Cornelius VANTAGE POST-MIX DISPENSER User Manual

Service/Maintenance Manual
IMPORTANT:
TO THE INSTALLER. It is the responsibility of the
Installer to ensure that the water supply to the dispensing equipment is provided with protection against backflow by an air gap as defined in ANSI/ASME A112. 1.2-1979; or an approved vacuum breaker or other such method as proved effective by test.
VANTAGE POST-MIX DISPENSER
Water pipe connections and fixtures directly connected to a potable water supply shall be sized, installed, and maintained according to Federal, State, and Local laws.
Part No. 312031004 January 26, 1996 Revised: March 3, 1998 Control Code C
THIS DOCUMENT CONTAINS IMPORTANT INFORMATION This Manual must
IMI CORNELIUS INC; 1998Ó
PRINTED IN U.S.A
TABLE OF CONTENTS
SAFETY INFORMATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RECOGNIZE SAFETY INFORMATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNDERSTAND SIGNAL WORDS 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FOLLOW SAFETY INSTRUCTIONS 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CO2 (CARBON DIOXIDE) WARNING 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SHIPPING, STORING, OR RELOCATING UNIT 1. . . . . . . . . . . . . . . . . . . . . . .
GENERAL INFORMATION 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TO THE USER OF THIS MANUAL 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLAIMS INSTRUCTIONS 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WARRANTY REFERENCE INFORMATION 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DESIGN DATA 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
THEORY OF OPERATION 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNIT WITH INTEGRAL (BUILT-IN) COLD CARBONATOR 4. . . . . . . . . . . . . .
UNIT REQUIRING REMOTE CARBONATOR 4. . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE AND MAINTENANCE 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PREPARING UNIT FOR SHIPPING OR RELOCATING 7. . . . . . . . . . . . . . . . . . . . .
HOOD AND FRONT ACCESS PANEL REMOVAL 7. . . . . . . . . . . . . . . . . . . . . . . . . .
HOOD REMOVAL 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FRONT ACCESS PANEL REMOVAL 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PERIODIC INSPECTION 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTMENTS 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CO2 REGULATORS ADJUSTMENTS 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTING DISPENSING VALVES WATER FLOW RATE 10. . . . . . . . . . . . .
ADJUSTING WATER-TO-SYRUP “RATIO” (BRIX) OF DISPENSED
PRODUCT 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING AND SANITIZING 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DAILY CLEANING OF UNIT 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SANITIZING POST-MIX SYRUP SYSTEMS 12. . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING DROP-IN REFRIGERATION ASSEMBLY CONDENSER COIL 15. . . .
CHECKING ICE WATER BATH 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING WATER TANK 16.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CARBONATOR WATER PUMP YEARLY MAINTENANCE OR AFTER
WATER SYSTEM DISRUPTIONS 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE CARBONATOR 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INTEGRAL (BUILT-IN) CARBONATOR 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
TROUBLESHOOTING UNIT 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WATER-TO-SYRUP ‘‘RATIO’’ TOO LOW OR TOO HIGH. 19. . . . . . . . . . . . . . .
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW REGULATOR DOES
NOT INCREASE TO DESIRED WATER-TO-SYRUP ‘‘RATIO’’ 19. . . . . . . . . . .
ADJUSTMENT OF DISPENSING VALVE SYRUP REGULATOR DOES NOT
DECREASE TO DESIRED WATER-TO-SYRUP ‘‘RATIO’’. 20. . . . . . . . . . . . . .
DISPENSED PRODUCT CARBONATION TOO LOW. 20. . . . . . . . . . . . . . . . . .
i 312031004
TABLE OF CONTENTS (cont’d)
DISPENSED PRODUCT COMES OUT OF DISPENSING VALVE CLEAR
BUT FOAMS IN CUP OR GLASS. 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DISPENSED PRODUCT PRODUCES FOAM AS IT LEAVES
DISPENSING VALVE. 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
NO PRODUCT DISPENSED FROM ALL DISPENSING VALVES 21. . . . . . . .
ONLY CARBONATED WATER DISPENSED. 21. . . . . . . . . . . . . . . . . . . . . . . . . .
ONLY SYRUP DISPENSED. 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING REFRIGERATION SYSTEM 21. . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR DOES NOT OPERATE. 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR WILL NOT STOP AFTER SUFFICIENT ICE BANK IS
PRODUCED. 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR OPERATES CONTINUOUSLY BUT DOES NOT FORM
SUFFICIENT ICE BANK. 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONDENSER FAN MOTOR NOT OPERATING. 22. . . . . . . . . . . . . . . . . . . . . . .
AGITATOR MOTOR NOT OPERATING. 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WARRANTY 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LIST OF FIGURES
Page
FIGURE 1. VANTAGE POST--MIX DISPENSER (FIVE-FLAVOR UNIT SHOWN) 4 FIGURE 2. PLUMBING DIAGRAM (FIVE-FLAVOR UNIT WITH INTEGRAL
CARBONATOR SHOWN) 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 3. PLUMBING DIAGRAM (FIVE-FLAVOR UNIT W/INTEGRAL CARB AND ONE NON-CARB
DRINK SHOWN) 5. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..
FIGURE 4. PLUMBING DIAGRAM (FOUR-FLAVOR UNIT REQUIRING
REMOTE CARBONATOR) 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 5. PLUMBING DIAGRAM (FIVE-FLAVOR UNIT REQUIRING
REMOTE CARBONATOR) 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 6. PARTS IDENTIFICATION (FIVE-FLAVOR UNIT WITH INTEGRAL
CARBONATOR SHOWN) 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 7. PARTS IDENTIFICATION (FIVE-FLAVOR UNIT REQUIRING REMOTE
CARBONATOR SHOWN) 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 8. UF-1 DISPENSING VALVE 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 9. WIRING DIAGRAM 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LIST OF TABLES
TABLE 1. DESIGN DATA 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
312031004
ii
SAFETY INFORMATION
Recognize Safety Information
This is the safety-alert symbol. When you see this symbol on our machine or in this manual, be alert to the potentially of personal injury.
Follow recommended precautions and safe operating practices.
Understand Signal Words
A signal word - DANGER, WARNING, OR CAUTION is used with the safety-alert symbol. DANGER identi­fies the most serious hazards.
DANGER
Safety signs with signal word DANGER or WARNING are typically near specific hazards.
General precautions are listed on CAUTION safety signs. CAUTION also calls attention to safety mes­sages in this manual.
WARNING
CAUTION
Follow Safety Instructions
Carefully read all safety messages in this manual and on your machine safety signs. Keep safety signs in good condition. Replace missing or damaged safety signs. Learn how to operate the machine and how to use the controls properly . Do not let anyone operate the machine without instructions. Keep your machine in proper working condition. Unauthorized modifications to the machine may impair function and/or safety and affect the machine life.
CO2(Carbon Dioxide) Warning
CO2Displaces Oxygen. Strict Attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Person­nel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
Shipping, Storing, Or Relocating Unit
CAUTION: Before shipping, storing, or relocating this Unit, the syrup systems must be sanitized and all sanitizing solution must be purged from the syrup systems. All water must also be purged from the plain and carbonated water systems. A freezing ambient temperature will cause residual water remaining inside the Unit to freeze resulting in damage to internal components of the Unit.
1 312031004
312031004
2
THIS PAGE LEFT BLANK INTENTIONALLY
3
312031004
GENERAL INFORMATION
TO THE USER OF THIS MANUAL
This is a Service and Maintenance Manual for the four and five-flavor Vantage Post-Mix Dispensers with integral (built-in) cold carbonators (see figure 2 or 3) or the four and five-flavor Dispensers requiring connection to re­mote carbonators (see figures 4 or 5).These Dispensers will hereafter be referred to as Units. Retain this manu­al as part of your equipment.
This Unit must be installed and serviced by a qualified Service Person. This Unit contains no User serviceable parts.
CLAIMS INSTRUCTIONS
Claims: In the event of shortage, notify the carrier as well as IMI Cornelius immediately. In the event of dam- age, notify the carrier. IMI Cornelius is not responsible for damage occurring in transit, but will gladly render assistance necessary to pursue your claim. Merchandise must be inspected for concealed dam­age within 15 days of receipt.
WARRANTY REFERENCE INFORMATION
Warranty Registration Date
(to be filled out by customer) Unit Part Number: Serial Number: Install Date: Local Authorized
Service Center:
DESIGN DATA
Table 1. Design Data
Part Number See Unit nameplate
Dimensions:
Height 18-1/2 inches Width 15-inches Depth 26-inches
Maximum Plain Water Pressure (Integral Carbonator Units Only) 45-psi (see NOTE)
Maximum Carbonator CO2Pressure (Integral Carbonator Units Only) 60-psi
Voltage/Amps See Unit nameplate
Operating Temperature 40° F to 100° F
NOTE: The plain water source water pressure must not exceed 45-psi. If water pressure exceeds 45-psi, a water pressure regulator must be used to regulate the water pressure.
312031004
4
5
31203100431203100
4
6
CARB WATER
INLET
SYRUP
INLET
CARB WATER
COOLING COIL
SYRUP
COOLING COIL (4)
1
DISPENSING
VALVE (4)
2
3
CARB WATER
INLET
CARB WATER
COOLING COIL
CARB WATER
MANIFOLD
4
FIGURE 4. PLUMBING DIAGRAM (FOUR-FLAVOR UNIT REQUIRING REMOTE CARBONATOR)
SERVICE AND MAINTENANCE
This section describes the service and maintenance procedures to be performed on the Unit.
IMPORTANT: Only qualified Service Personnel should service the internal components or electrical wiring.
DANGER: To avoid possible fatal electrical shock or serious injury to the operator, it is required that a GFCI (ground fault circuit interrupt) be installed in the electrical circuit for the domestic Units. It is required that an ELCB (earth leakage circuit breaker) be installed in
the electrical circuit for the export Units.
WARNING: Disconnect electrical power from the Unit to prevent personal injury before attempting any internal maintenance. Only qualified personnel should service the internal components or electrical wiring.
PREPARING UNIT FOR SHIPPING OR RELOCATING
CAUTION: This Unit is intended for indoor installation only. Do not install this Unit in an outdoor environment which would expose it to the outside elements.
CAUTION: Before shipping, storing, or relocating this Unit, the syrup systems must be sanitized and all sanitizing solution must be purged from the syrup systems. All water must
also be purged from the plain and carbonated water systems. A freezing ambient environment will cause residual water in the Unit to freeze resulting in damage to internal components.
HOOD AND FRONT ACCESS PANEL REMOVAL
(see applicable Figure 6 or 7)
HOOD REMOVAL
CAUTION: Do not place or store anything on top of the Unit.
Remove screw securing hood, then lift hood straight up off the Unit.
IMPORTANT: Circulating air, required to cool the refrigeration assembly condenser coil, is drawn in through grille on top of the hood and is exhausted out through grille on back of the lower housing assembly .
FRONT ACCESS PANEL REMOVAL
Remove two screws securing the front access panel, then remove the panel.
PERIODIC INSPECTION
1. Clean the drop-in refrigeration assembly condenser coil every 30-days as instructed. Cleaning the condenser coil should be performed by a qualified Service Person. DO NOT place objects on top of the
hood or on back side of the Unit. Restricting circulating air in and out of the Unit will cause the refrigeration system to overheat.
HOOD
HOOD RETAINING
SCREW
FRONT ACCESS
PANEL
FRONT ACCESS
PANEL RETAINING
SCREW (2)
DOUBLE LIQUID
INSULATION PAD
WATER TANK
OVERFLOW TUBE
115/24 VAC
TRANSFORMER
DROP-IN
REFRIGERATION ASS’Y
CHECK VALVE
CONDENSER
COIL
AGITATOR
MOTOR
CONTROL
BOX
CUP REST
DRIP TRAY
SYRUP INLET
TUBE (5)
CO2CHECK VALVE
DISPENSING
VALVE (5)
WATER TANK
DRAIN HOSE
CARBONAT OR
WATER TANK
FIGURE 6. PARTS IDENTIFICA TION (FIVE-FLAVOR UNIT WITH INTEGRAL CARBONA TOR SHOWN)
8312031004
HOOD
HOOD RETAINING
SCREW
FRONT ACCESS
PANEL
FRONT ACCESS
PANEL RETAINING
SCREW (2)
REFRIGERATION ASS’Y
WATER TANK
OVERFLOW TUBE
115/24 VAC
TRANSFORMER
DROP-IN
CONDENSER
COIL
AGITATOR
MOTOR
CONTROL
BOX
CUP REST
DRIP TRAY
SYRUP INLET
TUBE (5)
DISPENSING
VALVE (5)
CARB WATER INLET TUBE
WATER TANK
DRAIN HOSE
2. Check the dispensing valves for dripping that indicates leakage and repair as necessary .
ADJUSTMENTS
CO2REGULATORS ADJUSTMENTS
WARNING: CO2displaces oxygen. Strict attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is
suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Personnel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
NOTE: To readjust CO2regulator to a lower setting, loosen adjusting screw lock nut, then turn screw to the left (counterclockwise) until pressure gage reads 5 psi lower than new setting will be. Turn the adjusting screw to the right (clockwise) until the gage registers new setting, then tighten the lock nut.
Adjusting Carbonator CO2Regulator. UNIT WITH INTEGRAL (BUILT-IN) COLD CARBONATOR Adjust CO2regulator for the Unit integral (built-in) carbonator at 60-psi maximum. UNIT REQUIRING REMOTE CARBONATOR Adjust CO2regulator for the remote carbonator to CO2pressure specified in manual provided with the
carbonator.
Adjusting Syrup Source CO2Regulator.
SUGAR SYRUP TANKS CO2REGULATOR Adjust syrup tanks CO2regulator to a minimum of 45-psi.
SYRUP PUMPS (BAG-IN-BOX SYSTEM) Adjust the syrup pumps CO2regulator to 70-psi. DO NOT EXCEED MAXIMUM CO2PRESSURE SPECIFIED
ON THE SYRUP PUMPS.
ADJUSTING DISPENSING VALVES WATER FLOW RATE
(see Figure 8)
1. Remove cover from the dispensing valve by lifting the front cover up 1/4 inch and pulling forward.
2. Install syrup diversion tube assembly on the dispensing valve by pushing rubber end of the syrup diversion tube onto the syrup outlet of the inner nozzle.
3. Measure the water flow rate by dispensing water into a graduated cup for a set period of time.
NOTE: Adjusting screw stops are built into the valve to prevent leakage when the screws are adjusted too far clockwise. Stop adjusting clockwise when turning resistance increases. Turn the screw counterclockwise 1--1/2 turns after the stop are contacted.
4. Turn the water flow regulator adjusting screw to the left (counterclockwise) to decrease the water flow rate or turn the adjusting screw to the right (clockwise) to increase the water flow rate, then recheck the flow rate. Adjustments should be no more than 1/4 turn at a time.
5. Remove syrup diversion tube from the dispensing valve, then install cover on the dispensing valve.
10312031004
WATER FLOW
REGULAT OR
INNER NOZZLE
SYRUP FLOW
REGULAT OR
Counterclockwise
to Decrease
Clockwise
to Increase
NOZZLE
SYRUP DIVERSION
TUBE
RATIO CUP
FIGURE 8. UF-1 DISPENSING VALVE
ADJUSTING WATER-TO-SYRUP “RATIO” (BRIX) OF DISPENSED PRODUCT
(see Figure 8)
NOTE: Make sure the dispensing valve water flow rate is as desired before adjusting the valve for Water-to-Syrup ‘‘Ratio’’ (Brix) of the dispensed product.
Adjust Water--to--Syrup “Ratio” (Brix) of the dispensed product by using ratio cup (P/N 311100000) and syrup diversion tube assembly (P/N 319540000) as follows:
1. Remove cover from the dispensing valve by lifting front cover up 1/4 inch and pulling forward.
2. Install syrup diversion tube assembly on the dispensing valve by pushing the rubber end of the syrup diversion tube onto the syrup outlet of the inner nozzle.
Notice: Refer to syrup manufacturer’s recommendations on syrup package for water-to-syrup ratio.
3. Dispense enough to fill syrup diversion tube with syrup.
4. Hold large chamber of the ratio cup under the dispensing valve nozzle. Place free end of the syrup diversion tube into the syrup chamber marked for the proper ratio. Dispense approximately 6 ounces of water into the ratio cup. Water and syrup levels should be even in cup.
Note: Adjusting screw stops are built into the valve to prevent leakage when the screws are adjusted clockwise too much. Stop adjusting clockwise when turning resistance increases. Turn the screw counterclockwise 1--1/2 turns after the stop are contacted.
5. Adjusting Syrup Flow Regulator -- If water and syrup levels are uneven in the ratio cup, adjust by turning the dispensing valve syrup flow regulator adjusting screw labeled SYRUP as follows.
A. For less syrup, turn the adjusting screw counterclockwise no more than 1/4 turn at a time. B. For more syrup, turn the adjusting screw clockwise no more than 1/4 turn at a time.
6. Repeat water-to-syrup ratio test and adjust syrup flow regulator as many times as necessary until proper ratio of dispensed drink is achieved.
7. Remove syrup diversion tube assembly from dispensing valve.
8. Install dispensing valve front cover.
CLEANING AND SANITIZING
DAILY CLEANING OF UNIT
1. Remove cup rest from the drip tray .
2. Wash drip tray in place on the Unit, then rinse drip tray with hot water allowing water to drain out through the drain hose.
3. Wash cup rest, then rinse the cup rest with clean water. Install cup rest in the drip tray.
4. Clean all external surfaces of the Unit with a sponge. Rinse out the sponge with clean water, then wring excess water out of the sponge and wipe off all external surfaces on the Unit. Wipe Unit dry with a clean soft cloth. DO NOT USE ABRASIVE CLEANERS.
5. Remove nozzle and syrup diffusers from the dispensing valves. Place nozzles and syrup diffusers in sanitizing solution.
6. Wash the nozzles and syrup diffusers in sanitizing solution, then rinse them with potable water.
7. Re-install nozzles and syrup diffusers back on the dispensing valves.
SANITIZING POST-MIX SYRUP SYSTEMS
IMPORTANT: Only qualified Service Personnel should perform sanitizing procedure on the post-mix syrup systems.
The post-mix syrup systems should be sanitized every 90-days using a non-scented household liquid bleach containing a 5.25 % sodium hypochlorite concentration. Proceed as follows to sanitize the post-mix syrup systems.
1. Disconnect syrup supplies from syrup systems.
2. Rinse quick disconnects (syrup tanks systems) or bag-in-box connectors (syrup bag-in-box systems) in warm potable water.
STEP 1. WASH SYRUP SYSTEMS
3. Using a clean syrup tank (syrup tank system) or a five-gallon container (bag-in-box system), prepare a full tank or container of liquid dishwasher detergent by using 70_ F (21_ C) to 100_ F (38_ C) potable water and 0.5 oz. (15 ml) of liquid dishwasher detergent to one gallon of potable water. Stir detergent solution to thoroughly mix the solution.
4. Syrup Tank Systems. A. Observe and note CO2pressure setting on the syrup tanks CO2regulator, then re-adjust CO
regulator to 60 to 80-psi. Pressurize syrup tank containing detergent solution to 60 to 80-psi.
B. Connect detergent solution tank, pressurized at 60 to 80-psi, into one of the syrup systems.
12312031004
2
Bag-in Box Syrup Systems.
C. Install bag valves, cut from empty bag-in-box syrup containers, on ends of syrup containers syrup
outlet tubes connectors.
D. Place all syrup outlet tubes, with bag valves on their ends, in container containing detergent solution.
5. Flush the syrup system and dispensing valve as follows: A. Place waste container under applicable dispensing valve. B
B. Activate the dispensing valve for one minute to purge all water from and install sanitizing solution in
the syrup system and dispensing valve.
C. Continue to activate the dispensing valve in cycle
14312031004
25. Dispose of waste sanitizing solution in a sanitary sewer, not in a storm drain, then thoroughly rinse the inside and the outside of the container that was used for sanitizing solution to remove all sanitizing solution residue.
CLEANING DROP -IN REFRIGERATION ASSEMBLY CONDENSER COIL
(see applicable Figure 6 or 7)
CAUTION: The refrigeration assembly condenser coil must be cleaned every 30-days. Excessive accumulation of dust, lint, and grease on the condenser coil will restrict air flow
through the coil and cause the refrigeration system to overheat. Operating the refrigeration system in an overheated condition will eventually lead to compressor failure and will automatically void the factory warranty .
Clean the drop-in refrigeration assembly coil as follows:
1. Unplug Unit power cord from the electrical outlet.
2. Remove screw securing the hood, then lift the hood straight up to remove.
3. Vacuum or use a soft brush to clean the condenser coil. If available, use low-pressure compressed air.
4. Clean dust and dirt from around top of the drop-in refrigeration assembly.
5. Install hood on the Unit and secure with screw.
6. Plug Unit power cord into electrical outlet. The refrigeration system will start after a 2-minute time delay.
CHECKING ICE WATER BATH
(see Figure 6) A ‘‘gurgle’’ heard from the Unit indicates water level in the water tank is low and more water should be added for
maximum cooling. Before adding more water, check the ice water bath for cleanliness and check the water tank coils for excessive mineral deposit build-up.
1. Unplug Unit power cord from electrical outlet.
2. Remove screw securing the hood, then lift the hood straight up to remove.
3. Lift insulation pad covering front section of the water tank for visual inspection of the ice water bath and the ice bank.
4. Using a flashlight, inspect the ice water bath and ice bank for cleanliness.
CLEANING WATER TANK
(see Figure 6)
1. Unplug the Unit power cord from electrical outlet.
2. Close shutoff valve in plain water source line connected to the Unit.
3. Remove two screws securing the Unit front access panel, then remove the panel.
4. Extend the water tank drain hose (located on front of Unit) to a waste container or floor drain. Remove plug from end of the drain hose and allow the water tank to drain.
5. Remove screw securing the hood, then lift the hood straight up to remove from the Unit.
6. Unit With Integral (Built-In) Cold Carbonator. (see Figures 2 and 6) A. Disconnect plain water source line from Unit double liquid check valve assembly inlet. B. Disconnect carbonator water pump plain water outlet line from carbonated water tank plain water inlet
line.
7. Unplug the drop-in refrigeration assembly and electric dispensing valve power cords at connectors on front of the Unit.
CAUTION: The ice bank around the drop-in refrigeration assembly evaporator coils must be completely melted before attempting to lift the drop-in refrigeration assembly up and out of
the Unit lower cabinet assembly. Attempting to lift the drop-in refrigeration assembly and ice bank together up out of the Unit lower housing assembly may cause damage to the evaporator coils.
CAUTION: Never use an ice pick or other instrument to remove ice from the drop-in
refrigeration assembly evaporator coils. Such practice can result in a punctured
refrigeration circuit.
8. Allow the ice bank around the drop-in refrigeration assembly evaporator coils to completely melt. Hot water may be used to speed up the melting process.
9. Very carefully, lift the drop-in refrigeration assembly up and out of the Unit lower housing assembly..
10. Use a fiber brush and carefully clean mineral deposit build-up from the agitator motor shaft and the ice bank sensing bulb.
11. Wash inside of the water tank and the drop-in refrigeration assembly evaporator coils, then rinse with clean water.
12. Install plug in end of the water tank drain hose.
13. Very carefully, install drop-in refrigeration assembly in Unit lower housing assembly by reversing the removal procedure.
14. Unit With Integral (Built-In) Cold Carbonator. (see Figures 2 and 6) A. Connect carbonator water pump plain water outlet line to carbonated water tank plain water inlet line. B. Connect plain water source line to Unit double liquid check valve assembly inlet.
15. Fill the water tank with clean water until water runs out of the water tank overflow hose. USE
LOW-MINERAL-CONTENT WATER WHERE A LOCAL WATER PROBLEM EXISTS.
16. Plug Unit power cord into electrical outlet. The refrigeration system will start after a 2-minute time delay.
16312031004
17. Dispense from one of the dispensing valves to make the carbonator cycle on and off.
18. Check for water leaks and repair if leaks are found.
19. Install Unit hood and secure with screw.
20. Install Unit front access panel and secure with two screws.
CARBONATOR WATER PUMP YEARL Y MAINTENANCE OR AFTER WATER SYSTEM DISRUPTIONS
REMOTE CARBONATOR
The remote carbonator water pump water inlet strainer screen and the double liquid check valve must be inspected and cleaned at least once a year under normal circumstances and after any water system disruption (plumbing work, earthquake, etc.). Refer to manual provided with the remote carbonator for servicing procedure.
INTEGRAL (BUILT-IN) CARBONATOR
(see Figures 2 and 6)
Replacing Double Liquid Check Valve.
WARNING: The carbonator water pump double liquid check valve assembly must be replaced at least once a year under normal circumstances, and after any disruptions
(plumbing work, earthquake, etc.) to the water supply system that might cause turbulent (erratic) flow of water through the system. Foreign particles fouling the double liquid check valve could cause CO2gas to back flow into the water system and create a health hazard in the water system.
The carbonator water pump double liquid check valve assembly must be replaced at least once a year under normal circumstances and after any water system disruption (plumbing work, earthquake, etc.) to the water supply system.
Replacing CO2Gas Check Valve.
(see Figures 2 and 6) The CO2gas check valve must be replaced at least once a year under normal circumstances and after any
servicing or disruption of the CO2system.
FIGURE 9. WIRING DIAGRAM
18312031004
TROUBLESHOOTING
IMPORTANT: Only a qualified Service Person should service internal components or electrical wiring.
DANGER: Disconnect electrical power to the Unit to prevent personal injury before
attempting any electrical repairs to the internal components. If repairs are to be made to
one of the syrup systems, disconnect syrup supply from the system, then bleed system pressure before proceeding. If repairs will be made to the CO2or the carbonated water system, disconnect electrical power to the carbonator, shut off CO2and plain water supplies, then bleed systems pressures before proceeding.
TROUBLESHOOTING UNIT
Trouble Probable Cause Remedy
WATER-TO-SYRUP ‘‘RATIO’’ TOO LOW OR TOO HIGH.
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW REGULATOR DOES NOT INCREASE TO DESIRED WATER-TO-SYRUP ‘‘RATIO’’
A. Dispensing valve syrup flow
regulator not properly adjusted.
B. Syrup Tanks System.
CO2gas pressure to syrup tanks insufficient to push syrup out of tank.
Bag-In-Box System.
CO2gas pressure to syrup pumps insufficient to operate pumps.
A. No syrup supply. A. Replenish syrup supply.
B. Syrup Tanks system.
Syrup tanks CO2regulator out of adjustment.
Syrup Bag-In-Box System.
Syrup pumps CO2regulator out of adjustment.
A. Adjust Water-to-Syrup ‘‘Ratio’’ as
instructed.
B. Adjust CO2regulator for syrup
tanks as instructed.
Adjust syrup pumps CO2regulator as instructed.
B. Adjust CO2regulator for syrup
tanks as instructed.
Adjust syrup pumps CO2regulator as instructed.
C. Dispensing valve syrup flow
control or syrup line restricted. D. Improper syrup Baume. D. Replace syrup supply. E. Inoperative dispensing valve
syrup flow control. F. Tapered gasket inside tube
swivel nut connection distorted
from being overtightened
restricting syrup flow.
19 312031004
C. Sanitize syrup system as
instructed.
E. Repair dispensing valve syrup
flow control.
F. Replace tapered gasket. Make
sure it is properly seated.
Trouble RemedyProbable Cause
ADJUSTMENT OF DISPENSING VALVE SYRUP REGULATOR DOES NOT DECREASE TO DESIRED WATER-TO-SYRUP ‘‘RATIO’’.
DISPENSED PRODUCT CARBONATION TOO LOW.
DISPENSED PRODUCT COMES OUT OF DISPENSING VALVE CLEAR BUT FOAMS IN CUP OR GLASS.
A. Dirty or inoperative dispensing
valve syrup flow control.
A. Disassemble and clean
dispensing valve syrup flow regulator.
A. Carbonator CO2regulator out
of adjustment for existing
A. Adjust carbonator CO2regulator
as instructed. water conditions or temperature.
B. Air in carbonated water tank. B. Vent air out of carbonated water
tank by dispensing from
dispensing valve to make
carbonator water pump motor
cycle on.
C. Water, oil, or dirt, in CO
supply .
2
C. Remove contaminated CO2.
Clean CO2system (lines,
regulator, etc.) using a mild
detergent. Install a clean CO
2
supply .
A. Oil film or soap scum in cup
A. Use clean cups and glasses.
or glass.
B. Ice used for finished drink
is subcooled.
B. Do not use ice dir
20312031004
Trouble RemedyProbable Cause
DISPENSED PRODUCT PRODUCES FOAM AS IT LEAVES DISPENSING VALVE. (cont’d)
NO PRODUCT DISPENSED FROM ALL DISPENSING VALVES
ONLY CARBONATED WATER DISPENSED.
F. Dirty water supply. F. Check water filter. Replace
cartridge (see NOTE).
NOTE: If water supply is dirty, be sure to flush lines and carbonator carbonated water tank completely. It may be necessary to remove lines to the carbonated water tank, invert the tank, then flush tank and all inlet lines to remove any foreign particles or dirt.
A. No electrical power to Unit. A. Plug in Unit power cord or check
for blown power fuse or tripped circuit breaker. (Note: Fuse or circuit breaker are not part of Unit.)
B. Disconnected dispensing
valves power cord.
C. Disconnected or broken wiring
B. Connect dispensing valves power
cord.
C. Connect or replace wiring.
to dispensing valveS.
D. Inoperative 115 /24 VAC
D. Replace transformer.
transformer.
A. Out of syrup A. Replenish syrup supply as
instructed. B. Inoperable dispensing valve. B. Repair dispensing valve. C. Dispensing valve syrup flow
control not properly adjusted.
D. Dispensing valve syrup flow
control or syrup lines restricted.
ONLY SYRUP DISPENSED. A. Plain water inlet supply line
shutoff valve closed.
B. Carbonator not operating. B. Repair carbonator.
TROUBLESHOOTING REFRIGERATION SYSTEM
COMPRESSOR DOES NOT
A. Ice bank sufficient. A. Refrigeration not called for.
OPERATE.
B. Ice bank control board has
2-minute time delay.
C. Unit power cord unplugged or
drop-in refrigeration assembly power cord unplugged.
D. No power source (blown fuse
or tripped circuit breaker).
C. Adjust dispensing valve syrup
flow control (Water-to-Syrup
‘‘Ratio’’) as instructed.
D. Sanitize syrup system as
instructed.
A. Open plain water inlet supply line
shutoff valve.
B. Wait 2-minutes for compressor to
start.
C. Plug in Unit power cord or plug in
refrigeration assembly power
cord.
D. Replace fuse or reset circuit
breaker. (Note: Fuse or circuit
breaker are not part of Unit.) E. Low voltage. E. Voltage must be at least 103 volts
at compressor terminal when
compressor is trying to start. F. Loose, disconnected, or
broken wiring.
F. Tighten connections or replace
broken wiring.
21 312031004
Trouble RemedyProbable Cause
COMPRESSOR DOES NOT OPERATE.(CONT’D)
COMPRESSOR WILL NOT STOP AFTER SUFFICIENT ICE BANK IS PRODUCED.
COMPRESSOR OPERATES CONTINUOUSLY BUT DOES NOT FORM SUFFICIENT ICE BANK.
G. Inoperative overload protector
G. Replace inoperative part.
or start relay. H. Inoperative ice bank control. H. Replace ice bank control. I. Inoperative compressor. I. Replace compressor. A. Ice bank control probe
A. Replace ice bank probe.
damaged.
B. Ice bank control board
B. Replace ice bank control board.
inoperative. A. Cooling capacity is exceeded
by over-drawing.
B. Unit located in excessively hot
area or air circulation through
condenser coil is restricted.
A. Reduce amount of drinks drawn
per given time.
B. Relocate Unit or check and if
necessary , clean condenser coil as instructed.
NOTE: Ice bank freezes from bottom of evaporator upward. A
refrigerant leak or insufficient charge might show an ice bank at
bottom and not at the top of evaporator.
NOTE: If overload protector cuts out compressor, condenser fan
motor will continue to operate; otherwise; troubleshooting
condenser fan motor problems is same as for ‘‘COMPRESSOR
DOES NOT OPERATE’’ paragraph plus the following:
CONDENSER FAN MOTOR NOT OPERATING.
AGITATOR MOTOR NOT OPERATING.
A. Jumper cord loose or
disconnected from motor or
A. Tighten connections or
replace cord. terminal block. Broken wire in cord.
B. Inoperative condenser
B. Replace condenser fan motor.
fan motor.
A. Unit power cord or
A. Connect power cord(s). refrigeration assembly power cord unplugged.
B. No power source (blown fuse
or tripped circuit breaker).
B. Replace fuse or reset circuit
breaker. (Note: Fuse or circuit breaker are not part of Unit.)
C. Agitator motor propeller
C. Remove obstruction. obstructed.
D. Low voltage. D. Voltage must be at least 103 VAC
at compressor terminals when compressor is trying to start.
E. Loose, disconnected, or
broken wiring.
E. Tighten connections or replace
broken wiring.
F. Inoperative agitator motor. F. Replace agitator motor.
22312031004
WARRANTY
IMI Cornelius Inc. warrants that all equipment and parts are free from defects in material and workmanship under normal use and service. For a copy of the warranty applicable to your Cornelius, Remcor or Wilshire product, in your country, please write, fax or telephone the IMI Cornelius office nearest you. Please provide the equipment model number, serial number and the date of purchase.
IMI Cornelius Offices
AUSTRALIA D P.O. 210, D RIVERWOOD, D NSW 2210, AUSTRALIA D (61) 2 533 3122 D FAX (61) 2 534 2166 AUSTRIA D AM LANGEN FELDE 32 D A-1222 D VIENNA, AUSTRIA D (43) 1 233 520 D FAX (43) 1-2335-2930 BELGIUM D BOSKAPELLEI 122 D B-2930 BRAASCHAAT, BELGIUM D (32) 3 664 0552 D FAX (32) 3 665 2307 BRAZIL D RUA IT AOCARA 97 D TOMAS COELHO D RIO DE JANEIRO, BRAZIL D (55) 21 591 7150 D FAX (55) 21 593 1829 ENGLAND D TYTHING ROAD ALCESTER D WARWICKSHIRE, B49 6 EU, ENGLAND D (44) 789 763 101 D FAX (44) 789 763 644 FRANCE D 71 ROUTE DE ST. DENIS D F-95170 DEUIL LA BARRE D PARIS, FRANCE D (33) 1 34 28 6200 D FAX (33) 1 34 28 6201 GERMANY D CARL LEVERKUS STRASSE 15 D D-4018 LANGENFELD, GERMANY D (49) 2173 7930 D FAX (49) 2173 77 438 GREECE D 488 MESSOGION AVENUE D AGIA PARASKEVI D 153 42 D ATHENS, GREECE D (30) 1 600 1073 D FAX (30) 1 601 2491 HONG KONG D 1104 TAIKOTSUI CENTRE D 11-15 KOK CHEUNG ST D TAIKOKTSUE, HONG KONG D (852) 789 9882 D FAX (852) 391 6222 ITALY D VIA PELLIZZARI 11 D 1-20059 D VIMARCATE, ITALY D (39) 39 608 0817 D FAX (39) 39 608 0814 NEW ZEALAND D 20 LANSFORD CRES. D P.O. BOX 19-044 AVONDALE D AUCKLAND 7, NEW ZEALAND D (64) 9 8200 357 D FAX (64) 9 8200 361 SINGAPORE D 16 TUAS STREET D SINGAPORE 2263 D (65) 862 5542 D FAX (65) 862 5604 SPAIN D POLIGONO INDUSTRAIL D RIERA DEL FONOLLAR D E-08830 SANT BOI DE LLOBREGAT D BARCELONA, SPAIN D (34) 3 640 2839 D FAX (34) 3 654 3379 USA D ONE CORNELIUS PLACE D ANOKA, MINNESOTA D (612) 421-6120 D FAX (612) 422-3255
LD004
4/21/98
31203100423
IMI CORNELIUS INC.
CORPORATE HEADQUARTERS:
One Cornelius Place Anoka, Minnesota 55303-6234 (612) 421-6120 (800) 238-3600
Loading...