CORNING ONE OIU Quick Installation Sheet

Page 1
Optical Interface Unit (OIU) Quick Installation Sheet
CMA-263-AEN
GENERAL INFORMATION
• OIMe —optical module only; ber jumper is not included — compatible MTP®-LC APC harness cable is ordered separately (see Section 2 of this document)
• OIU chassis is supplied empty and only includes the factory-assembled fan module (FAM). All other modules (i.e., power supplies, controller, OIMe, OIXs, and FMMs) are ordered separately and must be installed.
This document describes the installation and connection procedures for the Corning® optical network evolution (ONE™) solutions optical interface unit (OIU) and relevant modules.
Note: The instructions for installing and connecting ber main modules (FMMs) in the OIU chassis are not in the scope of this document. For details, refer to the quick installation sheet provided with the module.
. REQUIRED KITS
The following kits are required for installing the OIU. If any of the listed items are missing, contact your Corning representative.
OIU Kit Qty Item
OIU Chassis (with blank panels) — with factory-assembled FAM and rack brackets
Fan Module (FAM) — one unit hosting four fans (factory installed in chassis rear)
RJ45 100 Base-T Ethernet Communication Cable, L = 2-2.15 m (P/N: 705900003) — ACM management connection
1
2
1
Table 1. Kits Required for OIU Installation
Corning Optical Communications
Quick Installation Sheet | CMA-263-AEN | Page 1
Page 2
. REQUIRED KITS (CONTINUED)
OIM Kit (1-12 according to order) Qty Item
Optical Interface Module 1
PSM Kit (AC or DC modules —
Qty Item
1 or 2 kits according to order)
PSM-AC: 100-240 VAC Power Supply Module including
1
standard IEC 60320-1 C13 cable
PSM-DC: 48 V DC Power Supply Module; 9 A maximum.; Includes six-pin terminal block connector
OIX Kit (1 or 2 according to order) Qty Item
Optical Interface Expander Module —provides RF
1
interface to headend unit (HEU)
ETM Kit Qty Item
Expander Termination Module — provides termination
1
for unused expander slot
ACM Kit Qty Item
Auxiliary Control Module — provides interface to
1 headend control module (HCM) for remote management and enables local management of unit
Table 1. Kits Required for OIU Installation (continued)
Corning Optical Communications
Quick Installation Sheet | CMA-263-AEN | Page 2
Page 3
. ADDITIONAL REQUIRED ITEMS (NOT PROVIDED)
. MTP®-LC APC harness cable (P/N: 37HP900162-006F) — consists of connector
for splitting bers (six) leading from OIM to ber management unit (FMU) EDGE™ module
2. Four rack-mount nuts and screws for securing unit in rack
3. Grounding tools and components:
• Grounding wire — grounding wire should be sized according to local and
Harness Cable
national installation requirements. The provided grounding lug supports 14 AWG to 10 AWG stranded copper (or 12 AWG to 10 AWG solid) wire conductors.
Note: The length of the grounding wire depends on the proximity of the switch to proper grounding facilities.
• Phillips-head screwdriver
• Crimping tool — for crimping grounding wire to the grounding lug.
• Wire-stripping tool — for removal of insulation from wire
. INSTALL UNIT IN -IN RACK
Notes: Up to four OIU chassis can be connected to a
single HEU
OIU chassis requires 4U rack height availability
Step 1: Determine the location of the OIU in the rack
while considering additional HEUs and OIUs and the lengths of the ERFCs (described in HEU quick installation sheet).
Figure 1 and Figure 2 describe the optimal rack
installations for 4x4 HEU-OIU congurations in shared and dedicated equipment scenarios.
Step 2: Referring to Figure 3, secure the units’ rack ears
to the rack frame as follows:
• Insert two screws halfway into the rack frame.
• Position the chassis on to the screws using the handles and the top and bottom half slots of the rack ears.
• Secure the unit in the rack via all applicable bracket holes using the appropriate rack nuts and screws.
Figure 1. 4x4 Rack Installation Diagram – Dedicated
Figure 2. 4x4 Rack Installation Diagram – Shared
Corning Optical Communications
Figure 3. Positioning Chassis in Rack
Quick Installation Sheet | CMA-263-AEN | Page 3
Page 4
. INSTALL ALL MODULES
Note: For modules with ejectors (i.e., OIM, OIX, and ACM)
– verify that the ejectors are completely open when inserting in dedicated slot and then push in until the module clicks in to the backplane. Figure 4 shows example of module type captive screws and ejectors.
Step 1: Refer to Figure 5 for module locations. Remove
blank panel and slide in the relevant module (chassis slots are 100 percent mistake proof):
• (One) ACM
• (One to two) PSM – for single-power supply installations, install the PSM in either (PSM) slot.
• (One to two) OIX – for single OIX installations, the second OIX slot must be occupied with an expander termination module (ETM).
• (One to 12) OIM — no need to terminate unoccupied OIM slot.
Step 2: Secure modules into the OIU backplane by:
Figure 4.Module Ejectors
• Closing ejectors rmly (for relevant modules)
• Tightening the captive screws
. GROUND CHASSIS
The grounding connection is performed via a two-hole, standard
barrel grounding lug located on the chassis rear panel (see Figure 6).
Prise de terre du châssis OIU:
La mise à la terre est réalisée en utilisant une cosse deux trous a
œillet standard, située à l’arriè du chassis OIU (voir Figure 6).
Figure 5. Location of OIU Chassis Modules
Figure 6. Location of Chassis Grounding Lug
Corning Optical Communications
Quick Installation Sheet | CMA-263-AEN | Page 4
Page 5
. GROUND CHASSIS (CONTINUED)
Step 1: Use a wire-stripping tool to remove approximately
0.4- in (10.9 mm) of the covering from the end of the grounding wire.
Step 2: Insert the stripped end of the grounding wire into
the open end of the grounding lug.
Step 3: Crimp the grounding wire in the barrel of the
grounding lug. Verify that the ground wire is securely attached to the ground lug by holding the ground lug and gently pulling on the ground wire.
Step 4: Prepare the other end of the grounding wire and
connect it to an appropriate grounding point at the site to ensure adequate earth ground.
. FIBER CONNECTIONS
Using an MTP®-LC APC harness cable:
• Connect the harness cables’ MTP® connector to the OIM MTP connector
• Remove the protective plastic covers and connect the (3) LC APC connection bers to the FMU EDGE™ module LC APC connections. See Figure 7.
ATTENTION! Take note of the ber numbering (i.e., 1/2/3).
. EXPANDER CONNECTIONS TO HEU
RF expander connections between the OIU and HEU are
performed using the ERFC cable (included in HEU order) and are described in the HEU quick installation sheet (CMA-267-AEN) provided with the unit. See Figure 8 for general view of connections.
Figure 7. OIMs Fiber Connections
Figure 8. OIX-to-RIX Expander Connection
Corning Optical Communications
Quick Installation Sheet | CMA-263-AEN | Page 5
Page 6
. POWER UP
Note: Only AC power connections are decsribed in this document. Refer to PSM-DC quick
installation sheet (CMA-365-AEN) provided with PSM-DC for wiring pinout.
Figure 9. PSM-AC Interfaces
ATTENTION!
• Approved power cable – the entire length of the power cable (or exible cord) and the insulation must be intact. The cable must be rmly connected to both the electrical plug and the unit itself.
• Standard plug – the use of a standard plug is mandatory. The use of a non-standard power plug can cause electrocution! Also, plugging a non-standard plug into a standard socket that does not correspond to the plugs’ shape, can damage the socket making it a safety hazard.
• Always disconnect all AC power sources from the unit before servicing (i.e., maintenance).
To power up the unit:
Connect the PSM-AC power connector to the AC power source using the provided AC power cable and turn power switch on. See Figure 9 for AC connector location.
• Power input: 100-240 VAC
• Power consumption (fully loaded chassis): 300 W (maximum);
ATTENTION!
• Câble d’alimentation qui est approuvé —la totalité de la longueur du câble d’alimentation (ou cordon souple) et de l’isolation doit être intact. Le câble doit être bien connecté à la fois à la prise électrique et l’appareil.
• Prise électrique standard — l’utilisation d’une che standard est obligatoire. L’utilisation d’un cordon d’alimentation non standard peut entraîner l’électrocution! De meme, brancher une che non­standard sur une prise standard ne correspondant pas à la forme de de la che, peut endommager la Prise, ce qui en fait un danger de sécurité.
• Débrancher toujours toutes les sources d’alimentation CA de l’unité avant l’entretien.
Pour mettre l’unité sous tension:
Branchez la prise d’alimentation du PSM-AC à la source d’alimentation secteur à l’aide du câble d’alimentation secteur fourni et allumer l’interrupteur. Voir Figure 9 pour l’emplacement du connecteur AC.
• Alimentation: 100-240 VAC
Corning Optical Communications
• Consommation maximale électrique (pour les châssis entièrement charges): 300 W ; 18 W par OIM
Quick Installation Sheet | CMA-263-AEN | Page 6
Page 7
. MANAGEMENT CONNECTIONS
Using the provided RJ45/RJ45 communication cable connect
the OIU ACM control module as follows:
• Referring to Figure 10 — for congurations with one HCM and up to four ACMs (e.g., one HEU and four OIUs), directly connect as follows:
From any …. To any ….
ACM “INTERNAL (TO HCM)” port
HCM “INTERNAL (TO ACM)” port
• For congurations with one HCM and more than four ACMs (e.g. , 4x4 HEU-OIU congurations) where there are only four available HCM “INTERNAL” ports:
From any …. To any ….
ACM”INTERNAL (TO ACM)” port
Other available ACM module “INTERNAL (TO ACM)” port
Refer to Figure 11 for schematic example of management
connections.
Note: Main HEU refers to HEU with HCM.
Figure 10. Direct OIU Management Connection
Figure 11. Schematic Example of 4x4 Management Connections
Corning Optical Communications
Quick Installation Sheet | CMA-263-AEN | Page 7
Page 8
. VERIFY NORMAL OPERATION
If OIU chassis is powered on, verify that the OIM and ACM (see Figure 12) module LEDs indicate normal operation:
Figure 12. OIM and ACM Status LEDs
Module LED Description
PSM PWR Status Green steady — power input detected
Off — no power
OIM LINK 1/2/3 Steady green — optical link power to/from the connected remote is normal
Off – no optical power from remote detected
RUN Blinking green — OIM software has initialized and is up and running
Off — power off
PWR Steady green — power input detected in OIMe
ACM PWR Steady green — power input detected by ACM
RUN Blinking green — ACM software up and running
SYS Steady green — overall status of the managed system OK
FAN Steady green — normal operation status for all fans
Table 2. OIMe and ACM Status LED Descriptions
Corning Optical Communications LLC • PO Box 489 • Hickory, NC 28603-0489 USA 800-743-2675 • FAX: 828-325-5060 • International: +1-828-901-5000 • www.corning.com/opcomm
Corning Optical Communications reserves the right to improve, enhance, and modify the features and specifications of Corning Optical Communications products without prior notification. A complete listing of the trademarks of Corning Optical Communications is available at www.corning.com/opcomm/trademarks. All other trademarks are the properties of their respective owners. Corning Optical Communications is ISO 9001 certified. © 2013, 2018 Corning Optical Communications. All rights reserved. CMA-263-AEN / March 2018
P/N 709C021301 A00