Cor HA-6400 User Manual

Page 1
HA−6400 Côr Home Automation Panel
Advanced Installation Instructions
.C
1
..
.I
Page 2
About navigating this electronic document: Throughout this document there are navigational links.
Wherever you see this symbol
...C.... you can click on it to return to the table of contents.
Wherever you see this symbol Wherever you see underlined blue text
Whenever you navigate to a new page, you can go back using Alt +
..... you can click on it to return to the index.
...... I
you can click on it to navigate to that reference.
(left arrow)
CONTENTS
WELCOME! 7........................................................................
Features & Benefits 7..................................................................
INCLUDED IN BOX 8..................................................................
Optional Accessories 8.................................................................
Front of CôrPanel 9.................................................................
Back of CôrPanel 10.................................................................
1 HARDWARE INSTALLATION 11.......................................................
What You Need 11....................................................................
Choose a Location 11..................................................................
1.1 Install the Battery 12...............................................................
1.2 Connect Power Lead to Panel 12......................................................
1.3 Install Côr Panel 12..............................................................
1.4 Connect Power 13.................................................................
2 SET UP CONNECTIONS 14...........................................................
2.1 Select a Permanent Connection Mode 14...............................................
2.2 Ethernet Setup 15.................................................................
2.3 Check Ethernet Connection to CôrApp 16.............................................
2.4 Option 2 Wi−Fi Setup 17............................................................
2.5 Set Up a Web Access Passcode for CôrApp 19.........................................
2.6 Scan for Wireless Networks 19.......................................................
2.7 Troubleshooting Wi Fi Setup 21......................................................
2.8 Check Wi Fi connection to Côr Panel 22..............................................
3 THE COR
SMART HOME APP 23..................................................
3.1 Install Côr App 23...............................................................
3.2 Using the App 24..................................................................
3.3 Troubleshooting Setup 28...........................................................
4 SYSTEM SETTINGS 29..............................................................
4.1 Learn Sensors into CôrHub 29......................................................
4.2 Learn in a Keyfob 34...............................................................
4.3 Programming Areas 37.............................................................
4.4 Programming the System 39.........................................................
4.5 Programming Channels 42...........................................................
4.6 Programming the Network 44........................................................
4.7 Programming Scenes 47.............................................................
4.8 Programming Schedules 50..........................................................
.C.
2
..
Page 3
4.9 Programming Holidays 52...........................................................
4.10 Programming Z−Wave Devices 54...................................................
Z−Wave Room Names 54..............................................................
Add a Z−Wave Device 54..............................................................
Z−Wave Device Association 55..........................................................
Z−Wave Maintenance 55...............................................................
4.11 Programming Cameras 57..........................................................
4.12 Check Event History 63............................................................
4.13 Check Connection Status 64........................................................
4.14 Check Details 64.................................................................
5 ADVANCED INSTALLATION USING WEB SERVER 65.................................
5.1 Advanced Programming, System 66...................................................
5.2 Advanced Programming, Sensors 75...................................................
5.3 Advanced Programming, Areas 79....................................................
Notes on Force Arming, Bypass, and Auto−Bypass 81........................................
5.4 Advanced Programming, Channels 87..................................................
Configure Email Reporting 89...........................................................
5.5 Advanced Programming, Communicator 90.............................................
5.6 Advanced Programming, Schedules 96.................................................
5.7 Advanced Programming, Actions 98...................................................
5.8 Advanced Programming, Arm−Disarm 103.............................................
5.9 Advanced Programming, Devices 105..................................................
5.10 Advanced Programming, Permissions 109.............................................
5.11 Advanced Programming, Area Groups 113.............................................
5.12 Advanced Programming, Menus 114..................................................
5.13 Advanced Programming, Holidays 115................................................
5.14 Advanced Programming, Sensor Types 116............................................
Sensor Types Table 119................................................................
5.15 Advanced Programming, Sensor Options 120...........................................
Sensor Options Table 123..............................................................
5.16 Advanced Programming, Event Lists 124..............................................
5.17 Advanced Programming, Channel Groups 125..........................................
Customize Reporting Codes 127.........................................................
Reporting Fixed Codes in Contact I.D. 129.................................................
5.18 Advanced Programming, Scenes 130.................................................
5.19 Advanced Programming, Speech Tokens 132...........................................
5.20 Advanced Programming, Cameras 134................................................
Add a Camera Method – Manual Entry 134................................................
Removing a Camera 134...............................................................
5.21 Advanced Programming, CôrHome Automation 142...................................
6 USERS AND PERMISSIONS 143−145...................................................
6.1 Add Users 143....................................................................
6.2 Users Submenus 145...............................................................
.C
3
..
.I
Page 4
6.3 Permissions 146...................................................................
7 CELLULAR RADIO SETUP 150−154...................................................
7.1 Install Optional Cellular Radio 150....................................................
7.2 Connect Power 151................................................................
7.3 Check Signal Strength 151...........................................................
7.4 Install External Antenna – Optional 152................................................
7.5 Check Cellular Connection to Côr App 154...........................................
8 CAMERA SETUP INSTRUCTIONS 156−166.............................................
8.1 Quick Setup 156...................................................................
8.2 Setting up Ethernet/Wi Fi transmission 156..............................................
8.3 Wi Fi Signal Strength 157...........................................................
8.4 Add Camera via Wi Fi for iOS Device 158..............................................
8.5 Add Camera via Wi Fi for Windows PC 158.............................................
8.6 Add Camera via Ethernet for iOS Device (non DHCP) 159.................................
8.7 Add Camera via Ethernet for Windows PC (non DHCP) 160................................
8.8 Add Camera via Ethernet (DHCP) 160.................................................
8.9 Add Camera to CôrApp 161........................................................
8.10 View Live Stream and Latest Clip 162................................................
8.11 Program event triggered camera clips 162..............................................
8.12 View event triggered clips in History 164..............................................
Remove Camera from Côr (if needed) 165...............................................
8.13 Change Default Camera Settings (Via TruVision Navigator) 165............................
8.14 Camera Troubleshooting 166........................................................
9 INSTALLATION USING KEYPAD 167−173..............................................
9.1 Basic Installation 167...............................................................
9.2 Learning Sensors into Côr 167......................................................
Sensor Types Presets 167...............................................................
9.3 Configure Sensor Names (optional) 168................................................
9.4 Record Sensor Names (optional) 170..................................................
9.5 Test Sensor Signal Strength 170......................................................
9.6 Remove a Sensor 171...............................................................
9.7 Change the User Type (optional) 171..................................................
9.8 Add a User / Keyfob 171............................................................
9.9 Record User Names (optional) 172....................................................
9.10 Remove a User 172...............................................................
9.11 Add a Keyfob 173................................................................
9.12 Remove a Keyfob 173.............................................................
PERSONALIZE YOUR CÔRPANEL 173−179............................................
9.13 Volume Level 173................................................................
9.14 Voice Annunciation 174............................................................
9.15 Full Menu Annunciation 174........................................................
9.16 Backlight Level 174...............................................................
9.17 Change Time and Date 175.........................................................
.C.
4
..
Page 5
9.18 Adjust Area Entry or Exit Times 175..................................................
9.19 Reset Installer Account 176.........................................................
9.20 Reset to Factory Default (optional) 176................................................
9.21 Table Mount (Optional) 176.........................................................
9.22 Wall Tamper Option 177...........................................................
9.23 Connecting Inputs 177.............................................................
9.24 Connecting Outputs 179............................................................
10 TESTING THE SYSTEM 180−181....................................................
10.1 Perform a Walk Test 180...........................................................
10.2 Perform a Siren Test 180...........................................................
10.3 Perform a Battery Test 180.........................................................
10.4 Perform a Communicator Test 181...................................................
10.5 Event History 181................................................................
11 GLOSSARY 182.....................................................................
Appendices 185−200..................................................................
A.1 DLX900 Software 185.............................................................
A.2 Troubleshooting DLX900 187.......................................................
A.3 Firmware upgrade using DLX900 188.................................................
A.4 Firmware upgrade using USBUP 189..................................................
A.5 System Status Messages 190.........................................................
A.6 App and Web Error Messages 191....................................................
A.7 Z−Wave Messages 192.............................................................
A.8 History Events 193................................................................
Event ID Table 193...................................................................
A.9 Event Reporting Class Table 196.....................................................
A.10 Action Events: Category and Types 197...............................................
A.11 Action Results Category and Action Results Event Types 198..............................
A.12 CôrHub Building Blocks 199.....................................................
A.13 CôrHub Web Server Tree 200.....................................................
Specifications 201....................................................................
UL SPECIFICATION 202−207...........................................................
Electrical: 202.......................................................................
Software Version: 202.................................................................
Installation Notes: 202.................................................................
Compatible Receivers: 202.............................................................
Listings and Approvals: 203............................................................
Minimum System Configuration: 203.....................................................
Abort: 203..........................................................................
Quick exit: 203.......................................................................
Exit delay extension: 203...............................................................
Exit Progress Annunciation: 204.........................................................
Entry Progress Annunciation: 204........................................................
Keyfob operation / System Acknowledgement: 204..........................................
.C
5
..
.I
Page 6
Canceling and preventing accidental alarms: 204............................................
Recent Closing: 205...................................................................
Sensor Tripping Instructions: 205........................................................
SIA CP−01−2010 Programmable Features 206..............................................
Smoke and heat detector locations: 207....................................................
PRODUCT WARNINGS 208.............................................................
WARRANTY DISCLAIMERS 208.........................................................
Disclaimer 208.......................................................................
Intended Use 209.....................................................................
Copyright 209.......................................................................
Trademarks and Patents 209............................................................
Regulatory Notices for USA 209.........................................................
Regulatory Notices for Canada 210.......................................................
INDEX CLICK ON ENTRIES TO NAVIGATE 211..........................................
.C.
6
..
Page 7
WELCOME!
Thank you for purchasing CôrHome Automation! Please read through this document before starting the installation.
Features & Benefits
256 Users – enough for even moderate sized businesses64 wireless sensors + 20 Keyfobs4 Areas/Partitions – split your system into smaller parts you can protect individuallyPersonal Voice Guided setup and menu prompts2 Hardwired inputs (can be doubled to total 4)2 Programmable Outputs85db piezo siren24 hour battery backupWi Fi 802.11 b/gWi Fi direct for setupIEEE 802.3 Compliant Ethernet
3G Cellular Radio Module, optional
.C
7
..
.I
Page 8
INCLUDED IN BOX
Check contents before beginning your installation.
Côr™ Panel
Transformer
Wall Bracket
Backup Baery Pack
Installaon
Manual
Full
Reference Guide
Available Online
Optional Accessories
Cellular Radio Modem ZW−HSPADesk Stand ZW−DS01Extension Antenna ZW−ANT3MBattery ZW−BAT23APower Supply ZW−PS9VUltra Secure IP Camera ZW−USW−3120
(Only works with Côr)
A list of available accessories is available online at www.CorHomeAutomation.com
Input/Output Lead
A160028
.
.C.
8
..
Page 9
FRONT OF CÔR PANEL
.C
9
..
.I
Page 10
BACK OF CÔR PANEL
Connections for the cellular radio module are located under the cover on the right.
.C.
10
..
Page 11
1 HARDWARE INSTALLATION
What You Need
Côr PanelCôr Accessories (Door/Window sensors, Motion sensors, Lighting modules, Door Locks, etc.)Devices, lights locks etc.)
A mobile or smart device, or computer for programming
List of homeowner users and PIN codes homeowner wish to addSmall Phillips screwdriverSmall Flathead screwdriverRouter supporting 802.11 b or 802.11g if using homeowner Wi Fi featuresIP access for optional cell moduleWi Fi/Ethernet access
Choose a Location
When choosing a location for your Côr Panel there are a number of appliances and areas to avoid which could interfere with the security system.
Choose a central location that optimizes signal strength (Wi Fi, 319.5, Z−Wave)A void TV and other electronic appliancesA void microwave ovensA void wet and moist areas such as bathrooms and toiletsA void cordless telephonesA void computers and wireless equipment
.C
11
..
.I
Page 12
1.1 Install the Battery
1.2 Connect Power Lead to Panel
Connect power lead from power supply to the back of the panel. The connector is keyed and fits only one way.
1.3 Install Côr Panel
Panel may be mounted on a wall (recommended) or on a table. For table mount information please reference Section 9.21 Install the bracket on a wall by using the supplied screws. Make sure the power lead can reach the panel when plugged in to a power source. NOTE: Holes in the wall supplying Ethernet, power, antenna or I/O connector must be in the shaded area to ensure the unit mounts flat on
the wall; See the drawing on the next page.
.C.
12
..
Page 13
Align the Côr Panel with the top clips on the wall bracket, and then push the Côr Panel so it sits flat against the wall.
NOTE: Ensure the screw on the underside of the panel is loosened enough so that the wall bracket clears the screw head; if not the panel may not fit flush against the wall. Then retighten the screw to ensure a secure fit.
1.4 Connect Power
Connect the power supply to receptacle.
!
WARNING
PERSONAL INJURY AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death and unit component damage.
Do not connect to a receptacle controlled by a switch.
.C
13
A160088
..
.I
Page 14
2 SET UP CONNECTIONS
2.1 Select a Permanent Connection Mode
Select a method to connect your Côr panel to a network so it can report events via Cloud, and allow you to configure settings using the built−in Web Server or Côr app. The recommended installation for security monitoring is to use IP as primary reporting with cellular backup. However IP only or cellular only installations may be used. For cellular radio setup reference Section 7.
Option 1 − Ethernet Setup – This is the easiest to set up. The Côr panel is set to use Ethernet by default. It requires a hardwired Ethernet connection to the panel. You will need to provide an Ethernet router and an internet connection for reporting and remote access.
Option 2 − Wi Fi Setup − This connects the Côr to a local Wi Fi network. You will need to provide a wireless router and a secure internet connection for reporting and remote access.
.C.
14
..
Page 15
2.2 Ethernet Setup
Connect power to your Côr panel.
If this panel was previously connected via Wi Fi, switch connection to Ethernet:
MENU
1.
2.
INSTALLER CODE
3.
7
4.
MENU
Connect an Ethernet cable to the rear of the panel and wait 10 sec for the local router to assign the panel an IP address.
On the panel press Menu – 8 – [PIN] – 6 and note the IP address announced. This is the IP address of your Côr panel. If you hear “IP address is not ready” then wait a further 30s and repeat this step. Open your web browser. Enter IP addr ess (For example:192.168.1.6). The Côr login screen should appear:
Enter your username and password. By default this is : installer and 9 7 1 3. You should now see a screen similar to one of the below.:
9
MENU
ENTER
Select main menu - Option 9, Advanced system conguration
Enter Installer code (By default thisis 9 7 1 3)
Toggles between WiFi or Ethernet connection unit Ethernet is on
Exits from Advanced system conguration menu
A160042
Your Côr panel is now successfully connected to your Ethernet network.
.C
15
..
.I
Page 16
2.3 Check Ethernet Connection to CôrApp
Login to the Côr Web Server from your laptop using the IP address announced. Press or click Settings.
Select Connection Status in the drop down menu.
Check that:
a. LAN Status should display Connected.
b. LAN Media should display Ethernet.
c. UltraSync−Status should display Connected.
d. UltraSync−Media should display LAN.
Settings Selector
Connection Status
Up
Down
Connection Status
LAN Status
LAN Media
Cell State
UltraSync Status
UltraSync Media
Radio Details
Cell Service
Signal Strength
Operator ID
Reload
Connected
Ethernet
Idle
Connected
LAN
No service
0
If it does not:
e. Check cable connection.
f. Check router settings.
.C.
Radio Technology
WiFi Details
WiFi SSID
WiFi Security Type
GSM
None
16
..
A160043
Page 17
2.4 Option 2 − Wi Fi Setup
Turn on Wi Fi Discovery Mode − this creates a local hot spot and provides direct access to the Côr panel from a mobile device such as a tablet, or laptop computer.
Enable Wi Fi on your tablet or laptop computer. On your mobile device, browse for available Wi Fi networks and select the ZeroWire_xxxx network to connect to it. NOTE: Note: Only a single user can connect at any time and there is no Wi Fi password.
Once connected, the Côr will be assigned a fixed IP address of 192.168.1.3.
Use your tablet or laptop computer to connect to Côr.
NOTE: Note: The wireless router must support 802.11 b or 802.11g.
Open your web browser and enter 192.168.1.3. The Côr. login screen should appear.
Enter your username and password, by default this is: installer and 9 7 1 3.
Press Sign In.
.C
17
..
.I
Page 18
You should now see a screen similar to one of the below:
Your Côr is now successfully connected to your Wi Fi network.
.C.
18
..
Page 19
2.5 Set Up a Web Access Passcode for CôrApp
For security, initial remote access via the Côr app is disabled by default. Follow these steps to enable it:
Select Network from the drop down menu. Enable remote access for the Côr App by changing the Web Access Passcode (WAP) with a unique eight digit code provided by the homeowner. This is an eight digit code that permits the homeowner remote access from their Côr mobile app. The default Web Access Passcode of 00000000 prevents remote access.
NOTE: If you are connecting to the system via the Local Area Network (LAN) the WAP is not required.
Press Save. “Program Success” will appear. For a detailed explanation of the function of the Web Access Passcode please see section 4.6 Programming the Network
2.6 Scan for Wireless Networks
Press Settings Select Wi Fi Setup form the drop down menu. Press Scan for Wireless Networks:
.
.C
19
..
.I
Page 20
Press the Wi Fi network name you wish Côr panel to connect to. Enter Wi Fi passcode then press OK. “Network Successfully selected” will appear as shown below. Upon connection to the Wi Fi network, the system will automatically logoff from the web browser.
On your mobile device, connect to the same Wi Fi network found by the scan. On the panel press Menu – 8 – [PIN] – 6 and write down the IP address announced. This is the IP address of your Côr panel. If you hear
“IP address is not ready” then wait a further 30 seconds and repeat this step.
Open your web browser.
Enter announced IP address. The login screen should appear:
Your Côr panel is now successfully connected to your Wi Fi network.
.C.
20
..
Page 21
2.7 Troubleshooting Wi Fi Setup
1. Cannot get an IP address Cause Solution
Connection does not work The wireless/router may not be configured for automatic DHCP or cer-
tain security settings may be enabled.
2. Network connections fail Cause Solution
Some newer routers will have these off at factory default. Some
802.11n access points may not accept 802.11g connections
Close the web browser on your device, and restart your wireless router, and start again from step 1.
Check your router settings and try again.
Check if Wi Fi router allows b and g connections. Check if router is within range and has good signal,
otherwise a Wi Fi range extender may help. Ensure auto−correct is turned off (when typing the
Wi Fi pass phrase). Ensure wireless router has DHCP enabled. Ensure wireless router does not have firewall or se-
curity rules that prevent additional connections. Ensure IP addresses are available; for example con-
nect a new device to it and verify it has an internet connection.
.C
21
..
.I
Page 22
2.8 Check Wi Fi Connection to Côr Panel
Login to the Web Server from your computer using the IP address announced which can be obtained by pressing Menu 8 − [Installer PIN]
− 6 on the Côrpanel. Press Settings in the drop down Menu at the top right.
Select or press Connection Status in the drop down menu.
Check that
a. LAN Status should display Connected.
b. LAN Media should display Wi Fi.
c. UltraSync−Status should display Connected.
d. UltraSync−Media should display LAN.
Settings Selector
Connection Status
Up
Down
Connection Status
LAN Status
LAN Media
Cell State
UltraSync Status
UltraSync Media
Radio Details
Cell Service
Signal Strength
Operator ID
Radio Technology
Reload
Connected
Wi Fi
Idle
Connected
LAN
No service
0
GSM
If it does not
e. Check cable connection.
f. Check router settings.
.C.
WiFi Details
WiFi SSID
WiFi Security Type
None
22
..
A160046
Page 23
3 THE CôrAPP
A160067
3.1 Install CôrApp
The Côr Smart Home is an app that allows you to control your Côr Home Automation System from an Apple iPhone/iPad, or Google Android device. First set up the Côr Web Server from Section 2 then download this app.
Carrier charges may apply and an Apple iTunes or Google account is required.
On Apple devices go to the App Store. On Android devices go to the Google Play store.
Search for Cor Home Automation.
Install the app for the Homeowner.
Press the icon on your device to launch it.
Press Add or + on the top right to add a new Site or the information callout icon to edit an existing Site.
Enter the information for the Site Name and Description that the homeowner wants to use.
The Serial Number is printed on the back of the panel.
The default Web Access Passcode of 00000000 disables remote access. To change it, login to Côr Web Server and go to Settings − Network. (Refer to Section 2.3.)
The default username and PIN code for the master user is User 1 and 1234. You may also use any other valid user account. Homeowner users will only see and have access to menus at their permission level.
Toggle the blue slider to the right if the homeowner wants to require a PIN for login.
The Notification Services will allow the user to receive notifications in the event of a triggered event. To enable this function, tap on the arrow and toggle the blue slider to the right to activate Push Notificaitons.
The Location Services will allow actions based on entering and exiting specific map areas using global positioning system (GPS) location of the user phone. To enable this function, tap on the arrow and toggle the blue slider to the right to activate GEO Actions and/or Check Status on Leaving.
Compatible Wi Fi thermostat from Carrier and Bryant can be added to the app by toggling the blue slider. The following screen will ask the user to login to their registered thermostat account and agree to the terms to authorize app access to the thermostat control.
Press Done button to save the details and to go back. Press the name of the Site to enter the main Overview screen of the Côr Home Automation system app.
.C
23
..
.I
Page 24
3.2 Using the App
The first screen that will appear once you connect is the Overview screen. This will display the status of your system and allows you to arm or disarm areas by pressing Arm Away, Arm Stay, or Disarm. From this screen, you can also enable Automations that have been programmed in the Côr app.
The menu bar is located along the bottom of the screen.
Press the Lights icon and on/off appliances. Please see Section 4.10 for Programming Z−Wave Devices. From this screen, you are able to dim or turn on/off light switches; and turn on/off power to plugged−in appliances or products. In addition, you can use the Automation feature to program your Côr Home Automation system to turn on these Z−Wave enabled modules and outlets at a certain time; or set up lights to turn on and off to mimic occupancy while you are away from your home.
.C.
to access Z−W ave enabled modules and outlets that are connected to the Côr Home Automation system for lighting
24
..
Page 25
Press the thermometer icon at the bottom of the menu bar to control your thermostats that are connected to your Côr Home Automation system. Using the red and blue arrow to the right of the screen, you can adjust your desired temperature setting to maintain comfort in your home. This screen also allows you to change the operational mode of your heating and air conditioning system by selecting either Heat, Cool, Auto or Off. In addition, you can control the fan operation either to run constantly On or in the Auto mode.
Press camera icon at the bottom of the menu bar to access the Wi−Fi cameras connected to the Côr Home Automation system. Pressing the Play icon in the center picture of the video will allow you to view live video streams from the camera. You can also view previously
recorded clips by pressing the Play icon
button to initiate the camera into recording mode.
.C
under Latest Clip section of the screen. Or if you want to record a video, press the Record
25
..
.I
Page 26
Press the Lock icon at the bottom of the menu bar to access Z−Wave enabled open and close devices such as Door Locks and Garage Door Openers. On this screen, you can check the status of a Z−Wave enabled door lock or garage door; and remotely lock the door or close the garage door.
.C.
26
..
Page 27
Press Sensors icon to view sensor status. From the Sensors screen you can press Bypass to ignore a sensor or press it again to restore it to normal operation. You may also turn on or off the Chime triggered then press the sensor Notification icon
to turn on or off.
feature. If you would like to be notified when a specific sensor is
.C
27
..
.I
Page 28
3.3 Troubleshooting Setup
1. Site Creation fails
Cause Solution
Check the serial number and web access passcode, match those in the CôrW eb Server set−up.
Settings are entered incorrectly
2. Cannot see local Wi Fi access point from smartphone
Cause Solution
Some hotspot access points may not accept 802.11g connections. Ensure your Wi Fi access point is able to accept 802.11b or
3. Network connections fail
Cause Solution Ethernet not working Wi Fi not working If connected by Wi Fi, check that the connection is working. Network not set
Web Access Passcode must not be 00000000. User Name must be entered with a space between the first and
last name and with correct capitalization.
802.11g.
If connected by Ethernet, check that the cable is plugged in and the connection is working.
Check Settings − Network − Enable UltraConnect is checked under Options.
4. Cannot get IP address
Cause Solution The wireless/router may not be configured for automatic DHCP
or certain security settings may be enabled.
5. Cannot access internet
Cause Solution
Mobile device has no access
6. Server connections fail
Cause Solution
Server addresses are incorr ect
7. Configuration setting changes fail
Cause Solution Devices are not responding to inputs
Check your router settings and try again.
Open a web browser on your mobile device to double check access.
T ry disabling Wi Fi on your device once the Côr panel is con- figured and using the 3G/4G data connection of the homeowner smartphone with the Côr app.
Check the UltraSync servers are correct. See
Advanced Programming, Cor Home Automation for reference.
a. Ethernet Server 1 − zw1.UltraSync.com:443 b. Ethernet Server 2 − zw1.UltraSync.com:443 c. Wireless Server 1 − zw1w.UltraSync.com:8081 d. Wireless Server 2 − zw1w.UltraSync.com:8081
Re−initialize equipment. Power cycle connected equipment in­cluding Côr Hub and customer supplied router(s).
.C.
28
..
Page 29
4 SYSTEM SETTINGS
These instructions describe how to program all of the devices, schedules and areas used by the system.
4.1 Learn Sensors into CôrHub
Connect to the Côr Web Server (either via Wi Fi Discovery Mode or Ethernet Setup. Enter your username and password. By default this is installer and 9713. Press Sign In. You should see a screen similar to one of the below:
From the Côrscreen app press the button then .
You are on the
Select the drop down menu under Sensors to see the list of programmable items.
Select Sensors.
page.
.C
29
..
.I
Page 30
Z-Wave Room Names Z-Wave Add/Remove Z-Wave Device Association Z-Wave Maintenance
A160049
At this point you can type the name of the sensor and define its profile, by determining the sensor type (Entry, 24 hour, fire, key switch, etc.) and the sensor options (bypass, force arm, Cross Zone, stay mode, etc.). You can also assign it a specific area. Each of these has a drop down menu to make selections.
.C.
30
..
Page 31
When all of your programming definition for the sensor is complete, press Learn. A notification box will appear below the Learn button. Activate the sensor. Consult the sensor manual for instructions; generally this is performed by opening the case and manipulating the tamper activator. This will send a tamper signal to the Côr panel. The notification box will alert you that a new device was found.
.C
31
..
.I
Page 32
The screen below shows a sensor learned in.
Name: Front Door Type: Entry Exit Delay 1 Option: Bypass Area Group: Area 1 Serial Number: A8E551
Note that the sensor Serial Number box has been populated after learning in the sensor.
Explanations of the sensor configurations appear on the next page.
Also reference Advanced Programming, Sensors, Section 5.2.
.C.
32
..
Page 33
Sensor Configuration Men
u
Option Default Function
Select Sensor to Configure 1 Sensor Choose among 64 sensors. Sensor Name Blank Custom 32 character name.
Sensor types determine the sensor attributes such
Sensor Type 3 Entry Exit Delay 1
Sensor Option 1 Bypass
Area Group 1 Area 1
Serial Number Blank
Tamper On
Disable Internal Reed Off
Norm Open External Contact Off
Signal Strength 0 Shows the last signal strength received. Voice Name 1 Blank Voice Name 2 Blank Voice Name 3 Blank Voice Name 4 Blank
as entry/exit, instant, etc. Additionally sensor types determine the siren attributes.
Sensor options determine the sensor attributes such as a sensor’s ability to be bypassed, force arm, Cross Zone, stay mode, etc. Additionally sensor options determine the sensors reporting attributes.
Assigning a sensor to an area will enable it to re­port.
This is the TXID of the wireless sensor, it can be manual entered or the sensor can be ”Learned” into panel.
Tamper switch on the wireless sensor is enabled or disabled.
The internal reed switch(es) on the wireless device can be disabled. Applies if the sensor is a device type 10.
The external input on wireless sensors can be en­abled. Check this box when external contact is nor­mally open. If the 60−362N−10−319.5 sensor is used the jumper pin does not have to be used. Ap­plies if the sensor is a device type 10.
This feature uses the internal voice vocabulary to name the sensor. These names will be announced in sequence when the sensor is opened while in the Chime mode.
When you are finished programming the Sensor
Press the Save button. A dialogue box appears. Press the OK button. A dialogue box appears. Press the OK button.
These dialogue boxes appear after any changes to the system are attempted/registered.
IMPORTANT: After you have finished programming a sensor, be sure to advance the sensor number in the drop down menu when programming the next sensor. Otherwise you will over−write the sensor configuration you just programmed.
.C
33
..
.I
Page 34
4.2 Learn in a Keyfob
Press then for the Settings Selector page.
Select the drop down menu under Sensors to see the list of programmable items. Select Keyfobs.
With the keyfobs screen selected you can choose the keyfob number to configure and select the user number to link to the keyfob.
.C.
34
..
Page 35
Give the keyfob a number (you are giving the keyfob a sensor number). Select the user and press Learn. A notification box will appear below the Learn button. Activate the keyfob. Consult the keyfob manual for instructions; generally this is performed by simultaneously pressing the Lock and Unlock buttons. This will send a tamper signal to Côr panel.
The notification box will alert you that a new device (keyfob) was found. The keyfob Serial Number box will be populated. Explanations of the Keyfob configurations appear on the next page.
.C
35
..
.I
Page 36
Option Default Function
Select Keyfob to Configure 65 Keyfob This is the starting Sensor number for Keyfobs.
User
Keyfob Configuration
Menu
When you are finished programming the Keyfob,
Police Off
No Siren on Police Off
Medical Off
Scene Off
Serial Number Blank
Use FOB Number as
Standard User
If ”Use FOB Number as Standard User” is used, when there is an activation on that Fob the Central Station report will come in with that sensor num­ber. If there is a user assigned to the fob that user number will come in on the Central Station Report. If no user is assigned it will show as user 999 in the Central Station Report.
Enabling this will enable the Police / Panic on the Fob, this will also be audible at the panel (top 2 buttons press at the same time).
With this enabled it will make the Police / Panic silent at the panel.
Enabling this will enable the Medical / Aux on the Fob. This will be an audible alarm at the panel. (bottom 2 buttons pressed at the same time)
By using the drop down menu one of 16 scenes can be activated.
This is the TXID of the Fob, it can be manually entered or the sensor can be ”Learned” into panel.
Press the Save button. A dialogue box appears. Press the OK button. A dialogue box appears. Press the OK button.
These dialogue boxes appear after any changes to the system are attempted/registered.
.C.
36
..
Page 37
4.3 Programming Areas
Select Areas from the drop down menu.
With the Areas screen selected you can choose an Area number to configure, give the area a name, and define attributes for that area. The Côr can support a total of 4 areas; each area is configured with its entry and exit times, area options, area timers, area type and reporting characteristics
Explanations of the Area configurations appear on the following pages.
Also reference Advanced Programming, Areas
, Section 5.3.
.C
37
..
.I
Page 38
Areas
n
s
Configuratio
Menu
Option Default Function
Select Area to Configure Area 1
Area Name Blank
Entry Time 1 (30−240) Seconds 30
Exit Timer 1 (45 − 255) Seconds 45
Area Timers
Area Option
Area
Reporting
Entry Timer 2 (30 − 240) Seconds 0
Exit Timer 2 (45 −255) Seconds 0 Stay Enter Timer (30 − 240)
Seconds
Quick Away Off
Quick Stay Mode Disarm Off
Manual Panic On Enables or Disables the Keypad Panic Manual Fire On Enables or Disables the Keypad Fire Manual Auxiliary On Enables or Disables the Keypad Auxiliary
Force Arm With Bypass Off
Area Account 0
Area Channels
30
1
Channel
Group
Use the drop down menu to select which of the 4 areas to program.
Each area can be configured with a custom 32 character name. The area name is displayed wherever an area is referenced on the Côr system.
Provides time to enter into the premises to deactivate the alarm system.
Provides time to exit the premise without activating the alarm system.
If there is a second entry door that requires more time to deactivate the alarm system.
If there is a second exit door that requires more time to leave.
When the system is armed to ”ST AY” this will be the entry time to deactivate the alarm system.
If enabled, the area can be armed in away mode with a single press. When area is armed via quick away mode, the closing user number is the default user of 999.
If enabled, this will allow the stay mode to be disarmed by pressing the stay key on the Côr panel. If the sys­tem is in alarm a PIN must be used.
If enabled, the area can be armed even if sensors are not ready. Any sensors that are not ready will NOT be auto­matically be bypassed and may cause an alarm condi­tion because they could still be in a not ready state once the area becomes armed. This option is overridden if the Force Arm With Auto− Bypass is enabled. Individual sensors can be made “force arm−able without auto−bypass” by leaving this area option off, then en­abling Forced Arm Enable in Sensor options, and dis­abling Sensor Inhibit (Bypass) in the Sensor Type Pro­file.
This account number is ONLY used when sending an email with a professionally monitored security alarm company. This should be the same as the Central Station account number, however if it is not this will not affect the Central Station reporting.
If enabled, the area can be armed even if sensors are not ready. Any sensors that are not ready will NOT be auto­matically be bypassed and may cause an alarm condi­tion because they could still be in a not ready state once the area becomes armed. This option is overridden if the Force Arm With Auto− Bypass is enabled. Individual sensors can be made “force arm−able without auto−bypass” by leaving this area option off, then en­abling Forced Arm Enable in Sensor options, and dis­abling Sensor Inhibit (Bypass) in the Sensor Type Pro­file.
When you are finished program­ming the Area settings, remember to save your changes.
.C.
38
..
Page 39
4.4 Programming the System
Select System from the drop down menu.
When the System screen is selected you can program several system wide settings, including the system clock and timers, as well as sensor options and reporting.
When you are finished programming the System settings, remember to save your changes.
Explanations of the System configurations appear on the following pages.
Also reference Advanced Programming, System, Section 5.1.
.C
39
..
.I
Page 40
System
Configuration
Menu
Date & Time
Time Zone
Daylight
Saving Time
System
Timers
Option Default Function
Date
Time (hh:mm:ss)
Hours Offset UTC 5ET Minutes Offset 0 This is used in other locations throughout the world.
Start Month Mar Standard Start W eek Second Standard End Month Nov Standard Start Month First Standard
Siren Time (0−99) Minutes 4
Battery T est Time (0− 99) Minutes 2
AC Failure Report Delay (0−999) Seconds
Cross Zone Time (30− 999) 300
Sensor Inactivity Time (0−65535) Minutes
300
0
Once it is connected to Côr the Date and time are automatically synced.
Once it is connected to Côr the Date and time are automatically synced.
Starting with EST is UTC−5, CST is UTC−6, MT is UTC−6, PST is UTC−7.
The siren time sets the time in minutes that the siren output is active.
The battery test time sets the duration in minutes that the Côr will perform a dynamic battery test. The Côr will perform a dynamic battery test at the disarming of the first area or at midnight once each 24−hour cycle. Dynamic battery test is disabled when the test duration is set to 0. Dynamic battery test can also be run manually from a keypad.
The AC fail report delay sets the duration in seconds that the AC power is lost or restored before a com­munication is initiated. AC restore will report when power is maintained for this same duration.
The Cross Zone time sets the duration in seconds whereby two or more sensors must trip before an alarm condition will be registered or the one sensor must trigger twice within this time period, or a con­tinuous trip longer than 10 seconds. This feature only applies to sensors with the Cross Zone feature set in sensor options.
Sensors programmed with Sensor Inactivity in the Sensor Options must be opened and closed within the time programmed here (in minutes). If they do not, a Sensor Inactivity will report. This feature can be enabled in the System Options menu. Default Sensor Inactivity option is off and this timer is set to 10080 minutes (7 days).
.C.
40
..
Page 41
System
Configuration
Menu
System
Timers
System
Options
System
Reporting
Option Default Function
This applies only to wireless sensors programmed as fire type. Sensors send a reduced packet count su­pervisory signal every 60 minutes (check your sen-
Fire Supervise Time (120−65535) Seconds
Burg Supervise Time (120−65535) 14400
Panel Sensor Doubling Off
Panel Box Tamper Off
System Sensor Tamper Off
Disable Hardwire Sensors On
Sensor Inactivity Off
System Channel
14400
1 Channel
Group
sor manual for most up to date details). If no super­visory signal is received by the panel within the time specified here then the sensor will be reported as missing. When set to 0 the default of 14,400 sec­onds (4 hours) will be used. Check your local regu­lations for the correct value to use.
This applies only to wireless sensors programmed as non−fire type. Sensors send a reduced packet count supervisory signal every 60 minutes (check your sensor manual for most up to date details). If no supervisory signal is received by the panel within the time specified here then the sensor will be re­ported as missing. When set to 0 the default of 43,200 seconds (12 hours) will be used. Check your local regulations for the correct value to use.
If enabled, the two (2) hardwired sensor inputs will be doubled to support four (4) sensors. The termi­nals for Sensor 1 will represent sensors 1 and 3, and the terminals for sensor 2 will represent sensor 2 and
4. This option cannot be selected for sensors other than the two sensors on the main panel. This option cannot be used in conjunction with the DEOL op­tion.
The Côr panel has a built−in normally closed tam­per switch that will sound the siren if the panel is removed from the wall. This option will enable or disable this tamper switch.
If enabled, the Côr panel will monitor all sensors, except fire sensors, for Dual End of Line (DEOL). A short or open circuit on a DEOL will activate sen­sor tamper alarms. This feature cannot be used if Panel Sensor Doubling is enabled.
If enabled, the Côr panel will disable all hard­wired sensor inputs.
If enabled, the Côr system will monitor each sen­sor for activations. If no activations occur within the sensor activity time then a failed sensor activity re­port may be reported via the selected communica­tion channel and a failed sensor activity message set in the Côr event log. For a sensor to be eligible for activity monitoring, it must have “Sensor Activi­ty” set in sensor options. Sensors programmed with Sensor Inactivity in the Sensor Options must be open and closed within the time programmed here (in minutes). If they do not, a Sensor Inactivity will report.
The Channel Group that the Côr will send system events to.
.C
41
..
.I
Page 42
4.5 Programming Channels
Select Channels from the drop down menu.
With the Channels screen selected you can program a communication path for events to be sent from the Côr panel to a selected destination.
The Côr panel can support a total of 16 channels; each channel is identified by a unique channel number, which cannot be altered, and remains as the key reference for each channel.
Choose a channel in the drop down menu and assign it attributes. Explanations of the Channel Configuration menu appear on the following page. If homeowner wants to get email notifications, select email
from the options and enter their email address.
Also reference Advanced Programming, Channels
When you are finished programming the Channel settings, remember to save your changes.
.C.
, Section 5.4.
42
..
Page 43
Channel
Configuration
Menu
Option Default Function
Select Channel to Configure 1 Central Station Primary Channel Name Central Station Primary Custom names of the selected channel can be created here.
This is the Account Number that will be reported with the
Account Number Blank
Format UltraSync
Desk Phone or Email Blank The phone number or email address of the selected destination.
Central Station Backup 1 Central Station Backup 2
Next Channel
Event List 1 Event List
Attempts 2
Email 1 Email 2 Email 3
Etc.
event in email reports. When UltraSync format is selected, this field will not be used.
This is the communication format for the selected channel. Select from: UltraSync Email
If the channel selected is unable to deliver the event to the selected destination, Côr will use this backup channel if the primary channel fails. The Next Channel specified here must be greater than the Channel Number.
Select the pre−programmed list of events that will be sent via this channel. The specific event in each event list is pro­grammed in Advanced Programming, Channels. See Channels Programming Event List.
Enter the number of times Côr should try to send the events to the UltraSync server. After the number of attempts has been exhausted the Côr will try the Next Channel if specified.
.C
43
..
.I
Page 44
4.6 Programming the Network
Select Network from the drop down menu.
Enter your network settings on this page.
Explanations of the Network configuration menu appear on the following pages. Remember to save your changes when you are finished
programming the Network setting.
.C.
44
..
Page 45
Network
Configuration
Menu
Option Default Function
LAN Configuration
IP Host Name −
Enable DHCP Off
Primary DNS −
Secondary DNS −
Wi Fi Configuration
Wi Fi Security type Blank WEP/WEP−128bit/WPA2−Passphrase
Wi Fi Password Blank
Remote Access PINS
WEB Access Passcode 0
Download Access Code 0
Automation User Name Blank Used when there is API integration.
Automation PIN Blank Used when there is API integration.
Options
A text label assigned to the Côr communicator so you do not have to remember the IP Address. Note: This only works on local LAN and with Microsoft Win­dows PC, or an Apple device with the .local extension. Does not work remotely over the internet.
Allows the Côr panel to be automatically assigned an IP address by the network.
The IP address assigned to the Côr which enables it to con-
IP Address −
Gateway −
Subnet −
Wi Fi SSID Blank Wi Fi Network name the Côr panel is connecting to.
Enable Ping On Allows the Côr panel to respond to the PING command.
nect to the local LAN. This will allow you to access the em­bedded web server from the Côr panel to program and view the status of the system. It is also used for alarm reporting.
If required, the IP address of the router which is needed when remote IP communications are used.
The subnet mask for the network. For example, 255.255.255.0 is the network mask for 192.168.1.0/24
The IP address of the Primary Domain Name Server. The DNS is used to translate host names for time servers and UltraSync servers.
The IP address of the Secondary Domain Name Server, used if the Primary DNS is not available.
Network password, which must match the password assigned to the WIFI SSID (access point). There can be no special char­terers, only Alphanumeric
The Côr app requires the W eb Access Code to get access to the panel. The default Web Access Passcode of 00000000 disables remote access. The system allows for an 8 digit nu­meric (only) code. Each owner should have a unique number.
Enables remote access for DLX900. The default Download Access Passcode of 00000000 prevents remote access.
.C
45
..
.I
Page 46
Network
Configuration
Menu
Option Default Function
Enable Ultraconnect (UltraSync) On
Monitor LAN Off
Always Allow DLX900 On
Enable Web Programming On
This is an automatic feature of Côr. It is recommended you leave this setting on. Enable this option to allow Côr to send email reports via the UltraSync servers. This is independent of the W eb Access Pass­code which when set to 00000000 will prevent the Côr app from connecting. If any channel is set to Email format reporting, then Côr will override ignore this setting and allow email reporting via Ultra­Sync cloud servers. If you wish to prevent connections of Côr to the UltraSynccloud servers, then uncheck this option and do not use the UltraSync reporting format. Also reference Communicator.
When the Monitor LAN option is enabled the panel will monitor the Ethernet port for a valid Ethernet cable. If the Ethernet cable is disconnected while this option is enabled and the panel is unable to communicate, it will log a Fail T o Communicate event.
Enabling this option will allow DLX900 to connect at any time if the correct Download Access Code is provided. Disabling this option provides greater security by only allowing DLX900 to connect when program mode is active. This allows the system to have DLX900 access disabled until a user on site with physical access to the keypad enters program mode with a valid PIN code. Côr will be in program mode if a user gains authorized access to menu 5, 8, or 9 on the keypad.
Enabling this option will allow Côr Web Server and app to al­ways display Installer menus regardless if the panel is in program mode or not. Disabling this option will hide the Installer menus on Côr Web Server and app unless program mode is active. This provides greater security by keeping web programming disabled unless a user on site with physical access to the keypad enters program mode with a valid PIN code. Côrwill be in program mode if a user gains access to menu 5, 8, or 9. Côr app requires a Web Access Code other than 00000000 to get access to the panel.
table in submenu 16 of Advanced Programming,
.C.
46
..
Page 47
4.7 Programming Scenes
Select Scenes from the drop down menu.
With the Scenes screen selected you can create scenes on schedules and determine which event types and device triggers will activate them.
Each scene can trigger up to 16 consecutive scene actions when certain conditions are met. This can save users time by automatically running multiple actions. A scene can be triggered manually, through a schedule, or via a system event.
Remember to save your changes when you are finished programming the Scene settings.
Explanations of the Scene Configuration Menu appear on the following pages.
Also reference Advanced Programming, Scenes
, Section 5.18.
.C
47
..
.I
Page 48
Settings Selector
Automations (Scenes)
Save
Select Scene to Congure:
3 Scene
Scene Name
Scene Trigger
When Should Scene Work
Always On
Scene Trigger Type
disabled
Activate Sensor
Device
disabled
Scene Result 1
Device
disabled
Scene Result 2
Device
Example Scene
1. Enter a Scene Name.
2. Select the Scene to Configure drop down menu to restrict when the scene will be enabled
3. Select the event that will trigger recording a video clip using the Scene Trigger drop down menu.
4. Select the Activate Sensor/Area/User/Action if applicable.
5. Select Device (1) Alarm System. This enables another drop down menu for Action Type. Choose the Action Type “Trigger Camera
Video Clip”, then the camera you wish to record a video clip when the event is triggered.
Action Type
Trigger Camera Video Clip
1 Front door
2 Indoor 3 Camera
Scene Result 1
(1) Alarm System
A160068
6. Press Save.
.C.
48
..
Page 49
Scene
r
r
Configuration
Menu
Option Default Function
Select scene to Configure
When should scene work Always On
Scene Trigge
Scene Trigger Type Disable
Activate Sensor Disabled
Scene Name
Scene Action 1
Action Device
Scene Action 1
Action Device
Scene Action 2
Action Device
Scene Action 3
Action Device
Scene Action 4
Action Device
Scene Action 5
Action Device
Scene Action 6
Action Device
Etc. Etc. Etc. Etc.
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
The Côr can support a total of 16 Scenes. Each Scene is identified by a unique number, which cannot be altered, and remains the key reference for each Scene.
Each Scene can be configured with a custom 32 character name. The name is displayed wherever a Scene is refer­enced on the Côr system.
Select the Schedule that controls when this Scene is active. If the current date and time is outside of the selected sched­ule, then the Scene will not run.
Select the event that will trigger this Scene. You can refer­ence Activate Events list in Advanced Programming,
Scenes.
Select which Area \ Sensor \ Schedule \ User \ Action \ Device will provide the trigger for the Scene.
Each scene can perform up to 16 Scene Actions. These are simplified actions that allow you to control devices on you system. There are two types of Scene Action
1. Alarm System Action
2. Z−Wave Device Action.
Alarm System Action Result T ype − The event of the Action Result to perform.
See Advanced Programming, Scenes and the Scene Action and Scene Action Events T ypes Result Number − Select the area / scene / camera number to control:
Z−Wave Device Action
To display Z−Wave Action Types you must first learn in a Z−Wave device. The Z−Wave device name will then ap­pear. Action Device – select the Z−W ave device you want to control Z−Wave Type 8 Setting 1 – depends on Z−Wave device. May include options such as On, Off, Heat, Cool, Auto, Up, Down, Lock, Unlock.
for reference.
.C
49
..
.I
Page 50
4.8 Programming Schedules
Select Schedules from the drop down menu.
With the Schedules screen selected you can create up to 16 schedules, each having four time and day periods.
Explanations of the Schedules Configuration menus appear on the following pages. Also reference Advanced Programming, Schedules, Section 5.6.
Remember to save your changes when you are finished programming the Schedules settings.
.C.
50
..
Page 51
Schedules
Configuration
Menu
Time and
Days 1−16
Option Default Function
The Côr can support a total of 16 schedules. Each
Select Schedule to Configure 1 Schedule 1
Schedule Name Schedule 1
Up to 16 Start and Stop times can be created. NOTE: Côr handles schedules that span midnight automatically.
Start Time (hh:mm) − Enter in the start time End Time (hh:mm) − Enter in the stop time Monday − Tuesday − Wednesday − Thursday − Friday − Saturday − Sunday −
Holiday 1 −
Holiday 2 − Same as Holiday 1 Holiday 3 − Same as Holiday 1 Holiday 4 − Same as Holiday 1
schedule is identified by a unique schedule number, which cannot be altered, and remains as the key ref­erence for each schedule.
Each schedule can be configured with a custom 32 character name. The area name is displayed wherev­er a schedule is referenced on the Côr system.
Enter in the days of the week the schedule is to be active
Enter in the holiday that this schedule will be fol­lowing. NOTE:When the holiday is enabled the schedule will not be active.
.C
51
..
.I
Page 52
4.9 Programming Holidays
#
Select Holidays from the drop down menu.
With the Holidays screen selected you can create up to four sets of holiday dates for Côr. Set the number, name and date range for each holiday. Holidays are then assigned to the schedules and used to deactivate the schedule while the holiday is active. Remember to save your changes when you are finished programming the Holidays settings.
Explanations of the Holiday configurations appear below. Also reference Advanced Programming, Holidays, Section 5.13.
Holiday
Configuration
Menu
Holiday
Start − End
Option Default Function
Côr supports up to 4 sets of holiday dates, each
Select Holiday
List to Configure
1 Holiday 2 Holiday 3 Holiday 4 Holiday
Holiday Name
Start Date n/a End Date n/a
n/a
n/a
set can have up to 16 date ranges. Holidays are used as part of Schedules to control access to the system on specified dates.
The Côr panel can support a total of 4 Holiday Sets. Each set is identified by a unique number, which cannot be altered, and remains as the key ref­erence for each area.
Each holiday can be configured with a custom 32 character name. The name is displayed wherever a Holiday is referenced on the Côr system.
Select the date range for the Holiday by specifying the start and stop date. A total of 16 ranges can be entered for each Holiday.
.C.
52
..
Page 53
Example Holiday List
Holiday 1 US Holiday List 2016 Date Range 1 − 01/01/2016 01/01/2016 New Year’s Day Friday, January 1 Date Range 2 − 30/05/2016 30/05/2016 Memorial Day Monday, May 30 Date Range 3 − 04/07/2016 04/07/2016 Independence Day Monday, July 4 Date Range 4 − 05/09/2016 05/09/2016 Labor Day Monday, September 5 Date Range 5 − 24/11/2016 24/11/2016 Thanksgiving Day Thursday, November 24 Date Range 6 − 26/12/2016 26/12/2016 Christmas Day (observed) Monday, December 26** Date Range 7 − Date Range 8 − Date Range 9 − Date Range 10 − Date Range 11 − Date Range 12 − Date Range 13 − Date Range 14 − Date Range 15 − Date Range 16 −
An office is not staffed during a public holiday and you want to prevent access to the building from staff on this date. First program the holiday dates in this section under “Holiday 1”, then go to Schedules and check “Holidays 1”, then assign that schedule to the User.
.C
53
..
.I
Page 54
4.10 Programming Z−Wave Devices
See the Z−Wave Configuration Menu later in this section.
Also reference Advanced Programming, Devices
, section 5.9.
Z−Wave Room Names
Select Z−Wave Room Names from the drop down menu.
From the drop down menu under Z−Wave Room Editor select a room to edit the name.
For this example we will change the name of Room 1 to Living Room. Type Living room in the form “Edit Room Name”. This can be a 32 character name. Press Save. The notification box will alert you that the Room Name is Saved. The drop down list has been updated for Room 1.
Z-Wave Room Editor
Z-Wave Room Editor
Z-Wave Room Editor
Z-Wave Room Editor
A160050
Add a Z−Wave Device
Select Z − Wave Add/Remove from the drop down menu.
1. Press Add
2. Initiate ADD mode on Z−Wave device. See your Z−Wave device’s manual for instructions. The notification box will alert you that the Device is added.
NOTE: If a Z−Wave device has been added before or to another system, you must first remove it before adding it to this system. To do this, press Remove, then activate LINK or REMOVE mode on the device.
3. Press Rooms.
4. Check that you can see the device you just added. Press a button such as ON or OFF to verify that you can control the device.
.C.
54
..
Page 55
Z-Wave Device Selector
Z−Wave Device Association
Select Z−Wave Device Association from the drop down menu.
Z-Wave Device Selector
A160051
Z−Wave Maintenance
Select Z −Wave Maintenance from the drop down menu. The Z−Wave Maintenance page main tile contains additional buttons from the settings tile.
Failed Device Functions: REPLACE: This option is used when a Z−Wave device is defective, and it allows the replacement of the device while keeping the same
Device number. The device number is what is used in Scenes association.
REMOVE: This option is used when a Z−Wave device is missing or is damaged to the point that it will not transmit signals. BACKUP: This saves the Z−Wave programming to the Côr panel. RESTORE: This restores the Z−Wave programming to the last time is was saved. RESET: This defaults all the Z−Wave programming in the Côr panel.
.C
55
..
.I
Page 56
Z-Wave Maintenance
Z-Wave
Configuration
Menus
Room Names
Device Selector
Device Association
Maintenance
A160052
Option Default Function
Z-Wave Room Editor Drop down to select room to edit Room Selection
Edit Room Name Room 1 Room Naming (up to 32 characters)
Device Room Location Drop down to select the room location
Device Name (1) Alarm
Check For High Power Add Option On
Association Functions
Add
Remove
Query
Association Selector Drop down list of all devices learned into the system.
Association Group
Failed Device Functions
Replace
Remove
Cancel
Network Maintenance Functions
Backup
Restore
Reset
Failed Device Selector Drop down list of all the failed devices.
.C.
56
..
Page 57
4.11 Programming Camera
Côr supports selected IP cameras. Contact your supplier for the correct model(s).
Use the installation steps below to add supported IP camera to the Côr Home Automation system. Once the camera has been connected to the same network as the Côr panel, proceed with adding the camera to the Côr panel in Step 9.
Also reference Camera Setup Instructions in Section 8.
Step 1
If you do not have truVision Device Manager, you will need to have the configuration program* installed on your laptop computer before you can begin. Included in the camera packaging is a small CD that you can use to install the program on your laptop computer.
The latest version sofware program can also be located at the Software section under the Downloads tab.
http://www.interlogix.com/video/product/truvision−device−manager in
T o begin installing the program, launch the Application file* and follow the steps in the Setup Wizard. Make sure to also install the WinPCap software that is part of the installation setup package.
*PC version only at this time.
Step 2
Power up the camera using the transformer power supply included in the camera packaging. Note that the camera may take 1−2 minutes to boot up once it receives power.
Step 3
Connect an Ethernet cable from a Wi Fi Router to the Ethernet RJ45 PoE port on the camera.
Step 4
From your laptop computer, open the Wireless Network setting and connect to the Router network. Locate and launch the truVision Device Manager icon on your laptop computer.
.C
57
..
.I
Page 58
The program will list cameras that are visible on the network.
Select the camera from the list that matches the Device Serial No. displayed on the screen to the serial number of the camera. The serial number can be located on the label of the camera box and is represented by a 9 digit number i.e. 539472371
Once you have selected the camera, the parameters of that camera will be displayed in the fields to the right of the screen. Write down the IPv4 Address and MAC Address associated with the camera.
Step 5
Launch the web browser using the connected Router network and type the IPv4 Address of the camera in the address field and hit Enter.
.C.
58
..
Page 59
Login into the truVision IP Camera web browser using the following credentials: User Name: admin (Case Sensitive) Password: 1234
Step 6
Once logged into the web portal, click the Configuration tab on the top tab.
Step 7
From the Configuration menu folders listed to the left of the screen, select Network. Then select the Wi Fi tab in the Network folder.
.C
59
..
.I
Page 60
Step 8
Locate and click the name of the Wi−Fi network that you wish to use from the Wireless List.
T ype the password for the Wi−Fi network that you selected in the Key 1 field box.
Press the Save button on the bottom right of the screen after you enter the Wi−Fi password.
Step 9
Login to the Côr Web Server from your laptop computer using the IP address announced from the Côr panel (Menu – 8 – [Installer PIN] – Enter – 6).
Once logged on the Côr Web Server, select Cameras from the drop down list in the Settings menu.
In the camera section, assign a name to the camera in the Camera Name field and type in the IPv4 Address and MAC Address noted from Step 4 in the respective fields.
Press Save after you have entered all the information.
.C.
60
..
Page 61
Step 10
Verify the camera is connected to the Côr Home Automation system by going to the Homeowner Côr App and pressing the camera icon
at the bottom of the menu bar to access the Wi−Fi cameras. Pressing the Play icon in the center picture of the video will allow you to
view live video streams from the camera.
You are now connected to the network via Wi−Fi!
.C
61
..
.I
Page 62
Camera Menu
Option Default Function
Scan for new cameras. -
Camera Configuration
Camera Name drop down (all cameras)
Camera Configuration
IP Address
MAC Address
Finds cameras added to the same IP network as Côr .
This name can be up to 32 characters. Make sure the name matches the name you have set up in the camera app.
Notification IP address assigned to the camera by the premises network.
MAC address assigned to the camera by the premises network.
.C.
62
..
Page 63
4.12 Check Event History
Côr allows you to check the history of events that have occurred in the system. Press History and this menu will appear:
Navigate to events recorded in the system with the arrow buttons. You can select the date for finding events and use the Event Filter dropdown menus to select among alarm events or video events. The system stores 1024 alarm events and 1024 video events. The display shows 10 events at a time.
.C
63
..
.I
Page 64
4.13 Check Connection Status
e
t
s
s
Select Connection Status from the drop down menu.
Also reference Advanced Programming, System, Section 5.1.
Connections Option Function
Connection Status
Not Linked, Configuring, Connected (Côr connection status)
1. Getting Details 6. Configuring Protocol
2. Configuring Modem 7. Getting Echo
3. Modem Connected 8. Connected
4. Configuring PPP 9. Terminating
5. Authenticating 10. Idle
1. Idle 5. Retry Delay
2. Selecting Service 6. Getting Server Hello
3. Making Connection 7. Connected
4. Disconnecting
WPA2 + AES WPA + AES WPA + TKIP/AES WPA + TKIP WEP
Connection Status Menu
LAN Status
LAN Media Wi Fi, Ethernet (method of Côrconnection)
Cell Stat
Ultra Connec
(UltraSync) Statu
UltraConnect
(UltraSync) Media
Radio Details
Cell Service No Service, Restricted Service, Valid Service
Signal Strength −113 to −51
Operator ID
Radio Technology GSM, UMTS
WI FI Details
WI FI SSID
WI FI Security T ype
Notification − Diagnostic
Wireless, LAN
4.14 Check Details
Select Details from the drop down menu.
Device Details Details
Control Name Device UID (Serial) Serial number of the Côr panel Ethernet MAC Address Ethernet MAC address assigned to the Côr panel by the premises network WI FI Mac Address WI FI MAC address assigned to the Côr panel by the premises network Control Model
Detail Statu
.C.
Firmware Version Hardware Version Bootloader Voice Version W ebsite Version Memory Map Version Menu String Version
of the Côr panel
64
..
Page 65
5 ADVANCED INSTALLATION USING WEB SERVER
Advanced settings are only accessible via the Côr Web Server from your computer using the IP address announced by pressing Menu 8− [Installer PIN] − 6, UltraSync app, or DLX900.
After loging into the Côr Web Server, press the Menu button then select Advanced from the drop down list.
You are on the
The Configuration Service page main tile contains different buttons than the settings tile.
BACK: Moves you back to the main selection. UP: Moves you up one option through the programming options. DOWN: Moves you down one option through the programming options.
ALL ON / ALL OFF: Allow you to select or deselect all the check boxes in menus like below.
page.
.C
65
..
.I
Page 66
5.1 Advanced Programming, System
Select System from the menu.
System Options is used to configure system wide options, such as time and dates, system timers and maintenance.
.C.
66
..
Page 67
System Clock
System Submenus
1 System Clock 2 Clock Date and Time
When connected to an IP network the Côr system clock synchronizes its time and date automatically with an Internet Time Server if configured in Advanced Programming, Communicator.
The Côr system clock can manage day, time, time sensor, and day light saving time settings to ensure ongoing accurate time.
3 Time Zone Hours Offset / Minutes Offset 4 Daylight Saving Time
Start Of DLST – Month 1 to 12 of year; Week of month 1 to 4 and last End Of DLST– Month 1 to 12 of year; Week of month 1 to 4 and last
.C
67
..
.I
Page 68
System General Options
1 General Options
Option Default Function
If enabled, the two (2) hardwired sensor inputs will be double to support four (4) sensors. The terminals for Sen sor 1 will represent sensors 1 and 3, and the terminals for
Panel Sensor Doubling Off
Panel Box Tamper Off
System Sensor Tamper Off
Enable Celsius Off Enable Celsius vs. Fahrenheit Scale.
Disable Hardwire Sensors On
Strobe on Away Off
System Alarm Latch On
Sensor Inactivity Off
sensor 2 will represent sensor 2 and 4. This option can not be selected for sensors other than the two sensors on the main panel. This option cannot be used in conjunc tion with the DEOL option.
The Côr panel has a built-in normally closed tamper switch that will sound the siren if the panel is removed from the wall. This option will enable or disable this tam per switch.
If enabled, the Côr panel will monitor all sensors, ex cept fire sensors, for Dual End of Line (DEOL). A short or open circuit on a DEOL will activate sensor tamper alarms. This feature cannot be used if Panel Sensor Dou bling is enabled.
If enabled, the Côr panel will disable all hardwired sen sor inputs. To utilize the hardwired sensors on the back of panel you must disable this feature.
If enabled, the system strobe will flash when an area is set in away mode. The strobe outputs must be config ured follow the area alarm event condition. The strobe is not activated on Disarm or Stay.
If enabled, system alarms such as tampers, low battery, A/C fail and trouble requires a user with “Reset System Alarms” enabled in their current Permission Options to reset the alarm condition. If disabled, system alarms do not latch and can be reset when a user arms or disarms an area.
If enabled, the Côr system will monitor each sensor for activations. If no activations occur within the sensor activ ity time then a failed sensor activity report may be report ed via the selected communication channel and a failed sensor activity message set in the Côr event log. For a sensor to be eligible for activity monitoring, it must have “Sensor Activity” set in sensor options. Sensors programmed with Sensor Inactivity in the Sensor Options must be open and closed within the time pro grammed here (in minutes). If they do not, a Sensor Inac tivity will report.
.C.
68
..
Page 69
System Timers
1 System Timers
Option Default Function
Siren Time (0-99) Minutes 4
Strobe Time (0-99) Hours 3
Battery Test Time (0-99) Minutes
AC Failure Report Delay (0-999) Seconds
Cross Zone Time (30-999) 300
Report Delay (15-45) Seconds
2
300
30
The siren time sets the time in minutes that the siren out put is active
The strobe time is the duration in hours that output pro grammed to follow the strobe time will activate. The valid time selection in this segment is 0 to 99 hours, where ‘0’ disables the Strobe Output.
The dynamic battery test time sets the duration in min utes that the Côr will perform a dynamic battery test. The Côrwill perform a dynamic battery test at the dis arming of the first area or at midnight once each 24-hour cycle. Dynamic battery test is disabled when the test duration is set to 0. Dynamic battery test can also be run manually from a keypad.
The AC fail report delay sets the duration in seconds that the AC power is lost or restored before a communication is initiated. AC restore will report when power is maintained for this same duration.
The Cross Zone Time sets the duration in seconds whereby two or more sensors must trip before an alarm condition will be registered or the one sensor must trig ger twice within this time period, or a continuous trip longer than 10 seconds. This feature only applies to sen sors with the Cross Zone feature set in sensor options.
The report delay is the duration in seconds that non-24 hour and non-fire type sensors will delay before report ing. This provides a valid user the opportunity to reset an unintended alarm condition before that event is reported
.C
69
..
.I
Page 70
Option Default Function
Holdup Delay (0-999) Seconds
Fire Verify Delay (0,120-255) Seconds
The holdup delay is the duration in second that a holdup delay sensor type will wait before it activates. If additional holdup activations occur during the holdup delay period then the holdup delay will immediately expire and set the
0
holdup alarm. If a holdup delay sensor type is de-acti vated during the holdup delay period then the holdup alarm will reset and not activate.
The fire alarm verification feature is designed to reduce false alarms reported by smoke detectors. The Côr will wait 40 seconds to allow the smoke sensor to power up and settle. If a second trip occurs after this but before the end of the Fire Verify Delay time, a fire
120
alarm will be generated. If no restoral is received after the first trip, a fire alarm will also be generated. The valid time selection in this segment is 120 to 255 seconds. The communicator will delay for a specified time before re porting the fire alarm
System Timers
Sensor Inactivity Time (0-65535) Minutes
Fire Supervise Time (120-65535) Seconds
Burg Supervise Time (120-65535) Seconds
0
14400
14400
Sensors programmed with Sensor Inactivity in the Sensor Options must be open and closed within the time pro grammed here (in minutes). If they do not, a Sensor Inac tivity will report. This feature can be enabled in “System Options”. See Section4.4. Default Sensor Inactivity option is off and this timer is set to 10080 minutes (7 days).
This applies only to wireless sensors programmed as fire type. Sensors send a reduced packet count supervisory signal every 60 minutes (check your sensor manual for most up to date details). If no supervisory signal is re ceived by the panel within the time specified here then the sensor will be reported as missing. When set to 0 the default of 14,400 seconds (4 hours) will be used. Check your local regulations for the correct val ue to use.
This applies only to wireless sensors programmed as non-fire type. Sensors send a reduced packet count supervisory signal every 60 minutes (check your sensor manual for most up to date details). If no supervisory signal is received by the panel within the time specified here then the sensor will be reported as missing. When set to 0 the default of 43,200 seconds (12 hours) will be used. Check your local regulations for the correct value to use.
.C.
70
..
Page 71
System Siren Options
1 Siren Options
Siren Once Per Sensor
Siren At System Away/Dis arm
Siren At End Of Exit
Siren At Arm Report
If enabled, the Côr panel will only activate the siren once per sensor in a given arm cycle and will not activate the siren again even if that siren time expires and that sensor reactivates. Every sensor will have one siren acti vation attempt before that sensor cannot reactivate the siren. If this option is not enabled, at the expiry of the siren time any sensor can reactivate the siren an unlimit ed number of times.
If enabled, the Côr panel will activate the built-in siren briefly each time the last area in the system is set in away mode or when the first area is disarmed. To enable this function by area, leave this option disabled in this sec tion, and enable the “Siren at System Away/Disarm” in section 5.3 you require.
If enabled, the Côr panel will activate the built-in siren briefly each time the system is set in away mode and the exit delay expires.
If enabled, the Côr panel will activate the built-in siren briefly every time the system is set in away mode, the exit delay expires and a successful system arm report is com pleted.
Advanced Programming, Areas for the area(s)
.C
71
..
.I
Page 72
System Service and
Test Options
1 Service and Test Options 2. Email Intervals
If enabled, Côr will report a system status email via one or more email channels. The number entered for Status Email Interval is the number of days between status re ports. For example entering a 7 will cause a report to be sent every 7 days. The interval starts from either the first time a program interval is entered or when the system is powered up.
3 Email Time 4 Service Phone Number
The status email time sets the time of day that the status email will report. This is set as 24-hour time in hours and minutes.
When a system condition needs repair, this number will be announced to the end-user. Typically this is the in stallation company.
.C.
72
..
Page 73
1 Status 2. LAN Status
This menu provides diagnostic information on the connection status of the xGen.
3 LAN Media 4 Cell State
System Service and
Test Options
5 UltraConnect Status (UltraSync) 6 UltraConnect Media (UltraSync)
Status of the connection to the cloud servers.
7 Cell Service 8 Signal Strength
When connected to the cellular radio net work this will display what level of service is provided. If the optional radio module is installed with a valid SIM card, and this shows restricted service, please contact your service provider as your SIM card may not be provisioned correctly.
If the optional radio module is installed with a valid SIM card, this will show the numeric signal level. If the reported value is -113 to -89 then installing an external antenna is recommended. If the reported value is -89 to -51 then the signal strength is OK.
.C
73
..
.I
Page 74
System Status
9 Operator ID 10 Radio Technology
System Counts
If the optional radio module is connected to the network this will display the ID of the network operator
1 Counts
Swinger Shutdown is a false alarm prevention feature prevents a single sensor from activating more than a programmed number of times during a single arming period. After a certain number of alarms caused by the same sensor within the same arming period, the Côr will then shutdown that sensor for the re mainder of that arming period. The sensor will be reactivated when the system is disarmed or rearmed to any security mode. See SIA CP-01-2010 Programmable Features
1 Automation Menu 2 Automation User Name
If the optional radio module is connected to the network this will display the connection technology such as GSM or UMTS.
Table for reference.
System Automation
Menu
Used when there is API integration.
3 Automation Pin
Used when there is API integration.
.C.
74
..
Page 75
5.2 Advanced Programming, Sensors
From the Advanced drop down list, select Sensors from the menu.
A sensor (sometime referred to as a zone or input) is a single physical hardwired connection or a non−physical wireless connection. Additionally sensors on the Côr system can be used as logic inputs within actions and / or be configured as one of many sensor types. See
Advanced Programming, Actions.
IMPORTANT: After you have finished programming a sensor, be sure to advance the sensor number in the drop down menu when programming the next sensor. Otherwise you will over−write the sensor configuration you just programmed.
Sensor Submenus
1 Sensor Number 2 Sensor Name
Each sensor can be configured with a custom 32 charac ter name. The sensor name is displayed wherever a sen sor is referenced on the Côrsystem.
3. First Sensor Profile
Sensor Submenus
The Côr panel can support a total of 64 sensors. Each sensor is identified by a unique sensor number, which cannot be altered, and remains as the key reference for each sensor.
Sensor profiles determine the sensor type (Entry, 24 hour, fire, key switch, etc.) and the sensor options (bypass, force arm, twin trip, stay mode, etc.). Sensor profiles also determine the area in which the sensor resides in. Addi tionally, each profile has a schedule that Côr uses to determine which of the two sensor profiles to use and when to use them.
.C
75
..
.I
Page 76
Sensor Submenus
4 Sensor Type
One of 32 configurable sensor types may be allocated to any sensor’s sensor type. Each sensor type can behave independently between an arm and disarmed state. Sensor types determine the sensor attributes, siren attributes, and sensor attribute options.
Here is an example of a preset sensor type:
Sensor Type – 1 – Day Sensor
.C.
76
..
Page 77
5 Sensor Options 6 Area Group (1-16)
One of 16 configurable area groups can be allocated to any sensor’s area group. Area groups are a list of Côr areas. When an area group is allocated to a sensor, that sensor will then belong to all the areas in the area group. If a sensor is assigned to multiple areas it will not arm until the last area is armed. It will also be disarmed when the first area is disarmed. Ensure the correct Area Group is assigned to a sensor. If an area Group with no areas is used, then the sensor will never report.
7 Schedule Number
Sensor Submenus
One of 32 configurable sensor options may be allocated to any sensor’s sensor op tions. Sensor options determine the sensor attributes such as a sensor’s ability to be bypassed, force arm, cross zone, stay mode, etc. Additionally sensor options de termine the sensor’s reporting attributes.
One of 16 configurable schedules can be allocated to any sensor’s schedule number. Sensor profile schedules determine when to allocate a sensor profile to a sensor. The first sensor profile has the highest priority and the second sensor profile has the low est priority. The panel will check if the current time and day fall within the schedule of the first sen sor profile or if the schedule is disabled (thus always active). If the schedule is ac tive then that profile is applied to that sen sor. If the first sensor profile’s schedule is not active then it will check the second sensor profile. If the schedule is active then that profile is applied to that sensor.
.C
77
..
.I
Page 78
8 User Number
The sensor user number feature is used whenever the sensor type is set to “keyswitch”. Instructions for users configuration are in Section 6 – Users and Permissions. One of 40 configurable users can be allocat ed to any sensor’s user number. Côrsensor profile user number is a powerful feature that is used to ap ply the selected user’s attributes to a keyswitch operation. When the keyswitch sensor is activated, Côr will check the user permissions and permission schedules to determine which areas are accessible. Addi tionally, area open and close reports will also report the user number selected in this option
NOTE: If the user number is programmed to 0, the Côr will use a default User number of 999 and will operate on all areas in the sensors area group.
9 Second Sensor Profile (Refer to First Sensor Profile)
Sensor Submenus
Example Diagram
.C.
78
..
Page 79
5.3 Advanced Programming, Areas
Select Areas from the drop down menu.
1 Area Number 2 Area Name
Areas Submenus
Areas Submenus
Areas Submenus
The Côr panel can support a total of 4 areas. Each area is identified by a unique area number, which can­not be altered, and remains as the key reference for each area.
3 Area Entry−Exit Times
Côr uses the area entry and exit timers to delay the activation of an alarm event when entry/exit sensor types are activated.
When an area is turned on, it will start an Exit 1 timer. While an Exit 1 timer is running – Entry 1, Entry 2, and Follower sensor types will not create an alarm.
When the Exit 1 timer expires it will start the Exit 2 timer. While an Exit 2 timer is running – Entry 2 sensors will not create an alarm.
Once all exit delays are expired, an activation on an Entry 2 sensor type will start an Entry delay with the Entry 2 time, and an activation of an Entry 1 sensor type will start an Entry delay with the Entry 1 time.
If an entry delay is running and a sensor is activated with an entry time that is less than the time remaining, the timer will be reduced to the time of that new sensor.
Activation of a Follower sensor while an entry timer is not running will create an instant alarm. If a sensor is in more than 1 area, the sensor will use the have the longest entry and exit delay time of the pro-
grammed area. If an area greater than 1 has the time set to 0, that area will use the time programmed in Area 1. Stay Entry Time
The stay entry time is the entry warning time that applies to all sensors armed in the stay mode. Entry 2 sensors will follow Entry 2 time and will ignore this setting. This stay entry time does not apply to any 24 hour sensor types.
Each area can be configured with a custom 32 charac­ter name. The area name is displayed wherever an area is referenced on the Côr system.
.C
79
..
.I
Page 80
Areas Submenus 4 Area Options
1. Arm/Disarm Reports If enabled, this area will send open and close reports via one or more appropriately configured channels.
2. Quick Away
If enabled, this area can be armed in away mode via a single away mode key press. When an area is armed via quick away mode, the closing user number is the default user of 999
3. Arm In Stay If No Exit
If enabled, Arm In Stay If No Exit will cause this area to arm in stay mode even when a user arms it in away mode, providing that an entry 1 or entry 2 sensor type is not triggered during the exit delay.
4. Quick Stay Mode Disarm
If enabled, this will allow the stay mode to be disarmed by pressing the stay key on the keypad. This is only possi­ble if there is no alarm active and the stay entry delay is currently running.
At the end of the stay entry delay or if there is an area alarm, the stay mode can only be disarmed via a valid user PIN.
5. Siren Chirp Away If enabled, Côr will activate the built−in siren briefly each time this area is set in away mode or disarmed with a key−switch sensor or wireless keyfob.
Areas Submenus
6. Siren Chirp Stay
If enabled, the Côr will activate the built−in siren briefly each time this area is set in stay mode with a key−switch sensor or wireless keyfob.
7. Force Arm With Bypass
If enabled, the area can be armed even if sensors are not ready. Any sensors that are not ready will automatically be bypassed. The bypass will be logged in the event history. The automatic bypass will be applied when the sensor is capable of causing an alarm condition due to a state change such as an area arming, schedule or action. This avoids false alarms. If an auto−bypassed sensor becomes ready after it is armed, that sensor will automatically remove the bypass, log the bypass restore, and optionally report the bypass restore. Individual sensors can be made “force armable with auto−bypass” by leaving this area option off, then enabling Forced Arm Enable in Sensor options, and enabling Sensor Inhibit (Bypass) in the Sensor Type Profile.
8. Force Arm W ithout Bypass
If enabled, the area can be armed even if sensors are not ready. Any sensors that are not ready will NOT be auto­matically be bypassed and may cause an alarm condition because they could still be in a not ready state once the area becomes armed. This option is overridden if the Force Arm With Bypass is enabled. Individual sensors can be made “force armable without auto−bypass” by leaving this area option off, then enabling Forced Arm Enable in Sensor options, and disabling Sensor Inhibit (Bypass) in the Sensor Type Profile.
9. Manual Fire
If enabled, the manual fire button will be enabled on keypads. Press and hold for 2 seconds to send a fire event. Default is on.
10. Manual Auxiliary
If enabled, the manual auxiliary button will be enabled on keypads. Press and hold for 2 seconds to send an auxil­iary event. Default is on.
11. Manual Panic
If enabled, the manual panic button will be enabled on keypads. Press and hold for 2 seconds to send a panic event. Default is on.
12. Use Area 1 Options
If enabled, the area will use Area 1 options. Default is on.
13. Bypass Requires PIN
If enabled, a valid PIN code with access to this area is required to bypass sensors in this area.
.C.
80
..
Page 81
Areas Submenus
Notes on Force Arming, Bypass, and Auto−Bypass
Normally to arm an area it must first be “Ready to Arm”. This means all sensors in that area must be closed. For example, if the front door is open, then a user would need to close it first and ensure there is no movement in
the reception area. This provides the Ready to Arm status in Area 1 that is needed before attempting to arm. This is
not always user friendly or practical.
The term force arm refers to the ability to arm an area even though sensors are not ready. It is usually only used with motion sensors as these are self−restoring and will be restored by the time the exit delay ends (e.g. the person arming the system leaves the building causing the Reception PIR to restore.)
If the front door is not closed properly then Area 1 would go into alarm at the end of the Exit time. To avoid this false alarm we enable “Force Arm With Auto−Bypass” so all sensors that are not closed (i.e. not ready) by end of the exit time will be “Auto−Bypassed”.
If after the Area is armed, that sensor restores (e.g. the person double checks and secures the front door) then the Auto−Bypass will be removed from the sensor and it will be active. If subsequently the sensor is triggered then Area will go into alarm.
Auto−bypass will be applied (if enabled, and if necessary) to a sensor whenever a change in state occurs that would result in an alarm condition. These include arming an area with a not−ready sensor, a sensor changing profile, Arm−Disarm function, or due to an action or schedule.
Enabling Auto−Bypass for the area will apply the feature to all sensors in that area as well. In general disabling “Sensor Auto−Bypass” is not recommended because of the potential to create a false alarm
but there are applications where it is desired. Use “Force Arm Without Auto−Bypass” at the area level to prevent sensors from being auto−bypassed when Force Armed.
.C
81
..
.I
Page 82
Areas Submenus
.C.
82
..
Page 83
Areas Submenus
5 Area Timers
Auto Arm Warning If the area type is Standard and Arm / Disarm is configured, this timer delays arming by the minutes entered.
If the area type is Timed Disarm, Man Down, or Guard Tour, this setting is a warning time given to a user once the user’ s Disarm Time, Man Down Time, or Guard Tour Time has expired. During this warning time a user can cancel the automatic re−arming and event report by entering their code, this will also restart the appropriate user timer. At the end of the warning time, Côrwill re−arm the area and send the appropriate event (closing, man down, guard tour fail).
If the area type is Early Open & Late Close, this timer sets the period after the start (opening) and after the end (closing) of the area type schedule that the area can be disarmed or armed. Otherwise an early to open or late to close report will be sent if enabled in user permissions. Fail to open and fail to close report will be sent if Arm−Dis­arm Reports is enabled in area options.
Valid values are from 0 to 99 minutes Local Alarm Reminder
If set, the local alarm reminder is the period in minutes between 0 and 999 that may elapse between actioning a local alarm and the local alarm reactivating if that sensor has remained open.
For example if a smoke detector is removed to change the battery the tamper will trip; if a user resets the alarm on the Côr system but does not replace the smoke detector within the local alarm reminder time, then the fire alarm tamper will retrigger.
6 Area T ype
.C
Standard
The area functions as normal.
Timed Disarm
Timed disarm is used when an authorized user can disarm an area for a predetermined period of time. At the end of this disarm time the area will start the auto−arm process ensuring that the area is not accidentally left disarmed.
The following conditions must be true before a timed area disarm function will occur. a. The area type must be set to Timed Disarm.
b. The area type schedule must be active. c. The users active profile’s permission must have; i. This area set in the permission’s timed disarm area group. ii. The permission must be in schedule. iii. The permission’s Area Type Override must NOT be set.
At the end of the user’s disarm time, the Area Type Delay will activate for the set period. At the end of the Area Type Delay period the area will arm and start the Exit Delay and if configured, report a closing using via the last user number to have time disarmed the area.
At anytime during the timed disarm period, authorized users with Area T ype Override set in their active profile can cancel the disarm time period by arming or disarming the area
The user’s permission determines how long the area will be disarmed for.
83
..
.I
Page 84
Areas Submenus
Man Down
Man down is used when an authorized user(s) is working in a hazardous area (or the like), and there is a require­ment that the user(s) regularly “check−in” to notify others that the user(s) is safe. If the authorized user(s) fails to perform this action the system can set an audible warning and send a report.
The following conditions must be true before man down function will occur. a. The area type must be selected to man down.
b. The area type schedule must be active (after the start time and before the end time). c. The uses active profile’s permission must have; i. This area set in the permission’s man down group. ii. The permission must be in schedule. iii. The permission’s Area Type Override must NOT be set.
The man down timer is set in the user’s permission. At the end of the user’s man down time, the Area Type Delay will activate for the set period. At the end of the Area Type Delay period the area will arm and if configured, report a man down alarm. At anytime during the man down period, authorized users with the Area T ype Override set in their active profile will cancel the man down time peri­od by disarming or disarming the area.
Guard Tour
Guard tour is used when an authorized user(s) (such as a guard) is required to regularly “check−in” to notify others that they have physically attended to a location(s) on the site. If the authorized user(s) fails to perform this action the system can set an audible warning and report a “Guard T our Fail” event.
The following conditions must be true before guard tour function will occur. a. The area type must be selected to guard tour. b. The area type schedule must be active (after the start time and before the end time). c. The uses active profile’s permission must have; i. This area set in the permission’s guard tour group. ii. The permission must be in schedule. iii. The permission’s Area Type Override must NOT be set.
The guard tour time is set in the user’s permission. At the end of the user’s guard tour time, the Area Type Delay will activate for the set period and keypad sounder
will be active. At the end of the Area T ype Delay period the area will arm and if configured, report a Guard Tour Fail alarm. At anytime during the guard tour period, authorized users with the Area T ype Override set in their ac­tive profile will cancel the guard tour time period by disarming or disarming the area.
Early Open/Late Close
If the area type is Early Open & Late Close, the Area T ype Delay sets the period after the start (opening) and the end (closing) of the area type schedule that the area must be either disarmed or armed.
For example, if the area type schedule is set between 8:00 AM (opening time) and 5:00 PM (closing time) and the Area Type Delay is set to 15 minutes; then the area must be disarmed between 8:00 AM and 8:15 AM otherwise if it is disarmed before 8:00 AM it is an early open, if it is disarmed after 8:15 AM it is late to open. Likewise the area must be armed between 5:00 PM and 5:15 PM otherwise if it is armed before 5:00 PM it is an early close, if it is armed after 5:15 PM it is late to close.
7 Area Type Schedule
.C.
One of 96 configurable schedules can be allocated to the area type schedule. The area type schedule determines the schedule that the selected area type is active. Area types are not active when the schedule is not active. If an area type schedule is disabled (always active) that area will always have the type characteristics programmed in Area Type.
84
..
Page 85
Areas Submenus
Area Type Delay
If the area type is Standard and Arm / Disarm is configured, this timer delays arming by the minutes entered. If the area type is Timed Disarm, Man Down, or Guard Tour, this setting is a warning time given to a user once the
user’ s Disarm Time, Man Down Time, or Guard Tour Time has expired. During this warning time a user can cancel the automatic re−arming and event report by entering their code, this will also restart the appropriate user timer. At the end of the warning time the Côr will re−arm the area and send the appropriate event (closing, man down, guard tour fail).
If the area type is Early Open & Late Close, this timer sets the period after the start (opening) and after the end (closing) of the area type schedule that the area can be disarmed or armed. Otherwise an early to open or late to close report will be sent if enabled in user permissions. Fail to open and fail to close report will be sent if Arm−Dis­arm Reports is enabled in area options.
Example Area Type – Early Open & Late Close Area T ype Schedule – 8:00 to 17:00 Area T ype Delay – 15 min User Permissions – Options – Open/close report, Early open report, Late close report Area Options – Arm−Disarm Reports
.C
85
..
.I
Page 86
Areas Submenus
8 Area Event Reporting/Account 9 Area Event Reporting/Channels
If set, the area account code is a system unique 4 to 10 digit code (format dependent) used to associate area related alarm reporting events to this area. If the area account code is equal to the default of 0, the channel account code will be used for this area’s alarm reporting events. If the channel account code is equal to the default of 0, the channel 1 account code is used. If the channel 1 account code is 0 then the account will be sent as 0
The channel group determines which communicator channel(s) area events will be reported to. If the bit corresponding to one of the 16 reporting channels is set to on, area events will always be reported to this channel. It is referred to as a primary reporting chan­nel. If a report is unsuccessful to a particular primary channel it will attempt that channel’s backup channels if there are any.
.C.
86
..
Page 87
5.4 Advanced Programming, Channels
h
t
Select Channels from the drop down menu.
The Côr panel can support a total of 16 channels; each channel is a communication path for events to be sent from the Côr panel to a selected destination.
Default configuration reserves Channels 1 – 3 for UltraSync format, Channels 4 – 16 are Email format.
Email is a “best−effort” system and there is no guarantee messages will be delivered by the network. When the network is busy, messages can be dropped. Central control room monitoring is highly recommended as each event is acknowledged on receipt to ensure an appropriate response can be made.
Installers have access to setup/modify all channels (1−16). Master Users have access to channels 7−16, which are used for email notifications. Standard users do not have access to channels.
Channels Submenus
1 Channel Number 2 Channel Name
Areas Submenus
The Côr panel can support a total of 16 channels. Each channel is identified by a unique channel num­ber, which cannot be altered, and remains as the key reference for each channel.
Channel 1 and channels 4−16 are configured as pri­mary reporting paths by default. Channel 1 is dis­abled by default. Use as Backup as the Format selec­tion has the effect of disabling reporting of a primary channel. The Format must be selected to a value other than Use as Backup to enable reporting. Channels 4−16 are configured as email reporting paths by de­fault.
Channels 2 and 3 are configured as backup reporting paths by default. Channel 2 is set to backup channel 1 and channel 3 is set to back up channel 2 by default. Note that the primary channel must set the Next Channel for back up reporting to function.
Custom names of the selected channel can be created here
3 Account Number
This is the Account Number that will be reported wit the event in email reports. When UltraConnect forma is selected, this field will not be used.
.C
87
..
.I
Page 88
Areas Submenus
4 Format 5 Device Number
This is the communication format for the selected channel. When Use as Backup is selected, the backup path will utilize the primary channel’s format. Note that the primary channel must set the Next Channel for back up reporting to function.
6 Destination Phone/Email 7 Next Channel 1−16
The email address or mobile device name (push notification) of the selected destination. When enabling push notifications in the Côr app, the device name will automatically be set in destination phone or email.
8 Event List 1−16 9 Attempts
.C.
Select the pre−programmed list of events that will be sent via this channel. The specific events in each event list are programmed.
88
Enter the number of times Côrshould try to send the events to the UltraSync server. After the number of attempts has been exhausted the Côr panel will try the Next Channel if specified.
..
Page 89
Configure Email Reporting
1. Login to Côr Web Server from your computer using the IP address.
2. Press Settings.
3. Select Channels in the drop down Menu.
4. Press Select Channel to Configure where the Format is already set to Email.
5. Enter an email address.
6. Select an Event List.
7. Enter a Channel Name for future reference.
8. Press Save.
Installer and Master User types can customize Event Listing for selective reporting.
.C
89
..
.I
Page 90
5.5 Advanced Programming, Communicator
Select Communicator from the drop down menu.
The Côr Communicator is a key component of the Côr System used in conjunction with the Channels feature to report events to a monitoring company or third party. In this menu you can configure the settings for various methods of reporting.
Communicator Submenus
1. General Options
Communicator Submenus
1. First Disarm Last Arm
If enabled, Côr will only send a closing report when the last area is armed. NOTE: The last area to arm must have open/close reports enabled. Côrwill only send an opening report when the first area is disarmed. This feature is used in place of Individual area Open and close. If you enable open and close in the area you will get both individual open and close and System open close.
2. Report Once Per Sensor
If enabled, this will limit reporting to only once per sensor each time you arm or disarm an area. This stops the control room or reporting destination to be flooded by multiple reports that the same sensor is being activated (for example the intruder may be moving around and is being picked up by the sensor on that sensor).
3. Suppress Force Arm Bypass
If enabled, Côr does not send bypass reports when a sensor is forced armed. If not enabled, when a sensor is forced armed and it remains in a state of creating an alarm, bypass reports are sent at the end of exit time. For ex­ample this would occur if it remains open at the end of the exit time, or due to change of sensor type caused by a schedule. If forced armed sensors re−close during the armed period, bypass restores are sent.
4. Immediate Restore
If enabled, Côr will immediately send all restorals as the sensor reports the event. If not enabled, Côr will send restoral events all at the same time when the marea is disarmed.
2 Auto Test/Intervals 3 Auto Test/Time
Enter the time at which the automatic test report should be sent. This should be in 24−hour format. For example 18:00.
.C.
Set day of the week to send an automatic test report to the system channel group . (Communicator\System Event Reporting\System Chan­nels). You may also set auto−test to Daily
90
..
Page 91
r
4 IP Configuration
e
5−6 IP Config Detail 7−10 IP Config Detail
Communicato
Submenus
Host Name
This is a text label assigned to the Côr communicator so you do not have to remember the IP Address.
NOTE: This only works on local LAN and with Micro­soft Windows PC, or an Apple device with the local extension. Does not work remotely over the internet.
IP Address
The IP address assigned to the Côr communicator to enable it to connect on to the local LAN. This will allow you access to the embedded web server from a web−enabled device to program and view th status of the system. It is also used for alarm report­ing.
Gateway
If required, the IP address of the router which is needed when remote IP communications are used .
Subnet
The subnet mask for the network. For example, 255.255.255.0 is the network mask for
192.168.1.0/24.
Primary DNS
The IP address of the Primary Domain Name Server. The DNS is used to translate host names for time servers and UltraSync servers
Secondary DNS
The IP address of the Secondary Domain Name Server, used if the Primary DNS is not available.
.C
91
..
.I
Page 92
r
11 Ports 12−14 IP Config Detail
The ports that the computer needs to communicate with the Côr system.
Defaults: HTTP Port = 80 HTTPS Port = 443 Download Port = 41796
15 Time Server
Communicato
Submenus
Enter the URL or IP address of a time server to allow Côr to automatically update and synchronise its clock without user intervention. The default is pool.ntp.org
16 IP Options
1. Enable DHCP
Allow the Côr panel to be automatically assigned an IP address by the network.
2. Require SSL
Feature no longer supported. Leave unchecked.
3. Enable Web Updates − RESER VED
Allows the Côr panel to update the web pages via a network. Go to Hostname/mpfsupload to update the web pages served by Côr. Does not update firmware.
4. Enable Ping
Allow the Côr panel to respond to the PING command
5. Enable Clock Updates
Allow the Côr internal clock to synchronise with the internet time server specified .
.C.
92
..
Page 93
6. Enable Web Program
Enabling this option will cause the Côr W eb Server and app to always display Installer menus regardless of if the panel is in program mode or not. Disabling this option will hide the Installer menus on the Côr Web Server and app unless program mode is ac­tive. This provides greater security by keeping web programming disabled unless a user on site with physical access to the keypad enters program mode with a valid PIN code.
Côr panel will be in program mode if a user gains access to menu 5, 8, or 9. The Côrapp requires the Web Access Code to get access to the panel.
7. Always Allow DLX900
Enabling this option will allow DLX900 to connect at any time if the correct Download Access Code is provided. Disabling this option provides greater security by only allowing DLX900 to connect when program mode is ac­tive. This allows the system to have DL900 access disabled until a user on site with physical access to the keypad enters program mode with a valid PIN code. Côr will be in program mode if a user gains authorised access to menu 5, 8, or 9 on the keypad
8. Monitor LAN
When the Monitor LAN option is enabled the panel will monitor the Ethernet port for a valid Ethernet cable. If the Ethernet cable is disconnected while this option is enabled, and the panel is unable to communicate, it will log a Fail To Communicate event.
9. Enable UltraConnect (UltraSync)
This is an automatic feature of Côr. It is recommended you leave this setting on. Enable this option to allow Côr to send email reports via the UltraSync servers. This is independent of the W eb Access Passcode which when set to 00000000 will prevent the Côr app from connecting. If any channel is set to Email format reporting, then Côr will override ignore this setting and allow email report­ing via UltraSync cloud servers. If you wish to prevent connections to the Côrcloud servers, then uncheck this option and do not use the Ultra­Sync reporting format.
Communicator Submenus
17 Radio Configuration 18 GPRS Username/Password
19 APN 20 Radio Options
.C
Access Point Name (APN) for the settings to set up a connection to the gateway between the cellular network and the public Internet.
93
..
.I
Page 94
21 SIM Preset 22 Remote Access
23 Panel Device Number
24 Download Access Code
Communicator Submenus
A number from 0 to 4,294,967,295 that must be entered in to the desktop software for remote access to take place.
25 Callback Server
If an IP address or host name is programmed into this feature, and “Call Back Before Download Session” is enabled, the Côr will disconnect for approximately 10 seconds and then connect to this IP address. This should be the IP address of the computer where DLX900 is installed, not the IP address of the Côr panel. IMPORTANT: the call back IP address should always be reviewed for accuracy before disconnecting.
26 Download Options
A variable length code for the computer user. This code gives the software complete authority over all menus including those that are locked. For convenience DLX900 will also try installer and 9−7− 1−3 to allow a connection for first time set up if the Download Access Code does not work This is why changing the default code is important
The default Download Access Passcode of 00000000 prevents remote access
Changing this code may lock out your control room monitoring service and prevent you from maintaining your system. It is advised you contact your control room before changing this code.
Users must have access to the Communicator menu in order to change this setting. This can be programmed in Menus, and assigning the “Advanced” menu.
.C.
1. Call Back Before Download
If a download is requested the Côrwill hang up and make a call to the Call Back Number. This is to increase the security of remote access.
2. Lock local Programming
Prevent changes to the Côrsystem via a keypad, all changes MUST be made using the remote access software.
3. Lock Communicator
Local programming locks all programming unless accessed with the Download Access code. Lock communicator locks local programming of communicator features unless accessed by the Download Access Code.
4. Lock Download
Prevents the programming of the Remote Access Menu without using the Download Access PIN.
5. Call Back at Auto Test
When an auto test is initiated, perform a call back to the number specified.
94
..
Page 95
27 Event Reporting / Channels 28 Event Reporting / Attempts
Communicator Submenus
Enter the Channel Group that the Côr will send system events to.
Example If Channel 1 is the primary, and Channel 2 is the backup for Channel 1, then when both channels fail it will go back to
Channel 1. This setting controls how many times Côr cycles back to Channel 1 before it gives up. The Channel Attempts setting controls how many times Côrstays on the channel before switching to the backup. Always check the max. number of attempts on all channels to avoid unexpectedly high communication charges. In the diagram below, Côr will try Channel 1 3 times, switch to Channel 2 and try 2 times, then go back to Channel 1.
This sequence is repeated 2 times in total. In total there will be 10 attempts.
This is the number of times the Côr will sequence back to the primary channel if the backup channels all fail. This applies to ALL communication attempts in­cluding sensor and area events.
.C
95
..
.I
Page 96
5.6 Advanced Programming, Schedules
Select Schedules from the drop down menu.
1 Schedule Number 2 Schedule Name
Schedules Submenus
Schedules Submenus
The Côr panel can support a total of 96 schedules. Each schedule is identified by a unique schedule num­ber, which cannot be altered, and remains as the key reference for each schedule.
3 Follow Action Number
Each schedule can be configured with a custom 32 char­acter name. The area name is displayed wherever a schedule is referenced on the Côrsystem.
If an action number is specified, then the schedule be­comes enabled when the action is true. When the action becomes false, then the schedule becomes disabled
Schedules can be used to control various parts of the system such as when a user’s permissions are applied. The “Follow Action Number” option allows you to use actions to control schedules.
The result is actions can control when permissions are applied, when area types are applied, sensor behaviors, when arm−disarm can occur, and when scenes play .
This allows you to create conditional schedules that only become active when certain conditions are met. For ex­ample you could create a user that only becomes active (because of the linked schedule) under certain conditions like a fire alarm.
.C.
96
..
Page 97
Follow Action
-
4 Times and Days Côr handles schedules that span midnight automatical
ly. For example, if a schedule is to cover Fri 8:00pm to Sat 6:00am, only check Friday and Côr will automati­cally manage the time after midnight.
If you check Friday and Saturday, the schedule will cov­er Fri 8:00pm – Sat 6:00am and Sat 8:00pm – Sun 6:00am.
Schedules
Submenus
Up to 16 sets of time and days can be specified here. 5 Start Time / End Time 6 Days / Holidays
Note: Holidays 1−4: If checked, it means the item as­signed this schedule will NOT have access during the specified holiday dates.
See Advanced Programming, Holidays dates.
to program these
.C
97
..
.I
Page 98
5.7 Advanced Programming, Actions
The Côr panel features powerful automation control which can interact with different parts of the system. It can perform functions based on the status of one or more system conditions.
These features are considered advanced programming and should only be changed by an installer with a thorough understanding of the features.
Each action has an on and off state. The state is controlled by up to 4 conditions called Action Events, each of which can have a range of items:
When all 4 Action Events are met, then the Action State (trigger) will be set. The Action State can be monitored by the main Côr Panel, Schedules, Devices with outputs, and Scenes to activate/deactivate.
For example, a strobe connected to Output 1 can be programmed to follow Areas 1 – 8 being armed.
Each Action can also directly control selected parts of your Côr when all 4 Action Events are met. This is called the Action Result. Its behavior also follows the Action State.
For example, when all areas are armed and there is activity on sensor 1, activate a camera recording.
Select Actions from the drop down menu.
.C.
98
..
Page 99
Actions
Submenus
Actions Submenus
1 Action Number 2 Action Name
Each Action can be configured with a custom 32 character name. The name is displayed wherever an Action is referenced on the Côr system.
3 Function
.C
The Côr panel can support a total of 32 Actions. Each Action is identified by a unique number, which cannot be altered, and remains as the key reference for each Action.
Note: All 32 actions are pre-programmed with the specified trigger. To create a new action, you need to modify one of these actions.
99
• Timed – The action state turns on for the time specified.
• Follow (Recommended) – The action state turns on once the Event conditions have been satisfied, then off once the Event conditions are not true.
• On Delay – The action state becomes on after the programmed time period unless logic result is no longer active.
• Off Delay – Follows the result of the logic equa tion, but remains active for the time programmed after the logic result is no longer active.
• On Pulse – Action state turns on for the pro grammed time or the active period of the logic re sult, whichever is the SHORTEST.
• Latch – The action state stays on once the Event conditions have been satisfied
..
.I
Page 100
4 Duration: Minutes 5 Duration: Seconds
Actions
Submenus
Where the Function requires duration, this deter mines, in minutes, how long the action should stay on.
6 Event(s) 1-4 and Results 7 Event Attributes
8 Event Category 9 Event Type
Where the Function requires duration, this deter mines, in seconds, how long the action should stay on.
.C.
Select the category of the first event. This will deter mine what events you can select in Event Type.
See the Action Events Category and Action Event types table in section A.10 for reference.
100
Select the event that you want the Action to moni tor.
See the Action Events Category and Action Event Types table in section A.10 for reference.
..
Loading...