Cornelius 2232 Installation Instructions Manual

Page 1
Installation Instructions
Post Mix Dispenser Model 2232
IMI CORNELIUS INC. One Cornelius Place Anoka, MN. 55303–1592 Telephone (800) 238–3600 Facsimile (612) 422–3232
Part No. 91633 February 16, 1993 Revised: August 5, 1993
THIS DOCUMENT CONTAINS IMPORTANT INFORMATION
This Installation Manual must be read and understood before starting to install or operate this equipment.
IMI CORNELIUS INC; 1993
Printed in U.S.A.
Page 2
Page 3
TABLE OF CONTENTS
GENERAL DESCRIPTION 1. . . . . . . . . . . . . . . . .
UNIT DESCRIPTION 1. . . . . . . . . . . . . . . . . . . .
THEORY OF OPERATION 2. . . . . . . . . . . . . . .
INSTALLATION 3. . . . . . . . . . . . . . . . . . . . . . . . . . .
UNPACKING AND INSPECTION 3. . . . . . . . . .
IDENTIFICATION OF LOOSE–SHIPPED
PA RT S 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SELECTING LOCATION 3. . . . . . . . . . . . . . . . .
INSTALLING UNIT 3. . . . . . . . . . . . . . . . . . . . . .
INSTALLING UNIT ON COUNTERTOP 3. . CONNECTING DRIP TRAY DRAIN HOSE TO
PERMANENT DRAIN 4. . . . . . . . . . . . . . . . .
CONNECTING SYRUP SOURCE LINES TO
UNIT 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONNECTING CARBONATED WATER LINES
TO UNIT 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONNECTING PLAIN WATER LINE
TO UNIT 4. . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONNECTING COMPRESSED AIR OR CO2
GAS LINE TO DISPENSER 4. . . . . . . . . . . .
CONNECTING CHILLED PLAIN WATER
OUTLET 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PREPARATION FOR OPERATION 8. . . . . . . . . .
OPERATORS INSTRUCTIONS 9. . . . . . . . . . . . .
OPERATING CONTROLS 9. . . . . . . . . . . . . . . .
OPERATING ICE PORTION–CONTROL
DISPENSING SYSTEM 9. . . . . . . . . . . . . . . .
OPERATING PORTION–CONTROL
DISPENSING VALVE 9. . . . . . . . . . . . . . . . . .
Unit power switch 9. . . . . . . . . . . . . . . . . . . . .
DAILY PRE–OPERATION CHECK 9. . . . . . . .
UNIT OPERATION 9. . . . . . . . . . . . . . . . . . . . . .
ADJUSTMENTS 10. . . . . . . . . . . . . . . . . . . . . . . .
Adjusting CO2 regulators 10. . . . . . . . . . . . . . .
Adjusting dispensing valves water flow rate 10
Adjusting water–to–syrup “ratio” of dispensed
product 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjusting portion–control sizes of dispensed
drinks 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjusting ice portion–control system 10. . . . .
REPLENISHING CO2 SUPPLY 10. . . . . . . . . . .
REPLENISHING SYRUP SUPPLY 10. . . . . . . .
REPLENISHING ICE BIN ICE SUPPLY 10. . . .
CLEANING AND SANITIZING 10. . . . . . . . . . . .
Page
Page
Daily cleaning of unit exterior 10. . . . . . . . . . .
Weekly cleaning of dispensing valves 10. . . .
Cleaning ice bin interior and sanitizing syrup
SYSTEMS 10. . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING CO2 SYSTEM GAS CHECK
VALVES 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE AND MAINTENANCE 11. . . . . . . . . . . .
PREPARING UNIT FOR SHIPPING,
RELOCATING, OR STORING 11. . . . . . . . . . . .
ICE BIN COVER, PANELS, AND CUP REST
REMOVAL 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ICE BIN COVER 11. . . . . . . . . . . . . . . . . . . . . .
PANELS 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DRIP TRAY 11. . . . . . . . . . . . . . . . . . . . . . . . . .
PERIODIC INSPECTION 11. . . . . . . . . . . . . . . .
ADJUSTMENTS 11. . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTING CO2 REGULATORS 11. . . . . . .
ADJUSTING DISPENSING VALVES WATER
FLOW RATE 13. . . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTING WATER–TO–SYRUP “RATIO” OF
DISPENSED PRODUCT 14. . . . . . . . . . . . . . .
DISPENSED DRINK PORTION–CONTROL
ADJUSTMENT (DOLE AND CC–1
DISPENSING VALVES) 15. . . . . . . . . . . . . . . .
ICE PORTION CONTROL SYSTEM THEORY OF
OPERATION 15. . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING AND ADJUSTING THE DISPENSER
ICE PORTION–CONTROL SYSTEM 16. . . . . .
“CLEAN MODE” (FLASHING
RED/AMBER L.E.D) 16. . . . . . . . . . . . . . . . . .
“NORMAL ICE PORTION–CONTROL
ADJUSTMENT MODE”
(SOLID AMBER L.E.D) 16. . . . . . . . . . . . . . . .
“EXTRA ICE ADJUSTMENT MODE” (SOLID
RED L.E.D.) 16. . . . . . . . . . . . . . . . . . . . . . . . . .
REPLENISHING CO2 SUPPLY 19. . . . . . . . . . .
REPLENISHING SYRUP SUPPLY 19. . . . . . . .
SYRUP FLAVOR CHANGE 19. . . . . . . . . . . . . .
REPLENISHING ICE BIN ICE SUPPLY 19. . . .
CLEANING AND SANITIZING 19. . . . . . . . . . . .
PERIODIC CLEANING OF ICE CHUTE 19. .
DAILY CLEANING OF UNIT EXTERIOR 19.
WEEKLY CLEANING OF DISPENSING
VALVES 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING ICE BIN INTERIOR AND
SANITIZING SYRUP SYSTEM 20. . . . . . . . .
CLEANING CO2 GAS CHECK VALVES 21. . . .
i
91633
Page 4
TABLE OF CONTENTS (cont’d)
LIST OF FIGURES
FIGURE 1. ICE/SOFT DRINK DISPENSER 1. . FIGURE 2. FLOW DIAGRAM (TYPICAL
INSTALLATION) 5. . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 3. COUNTERTOP CUTOUT 6. . . . . . . .
FIGURE 4. DISPENSER PLUMBING DIAGRAM 7
FIGURE 5. PARTS IDENTIFICATION 12. . . . . . . .
FIGURE 6. DOLE DISPENSING VALVE 13. . . . . .
FIGURE 7. CC–1 DISPENSING VALVE 13. . . . . .
FIGURE 8. DISPENSING VALVE
PORTION–CONTROL COVER 14. . . . . . . . . . . . .
FIGURE 9. ICE PORTION–CONTROL SWITCH
MODULE 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 10. CLEAN MODE
(CLEAN ICE CHUTE) 17. . . . . . . . . . . . . . . . . . . . .
FIGURE 11. NORMAL ICE PORTION–CONTROL
AND EXTRA ICE ADJUSTMENT MODE 18. . . . .
FIGURE 12. CO2 GAS CHECK VALVE 21. . . . . .
FIGURE 13. DISPENSER WIRING DIAGRAM 22 FIGURE 14. INSTRUCTIONS FOR CRIMPING
TUBE CLAMPS 23. . . . . . . . . . . . . . . . . . . . . . . . . . .
LIST OF TABLES
TABLE 1. DESIGN DATA 2. . . . . . . . . . . . . . . . . . .
TABLE 2. LOOSE-SHIPPED PARTS 3. . . . . . . . .
91633
ii
Page 5
GENERAL DESCRIPTION
IMPORTANT: To the user of this manual - This manual is a guide for installing, operating, and maintaining this equipment. Refer to the Table of Contents for page location of detailed in­formation or answers to questions that arise during the installation, operation, service and maintenance, or troubleshooting.
This section provides a description, theory of opera­tion, and design data for the six-flavor Model 2232 Ice/Soft-Drink Post-Mix dispenser (see FIGURE 1) hereinafter referred to as the Unit.
UNIT DESCRIPTION
The Unit is compact and may be installed on an is­land or on a front or rear counter. Carbonated water, plain water, and syrup are cooled as they flow through a sealed-in aluminum coldplate located in the bottom of the Unit ice bin. The Unit is equipped with six adjustable portion control dispensing valves that will dispense a “S” (small), “M” (medium), “L” (large), or an “XL” (extra-large) finished post-mix drink. The Unit is also equipped with an adjustable portion-control ice dispensing system that may be adjusted to dispense just the right amount of ice in a small, medium, large, or extra-large cup just prior to dispensing a soft drink into the cup.
Installation of LOOSE-SHIPPED PARTS, installation of Unit on the countertop, connecting carbonated water, plain water, syrup, and air or CO2 to the Unit, filling the ice bin with ice, plugging the Unit power cord into an electrical outlet, and performing the nec­essary adjustments is all that is required for Unit op­eration.
FIGURE 1. ICE/SOFT DRINK DISPENSER
CAUTION: Before shipping, storing, or relocating this Unit, the syrup
systems must be sanitized and all sanitizing solution must be purged from the syrup systems. All water must also be purged from the plain and carbonated water systems. A freezing ambient environment will cause residual water in the Unit to freeze resulting in damage to internal components.
1
91633
Page 6
Table 1. Design Data
Unit Part Number
115V, 60 HZ, Dispenser with Dole Dispensing valves 115V, 60 HZ Dispenser with CC-1 Dispensing Valves 220V, 50HZ, Dispenser with Dole Dispensing Valves 220, 50HZ, Dispenser with CC-1 Dispensing Valves
Overall Dimensions:
Width 22 in. Height 36 5/16 in. Depth 32 7/16 in. Weight 248 Pounds Ice Bin Storage Capacity 150 Pounds Ambient Operating Temperature 40_ to 100_F
Electrical Requirements:
60 HZ UNIT:
Operating Voltage and Current See Unit
Nameplate
Dispensing Valves 24V, 60HZ
50 HZ UNIT:
Operating Voltage and Current See Unit
Nameplate
Dispensing Valves 24V, 50HZ
02632 02634 02633 02635
remote carbonator, syrup tanks, and to the dispenser to operate the ice portion control system. Plain wa­ter enters the carbonator water tank and is carbon­ated by regulated CO2 gas also entering the tank. When dispensing valves are activated, CO2 gas pressure exerted upon contents of syrup tanks, pushes syrup from tanks, through dispenser cold­plate coils, and on to the dispensing valves. Carbon­ated water is pushed from the carbonator water tank by CO2 gas head pressure and is pushed through the dispenser coldplate cooling coils to the dispens­ing valves. Syrup and carbonated water meet at the dispensing valves resulting in carbonated drinks be­ing dispensed. No. 2 dispensing valve (second dis­pensing valve from the left facing the dispenser) is set up at the factory to dispense a “still” (non–car- bonated) drink which requires plain water rather than carbonated water to be present at the dispensing valve.
If desired, No. 2 dispensing valve may be con­verted to also dispense a carbonated drink by dis­connecting its plain water line from the chilled plain water circuit inside the Dispenser and connecting the water line to an available carbonated water outlet on the outlet side of the coldplate (see FIGURE 2)
A Dispenser insulated plain water outlet line labeled CHILLED WATER, connected to the chilled plain water circuit inside the Dispenser, is available to pro­vide chilled plain water to a remote plain water Dis­penser or other equipment requiring chilled plain water.
THEORY OF OPERATION
(SEE FIGURE 2)
A CO2 cylinder delivers CO2 (carbon dioxide) gas through adjustable secondary CO2 regulators to a
91633
2
Page 7
INSTALLATION
UNPACKING AND INSPECTION
NOTE: The Ice/Drink dispenser was thoroughly inspected before leaving the factory and the car­rier has accepted and signed for it. Any damage or irregularities should be noted at the time of delivery (or not later than 15 days from the date of delivery) and immediately reported to the de­livering carrier. Request a written inspection re­port from Claims Inspector to substantiate any necessary claim. File claim with the delivering carrier, not with IMI CORNELIUS INC.
1. Unpack the Unit and remove all shipping tape and packing materials.
2. Unpack LOOSE–SHIPPED parts. Make sure all items are present and in good condition.
Table 2. Loose-Shipped Parts
Item
No. Part No. Name Qty.
1 52077 Drain Hose, 5ft. 1 2 70750 Clamp, Drain Hose 1 3 70798 Tool, Dole
Dispensing Valve
4 70861 Cup Rest 1
IDENTIFICATION OF LOOSE–SHIPPED PARTS
1. DRAIN HOSE (item 1) to be connected to drip tray and secured with CLAMP, DRAIN HOSE (item 2).
2. TOOL, DOLE DISPENSING VALVE (item 3) used to turn water and syrup shutoff valves on dispensing valve mounting block to ON or OFF position.
3. CUP REST (item 4) to be installed on drip tray.
SELECTING LOCATION
This Unit may be Island–mounted or installed on a front or rear counter. Locate the Unit so the following requirements are satisfied.
1. A properly grounded electrical outlet with proper electrical requirements fused at 15 – Amps (“slow–blow”) or circuit connected through an equivalent HACR circuit breaker must be lo­cated close to the Unit. No other electrical equipment should be connected to this circuit. ALL ELECTRICAL WIRING MUST CONFORM TO NATIONAL AND LOCAL ELECTRICAL CODES.
2. Near a permanent drain to route and connect Unit drip tray drain hose.
3. Allow sufficient room above the Unit to remove Ice bin cover to replenish ice supply.
INSTALLING UNIT
INSTALLING UNIT ON COUNTERTOP
1. Locate exact location on countertop where Unit will be installed.
2. Refer to FIGURE 3 for instructions to cut indi­cated hole in countertop.
3. Remove Unit ice bin cover, then very carefully
1
tip Unit over on its back.
4. Install DRAIN HOSE, 5–FT. (item 1) on drip tray drain fitting. Secure connection with CLAMP, DRAIN HOSE (item 2).
5. Very carefully, restore Unit to its upright position.
6. Slide Unit into its operating position on counter­top.
NOTE: To comply with National Sanitation Foundation (NSF) requirements, Unit base must be sealed to countertop and all access holes to in­side of Unit base must be sealed with permagum or equivalent sealant material.
7. To comply with National Sanitation Foundation (NSF) requirements, seal Unit base to counter­top as follows:
A. Tilt Unit up to expose bottom of base.
3
91633
Page 8
B. Liberally apply sealant such as Dow Corn-
ing RTV731 or equivalent on base bottom edges.
C. Lower Unit into operating position on coun-
tertop.
D. Apply additional sealant around bottom of
Unit base. Seal must have a minimum ra­dius of 1/2 inch to prevent crevices and to insure a complete seal.
8. Remove two screws securing dispenser back panel. Remove panel for access to drip tray drain hose, power cord, and inlet and outlet lines.
9. Route drip tray drain hose, power cord, and inlet and outlet lines down through hole cut in coun­tertop.
10. Seal all access holes to inside of Unit base with permagum or equivalent sealant.
11. Install CUP REST (item 4) in drip tray.
CONNECTING DRIP TRAY DRAIN HOSE TO PERMANENT DRAIN
NOTE: Drip tray drain hose routed to a waste container is not recommended due to sanitation and cleaning problems. Connection of drain hose to a permanent drain is recommended.
Preferably, route lower end of drip tray drain hose to a permanent drain and connect.
CONNECTING SYRUP SOURCE LINES TO UNIT
(SEE FIGURE 2)
NOTE: Unit syrup inlet lines are labeled to identi­fy the dispensing valves they serve. For exam­ple: line labeled “S1” must be connected to syrup source line that provides syrup to be dis­pensed from No. 1 dispensing valve (No. 1 dis­pensing valve is valve on left side when facing front of Unit).
CONNECTING PLAIN WATER LINE TO UNIT
(SEE FIGURE 2)
Plain water connected to the Unit plain water inlet line labeled PLAIN WTR provides chilled water for the No. 2 dispensing valve, still (non–carbonated) drink and also provides chilled water out of the Unit plain water outlet line that may be used to provide chilled water to a plain water dispenser or other equipment requiring chilled water. No. 2 dispensing valve may also be converted to to dispense a car­bonated drink by connecting its plain water inlet line to an available carbonated water outlet on the outlet side of the coldplate (see FIGURE 2).
Proceed as follow to connect plain water to Unit plain water line labeled PLAIN WTR”.
1. Route plain water line from plain water source up to Unit.
2. Connect plain water source line to Unit plain water inlet line labeled PLAIN WTR”.
CONNECTING COMPRESSED AIR OR CO
2
GAS LINE TO DISPENSER
(SEE FIGURE 2)
IMPORTANT: A Compressed Air or CO2 Filter must be connected into the CO2 line connected to the Dispenser to operate the ice portion control system.
Regulated and filtered CO2 gas pressure or com­pressed air is required to operate the dispenser por­tion–control ice dispensing system. Proceed as follows to connect CO2 gas pressure source line to the Dispenser.
1. Connect and route CO2 line from outlet side of the CO2 Regulator Assembly up to the Dispens­er.
2. Connect CO2 source line to Dispenser CO2 inlet line labeled “AIR/CO2”.
1. Route syrup source lines from syrup tanks loca­tion up to Unit.
2. Connect syrup source lines to Unit syrup inlet lines labeled “S1” through “S6”.
CONNECTING CARBONATED WATER LINES TO UNIT
(SEE FIGURE 2)
1. Route carbonated water source lines from car­bonator location up to Unit.
2. Connect carbonated water source line to Unit carbonated water inlet lines labeled CO2 WTR”.
91633
CONNECTING CHILLED PLAIN WATER OUTLET
(SEE FIGURE 2)
The Unit plain water outlet line labeled “CHILLED WATER may be used to provide chilled water to a plain water dispenser or other equipment requiring chilled water. Proceed as follows to connect chilled water line to other equipment.
1. Connect and route insulated plain water line from equipment requiring chilled plain water up to Unit.
2. Connect insulated plain water line to Unit plain water outlet line labeled CHILLED WTR”.
4
Page 9
916335
PLAIN
WATER
SOURCE
WATER
SHUTOFF
VALVE
WATER PRESSURE
REGULATOR
WATER FILTER
REMOTE
CARBONATOR
DISPENSER ICE PORTION–CONTROL
SECONDARY CO
2
REGULATOR
DIET SYRUP
SECONDARY CO
2
REGULATOR
SUGAR SYRUP
SECONDARY CO
2
REGULATOR
PRIMARY
CO2 REGULATOR
GAS CHECK
VALVE (7)
CO2 CYLINDER
COLD PLATE
DISPENSER
CARBONATED
WATER MANIFOLD
DISPENSING
VALVE (6)
STILL
DRINK
DIET
DRINK
PORTION CONTROL
ICE DISPENSING CHUTE
ICE GATE SLIDE
GATE CYLINDER
GATE SOLENOID
SYRUP TANKS (6)
CHILLED PLAIN WATER OUTLET LINE A PLAIN WATER DISPENSER OR OTHER EQUIPMENT REQUIRING CHILLED WATER MAY BE CONNECTED TO DISPENSER CHILLED PLAIN WATER OUTLET LINE.
LINE LEGEND CO
2
PLAIN WA TER CARB WATER SYRUP
6
65
5
4
4
3
3
2
2
1
1
CW
CW
PW
S1
S2
S3
S4
S5
S6
CO
2
PLUGGED
CARBONATED
WATER
OUTLET
FIGURE 2. FLOW DIAGRAM (TYPICAL INSTALLATION)
CO2/AIR FIL TER
Page 10
22
1
1
15
1
3
16
14
OPENING
8
AVAILABLE FOR HOSE OUTLETS
5
-18
THREADED HOLE LOCATIONS
16
FRONT OF UNIT
1
4
2
OPENING
1
14
4
OPENING IN CABINET
BOTTOM FOR DRAIN
AND BEVERAGE HOSES
OPTIONAL LOCATION FOR
COUNTER TOP CUTOUT
3
19
4
TOP VIEW
(COUNTER CUT OUT/OPTIONS)
18
25 32
1
31
4
1
1
8
ALL DIMENSIONS ARE IN INCHES
FIGURE 3. COUNTERTOP CUTOUT
691633
Page 11
STILL DRINK
(NON–CARB)
DISPENSING
VALVE(6)
PLUG
(SEE
NOTE 2)
CARBONATED
WATER MANIFOLD
123 456
COLD PLATE
SYRUP INLET LINES
POTABLE
WATER
AIR/CO
(50–PSI MAX)
POTION CONTROL
ICE DISPENSING
CHUTE
ICE GATE
SLIDE
GATE
CYLINDER
GATE
SOLENOID
2
SYRUP INLET
NOTE1: THE DISPENSER IS EQUIPPED WITH A COLD PLATE CHILLED PLAIN WA TER OUTLET LINE THAT MAY BE USED TO PROVIDE CHILLED WATER TO A PLAIN WATER DISPENSER OR OTHER EQUIPMENT REQUIRING CHILLED WATER.
NOTE 2: NO. 2 DISPENSING VALVE MAY BE CONVERTED TO ALSO DISPENSE A CARBONATED DRINK BY CONNECTING ITS PLAIN WATER INLET LINE TO PLUGGED CARBONA TED WATER OUTLET FITTING ON THE CARBONATED WA TER MANIFOLD.
LINE
CARB WATER
LINE LEGEND AIR/CO
2
PLAIN WATER
CARB WATER
SYRUP
CHILLED PLAIN
WATER
(SEE NOTE 1)
FIGURE 4. DISPENSER PLUMBING DIAGRAM
916337
Page 12
PREPARATION FOR OPERATION
CAUTION: BEFORE OPENING CO
2
CYLINDER SHUTOFF VALVE. Make sure primary and secondary CO
2
regulators adjusting screws are turned to the left (COUNTERCLOCKWISE) until all tension is relieved from adjusting screws springs. Also, make sure the Dispenser Ice Portion Control CO2 Regulator/Filter Assembly adjustment knob is turned all the way to the left (counterclockwise). PULL UP ON ADJUSTMENT KNOB TO UNLOCK BEFORE ATTEMPTING TO TURN.
1. Open CO2 cylinder shutoff valve slightly to allow lines to slowly fill with gas, then open valve fully to back–seat valve. (Back–seating valve prevents leakage around valve shaft).
2. Check all CO2 connections for leaks. Tighten any loose connections.
3. Adjust primary CO2 regulator for carbonator and secondary CO2 regulator for syrup tanks and the CO2 Regulator/Filter Assembly for the dispenser ice portion–control system as follows
Carbonator Primary CO2 Regulator.
Dispenser Ice Portion–Control CO2 Regulator/filter assembly
A. Pull up on regulator adjustment knob to un-
lock.
B. Turn regulator adjustment knob to the right
(clockwise) until regulator gauge registers 50–PSI (Max), then push knob down to lock.
4. Check entire CO2 system connections for leaks. Tighten any loose connections.
5. Open plain water inlet supply line shutoff valve. Check for water leaks and tighten any loose con­nections.
6. Plug carbonator power cord into electrical outlet. Carbonator will start and continue to operate until carbonated water tank is full.
7. Place CUP REST (item 4) in drip tray.
8. Plug Unit power cord into electrical outlet.
9. Place Unit power switch on side of Unit in “ON” position.
10. Dispense from each dispensing valve until all air is purged from the plain and carbonated water sys­tems.
IMPORTANT: All syrup systems must be sanitized and Unit ice bin must be thoroughly cleaned before Unit is put into operation.
Refer to manual provided with carbonator and adjust primary CO2 regulator for carbonator operating pres­sure.
Sugar Syrup Tanks Secondary CO2 Regulator Adjust sugar syrup tanks secondary CO2 Regulator at
45–psig for syrup lines up to 10–feet in length plus one pound for each additional length of 10–feet, plus one pound for each 2–feet of vertical lift. For example: If syrup line total length is 30–feet and total vertical lift is 6–feet, then 45–psi + 2–psig (1–pound for every 2–feet of vertical lift which is 6–feet); total equals 45 + 2 + 3=50–psig CO2 regulator setting. Loosen lock nut on CO2 regulator adjusting screw, turn adjusting screw to the right (clockwise) until gage registers desired pres­sure, then tighten lock nut.
Low–Calorie (diet) Syrup Tank Secondary CO Regulator.
Adjust low–calorie (diet) soft drink tank secondary CO regulator at 10–psig for syrup lines up to 30–feet in length. Syrup lines longer than 30–feet in length may require a slightly higher CO2 regulator setting to 12–psig maximum. Excessive CO2 pressure may cause low–calorie syrup carbonation resulting in foam.
11. Sanitize all syrup systems and thoroughly clean ice bin interior as instructed.
12. Remove ice bin cover.
IMPORTANT: Do not use hard–frozen (below 32_F) ice. After ice is removed from a freezer, allow the ice to sit at room temperature for approximately 1/2 hour before placing it in the bin. Ice to be used to fill ice bin must be in the form of small cubes, chunklets, or cracked ice (DO NOT USE FLAKE OR CRUSHED ICE).
13. Observing preceding IMPORTANT note, fill ice bin with small cubes, chunklets, or cracked ice.
14. Install ice bin cover. ICE BIN COVER HAS TO BE IN INSTALLED POSITION ON UNIT BEFORE ICE AGITATOR WILL OPERATE.
15. Connect full syrup tanks into syrup systems.
16. Dispense from all dispensing valves to purge all air
2
from syrup systems.
17. Adjust all dispensing valves for water flow rate as instructed.
2
18. Adjust all dispensing valves adjustable syrup flow controls for water–to–syrup “Ratio” of dispensed product as instructed.
19. Adjust all portion sizes of ice dispensed as instructed.
891633
Page 13
OPERATORS INSTRUCTIONS
OPERATING CONTROLS
OPERATING ICE PORTION–CONTROL DISPENSING SYSTEM
(SEE FIGURE 8)
Normal portion–control ice dispensing may be per- formed by holding appropriate size cup under the ice chute, then press and release desired Small, Medium, Large, or Extra Large cup ice dispense switch. Desired ice portion will be dispensed into the cup. Extra ice may be dispensed into the cup by first pressing the Y (increase) ice dispense switch, then press the desired Small, Medium, Large, or Extra Large cup ice dispense switch.
The ice portion–control system may be adjusted as instructed.
OPERATING PORTION–CONTROL DISPENSING VALVE
(SEE FIGURE 8)
Portion–control Drink Dispensing.
A. Dispense appropriate portion size of ice in ap-
propriate size cup.
B. Hold cup containing ice under dispensing
valve nozzle.
DAILY PRE–OPERATION CHECK
1. Make sure CO2 cylinder primary CO2 regulator as­sembly 1800–psi gage indicator is not in shaded (change CO2 cylinder) portion of dial. If so, CO cylinder is almost empty and must be replaced as instructed.
2. Sufficient syrup supply in all syrup tanks. If not, replenish syrup supply as instructed.
3. Make sure ice supply in ice bin is adequate. If not, replenish ice supply as instructed.
4. Make sure drip tray is clean and clean cup rest is in place in drip tray.
UNIT OPERATION
1. Make sure unit power switch is in the “ON” posi- tion.
2. Make sure ice supply in ice bin is adequate. If not replenish ice supply as instructed.
3. Make sure ice bin cover is in place on top of ice bin.
4. Hold appropriate size cup under ice chute.
2
Note: Dispensing of a portion control drink may be stopped by pressing the “CANCEL/POUR” switch. Drinks may be manually dispensed (non–portion control) by pressing and holding the “CANCEL/ POUR switch.
C. Press appropriate S (Small), M (Medium),
L (Large), or XL (Extra Large) dispense
switch to dispense product into cup.
Dispensing Plain or Carbonated Water Only. Dole Dispensing Valves – Hold cup under No. 2 dis-
pensing valve nozzle, then press “WATER switch to dispense plain water. To dispense carbonated water, hold cup under No. 5 dispensing valve and press SODA switch.
CC–1 Dispensing Valve – Hold cup under No. 2 dis­pensing valve nozzle then operate water lever on valve. To dispense carbonated water, hold cup under No. 5 dispensing valve and operate water lever.
UNIT POWER SWITCH
Power switch is located on the left side of the Unit and must be in the “ON position before dispensing valves will operate. Power switch in the OFF position does not inter­rupt power to the Ice Agitator Motor.
5. Press and release desired Small, Medium, Large, or Extra Large ice dispense switch. Desired ice portion will be dispensed into cup.
Extra ice may be dispensed into the cup by first pressing the Y (increase) ice dispense switch then press the de­sired Small, Medium, Large, or Extra Large cup ice dis­pense switch.
6. Hold cup containing ice under dispensing valve nozzle.
Note: Dispensing of a portion–control drink may be stopped by pressing the “CANCEL/POUR” switch. Drinks may be manually dispensed (non–portion control) by pressing and holding the “CANCEL/ POUR switch.
7. Press appropriate “S” (Small, “M” (Medium), “L” (Large), or “XL” (Extra Large) dispense switch to dispense product into cup containing ice.
8. Only plain or carbonated water may be dispensed as follows.
Dole Dispensing Valve.
A. Place cup under dispensing valve with “WA-
TER or SODA dispense switch on its front cover.
916339
Page 14
B. Press applicable “WATER or SODA switch
to dispense plain water or carbonated water.
CC–1 Dispensing Valve.
C. Place cup under carbonated drink dispensing
valve or under non–carbonated (still drink) dispensing valve with water lever on valve.
REPLENISHING CO2 SUPPLY
CO2 supply should be checked daily and if necessary, replenished as instructed.
REPLENISHING SYRUP SUPPLY
D. Operate dispensing valve water lever to dis-
pense applicable plain or carbonated water only.
ADJUSTMENTS
ADJUSTING CO2 REGULATORS
CO2 regulators should be periodically checked for proper pressure settings and if necessary, adjusted as instructed.
ADJUSTING DISPENSING VALVES WATER FLOW RATE
Dispensing valves water flow regulators may be ad­justed to vary amount of water dispensed as instructed.
ADJUSTING WATER–TO–SYRUP “RATIO” OF DISPENSED PRODUCT
Water–to–syrup “Ratio” of dispensed product should be checked periodically and if necessary, adjusted as instructed.
ADJUSTING PORTION–CONTROL SIZES OF DISPENSED DRINKS
Syrup supply should be checked daily and if necessary, replenished as instructed.
REPLENISHING ICE BIN ICE SUPPLY
Fill ice bin with ice as instructed.
CLEANING AND SANITIZING
DAILY CLEANING OF UNIT EXTERIOR
Daily cleaning of unit exterior should be performed at end of daily operation as instructed.
WEEKLY CLEANING OF DISPENSING VALVES
Dispensing valves should be cleaned as least once a week as instructed.
CLEANING ICE BIN INTERIOR AND SANITIZING SYRUP SYSTEMS
Ice bin interior should be cleaned and syrup systems should be sanitized as instructed every 30 days follow­ing Sanitizer Manufacturers recommendations.
Portion–control sizes S (Small), M (Medium), L (Large), or “XL” (Extra Large) of dispensed drinks may be adjusted as instructed.
ADJUSTING ICE PORTION–CONTROL SYSTEM
The ice portion–control system may be adjusted as instructed.
CLEANING CO2 SYSTEM GAS CHECK VALVES
(SEE FIGURE 2 AND FIGURE 12 )
The CO2 system gas check valves must be inspected and serviced at least once a year under normal condi­tions and after any CO2 system servicing or disruption as instructed.
1091633
Page 15
SERVICE AND MAINTENANCE
IMPORTANT: Only qualified personnel should service internal components or electrical wiring
PREPARING UNIT FOR SHIPPING, RELOCATING, OR STORING
CAUTION: Before shipping, storing, or relocating this Unit, the syrup
systems must be sanitized and all sanitizing solution must be purged from the syrup systems. All water must also be purged from the plain and carbonated water systems. A freezing ambient environment will cause residual water in the Unit to freeze resulting in damage to internal components.
ICE BIN COVER, PANELS, AND CUP REST REMOVAL
(see FIGURE 5)
ICE BIN COVER
Lift ice bin cover straight up off Unit to remove. ICE BIN COVER MUST BE IN PLACE ON UNIT BEFORE ICE AGITATOR WILL OPERATE.
PANELS
Cup Lid Holder Panel. Remove two screws securing cup lid holder panel, then
remove panel.
PERIODIC INSPECTION
1. Check each dispensing valve for dripping that indi­cates valve is leaking and repair as necessary.
2. Periodically check and make sure drip tray drain is not clogged.
ADJUSTMENTS
ADJUSTING CO2 REGULATORS
(see FIGURE 2)
Carbonator Primary CO2 Regulator. Refer to manual provided with carbonator and adjust
primary CO2 regulator for carbonator operating pres­sure.
Sugar Syrup Tanks Secondary CO2 Regulator. Adjust sugar syrup tanks secondary CO2 regulator at
45–psig for syrup lines up to 10–feet in length plus one pound for each additional length of 10–feet,plus one pound for each 2–feet of vertical lift. For example; if syrup line total length is 30–feet and total vertical lift is 6–feet, then 45–psig + 2–psig (1–pound for every 2–feet of vertical lift which is 6–feet); total equal 45 + 2 + 3 = 50–psig CO2 regulator setting. Loosen lock nut on CO2 regulator adjusting screw, turn adjusting screw to the right (clockwise) until gage registers desired pres­sure, then tighten lock nut.
Ice Portion–Control Switch Module Panel. Remove two thumb screws securing ice portion–control
switch module panel, then remove panel. Lower Access Panel.
Remove two screws securing lower access panel , then remove panel.
Cup Rest. Lift cup rest straight up off drip tray to remove.
DRIP TRAY
1. Remove cup rest.
2. Remove lower access panel as instructed.
3. Pull two retaining pins securing drip tray, then re­move tray.
Low–Calorie (diet) Syrup Tank Secondary CO Regulator.
Adjust low–calorie (diet) soft drink tank secondary CO regulator at 10–psig for syrup lines up to 30–feet in length. Syrup lines longer than 30–feet in length may require a slightly higher CO2 regulator setting to 12–psig maximum. Excessive CO2 pressure may cause low–calorie syrup carbonation resulting in foam.
Dispenser Ice Portion–Control CO2 Regulator/filter assembly
1. Pull up on regulator adjustment knob to unlock.
2. Turn regulator adjustment knob to the right (clock­wise) to increase CO2 pressure (50–PSI Max) or turn knob to the left (counterclockwise) to decrease CO2 pressure.
3. Push knob down to lock.
2
2
9163311
Page 16
ICE BIN COVER
THUMBSCREW
ICE AGIT ATOR
DISC
CUP LID
HOLDER PANEL
ICE PORTION–CONTROL
SWITCH MODULE
PANEL
ICE CHUTE
LOWER ACCESS PANEL
ICE AGIT ATOR
DISPENSING
VALVE (6)
RETAINING
PIN(2)
CUP REST
DRIP TRAY
FIGURE 5. PARTS IDENTIFICATION
1291633
Page 17
ADJUSTING DISPENSING VALVES WATER FLOW RATE
SYRUP AND W A TER
SHUTOFF VALVES
IN OPEN POSITION
10. Turn syrup shutoff valve (right–side shutoff valve) to the OPEN (extreme CLOCKWISE) position.
11. Install top cover on dispensing valve and secure with screw.
12. Install front cover on dispensing valve.
ADJUSTABLE SYRUP
AND WATER
FLOW CONTROLS
FIGURE 6. DOLE DISPENSING VALVE
Dole Dispensing Valve. (see FIGURE 6)
1. Remove syrup line quick disconnect from syrup tank serving dispensing valve water flow rate check will be preformed on.
2. Remove front cover from dispensing valve by pull­ing out on bottom of cover.
3. Remove top cover from dispensing valve by loos­ening screw on front of valve, then remove cover.
4. Turn syrup shutoff valve (right–side shutoff valve) to the CLOSED (extreme COUNTERCLOCK­WISE) position.
NOTE: Do not confuse syrup and water shutoff valves with dispensing valve flow controls adjust­ing screws.
13. Connect syrup line quick disconnect to syrup tank outlet.
ADJUSTABLE
WATER CONTROL
ADJUSTABLE
SYRUP CONTROL
FIGURE 7. CC–1 DISPENSING VALVE
CC–1 Dispensing Valve (see FIGURE 7)
1. Remove syrup line quick disconnect from syrup tank serving dispensing valve water flow rate check will be performed on.
2. Remove applicable dispensing valve portion con­trol cover by sliding cover up and off top cover.
3. Remove dispensing valve top cover by loosening screw securing cover, then lift cover up and off.
5. Position volume cup under dispensing valve nozzle.
6. Press CANCEL/POUR switch and hold for 4 se­conds.
NOTE: 10 fl ounces (296 ml) of water should be dispensed into cup for sugar based drinks and 7.6 fl ounces (225 ml) for sugar–free based drinks.
7. If the water volume is correct. proceed with Step 9 If the flow rate is not correct, proceed with Step 8 .
8. Turn dispensing valve water flow control adjusting screw to the right (CLOCKWISE) to increase or to the left (COUNTERCLOCKWISE) to decrease the flow of water.
9. Repeat Steps 2 through 7 for each dispensing valve until all valves are checked and/or calibrated (as required). Water flow rate check is complete.
4. Position volume cup under dispensing valve nozzle.
5. Press CANCEL/POUR switch and hold for 4–se- conds.
NOTE: 10 fl ounces (296 ml) of water should be dis­pensed into cup for sugar based drinks and 7.6 fl ounces (225 ml) for sugar–free based drinks.
6. If the water volume is correct, proceed with Step 10 If the flow rate is not correct, proceed with step
7.
7. Remove plastic cover from water flow regulator labeled “WATER.
8. Turn dispensing valve water flow regulator adjust­ing screw to the right (CLOCKWISE) to increase or to the left (COUNTERCLOCKWISE) to decrease the flow of water.
9163313
Page 18
NOTE: One (1) turn of the water flow regulator ad­justing screw will change the water flow rate approximately 2 fl ounces (59 ml) per 4 second draw.
6. Press valve cover “CANCEL/POUR” switch and dispense approximately five ounces of water into ratio cup. Water and syrup levels should be even in ratio cup.
9. Install plastic cover on water flow regulator.
10. Install dispensing valve top cover and secure with screw.
11. Install portion control cover on top cover by sliding portion control cover down into place on top cover.
12. Connect syrup line quick disconnect to syrup tank outlet.
L.E.D.
INDICATOR
LIGHT
SODA OR
WATER BUTTON
CANCEL/POUR
SWITCH
7. If water and syrup levels are not even in ratio cup, turn valve (see Figure 6) syrup flow regulator la­beled S4 (right–side regulator) adjusting screw to the left (counterclockwise) for less syrup or to the right (clockwise) for more syrup.
8. Repeat water–to–syrup “Ratio” test and adjust valve syrup flow regulator as many times as nec­essary until proper ratio of dispensed drink is achieved.
9. Remove the syrup/water separator by turning and pulling down.
10. Install nozzle on valve by pushing up and turning until it is locked.
11. Install dispensing valve front cover.
CC–1 Dispensing Valve (see Figure 7)
1. Remove dispensing valve portion control cover by sliding cover up off top cover.
2. Remove dispensing valve top cover by loosening screw securing cover, then lift cover up and off.
FIGURE 8. DISPENSING VALVE PORTION–CON-
TROL COVER
ADJUSTING WATER–TO–SYRUP “RATIO” OF DISPENSED PRODUCT
Dole Dispensing Valve (see Figure 6)
1. Remove dispensing valve front cover (pull from bottom edge).
2. Remove dispensing valve nozzle by turning and pulling down.
3. Install syrup/water separator on dispensing valve by pushing up and turning to tighten.
4. Press valve cover “CANCEL/POUR” switch (see FIGURE 8) momentarily to fill separator with syrup.
5. Place the ratio cup under the separator, the large section of the cup under the large round body of the separator and the small section of the cup un­der the extended arm, which is the syrup tube.
3. Remove nozzle from dispensing valve by turning nozzle and pulling down.
4. Remove syrup diffuser from dispensing valve by pulling diffuser down and out of valve.
5. Place the syrup/water separator on the dispensing valve by pushing up and turning to tighten.
6. Press portion control cover CANCEL/POUR switch (see FIGURE 8) momentarily to fill separator with syrup.
7. Place the ratio cup under the separator, the large section of the cup under the large round body of the separator and the small section of the cup un­der the small tube, which is the syrup tube.
8. Press valve cover “CANCEL/POUR” switch and dispense approximately five ounces of water into ratio cup. Water and syrup levels should be even in the ratio cup.
9. If water and syrup levels are not even in ratio cup, turn dispensing valve (see FIGURE 7) syrup flow regulator labeled “SYRUP” adjusting screw to the left (counterclockwise) no more than 1/4–turn at a time for less syrup or to the right (clockwise) no more than 1/4–turn at a time for more syrup.
10. Repeat Water–to–Syrup “Ratio” test and adjust syrup flow regulator as many times as necessary until proper ratio of dispensed drink is achieved.
1491633
Page 19
11. Remove the syrup/water separator by turning and pulling down.
12. Install syrup diffuser on dispensing valve.
13. Install nozzle on valve by pushing up and turning until it is locked.
14. Install top cover on valve and secure with screw.
15. Install portion–control cover on dispensing valve.
DISPENSED DRINK PORTION–CONTROL ADJUSTMENT (DOLE AND CC–1 DISPENSING VALVES)
SEE FIGURE 8.
NOTE: In case of electrical power failure, dispens­ing valves portion controls have full memory func­tion.
1. At the same time press and hold S (small) andXL (extra large) dispense switches (see FIGURE
8) on dispensing valve front cover until L.E.D. indi­cator light on cover starts blinking. Blinking L.E.D. indicates portion control set mode has been acti­vated.
2. Dispense small portion of ice in a small drink size cup, then place cup under dispensing valve nozzle.
Dispensing of a portion control drink may be stopped by pressing the “CANCEL/POUR” switch. Drinks may be manually dispensed (non–portion control) by pressing the CANCEL/POUR switch.
S (SMALL)
M (MEDIUM)
L (LARGE)
XL (EXTRA LARGE)
INCREASE
Y
INDICATOR
DECREASE
L.E.D. LIGHT
B
FIGURE 9. ICE PORTION–CONTROL SWITCH MOD-
ULE
ICE PORTION CONTROL SYSTEM THEORY OF OPERATION
3. Press and hold switch labeled “S” (small) on dis­pensing valve cover until cup is filled with product to desired level, then release switch.
4. With exception of using an appropriate size cup containing appropriate portion of ice, repeat steps 2 and 3 to adjust sizes of drinks dispensed when pressing M (medium), L (large), or XL (extra large) switches.
5. After all portion sizes of dispensed drinks have been adjusted, press and release “CANCEL/ POUR switch to cancel portion control set mode and return to portion control operation.
Any one of the dispensing valves portion sizes may be re­programmed by at the same time pressing and holding the S (small) and XL (extra large) dispense switches (acti­vate set mode), reprogram drink size, then press CAN­CEL/POUR SWITCH to return to portion control opera­tion.
A vertical plastic cylinder (ice chute) located on front of the dispenser is filled with ice by a revolving ice agitator located inside the ice bin. Ice is stored in the ice chute and is replenished after each ice dispensing operation. An ice gate, located in bottom of the ice chute, closes off bottom of the ice chute and supports the column of stored ice. The electronic selector/controller determines the duration of time the ice gate remains open when dispensing ice which controls the portion (amount) of ice that is dispensed. After ice has been dispensed, the controller starts the ice agitator which refills the ice chute. The controller also allows the next ice portion to be dispensed without waiting for the ice chute to be to­tally refilled. If there is not enough ice in the ice chute to dispense the next ice portion selection, the green L.E.D. (located on the ice dispense switch module) will flash until the ice chute has been refilled enough to al­low an ice portion to be dispensed.The green L.E.D. will be turned on after the ice chute has been refilled which signals that an ice portion may be selected and dis­pensed.
9163315
Page 20
CLEANING AND ADJUSTING THE DISPENSER ICE PORTION–CONTROL SYSTEM
There are three independent modes that may be en­tered into on the Ice Portion–Control System. They are the “Clean Mode”, “Normal Ice Portion–Control Adjust­ment Mode”, and the “Extra Ice Adjustment Mode”. To enter into each of these three modes, the person must start from the “Normal Operating Mode” (green L.E.D. indicator light on) and use the Y (increase) and the B (decrease) switches on the ice portion–control switch module (see FIGURES 9, 10, and 11 ) to step through to the desired mode. Proceed as follows.
CLEAN MODE (FLASHING RED/AMBER L.E.D.)
The dispenser ice chute must be periodically removed and cleaned and sanitized. Refer to FIGURES 9 and 10 for instructions to clean and sanitize the ice chute.
NORMAL ICE PORTION–CONTROL ADJUSTMENT MODE (SOLID AMBER L.E.D)
The S (small), M (medium), L (large), and the XL (extra large) sizes of dispensed ice may be increased or decreased as desired. Refer to FIGURES 9 and 11 for instructions to adjust ice portion sizes.
EXTRA ICE ADJUSTMENT MODE (SOLID RED L.E.D.)
Extra ice may be dispensed into the cup by first press­ing the Y (increase) ice dispense switch, then dis­pense the desired normal ice portion size into the cup. Refer to FIGURES 9 and 11 for instructions to adjust sizes of dispensed extra ice portions.
1691633
Page 21
FIGURE 10. CLEAN MODE (CLEAN ICE CHUTE)
Thumb Screws (4)
Service Panel Removed
Clean Mode
(Clean Ice Chute)
Normal Operating Mode
(Solid Green LED)
Ice Portion Control
Ice Chute
This Mode permits cleaning
of the Ice chute.
START HERE
YBd
Program L E D
Ice Chute
Strap
Screws
Service Panel
Thumb Screw
Service Panel
Press B & Y at the same time, then
immediately release
LED Flashing Red/Amber
(Clean Mode)
Press any Portion Switch
Remove Service Panel Thumbscrews,
Then remove the panel
Remove Ice Chute Strap Screws,
Then Remove Strap
Remove the Four Thumbscrews securing
the Ice Chute. Remove the
Chute and gate cover.
Wash ice chute, gate slide, and gate cover in detergent soap solution, then rinse thor­oughly with plain water.
Sanitize inside of ice chute, gate cover, and gate slide (refer to sanitizing syrup system for sanitiz­ing solution mixture).
This empties ice from the chute
Removal of the ice chute interrupts
power to the Dispenser.
(Flashing red LED will turn off)
Replace all Parts in Reverse Order
of Removal
Portion Control will automatically return
to Normal Operating Mode.
(Solid Green LED)
9163317
Page 22
Normal Ice PortionĆControl
Adjust Mode
Normal Operating Mode
(Solid Green LED)
Press Y & B at the same time, then
immediately release
LED Flashing Red/Amber
Press Y &B at the same time, then
immediately release
Normal Portion-Control Mode
(Solid Amber LED is on)
Extra Ice Adjustment Mode
This mode is used to adjust
ice portion sizes
IMPORTANT If no adjustments are made within 60 seconds, ice dispensing will return to normal oper­ating mode.
Adjustment Panel L.E.D. Indicator Light
Decrease
B
Y
1. Press and hold the desired ice portion selection but­ton to be adjusted.
2. While holding the portion selection button, momen­tarily press the increase (Y) or decrease (B) to change the amount of ice dispensed. Each time the B or Y is pressed the ice portion will change. A slow flashing LED means the portion is set at minimum. A fast flashing LED means the portion is set at maximum.
3. After adjustment has been made, release the portion selection button. The green LED will flash for 5 se­conds. Within this 5 sec., press cup size button being adjusted to take a sample. After 5 seconds the LED will return to solid amber (Normal adjustment mode). A solid red LED will be displayed briefly after dis­pensing a sample if the ice gate cylinder switch was shorted; a flashing red LED indicates an open in the ice gate cylinder switch wiring or an ice gate binding condition.
4. Repeat process until proper portion size is obtained.
Increase
Normal Operating Mode
(Solid Green LED)
Press Y & B at the same time,
then immediately release
LED Flashing Red/Amber
Start Here
No
Is the ice portion set as desired?
Go to the next ice portion
and repeat programming
Momentarily press B and Y at the same time to go to Extra Ice Adjust
Yes
Adjust
Mode. Red LED will be turned on.
Press Y & B at the same time
then immediately release
No Adjustment
Momentarily press B and Y at the
Solid Amber LED is "ON"
same time to return to the normal operating mode. Green LED will be turned on.
Press Y &B at the same time,
then immediately release
Extra Ice Adjustment Mode
(Solid red LED is "ON")
Same adjustment procedure as normal
ice portionĆcontrol adjust mode
Note: To return ice portion control to factory settings, the ice portion control must be in the Normal Ice Adjustment Mode (Solid Amber
LED). Then, at the same time, press and hold the small and extra large buttons for 1 second. The LED will go from amber to red and back to amber which signals that the portion sizes have been returned to the factory settings.
FIGURE 11. NORMAL ICE PORTION–CONTROL AND EXTRA ICE ADJUSTMENT MODE
1891633
Page 23
REPLENISHING CO2 SUPPLY
WARNING: CO2 Displaces Oxygen. Strict Attention must be observed in
the prevention of CO2 (carbon dioxide) gas leaks in the entire CO2 and soft drink system. If a CO particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Personnel exposed to high concentration of CO will experience tremors which are followed rapidly by loss of consciousness and suffocation.
gas leak is suspected,
2
gas
2
SYRUP FLAVOR CHANGE
Sanitize applicable syrup system as instructed, then install full tank of new flavor syrup.
REPLENISHING ICE BIN ICE SUPPLY
1. Remove ice bin cover.
IMPORTANT: IMPORTANT: Do not use hard–frozen (below 32_F) ice. After ice is removed from a freezer, allow the ice to sit at room temperature for approximately 1/2 hour before placing it in the bin. Ice to be used to fill ice bin must be in the form of small cubes, chunklets, or cracked ice (DO NOT USE FLAKE OR CRUSHED ICE).
NOTE: When indicator on CO2 cylinder regulator assembly 1800–psi gage is in shaded (change CO cylinder) portion of dial, CO2 cylinder is almost empty and should be changed.
1. Fully close (clockwise) CO2 cylinder valve.
2. Slowly loosen CO2 regulator assembly coupling nut allowing CO2 pressure to escape, then remove regulator assembly from empty CO2 cylinder.
3. Unfasten safety chain and remove empty CO2 cyl­inder.
WARNING: To avoid personal injury and/or property damage, always
secure CO2 cylinder with safety chain to prevent it from falling over. Should the valve become accidentally damaged or broken off, CO2 cylinder can cause serious personal injury.
4. Position CO2 cylinder and secure with safety chain.
2. Observing preceding IMPORTANT note, fill ice bin
2
with small cubes, chunklets, or cracked ice.
3. Install ice bin cover (ICE BIN COVER MUST BE IN INSTALLED POSITION FOR ICE AGITATOR TO OPERATE).
CLEANING AND SANITIZING
PERIODIC CLEANING OF ICE CHUTE
The ice chute on front of dispenser must be periodically removed and cleaned. Refer to FIGURES 9 and 10 CLEAN MODE (CLEAN ICE CHUTE) for removal and cleaning procedure.
DAILY CLEANING OF UNIT EXTERIOR
1. Remove cup rest from drip tray.
2. Wash out drip tray, then rinse tray with warm water allowing water to run down drain hose. MAKE SURE DRIP TRAY DRAIN HOLE AND DRAIN HOSE ARE NOT CLOGGED WHICH WOULD PREVENT WATER FROM EXITING DRIP TRAY THROUGH DRAIN HOSE.
5. Make sure gasket is in place inside CO2 regulator coupling nut,then install regulator on CO2 cylinder,
6. Open (counterclockwise) CO2 cylinder valve slight­ly to allow lines to slowly fill with gas, then open valve fully to back–seat valve. (Back–seating valve prevents leakage around valve shaft).
7. Check CO2 connections for leaks, Tighten loose connections.
REPLENISHING SYRUP SUPPLY
1. Remove CO2 disconnect (grey) and syrup discon­nect (black) from empty syrup tank, then remove tank.
2. Place full syrup tank in position, then connect CO disconnect (grey) and syrup disconnect (black) to full syrup tank.
3. Wash cup rest, then rinse cup rest with clean wa­ter. Install cup rest in drip tray.
4. Clean all external surfaces of unit with sponge. Rinse out sponge with clean water, then wring ex­cess water out of sponge and wipe off external sur­faces. Wipe dry with clean soft cloth. DO NOT USE ABRASIVE TYPE CLEANERS.
WEEKLY CLEANING OF DISPENSING VALVES
1. Remove nozzle from dispensing valve by turning nozzle and pulling down.
2. Dole Dispensing Valve. A. Remove diffuser/syrup tube from dispensing
valve by pulling down.
2
B. Place diffuser/syrup tube and nozzle in sani-
tizing solution.
9163319
Page 24
3. CC–1 Dispensing Valve. A. Remove syrup diffuser from dispensing valve
by pulling down.
B. Place syrup diffuser and nozzle in sanitizing
solution.
4. Using a clean sanitized towel, wipe inside diffuser area.
6. Using nylon brush (DO NOT USE WIRE BRUSH) and detergent soap solution, scrub entire interior surface of ice bin.
7. Rinse entire inside area of bin with plain water.
8. Wash ice agitator disc, ice agitator, and ice bin cover in detergent soap solution.
9. Rinse ice agitator disc, ice agitator, and ice bin cover thoroughly with plain water.
5. Using a nylon pot brush, clean removed parts with sanitizing solution.
6. Install removed parts on dispensing valve.
CLEANING ICE BIN INTERIOR AND SANITIZING SYRUP SYSTEM
The ice bin interior should be cleaned and syrup sys­tems sanitized every 30–days
Cleaning Ice Bin Interior.
WARNING: The ice bin contains hazardous moving parts. Do not
attempt to clean ice bin until Unit power cord is disconnected from electrical outlet.
CAUTION: DO NOT USE CHLORINE
CLEANSING POWDERS FOR
CLEANING. Use of chlorine cleaning powders will cause corrosive action on metal components. DO NOT USE SOLVENTS OR OTHER CLEANING AGENTS AS THEY MAY ATTACK THE PLASTIC MATERIAL.
1. Unplug Unit power cord from electrical outlet.
10. Install ice agitator and ice agitator disc on motor shaft and secure with thumbscrews.
11. Using a clean container, prepare a sanitizing solu­tion using 1/2 ounce of household bleach (Sodium Hypochlorite) to one gallon of cold (Ambient) pota­ble water (200–PPM).
12. Using a plastic bristle brush (DO NOT USE A WIRE BRUSH), scrub ice bin cover, ice agitator, ice agitator disc, and entire inside area of ice bin with sanitizing solution.
13. Slowly pour remaining sanitizing solution into ice bin which will allow sanitizing solution to run down over cold plate surface and out through drip tray to the permanent drain.
Sanitizing Syrup System.
CAUTION: Do not allow sanitizing solution to remain in syrup systems
longer than recommended contact time. Exceeding contact time will result in damage to stainless steel components.
WARNING: Flush sanitizing solution
from syrup systems as instructed.
Residual sanitizing solution left in systems could create a health hazard.
2. Remove ice bin cover.
3. Using warm water, melt ice inside ice bin and on top of coldplate. BE CAREFUL NOT TO USE TOO MUCH WARM WATER AT A TIME AS FLOOD­ING OF DRIP TRAY MAY OCCUR DUE TO WA­TER NOT EXITING DRIP TRAY INTO DRAIN HOSE FAST ENOUGH.
4. Remove thumbscrew securing ice agitator disc and ice agitator on motor shaft.
5. Remove ice agitator disc and ice agitator by pulling them straight up off motor shaft.
NOTE: Lime and scale deposits may be removed from metal components by using a cleaner such as Calgon Liquid Ice Machine Cleaner.
1. Remove dispensing valves nozzles, wash in mild detergent, then reinstall nozzles on valves.
2. Disconnect electrical power to carbonator.
3. Shut off the main water supply, then close CO regulator to the carbonator.
4. Disconnect syrup tanks from the syrup systems.
5. Activate the dispensing valves to purge remaining carbonated water from the carbonated water sys­tem.
6. Use clean empty syrup tanks for each of the fol­lowing:
A. Cleaning tank – fill with hot (120° to 140 ° F)
potable water.
2091633
2
Page 25
B. Sanitizing tank – Fill with a chlorine sanitizing
solution with a strength of one ounce of household bleach (sodium hypochlorite) to two gallons of cold (ambient) potable water (200–PPM).
7. Repeat the following procedure to clean and sani­tize each of the syrup systems.
A. Connect the cleaning tank containing potable
water to one of the syrup systems, then con­nect CO
to tank.
2
B. Activate dispensing valve and dispense until
syrup is purged from system and only water is dispensed.
C. Disconnect cleaning tank containing potable
water from syrup system.
D. Connect tank containing sanitizing solution
into the syrup system.
E. Activate the dispensing valve until water is
purged from the syrup system and until only sanitizing solution is dispensed. Allow sanitiz­ing solution to remain in the syrup system for twenty minutes before proceeding to next step.
8. Open CO
regulator to carbonator, open main wa-
2
ter supply, then connect electrical power to carbo­nator.
9. Dispense from all dispensing valves until a proper drink is dispensed. MAKE SURE DISPENSED DRINK ARE FREE FROM OFF–TASTE.
F. Disconnect tank containing sanitizing solution
from the syrup system.
G. Connect tank containing syrup into the syrup
system.
H. Dispense from dispensing valve until all sani-
tizing solution has been dispensed from syrup system and only syrup is dispensed.
I. Repeat preceding steps A through H to clean
and sanitize remaining syrup systems.
FIGURE 12. CO2 GAS CHECK VALVE
CLEANING CO2 GAS CHECK VALVES
(see FIGURES 2 AND 12)
The CO2 gas check valves must be inspected and serv­iced at least once a year under normal conditions and after any servicing or disruption of the CO2 system. ALWAYS REPLACE QUAD RING SEAL EACH TIME GAS CHECK VALVES ARE SERVICED.
9163321
Page 26
FIGURE 13. DISPENSER WIRING DIAGRAM
2291633
Page 27
FIGURE 14. INSTRUCTIONS FOR CRIMPING TUBE CLAMPS
9163323
Page 28
THIS PAGE LEFT BLANK INTENTIONALLY
2491633
Page 29
TROUBLESHOOTING
2
IMPORTANT:
WARNING: Disconnect electrical power to unit to prevent personnel injury before attempting any internal maintenance. Only qualified personnel should service internal
components or electrical wiring. If repairs are to be made to CO2, syrup, or water systems, shut off CO2 and plain water supplies, discount carbonator power cord, disconnect syrup tanks, and bleed systems pressures before proceeding
TROUBLESHOOTING POST–MIX SYSTEM
Trouble Probable Cause Remedy
WATER–TO–SYRUP “RATIO” TOO LOW OR TOO HIGH.
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES NOT INCREASE TO DESIRED WATER–TO–SYRUP “RATIO” .
A. Dispensing valve syrup flow
control not properly adjusted.
B. CO2 gas pressure to syrup
tanks insufficient to push syrup
A. Adjust Water–to–Syrup “Ratio” as
instructed.
B. Adjust secondary CO
for syrup tanks as instructed.
out of tanks.
A. No syrup supply.
A. Replenish syrup supply as
instructed
B. Syrup tank quick disconnects
not secure.
C. Syrup tanks secondary CO
regulator out of adjustment.
D. Dispensing valve syrup flow
control, syrup tank quick
B. Secure quick disconnects. C. Adjust syrup tanks secondaryC. Syrup tanks secondary CO
C. Adjust syrup tanks secondary
2
CO2 regulator as instructed.
D. Sanitize syrup system as
instructed. disconnect, or syrup line restricted.
E. Improper Baume of syrup. E. Replace syrup supply. F. Dirty or inoperative dispensing
valve syrup flow control.
F. Disassemble and clean
dispensing valve syrup flow
control.
G. Tapered nylon washer inside
tube swivel nut connection
G. Replace nylon washer. Make
sure it seats properly. distorted from being overtightened restricting syrup flow.
regulator
2
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES NOT DECREASE TO DESIRED WATER–TO–SYRUP “RATIO”.
DISPENSED PRODUCT CARBONATION TO LOW.
A. Dirty or inoperative dispensing
valve syrup flow control.
A. Disassemble and clean
dispensing valve syrup flow
control.
A. Carbonator primary CO
regulator out of adjustment for existing water conditions or
2
A. Adjust carbonator primary CO
regulator (Reference manual
provided with carbonator). temperature.
B. Air in carbonator tank. B. Vent air out of carbonator tank
through relief valve. Activate
dispensing valve No. 1 to make
carbonator pump cycle on.
2
9163325
Page 30
Trouble RemedyProbable Cause
DISPENSED PRODUCT CARBONATION TO LOW. (cont)
DISPENSED PRODUCT COMES OUT OF DISPENSING VALVE CLEAR BUT FOAMS IN CUP.
DISPENSED PRODUCT PRODUCES FOAM AS PRODUCT LEAVES DISPENSING VALVE.
C. Water, oil, or dirt, in CO
supply.
2
C. Remove contaminated CO2.
Clean CO
system (lines,
2
regulator, etc) using a mild detergent. Install a clean CO supply.
A. Ice used for finished drink is
subcooled.
B. Insufficient ice supply in
dispenser ice bin.
A. If using purchased ice allow ice to
melt slightly before using.
B. Replenish ice supply as
instructed. C. Oil film or soap scum in cups C. Use clean cups. A. Carbonator primary CO
regulator CO2 pressure set to
2
A. Reduce carbonator CO2 regulator
setting.
high for existing water conditions or temperature.
B. Syrup over carbonated with
CO2 as indicated by bubbles in inlet syrup lines leading to dispenser.
B. Remove syrup tanks quick
disconnects. Relieve tank CO
pressure, shake tank vigorously,
then relieve tank CO2 pressure as
many times as necessary to
remove over–carbonation.
2
2
NO PRODUCT DISPENSED FROM ALL DISPENSING VALVES.
C. Dispensing valve restricted or
dirty.
D. Tapered nylon washer inside
carbonated water line swivel
C. Sanitize syrup system as
instructed.
D. Replace nylon washer. Make
sure it is properly seated.
nut connector distorted restricting carbonated water flow.
E. Dirty water supply. E. Check water filter. Replace
cartridge.
Note: If water supply is dirty, be sure to flush lines and carbonator complete­ly. It may be necessary to remove lines to carbonator tank, invert tank and flush tank and all inlet lines to remove any foreign particles or dirt.
A. Dispenser rocker–type power
switch in OFF position.
B. No electrical power to
dispenser.
C. Disconnected or broken wiring
A. place power switch in ON
position.
B. Plug in dispenser power cord, or
check fuse or circuit breaker.
C. Connect or replace wiring.
to dispensing valves. D. Loose ground connection. D. Have ground connection repaired. E. Inoperative dispenser
E. Have transformer replaced.
transformer
2691633
Page 31
Trouble Probable Cause Remedy
NO PRODUCT DISPENSED FROM ONE DISPENSING VALVE.
ONLY CARBONATED WATER DISPENSED.
A. Broken or disconnected wiring. A. Connect wiring or have repaired.
B. Inoperative dispensing valve.
B. Have dispensing valve repaired.
Inoperative dispensing valve. C. Inoperative portion control. C. Replace portion control cover. A. Quick disconnects not secure
on syrup tanks.
A. Secure quick disconnects on
syrup tanks.
B. Out of syrup. B. Replenish syrup supply as
instructed.
C. CO2 regulator for syrup tanks
not properly adjusted.
C. Adjust syrup tank CO
as instructed.
regulator
2
D. Inoperable dispensing valve. D. Have dispensing valve repaired. E. Dispensing valve syrup flow
control not properly adjusted.
E. Adjust dispensing valve syrup
flow control (Water–to–Syrup Ratio) as instructed.
F. Dispensing valve syrup flow
control, syrup tank quick
F. Sanitize syrup system as
instructed. disconnect, or syrup lines restricted.
ONLY SYRUP DISPENSED. A. Plain water inlet supply line
shutoff valve closed.
B. Carbonator power cord
unplugged from electrical outlet.
C. Carbonator CO2 regulator not
properly adjusted.
DISPENSING VALVE WILL NOT DISPENSE ANY
A. Portion control not properly
adjusted.
PORTION CONTROL SIZE DRINK.
B. Portion control cover electrical
wiring disconnected. electrical wiring.
C. Inoperable portion control. C. Replace portion control cover.
NO RESPONSE FROM ONE
A. Inoperable portion control. A. Replace portion control cover. OF THE PORTION CONTROL SWITCHES OR THE CANCEL/POUR SWITCH.
A. Open plain water inlet supply line
shutoff valve.
B. Plug carbonator power cord into
electrical outlet.
C. Adjust carbonator CO2 regulator
(Reference manual provided with carbonator).
A. Adjust all portion sizes on
dispensing valve as instructed.
B. Connect portion control cover
9163327
Page 32
TROUBLESHOOTING ICE DISPENSING SYSTEM
Trouble
Probable Cause Remedy
NO ICE DISPENSED A. Ice bin cover not in place. A. Install ice bin cover.
B. Insufficient ice supply in ice
bin.
C. Ice in ice bin bridged (stuck
B. Replenish ice supply as
instructed.
C. Gently tap on ice to break it loose.
together).
D. No electrical power to
dispenser.
E. Insufficient or no CO2 supply
D. Plug in dispenser power cord, or
check fuse or circuit breaker.
E. Restore CO2 supply to dispenser.
to dispenser.
F. Inoperative ice portion
F. Replace ice portion controller.
controller. G. Inoperative ice agitator motor. G. Replace ice agitator motor. H. Inoperative gate cylinder. H. Replace gate cylinder. I. Inoperative gate solenoid I. Replace gate solenoid.
2891633
Page 33
IMI CORNELIUS INC. One Cornelius Place Anoka, MN. 55303–1592 Telephone (800) 238–3600 Facsimile (612) 422–3232
Installation Instructions
WARRANTY
IMI Cornelius Inc. warrants that all equipment and parts are free from defects in material and workman­ship under normal use and service. For a copy of the warranty applicable to your Cornelius product, in your country, please write, fax or telephone the IMI Cornelius office nearest you. Please provide the equipment model number and the date of purchase.
IMI Cornelius Offices
AUSTRALIA D P.O. 210, D RIVERWOOD, D NSW 2210, AUSTRALIA D (61) 2 533 3122 D FAX (61) 2 534 2166
D AM LANGEN FELDE 32 D A-1222 D VIENNA, AUSTRIA D (43) 1 233 520 D FAX (43) 1-2335-2930
AUSTRIA
D BOSKAPELLEI 122 D B-2930 BRAASCHAAT, BELGIUM D (32) 3 664 0552 D FAX (32) 3 665 2307
BELGIUM
D RUA ITAOCARA 97 D TOMAS COELHO D RIO DE JANEIRO, BRAZIL D (55) 21 591 7150 D FAX (55) 21 593 1829
BRAZIL
D TYTHING ROAD ALCESTER D WARWICKSHIRE, B49 6 EU, ENGLAND D (44) 789 763 101 D FAX (44) 789 763 644
ENGLAND FRANCE
D 71 ROUTE DE ST. DENIS D F-95170 DE UIL LA BARRE D PARIS, FRANCE D (33) 1 34 28 6200 D FAX (33) 1 34 28 6201
GERMANY GREECE HONG ITALY NEW SINGAPORE SPAIN USA
D CARL LEVERKUS STRASSE 15 D D-4018 LANGENFELD, WEST GE RMANY D (49) 2173 7930 D FAX (49) 2173 77 438
D 488 MESSOGION AVENUE D AGIA PARASKEVI D 153 42 D ATHENS, GREECE D (30) 1 600 1073 D FAX (30) 1 601 2491
KONG D 1104 TAIKOTSUI CENTRE D 11-15 KOK CHEUNG ST D TAIKOKTSUE, HONG KONG D (852) 789 9882 D FAX (852) 391 6222
D VIA PELLIZZARI 11 D 1-20059 D VIMARCATE, ITALY D (39) 39 608 0817 D FAX (39) 39 608 0814
ZEALAND D 20 LANSFORD CRES. D P.O. BOX 19-044 A VONDAL E D AUCKLAND 7, NEW ZEALAND D (64) 9 8200 357 D FAX (64) 9 8200 361
D 16 TUAS STREET D SINGAPORE 2263 D (65) 862 5542 D FAX (65) 862 5604
D POLIGONO INDUSTRAIL D RIERA DEL FONOLLAR D E-08830 SANT BOI DE LLOBREGAT D BARCELONA, SPAIN D (34) 3 640 2839 D FAX (34) 3 654 3379
D ONE CORNELIUS PLACE D ANOKA, MINNE SOTA D (612) 421-6120 D FAX (612) 422-3255
29
Loading...