INSTALLATION INSTRUCTIONS
CopperSmith Remote Blower / Ventilators
READ AND SAVE THESE INSTRUCTIONS
Before beginning installation, please thoroughly read and become familiar with these instructions. Installation and
service must be completed by a qualified installer. Failure to properly install this product may void the warranty.
Installer:
Owner:
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS
OBSERVE THE FOLLOWING:
Use this unit only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.
Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to
prevent power from being switched on accidentally. When the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a tag to the service panel.
Please leave these installation instructions with the range hood installation instructions.
Please leave these installation instructions for local electrical inspector’s use and for future reference.
WARNINGS: Must be followed carefully to avoid personal injury.
IMPORTANT: Must be followed carefully to avoid damage.
TIPS: Contain helpful information to facilitate installation.
Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction.
CAUTION: For General Ventilation Use Only. Do Not Use To Exhaust Hazardous or Explosive Material and Vapors.
CAUTION: This unit has an unguarded impeller. Do not use in locations readily accessible to people or animals.
WEAR HAND PROTECTION AND STAY CLEAR OF SHARP EDGES! The compactness and adaptability of the
model PSD blower permits easy installation. The units are shipped fully assembled and can be mounted at any
angle. For mounting suggestions see pages 3 & 4. Because this unit has rotating parts, safety precautions should
be exercised during all phases of installation, operation and maintenance. Remove unit from package and inspect
before installation. If damaged, report damage to carrier. DO NOT operate this unit with visible damage to the blower
or impeller assembly. Screen guards must be installed when blower will be within reach of personnel, within (7) feet
of the working area, or when advisable for safety.
WARNING! DO NOT CONNECT POWER SUPPLY until blower is completely installed.
Make sure electrical service to the blower is locked “OFF” position.
Check voltage at blower to see if it corresponds to the motor name plate. Installation work and electrical wiring
must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated
construction.
Sufficient air is needed for proper combustion and exhausting of gasses through the flue (chimney) of fuel
burning equipment, (e.g., gas water heater, gas furnace) to prevent back drafting.
Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the
National Fire Protection Association (NFPA) and the American Society for Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE) and the local code authorities.
When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities. Ducted
blowers must always be vented to the outdoors.
If this unit is to be installed over a tub or shower, it must be marked as appropriate for the application and be
connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch circuit.
NEVER place a switch where it can be reached from a tub or shower.All units are suitable for use with solid-state speed control.
WARNING! TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
Sufficient air is needed for proper combustion and exhausting of gasses through the flue (chimney) or fuel burning
equipment to prevent back drafting. Follow the heating equipment manufacturer's guideline and safety standards
such as those published by the National Fire Protection Association (NFPA) and the American Society for Heating,
Refrigeration and Air Conditioning Engineers (ASHRAE) and the local code authorities.
When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.Duct blowers must always be vented to the outdoors.
For best and quietest performance, the Remote Blower should be installed in the attic, near or slightly
beyond the mid-point of the duct system. In installations requiring the blower be in a chase or hood over the
range (e.g., no attic above the kitchen), the duct silencer will not be as effective in absorbing motor noise. In addition, there will likely be motor sound transmitted through the walls of the chase, bypassing the duct silencer.
Given the high performance of CopperSmith Remote Blowers, it is highly recommended that the blower
NOT be attached directly to the liner or in a chase immediately above the liner unless a CopperSmith
brand duct silencer is installed between the blower and liner and neoprene lined FC Clamps* are used.
CopperSmith brand Professional Series ventilation systems can be installed in an infinite variety of configurations.
The Remote Blower and Duct Silencer can be installed at any angle.
Connecting the Blower / Ventilator
er properly aligning and supporting the blower, connect it to the duct. Fasten in place by using sheet metal
Aft
screws and tape or preferably FC Clamps*. Fast Clamps (FC Clamps) are the recommended connectors for
connecting the blower to the duct system. FC Clamps are easy to connect and work extremely well as a vibration
absorber and noise suppressor. They are made of steel and are lined with 0.3” neoprene pad. If FC Clamps are
used to connect the blower to the duct, it is not as necessary to use them on the Duct Silencer for vibration
suppression. FC Clamps are available from CopperSmith.
CAUTION: DO NOT hang PSD model blowers / ventilators from the FC Clamp’s hanging tabs. Instead, use
the integral brackets bolted to the blower housing.
Hanger type vibration isolators and suspension hardware (e.g., threaded rod, slotted angle iron, hurricane strap)
are not supplied with blower. If the blower is suspended with these items, they will absorb much of the motor’s
minor vibration.
For more information about vibration absorbers, visit the following internet sites:
www.grainger.com (e.g., for WW Grainger Item 4C879)
www.vibration-absorbers.com
www.vibrationiso.com
*FC Clamps are available from CopperSmith.
Ask for model number FC6 (6”), FC8 (8”) or FC10 (10”), 2 per box.
Follow all applicable codes when installing this unit.
1. Build and install wood supports to framing structure for blower
mounting.
2. Attach blower directly to wood supports.
The Remote Blower’s mounting brackets are designed for flexible
and easy installation at any angle-horizontal, vertical or diagonal.
The brackets should be bolted directly to a 2” x 4” type wood
framing structure (e.g., an attic truss) or suspended by threaded
rod, slotted angle-iron or hurricane strap. The installation should
be sufficient to support the blower’s weight.
Follow all applicable codes when installing this unit.
1.Equipment should be hung in position with temporary fixtures
that can be removed after vibration hangers* are installed.
2.Optional vibration hanger may be fastened directly to the
Detail
*IMPORTANT NOTE: Hanger-type vibration isolators and suspension hardware (e.g., threaded rod, slotted angle
iron, hurricane strap) are not supplied with blower. If the blower is suspended with these items, they will absorb
much of the motor’s minor vibrations.
Vibration
Mount
structure or somewhere between the suspended unit. Be sure
not to over tighten the neoprene element. Install hangers.
3.If threaded rod is used, turn nuts on rod assembly clockwise
one complete turn on each hanger. Repeat this procedure
until temporary hanging fixtures are loose and blower is
suspended completely on t
4.Remove temporary fixtures and level ducting and blower by
taking additional turns on the spring / top hanger rod nut as
required.
he vibration hangers.
For more information about vibration absorbers, visit the following internet sites:
www.grainger.com (e.g., for W.W. Grainger Item 4C879)
www.vibration-absorbers.com
www.vibrationiso.com
Ensure the power supply is disconnected before
proceeding.
Verify that the power supply matches the ratings found
on the blower data label before proceeding.
The complete blower unit must be properly grounded at
all times when electrical power is applied.
Do not ground the appliance with the neutral (white)
house supply wire. A separate ground wire must
utilized.
2.99
4.84
be
Capacitor
Failure to complete electrical connections properly may
result in damaged or non-functional systems. Follow
instructions carefully to ensure proper installation.
Wiring Diagram (for connecting “Remote” blowers to CopperSmith Pro & Standard Series liners*)
120V Red
Ventilator
Green, Ground
Black120 volt AC from electrical panel (usually black) to liner
WhiteNeutral from electrical panel (white) to liner
GreenGround from electrical panel (usually green) to liner
Red120 volt AC variable control from liner to 120 volt AC of variable speed ventilator (usually black)
CAUTION: Do NOTconnect this wire to a 3-speed blower.
White (N)
120V Black
(L)
Green
Liner Models:
CSPI Series
CSCI Series
Excluding...
3-speed motor
House Electrical
Panel
models, which all
have a
-6 or -12
at the end of
model number.
Liner
BLKWHTGRNRED
It is the owner’s responsibility to ensure that a qualified person performs the electrical connection of this appliance. The electrical installation, including minimum supply wire size, must comply with the National Electric Code ANSI/NFPA 70-1990 (or latest revision) and local
codes and ordinances. A copy of this standard may be obtained from: National Fire Protection Assoc., 1 Batterymarch Park, Quincy, MA
02269
CopperSmith warrants its CopperSmith Professional Series kitchen ventilation products to the original user,
to be free of defects in materials and workmanship for three (3) years from the date of purchase.
CopperSmith, at its option, will repair or replace the complete unit or any defective component without charge.
This warranty may be voided if any unauthorized service, alterations or repairs are made to the product.
What is Not Covered
Normal maintenance and service of any product that has been subject to misuse, negligence, accident or
installation inconsistent with the recommended installation instructions.
Product used other than for normal in-home use or products used outside of the United States.
Damage to the product caused by accident, fire, flood or other acts of God.
Service calls to educate the customer in the proper use and care of the product, correct faulty installation,
change fuses or reset breakers.
CopperSmith disclaims and excludes any liability for implied warranties or for incidental or consequential damages
wherever permitted by law. There are no implied warranties of merchantability or fitness for a particular use or
purpose. This warranty gives you specific legal rights and you may also have other rights, which vary from state
to state.
#
For Service
If you need service, contact Customer Service at the address or phone number below. Provide the model number,
serial number, part identification, and details of the problem. Proof of purchase must be provided.
Warranty Rev. 09/18/16
CopperSmith has a policy of continuous improvements and reserves the right to modify (at anytime and without