The deliverer of your equipment (freight company, distributor or dealer) is responsible for loss or damage
of your shipment. All claims must be filed with the deliverer of your equipment. Please follow the steps
below to determine if your shipment is satisfactory or if a claim must be filed:
1. Check the number of products delivered against the number of products listed on the delivery receipt. Should the totals not match, have the driver note all errors on both copies and both you and
the driver sign and date said notation.
2. Inspect all cartons for visible damage. Open and inspect as required before the driver leaves and
have him or her note any damage on the receipts. All damaged claims must be inspected within 15
days of delivery. Notify your carrier immediately if concealed damage is found after delivery.
3. Should concealed damage be found when product is unpacked, retain the packing material and the
product and request an inspection from the deliverer.
4. All claims for loss or damage should be filed at once. Delays in filing will reduce the chance of
achieving a satisfactory resolution to the claim.
SPECIFICATIONS, ICE CUBER
The following table contains equipment specification information for the Ice Cubers.
UNIT
Volts115230220
Phase1
Hertz6050
No. Wires2+Ground
MIN. CIRCUIT
Amps2015
MAX. FUSE SIZE
Amps2015
REFRIGERANT
TypeR404A
Weight (oz)171517151715
Weight (g)482425482425482425
COMPRESSOR
Volts115230220
Phase1
Hertz6050
LRA512426
RLA11.55.75.3
CONDENSER FAN MOTOR
Volts115230220
Phase1
Hertz6050
Amps1.7NA1.2NA0.75NA
Watts50NA60NA50NA
WATER PUMP
Volts115230220
Phase1
Hertz6050
Amps0.880.5
Watts1/401/30
Important: All product supply voltage specifications are –5%/+10% for proper component operation.
630460042INS
1
INSTALLATION INSTRUCTIONS
Installation and start-up of the equipment should be performed by the distributor or the dealer’s professional staff.
LOCATION OF EQUIPMENT
For maximum performance the location should be away from heat sources such as ovens, direct sunlight,
hot air discharge, etc.
To reduce cost of maintenance and loss of efficiency, avoid placing air-cooled equipment in areas where
grease, flour and other airborne contaminants are present. Allow clearance at the front for proper air circulation. Restricted air circulation will affect the efficiency and required maintenance of the product.
IMPORTANT: Never operate your equipment in room temperature below 50_F (10_C) or above
100_F (38_C). Should the location of your product ever be exposed to freezing temperatures, it
must be shut down and winterized.
FIGURE 1. INSTALLATION
PLUMBING CONNECTIONS
1. All plumbing lines and connections must conform to local and national plumbing codes.
2. Line shut-off valves must be located in supply water lines for cuber and condenser if product is water-cooled. Water supply to water-cooled condenser must include a stand-pipe to prevent “water
hammer”.
3. Should your local water supply quality require the installation of a water filter system, consult your
local distributor or dealer for proper size required.
4. Water supply pressure must not be lower than 20 PSI (1.37 BAR), nor should it exceed 120 PSI
(8.16 BAR).
Important: Water filters larger then 5 microns do not give proper protection. Water pressures
above 80 PSI (5.44 BAR) will destroy the filter.
Important: Bin and cuber drain lines must never be connected together and must be vented.
2
630460042INS
Loading...
+ 9 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.