset Recessed – operation requires
insertion of fine blunt instrument. Press and hold with Restart for 5 seconds then release to restore factory default settings.
Indicators Power On when supply IN is within protection
limits.
Run Flash every 1s (typ) during operation.
Ethernet Link On when Ethernet network present.
Ethernet Activity On during any data activity on
connected Ethernet network.
Connections DC-Power Centre pin positive. 5.5mm/2.0mm
barrel connector
Ethernet (RJ45) Auto MDIX crossover if required.
C-Bus (2 pin plug) TE Connectivity 5.08mm pitch Termi
Blok
Weight 198g Nominal, SmartSERVER only
including mounting screws (2).
Dimensions (WxHxD)
106.5 x 56.5 x 47mm Nominal, not including rear C-Bus connector.
Table 3: Abbreviated Physical Specifications
1.4 Important Information
1.4.1 General Disclaimer
The information in this manual is provided in good faith. Whilst Correlate has endeavoured to ensure the relevance and accuracy of the information, it assumes no responsibility for any loss incurred as a result of its use.
1.4.2 Limitations of Usage
The products offered by Correlate are not endorsed for life or safety critical applications. They should never be used as
the primary, principle or only means to achieve a purpose, where failure to operate could have unacceptable consequences.
Unless specifically identified within the product specification all of Correlate's products are intended for indoor use only and are
not developed for use in explosive or otherwise dangerous environments.
Correlate does not recommend or endorse use of its products in any of the applications mentioned above.
Other situation may exist where the use of Correlate's products are not appropriate. Installation of equipment should only be carried out by personnel able to adequately assess the suitability and safety of any particular potential installation.
1.4.3 Copyright and Trademarks
© Copyright Correlate Pty Ltd 2015. All rights reserved.
© Copyright Correlate Pty Ltd 2015
Page 3 of 4
A
Page 4
SmartSERVER
Physical Installation Guide
SmartSERVER building 001-10134 Rev. 1 automation products
This material is copyright under Australian and international laws. Except as permitted under the relevant law, no part of this work may be reproduced by any process without prior written permission of and acknowledgement to Correlate Pty Ltd.
A
,
B
and SmartSERVER are trademarks of Correlate Pty Ltd.
Clipsal and C-Bus are registered trademarks of Clipsal Australia Pty Ltd.
1.4.4 Contact Correlate
If you need to contact us:
Function Email address
Technical Support:
Sales:
Enquires of a
general nature:
Table 4: Correlate e-mail contact addresses
All written correspondence should be sent to:
Correlate Pty. Ltd. P.O. Box 580 Church Point NSW 2105 Australia
Please note, return items will NOT be accepted at our P.O. box address. If you have a warranty claim please first contact Correlate to receive an RMA number and return address details
© Copyright Correlate Pty Ltd 2015
Page 4 of 4
A
Loading...