Cornelius Remcor CH1500-A, CH Series, Remcor CH1502-A, Remcor CH1503-A, Remcor CH951-A Operator's Manual

IMI CORNELIUS REMCOR INC g 500 REGENCY DRIVE g GLENDALE HEIGHTS, IL 60139--2268
Telephone (800) 551--4423 Facsimile (800) 519--4423
CHILLER (“CH” SERIES)
Operator’s Manual
Models: CH 951-A
CH 1500-A CH 1502-A CH 1503-A
THIS DOCUMENT CONTAINS IMPORTANT INFORMATION This Manual must be read and understood before installing or operating this equipment
IMI CORNELIUS INC; 1995--99Ó
PRINTED IN U.S.A
TABLE OF CONTENTS
GENERAL INFORMATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INTRODUCTION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNPACKING AND INSPECTION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DESIGN DATA 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHILLER INSTALLATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LOCATION OF CHILLER 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL CONNECTIONS 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PROCESS CONNECTIONS 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHILLER OPERATION 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PROCESS LIQUID FLOW 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PHASE PROTECTION / 3--PHASE MONITOR OPTION 3. . . . . . . . . . . . . . . . . . .
PHASE PROTECTION / 3--PHASE OPTION ADJUSTMENT 3. . . . . . . . . . . . . . .
COOLING OPERATION 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TEMPERATURE INDICATOR/CONTROLLER (THERMOSTAT) 4. . . . . . . . . . . .
START--UP 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
THERMOSTAT CONTROL 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHILLER MAINTENANCE 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONDENSER 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FAN MOTOR 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PUMP MOTOR 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CIRCULATION SYSTEM 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FILTERS/STRAINERS 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
CHILLER DOES NOT OPERATE, CONTROL POWER LIGHT “OFF” 7. . . . . . . . .
PUMP DOES NOT OPERATE, BUT COOLING LIGHT IS ”ON”. 7. . . . . . . . . . . . . .
CHILLER DOES NOT COOL, AND COOLING LIGHT IS ”OFF”. 7. . . . . . . . . . . . .
PUMP RUNS, COMPRESSOR ”SHORT CYCLES”. 7. . . . . . . . . . . . . . . . . . . . . . . .
UNIT RUNS CONTINUOUSLY, BUT IS NOT COOLING PROCESS LIQUID
ENOUGH. 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHILLER DOES NOT OPERATE, BUT COOLING LIGHT IS “ON” AND SAFETY
LIGHT IS “ON”. 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WARRANTY 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LIST OF FIGURES
FIGURE 1. “CH” SERIES CHILLERS 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 2. CONTROL PANEL 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 3. CH SERIES TEMPERATURE CONTROLLER 5. . . . . . . . . . . . . . . . . . .
FIGURE 4. CABINET SECTION EXPLODED VIEW 9. . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 5. ELECTRICAL BOX ASSEMBLY EXPLODED VIEW 11. . . . . . . . . . . . . .
FIGURE 6. PUMP AND TANK ASSEMBLY 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LIST OF TABLES
TABLE 1. DESIGN DATA 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
i
92266
GENERAL INFORMATION
INTRODUCTION
The REMCOR ”CH” Series Recirculating Liqu id Chiller is designed to provide an accurate, reliable, and user-­friendly system for cooling a continuous flow of pure liquid and keep that liquid a t a constant temperature in vari­ous closed loop or tank coolin g applications.
The ”CH” Series Chiller consists of an air--cooled refrigeration system housed in a sturdy shee t metal frame and cabinet. A standard pump and insulated liqu id reservoir package provides a complete liquid cooling and circu­lating system.
The ”CH” Series Chiller is designed to operate in a clean laboratory or industrial environment where ambient temperatures ran ge from 40 to100° F (5 to 38° C). With proper installation, operation, and maintenance, the ”CH” Series Chiller will provide years of trouble free service.
UNPACKING AND INSPECTION
This unit was thoroughly inspected be fore leaving the factory and the carrier has accepted and signed for it. Any d amage or irregularities should be noted at the time of delivery and immediately reported to the carrier. Re­quest a written inspection report from the Claims Inspector to substantiate any necessary claims. In the event that a n immediate replacement is necessary,please contact REMCOR Chiller Sales at 1--800--551--4423.
DESIGN DATA
T able 1. Design Data
CH951 CH1500 CH1502 CH1503
Cooling Capacity:
BTU/hr (W) at 80_ F(27_ C) and
70_ F (21_ C) Liq uid Temperature. Compressor Horsepower 1 (.746 kW) 1 1/2 (1.12 kW) 1 1/2 (1.12 kW) 1 1/2 (1.12 kW) Electrical Data:
Voltage/Phase/Hertz/Amperage Refrigerant Type: R134a R22 R22 R22 Reservoir Capacity 6.0 ga llons (22.7
Physical Dimensions, Width ¢ Depth ¢ Height:
Fittings:
Process Conn ections 3/4” FPT (S/S) 3/4I FPT (S/S) 3/4I FPT (S/S) 3/4I FPT (S/S)
12,000 (3,515) 18,000 (5,272) 18,000 (5,272) 1 8,000 (5,272)
230/1/60
11.0 Amps
liters)
22I¢ 26.5XI¢
38.25I
(56cm ¢ 67cm
¢ 97cm)
230/1/60
13.0 Amps
6.0 gallons (22.7 liters)
22I¢ 26.5XI¢
38.25I
(56cm ¢ 67cm
¢ 97cm)
230/3/60
16.4 Amps
6.0 gallons (22 .7 liters)
22I¢ 26.5XI¢
38.25I
(56cm ¢ 67cm
¢ 97cm)
460/3/60
10.0 Amps
6.0 gallons (22.7 liters)
22I¢ 26.5XI¢
38.25I
(56cm ¢ 67cm
¢ 97cm)
CHILLER INSTALLATION
Location of Chiller
THE CHILLER MUST BE LOCATED NEAR A PROPERLY GROUNDED ELECTRICAL OUTLET. THE CIR­CUIT SHOULD BE FUSED AND NO OTHER ELECTRICAL APPLIANCE SHOULD BE CONNECTED TO THE CIRCUIT. ALL ELECTRICAL WIRING MUST CONFORM TO NATIONAL AND LOCAL ELECTRICAL CODES.
The Chiller must be located in a well ventilated, indoor a rea where ambient temperatures will remain above 40_ F (5_ C) and will never increase above 100_ F (38_ C). To obtain optimum cooling capacity ,the ambient temperature should be at or below 80_ F (27_ C).
1
92266
It is very important that the air intake and discharge sides of the chiller are not obstructed by other free standing objects. A minimum of two feet of space on all four sides of the chille r will be sufficient to prevent air flow ob­structions.
It is also important to direct any hot air discharge from other equipment away from the air intake side of the chill­er. Condenser air entering the “CH” unit should be below 100_ F (38_ C) .Condenser air temperatures above 100_ F (38_ C) can cause the high pressure safety control to shut down the unit.
Electrical Connections
All wiring must conform to the National Electric Code and any applicable local codes. The “CH” unit must b e PERMANENTLY wired by means of electrical conduit to a properly fused disconnect of
proper amperage OR wired to a prop erly rated power cord and plugged into an outlet with the appropriate dis­connect a nd amperage rating. The electrical junction box includes a four terminal strip for power supply connec­tions. The DATA PLATE located beside the junction box indicates the phase, voltage and amperage of the chiller.
Process Connections
Follow standard plumbing practices and local codes in making liquid connections. The Chiller inlet and outlet connections are 3/4”--inch FPT couplings. It is recommended that 3 /4--inch I.D. or larger flexible hose and tube fittings be used as process connections. Lines should be routed with as few bends as possible. Prevent lines from running near radiators, hot water pipes, etc. Any lengths of tubing that are exposed to high ambient tem­peratures should be insulated to prevent condensation and/or sign ificant liquid heat gain.
Once the system has been properly plumbed, it is important that the circulation system be filled with liquid. Th e reservoir can be filled by removing the fill port cap located on top of the Chiller. After ensuring that the drain is closed, fill the reservoir via the fill po rt with pure liquid until the liquid level sight glass on the front of the unit indi­cates ”FULL”. Th e fill port cap should then be replaced prior to operation.
DATAPLATE/SERIAL NO.
35.138
37.638
CONTROL PANEL
TEMPERATURE CONTROLLER
FILL PORT
PRESSURE GAUGE
”FULL”
RESERVOIR LEVEL INDICATOR DRAIN
38.224
14.000
JUNCTION BOX TERMINAL STRIP
INTERLOCK STRIP (IF APPLICABLE)
OUTLET
INLET
21.963
FRONT
92266
REAR
FIGURE 1. “CH” SERIES CHILLERS
2
Chiller Operation
WARNING: NEVER OPERATE THE CHILLER WITH THE PANELS REMOVED. ALWAYS USE THE POWER SWITCH TO TURN OFF THE CHILLER WHEN IT IS NOT BEING
USED. ALWAYS ENSURE THAT ALL AIR INLETS AND OUTLETS ARE FREE FROM OBSTRUCTION. BE SURE THAT THE RESERVOIR IS FILLED WITH FLUID PRIOR TO POWERING UP THE UNIT.
Process Liquid Flow
After ensuring that the system piping is free from ob struction, that all valves are open, and the reservoir is full, push the CONTROL POWER switch to the ”ON” p osition. The pump should now be operating.
On three phase units such as the CH1502 and CH1503, it is important to check the pump rotation. Remove the left sid e panel, push the POWER button in, and observe the motor shaft. Make sure that the shaft is rotating in the direction of the a rrow indicated on the pump housing. If the rotation is incorrect, reverse two of the three in­coming power supply leads at the terminal strip.
NOTE: Running the pump in reverse for too long will result in permanent pump damage. The Phase Protection/3--Phase Monitor Option will prevent the pump from operating backwards. See the full de­scription of the option for complete explanation.
All Chillers with pumps are supplied with a pressure reg ulating valve on the pump discharge. This valve is pre­set a t the factory to ensure that system pressure does not exceed the capabilities of the pump motor and/or pip­ing. If this valve requires ad justment, please contact the REMCOR Service Group for the proper setting procedure and p ressures.
Once the flow has been established the thermostat can be p rogrammed to the desired set--point.
Phase Protection / 3--Phase Monitor Option
The 3--Phase Monitor detects phase loss, low voltage, and phase reversal b y continuously monitoring the 3--Phase power lines for abnormal conditions. When correct voltage and phase rotation are applied, the internal relay will en ergize. A fault condition will de--energize the relay. When the fault is corrected, the monitor will auto­matically reset. Both T rip and Norm condition indicators are provided on the relay to aid in adjustment and sys- tem trouble--shooting.
This control is located in the enclosure labeled “Monitor” on top of the electrical box.
Phase Protection / 3--Phase Option Adjustment
The following procedure will a llow the 3--Phase Monitor to achieve a trip point just below the nominal phase-to­phase voltage, where the unit is applied.
Rotate the adjustment control fully clockwise, or until the red (Trip) indicator illuminated. Slowly rotate the adjustment control in a counter-clockwise direction, just until the green (Norm) indicator illuminates. At this point, the 3--Phase Monitor is the most sensitive to irregular power line condition s. If nuisance tripping occurs, turn the control slightly further counter--clockwise.
3
92266
COOLING OPERATION
REMCOR CHXXX SERIES CHILLER
CONTROL
POWER
FIGURE 2. CONTROL PANEL
Temperature Indicator/Controller (Thermostat)
COOLING
WHITE INDICATOR/PUSH BUTTON
SAFETY
CONTROL PANEL
RED INDICATOR
GREEN INDICATOR
Combines a precise temperature control and easy programmability with a convenient LED temperature readout that indicates system liquid temperature (2_ F Differential). To adjust thermostat, see next section.
1. CONTROL POWER SWITCH/LIGHT A simple ON/OFF push--bu tton that switches power to the 24 volt control circuit. When the switch is
pressed, the white light on the push--button illuminates to indicate that Chiller Control Power is present. Light is no longer illuminated when button is returned to ”OFF” position.
2. COOLING LIGHT A gre en light that illuminates to indicate that the refrigeration system is operating. This light may cycle on
and off in response to the thermostat or in response to HOT GAS BYPASS if the u nit is equipped with the hot--gas bypass option .
3. SAFETY LIGHT A red light that illuminates to indicate that a problem is present with the chiller. The safety light will illumi-
nate under the following conditions: A. High Refrigerant Pressure B. Low Refrigerant Pressure C. Low Reservoir Level (Alarm also sounds) D. Low Evaporator Temperature It is important to note that each of these conditions will shut down the ”CH” unit. For additional protection to
your equipment, some models are equipped with a LOW FLOW INTERLOCK which terminates p ower to your equipment in the event that liquid flow from the ”CH” unit drops below 1.25 GPM.
92266
4
START--UP
IT IS IMPORT ANT THAT THE LIQUID LEVEL SIGHT GLASS READS ”FULL”. IN THE EVENT THAT THE RESERVOIR IS EMPTY, THE UNIT WILL REMAIN OFF UNTIL AN ADEQUATE LEVEL OF LIQUID IS AT­TAINED. MAKE SURE CHILLER POWER IS ”OFF” PRIOR TO FILLING RESERVOIR.
Push CONTROL POWER button IN. All alarm indicators should be extinguished and the Chiller system will cycle in order to maintain the established set-point. The Chiller is now ready for normal operation.
Thermostat Control
up
down
7
FIGURE 3. CH SERIES TEMPERATURE CONTROLLER
The following procedure should be followed to adjust the thermostat for any liqu id cooling application:
1. Push the ”SET” bu tton located to the right of the digital display. This will display the current set-point pro­grammed in the thermostat.
2. The set-point can only b e adjusted while being displayed. To adjust the set-point, push the ”UP” or ”DOWN” button until the desired set point is displayed on the thermostat.
3. Once the desired set-point is displayed, wait several seconds and the thermostat will display the process liquid temperature. The set-point can be viewed at any time by pressing the ”SET” button.
The parameter settings of the thermostat have been preset a t the factory. The range of the thermostat is 40_ F (5_ C) to 100_ F (38_ C). If operation outside of this range is desired , please contact the REMCOR TECHNICAL SERVICE DEPARTMENT at 1--800--551--4423.
0
_F
out
set
CHILLER MAINTENANCE
WARNING: Disconnect electrical power before performing any maintenance on the Chiller.
Condenser
On air cooled chillers, the CONDENSER FINS should be cleaned by blowing compressed air through the con­denser from the fan side. Dirt and debris accumulate on the condenser fins over time, and this build up can se­verely reduce the performance of the Chiller. Cleaning of the CONDENSER FINS should be done approximately every three months, depending upon the cleanliness of your application.
Fan Motor
On air cooled chillers the condenser FAN MOTOR should be lubricated every 6 months with a few drops of SAE 10 oil.
5
92266
Pump Motor
The PUMP MOTOR should be lubricated with thirty drop s of SAE 20 oil once a year.
Circulation System
The CIRCULATION SYSTEM should be drained and flushed pe riodically to avoid build up and possible flow re­striction caused by contaminants.
Filters/Strainers
The FILTER located insid e of the unit at the inlet of the pump should be cleaned periodically depending on ap­plications. If a reduction in flow or cavitation of the pump occurs, remove the in--line FILTER, back-flush it with water, rinse, and replace.
92266
6
TROUBLESHOOTING
WARNING: Disconnect electrical power to the Chiller to prevent personal injury before attempting any internal maintenance. Only qualified personnel should service internal components or electrical wiring.
TROUBLE PROBABLE CAUSE REMEDY
CHILLER DOES NOT OPERATE, CONTROL POWER LIGHT “OFF”
PUMP DOES NOT OPERATE, BUT COOLING LIGHT IS ”ON”.
A. No Power To Unit. A. Check Main disconnect fuses,
wiring, and power lead to unit.
B. Defective Control Power
Switch. C. Defective Control Transformer. C. Replace Transformer D. Wrong Voltage Supplied to
Unit. E. 3--Phase Monitor tripped. E. Check for correct voltage level on
A. Line to or from Chiller is
restricted.
B. Internal or external filter is
blocked with debris. C. Pump Contactor is
defective. D. Damaged pump motor or
impeller.
B. Replace Switch
D. Supplied Voltage Must be within
± 10% of nameplate rating.
each phase of incoming 3--phase power. Check for correct phase rotation.
A. Inspect lines and remove any
obstructions.
B. Remove filter, back-flush, and
replace.
C. Replace.
D. Replace pump motor or impeller.
CHILLER DOES NOT COOL, AND COOLING LIGHT IS ”OFF”.
PUMP RUNS, COMPRESSOR ”SHORT CYCLES”.
UNIT RUNS CONTINUOUSLY, BUT IS NOT COOLING PROCESS LIQUID ENOUGH.
A. Thermostat is defective. A. Replace Thermostat
A. No process load on
chiller. B. Refrigerant is low. B. Check refrigerant charge. A. Condenser is restricted. A. Clean condenser.
B. Unit low on refrigerant. B. Call Service. C. Inefficient compressor. C. Call Service. D. Unit is undersized for
application.
A. Increase process load.
D. Call REMCOR Chiller Sales Rep.
TROUBLE REMEDYPROBABLE CAUSE
CHILLER DOES NOT OPERATE, BUT COOLING LIGHT IS “ON” AND SAFETY LIGHT IS “ON”.
A. Unit is operating under high
pressure conditions.
B. Unit is operating under low
pressure conditions.
C. Unit is operating under low
level conditions.
D. Unit is operating under low
temperature conditions.
A. Check for dirty condenser fins or
obstruction of chiller air intake. Press high pressure manual reset switch.
B. Check sight glass, if bubbles are
seen, leak check unit and recharge with refrigerant.
or If no bubbles are seen, replace defective TXV.
C. Add liquid to reservoir via fill port.
or If level is above switch, replace float switch.
D. Low or no process liquid flow.
Ensure that there is adequate flow through system plumbing.
or Process liquid is too cold, below 35_ F. Increase thermostat setting.
or
Defective thermostat, replace.
When servicing a REMCOR Chiller, it is important to note all information provided on the DATA PLATE located in the upper rear of the unit. If technical assistance is needed, the REMCOR Service Technician will need this information along with any description of the problem(s) you are encountering. The serial number and other information will also be required when ordering replacement parts and any other Warranty Claims.
92266
8
13
13
17 41
10
43
42
46
51
28
16
27
39
48
17
49
35
32
11
15
23
24
25
35
26
44
47
33 45 50
6
33 50 52
5
35
32
39
36
16
9
17
22
12
17
38
37
34
40
1
3
4
31
21
19
18
16
36
2
7
29
14
30
20
35
8
FIGURE 4. CABINET SECTION EXPLODED VIEW
922669
CABINET SECTION
Index
No.
Part No. Qty Name
1 15166 1 Frame 2 15207 2 Support Panel (CH 951)
15426 2 Support Panel (CH 1502)
3 61170 1 Pump and Tank Ass’y (CH 951; See
61167 1 Pump and Tank Ass’y (CH 1502; See
4 70190 2 Screw,HexHd,No.8-32By1/2-In.
5 15159 1 Support, Condenser 6 15172 1 Fill Port Ass’y 7 15165 2 Panel, Side (CH 951)
15427 2 Panel, Side (CH 1502)
8 15164 2 Panel, Rear (CH 951)
15425 2 Panel, Rear (CH 1502)
9 33437 1 Electrical Box Ass”y (CH 951; See
33585 1 Electrical Box Ass”y (CH 1502; See
10 15167 1 Lid (CH 951)
15428 1 Lid (CH 1502)
11 61061 1 Condenser Ass’y (CH 951)
61168 1 Condenser Ass’y (CH 1502)
12 70217 4 Screw,HexHd,No.8--32 By 1/2-In.
13 70178 6 Screw,PhilHd,No.8--32 By 1/2-In.
14 15163 1 Panel, Front (CH 951)
15424 1 Panel, Front (CH 1502) 15 32386 2 Thermostat Control, 24v 16 70076 14 Hex Nut, No. 8-32 17 70121 24 Lockwasher 18 28876 2 Coupling Ass’y 19 70778 4 Caster 20 70923 2 Handle 21 32452 1 Terminal Block 22 31036 1 Electrical Box, 4-In.
Figure 6)
Figure 6)
Long
Figure 5)
Figure 5)
Long
Long
Index
No.
Part No. Qty Name
23 32807 1 Indicator Light, Red, 24v 24 32808 1 Indicator Light, Green, 24v 25 32806 1 Switch, White, Lighted 24v 26 71058 1 Gauge, Pressure (CH 951)
70950 1 Gauge, Pressure (CH 1502) 27 70325 2 Clamp 28 70951 8 Fastener,ClipOn 29 70952 8 Retainer,PushOn 30 70953 8 Screw,SlHd,Fastener 31 70030 4 Nut 32 70274 8 Screw,CapHexHd,No.5/16-18By
33 70048 7 Lockwasher 34 70018 7 Hex Nut, 1/4-20 35 70171 20 Screw, Phil Hd, No.8-32 By 3/8-In.Long 36 70028 12 Nut, 5/16-18 37 70065 4 Lockwasher 38 70268 4 Screw,CapHexHd,1/4-20By1-In.Long 39 70070 8 Flatwasher 40 32588 1 Probe, Temperature 41 70877 14 Nutsert 42 51282 1 Adaptor, 3/4-MPT By 1/2-Barb 43 71042 1 Clamp, Hose 44 60734 1 Solenoid Valve,HotGas 45 70344 1 Bracket, Drier 46 70475 1 Clamp, TX Valve 47 60686 1 Filter Drier 48 61003 1 TX Valve 49 60975 1 Valve,AutoExpansion 50 70032 5 Screw,CapHexHd,1/4-20By1/2-In.
51 33283 1 Coil, Solenoid 24v 52 22850 1 Bracket, TX Valve
3/4-In. Long
Long
92266 10
24 23
4
16
22
19
6
18
FIGURE 5. ELECTRICAL BOX ASSEMBLY EXPLODED VIEW
ELECTRICAL BOX ASSEMBLY
Item
No.
Part
No. Qty . Name
1 15269 1 Electrical Box 2 309060 1 Terminal Board 3 31001 1 Thermostat 4 32804 1 Transformer, 24V 50VA 5 32922 1 Contactor,Compressor 6 33082 1 Relay,24V 7 33339 1 Alarm, 24V 8 33573 1 Wire Harness, Main Power (CH 951; Not
Shown)
33607 1 Wire Harness, Main Power (CH 1502;
Not Shown)
9 33574 1 Wire Harness, Condenser (CH 951; Not
Shown)
33608 1 Wire Harness, Condenser (CH 1502;
Not Shown) 10 33575 1 Wire Harness, Alarm (Not Shown) 11 33576 1 Wire Harness, Switch (Not Shown)
18
5
Item
No.
12 33577 1 Wire Harness, Hot Gas (CH 951; Not
13 33578 1 Wire Harness, Thermostat (Not Shown) 14 50459 1 Heyco Bushing 15 50767 1 Heyco Bushing 16 60501 1 High Pressure Control 17 70018 2 Hex Nut, 1/4-20 18 70190 11 Screw, Hex Washer Hd, No. 8-32 By
19 70215 6 Screw,SlWasher Hd, No. 8-32 By
20 70263 2 Screw,CapHexHd,1/4-20By3/4-In.
21 70475 1 Clamp, Alarm 22 15270 1 Cover,ElectricalBox 23 70121 1 Lockwasher,No.8 24 70171 1 Screw,PhilTruss Hd, No. 8-32 By
18
3
12
21
15
7 14
17
20
Part
No. Qty . Name
Shown)
33606 1 Wire Harness, Hot Gas (CH 1502; Not
Shown)
1/2-In. Long
1/4-In. Long
Long
3/8-In. Long
9226611
17
35
23
18
28
43
13
11 12
44 18
16
17 18
18
26
19
6
41
31
28
29
35
9
14
46
22
16
28
10
18
16
18
16
42
35
22
47
46
45
38
14
2
14
15
24 33
14
25
27
3535
32
33
19
17
4
18
21
40
3
8
48
7
34
39
37
1
30
32
30
16
36
18
35
FIGURE 6. PUMP AND TANK ASSEMBLY
92266 12
17
20
30
5
PUMP AND T ANK ASSEMBLY
Item
No.
Part
No. Qty . Name
1 15162 1 Base 2 53206 1 Tank 3 53192 1 Cover 4 27866 1 Thermalwell 5 61169 1 Evaporator 6 32382 1 Motor,Pump,1/3HP115/230V 7 53223 1 PVC Valve 8 50351 1 Tube, .500 I.D. By 28-In. Long
9 33159 2 Sensor,LowLevel 10 70028 4 Hex Nut, 5/16-18 11 70274 4 Screw, Cap, Hex Hd, No. 5/16-18 By
3/4-In. Long 12 70065 4 Lockwasher 13 70070 4 Flatwasher 14 50991 4 Bulkhead, 1/2 I.D. 15 51842 1 Bulkhead, 3/4 I.D. 16 41266 6 Elbow,1/2-NPT, Stainless Steel (CH
951)
40904 6 Elbow,1/2-NPT, Brass (CH 1502)
17 41474 4 Bushing, Fitting, 3/4-NPT By 1/2-NPT,
Stainless Steel (CH 951)
41485 4 Bushing, Fitting, 3/4-NPT By 1/2-NPT,
Brass (CH 1502) 18 41468 9 Fitting, 1/2-MPT By 3/4-Barb, Stainless
Steel (CH 951)
8 Fitting, 1/2-MPT By 3/4-Barb, Brass (CH
1502)
19 41488 3 Fitting, 1/2-MPT, 2 1/2-In. Long,
Stainless Steel (CH 951)
41444 2 Fitting, 1/2-MPT, 2 1/2-In. Long, Brass
(CH 1502) 20 41476 1 Fitting, Tee, 3/4-NPT,StainlessSteel
(CH 951)
41040 1 Fitting, Tee, 3/4-NPT,Brass(CH1502)
21 41470 2 Fitting, Elbow,1/2-NPT, Stainless Steel
(CH 951)
41443 1 Fitting, Elboe, 1/2-NPT, Brass (CH 1502) 22 51075 2 Elbow,1/2-MPTBy1/2-Barb 23 71045 10 Clamp, Tube 24 41438 1 Filter, Water 25 24676 1 Thermowell 26 41461 1 Bypass Valve,StainlessSteel(CH951)
40645 1 Bypass Valve,Brass(CH1502) 27 70018 4 Hex Nut, 1/4-20 28 41268 3 Tee, 1/2-FPT,StainlessSteel(CH951)
40903 3 Tee, 1/2-FPT,Brass(CH1502)
Item
No.
Part
No. Qty . Name
29 41473 1 Nipple, 1/2-NPT, Stainless Steel (CH
951)
40902 1 Nipple, 1/2-NPT, Brass (CH 1502)
30 41477 2 Nipple, 3/4-NPT, Stainless Steel (CH
951)
41442 3 Nipple, 3/4-NPT, Brass (CH 1502)
31 41478 1 Fitting, 1/2-MPT, Stainless Steel (CH
951)
41495 1 Fitting, 1/2-MPT, Brass (CH 1502)
32 41467 2 Fitting, Elbow,3/4-NPT, Stainless Steel
(CH 951)
41096 2 Fitting, Elbow,3/4-NPT, Brass (CH 1502)
33 41462 2 Fitting, Elbow,3/4-NPTBy3/4-Barb,
Stainless Steel (CH 951)
40841 2 Fitting, Elbow,3/4-NPTBy3/4-Barb,
Brass (CH 1502) 34 51425 1 Plug, 1/4-MPT 35 53157 1 Tube, .750 I.D. By 3-In. Long
53157 1 Tube, .750 I.D. By 6-In. Long 53157 1 Tube, .750 I.D. By 7-In. Long 53157 1 Tube, .750 I.D. By 8-In. Long 53157 1 Tube, .750 I.D. By 10 1/2-In. Long
53157 1 Tube, .750 I.D. By 22-In. Long 36 31971 1 Switch, Flow,Brass(CH1502) 37 26198 2 Bracket, Tank 38 51704 1 Fitting, 3/8-PVC 39 53226 1 Fitting, Coupler,3/8-PVC 40 53225 1 Fitting, 3/8-PVC By 1 1/2-In. Long 41 32385 1 Clamp, Pump to Motor 42 32384 1 Pump (CH 951)
32357 1 Pump (CH 1502) 43 30121 1 Electrical Cord 44 51350 1 Tube, .250 I.D. By 30-In. Long 45 50351 1 Tube, .500 I.D. By 25-In. Long 46 71042 3 Clamp, Tube 47 51280 1 Fitting, Elbow,3/4-Barb(CH1502) 48 70325 2 Clip
9226613
WARRANTY
IMI Cornelius Inc. warrants that all equipment and parts are free from defects in material and workmanship un­der normal use and service. For a copy of the warranty applicable to your Cornelius, Remcor or W ilshireprod­uct, in your country, please write, fax or telephone the IMI Cornelius office nearest you. Please provide the equipment model number, serial number and the date of purchase.
IMI Cornelius Offices
AUSTRALIA D P.O. 210, D RIVERWOOD, D NSW 2210, AUSTRALIA D (61) 2 533 3122 D FAX (61) 2 534 2166 AUSTRIA D AM LANGEN FELDE 32 D A-1222 D VIENNA, AUSTRIA D (43) 1 233 520 D FAX (43) 1-2335-2930 BELGIUM D BOSKAPELLEI 122 D B-2930 BRAASCHAAT , BELGIUM D (32) 3 664 0552 D FAX (32) 3 665 2307 BRAZIL D RUA ITAOCARA 97 D TOMAS COELHO D RIO DE JANEIRO, BRAZIL D (55) 21 591 7150 D FAX (55) 21 593 1829 ENGLAND D TYTHING ROAD ALCESTER D WARWICKSHIRE, B49 6 EU, ENGLAND D (44) 789 763 101 D FAX (44) 789 763 644 FRANCE D 71 ROUTE DE ST. DENIS D F-95170 DEUIL LA BARRE D PARIS, FRANCE D (33) 1 34 28 6200 D FAX (33) 1 34 28 6201 GERMANY D CARL LEVERKUS STRASSE 15 D D-4018 LANGENFELD, GERMANY D (49) 2173 7930 D FAX (49) 2173 77 438 GREECE D 488 MESSOGION AVENUE D AGIA PARASKEVI D 153 42 D ATHENS, GREECE D (30) 1 600 1073 D FAX (30) 1 601 2491 HONG KONG D 1104 TAIKOTSUI CENTRE D 11-15 KOK CHEUNG ST D TAIKOKTSUE, HONG KONG D (852) 789 9882 D FAX (852) 391 6222 ITALY D VIA PELLIZZARI 11 D 1-20059 D VIMARCATE, ITALY D (39) 39 608 0817 D FAX (39) 39 608 0814 NEW ZEALAND D 20 LANSFORD CRES. D P.O. BOX 19-044 AVONDALE D AUCKLAND 7, NEW ZEALAND D (64) 9 8200 357 D FAX (64) 9 8200 361 SINGAPORE D 16 TUAS STREET D SINGAPORE 2263 D (65) 862 5542 D FAX (65) 862 5604 SPAIN D POLIGONO INDUSTRAIL D RIERA DEL FONOLLAR D E-08830 SANT BOI DE LLOBREGAT D BARCELONA, SPAIN D (34) 3 640 2839 D FAX (34) 3 654 3379 USA D ONE CORNELIUS PLACE D ANOKA, MINNESOTA D (612) 421-6120 D FAX (612) 422-3255
LD004
4/21/98
92266
14
THIS PAGE LEFT BLANK INTENTIONALLY
9226615
IMI CORNELIUS INC.
CORPORATE HEADQUARTERS:
One Cornelius Place Anoka, Minnesota 55303-6234 (612) 421-6120 (800) 238-3600
Loading...