Coopra 40C, 15B, 15C, 37K, 37B Installation Manual

...
EN
Installation manual
40C
Gas boiler for Heating E40C
2011 585 E
Coopra Advanced Heating Technologies Installation manual E40C
2
CONTENTS
CHAPTER 1. GENERAL ……………….………….. 3 Use of application General safety regulations Environmental conditions Water quality Standards / Guidelines Conditions of delivery
1.1. Display …………………………………….…….. 4
1.2. PCB configuration
1.3. Operation indications
1.3.1. Normal state
1.3.2. Blocking state
1.3.3. Lock-out state
1.4. Menu Structure
1.4.1. View mode
1.5. Dimensional sketch
1.5.1. Technical data
1.5.2. Boiler components
1.6. Connection diagram
1.7. Operation
1.8. Boiler types
1.8.1. Coopra 40C
1.8.2. Technical characteristic
1.9. Electricity connection
1.10. Configuration of flue tube and air supply
1.10.1. Permitted flue resistance Type 40
1.11. Circulation pumps
1.11.1. Boiler pump
1.11.2. Secondary system pump
CHAPTER 2. INSTALLATION …………………….. 15
2.1. Mounting the assembly bracket
2.2. Water and gas connections
2.2.1. Gas connection
2.2.2. Water connections
2.2.3. Safety valve and Draconin connection
2.3. Expansion vessel
2.4. Filling and draining device
2.5. Dirt filter
2.6. Differential bypass valve
2.7. Unpacking the boiler
2.8. Fitting the flue tube and air supply
2.8.1. Connecting flue and air (2-pipe system)
2.8.2. Connecting flue/air adapter (80/125 mm)
2.8.3. Connecting flue/air adapter (60/100 mm)
2.9. Suspension
2.10. Green connector block
CHAPTER 3. REGULATIONS ……………..…….. 18
3.1. Central heating regulations
3.1.1. Modulation on flow sensor
3.1.2. Modulation on return sensor
3.1.3. Modulation on system sensor
3.2. Thermotats
3.2.1. On/off room thermostat
3.2.2. OpenTherm control
3.2.3. 0÷10V control
3.2.4. Outdoor sensor
CHAPTER 4. COMMISSIONING …………...…….. 20
4.1. Supply connection
4.2. Mains switch
4.3. Burner situation
4.3.1. Burner is on
4.3.2. Burner is off
4.4. Water pressure
4.5. Gas / Air Ratio
4.6.1. Full load
4.6.2. Low load
4.7. Changing over to LPG (G30/G31)
4.7.1. Full load on LPG (G30)
4.7.2. Low load on LPG (G30)
4.7.3. Labelling
CHAPTER 5. BURNER DEMAND and MONITORING
……………………………………………………….... 23
5.1. Standby
5.2. Pre purge
5.3. Ignition
5.4. In operation
5.5. Post-purge
5.6. Pump after run
5.7. Lock-out
5.8. Frost protection
5.9. System pressure monitoring
5.10. Flue temperature sensor
5.11. Limiter
5.12. Glow plug protection
CHAPTER 6. PERIODICAL MAINTENANCE …….. 25
6.1. Check the CO2 percentage on full load
6.2. Check the heat input
6.3. Clean the condensation water drain
6.4. Check the ionisation current
6.5. Water pressure
6.6. Service mode
CHAPTER 7. MALFUNCTIONS …..………...…….. 26
7.1. Serial connection
7.2. No signal on the display
7.3. Boiler does not respond to heat demand
7.4. Fitting instructions for the pressure sensor
7.5. Fitting instructions for the safety valve
7.6. Malfunction code 'F' (flashing)
7.6.1. Gas control will not open (no voltage)
7.6.2. Gas control will not open (gas inlet pressure high)
7.6.3. Gas control will not open (coils defective)
7.6.4. Check function of gas control
7.6.5. Check glow plug (no ignition)
7.6.6. Check the fan impedance
7.6.7. Gas/air mixture is not correctly adjusted
7.6.8. Inspection ionisation probe
7.6.9. Temperature sensors
CE-Certificate ………………..……………………… 28
Coopra Advanced Heating Technologies Installation manual E40C
3
CHAPTER 1. GENERAL
Use of application
The appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
General safety regulations
The installation may only be performed by a recognised installer. Take note that internal parts of the boiler can carry a dangerous electrical voltage (230 Volt). Take note that the boiler, the various pipes and the flue gas exhausted by the boiler can reach high temperatures (up to 90°C).
Before carrying out maintenance activities in or on the boiler, you must close the gas tap, switch off the electricity supply and pull the mains plug out of the socket
Environmental conditions
The area in which the boiler is installed must satisfy the applicable regulations. The wall must be able to bear the weight of the boiler (loaded weight approx. 40 kg). If you use a different assembly surface than a bricky wall of sufficient thickness, you must select suitable fixtures yourself and properly install the boiler. The boiler may not be fitted in a chemically aggressive environment. The boiler with air feed and flue gas exhaust satisfies the requirements of protection class IP44 and may therefore be installed in a wet area. Although the boiler is fitted with an internal frost protection, it may not be exposed to extremely low ambient temperatures (lower than -10°C).
Water quality
Fill the system with tap water. The composition and quality of the system water has a direct effect on the performance of the total system and the life of the boiler. At own risk is the addition and use of chemicals, water softeners, oxygen binders, de-aerators, aerators and water filters as they increase the chance of malfunctions. Generally, the build-up of undesired deposits can lead to leakages with fatal damage. No warranty when corrosive elements of certain additives have attacked the boiler.
Regulations applicable to hot water
Ask for the locally applicable regulations at the local water company as they are different in some areas.
Standards / Guidelines
With the installation of the boiler, all local regulations must be followed, where applicable, including the provisions of the following standards and guidelines:
Building Regulations
Regulations for natural gas installations
Regulations for LPG (if applicable)
Guidelines for existing gas installations
Safety requirements for heating installations
Safety provisions for low voltage installations
General regulations for drinking water installations
Water authority regulations
Ventilation in dwellings
Supply of combustion air and exhaust
House sewerage in homes and dwellings
Fire Brigade regulations
Factory Act regulations
Conditions of delivery
Coopra Advanced Heating Technologies b.v. supplies its products according to the general conditions of delivery for the metal and electro technical industry. Registered with the Clerk of the District Court at Den Haag on 19 October 1998 under no. 119/1998.
Coopra Advanced Heating Technologies Installation manual E40C
4
1.1. Display
Open the door of the casing for display operation. On the Status display is the status indication shown. On the 3 right segments, the Reading display, values of the temperature, pressure, etc are shown.
Push-buttons from left to right: MIN, PLUS and Set/Reset
Left of the Status display is a LED informing the situation of the boiler. LED is ON = burner is ON LED is OFF = burner is OFF LED is FLASHING = boiler is in LOCK-OUT
Right of the Reading display is a LED, active for TWIN boilers only.
1.2. PCB configuration
Parameter A=2 is for single boilers 15B; 15C; 37K; 37B; 37C and also 40C Parameter A=1 is for TWIN boiler 80C; set as SLAVE Parameter A=0 is for TWIN boiler 80C; set as MASTER
Parameter H is to set for correct type of application.
1.3. Operation indications
To protect the system from the result of failures and/or excessive conditions, several protection functions are implemented.
1.3.1. Normal state The boiler is stand-by or heating. During heating the burner may be switched off temporarily when the regulated water temperature is above setpoint.
1.3.2. Blocking state Blocking protection is used when a certain condition must block the system during this condition, but when this condition is not valid anymore, the system automatically may run normal again. A blocking state is indicated by a fixed letter or number on the Status display. Depending on the blocking state the Reading display is used normal or can have extra information regarding the blocking state. The blocking state cannot be reset by the user. The control automatically goes to normal state when the conditions are normal again.
1.3.3. Lock-out state Lock-out protection is used when a certain condition must lock the system until the user resets the system. These conditions are often more safety related then blocking conditions. A lockout state is indicated by a blinking letter or number on the left display character position. Depending on the lockout state, the right characters of the display are empty or have extra information regarding the lockout state.
The Alarm output is active, and the running LED on the display left hand side blinks. To reset the system after a lock-out, press and hold the Set/Reset button for more than 1 second. Some lock-out situations can only be removed by power restoration.
Note: With repeating failures in short period of time always let your installer or maintenance man check and repair unconditionally.
(-)
button
(+)
button Set/Reset
Status
Reading
Coopra Advanced Heating Technologies Installation manual E40C
5
Status Reading
1.3.1. Normal state (continuous code)
P
With initialisation and after restoration of supply power de-aeration programme runs for 2 minutes. The boiler pump and 3-way valve (if applicable) switch several times, with the purpose to move eventual air out of the boiler; burner off
0
Stand-by (no heat demand)
C
Heating heat demand, temperature above setpoint, burner off
C.
Heating heat demand, temperature below setpoint, burner on
J
Heating heat demand, 3 minutes anti-cycling time, burner off
c
Pump after run heating mode, burner off
d
DHW heat demand, temperature return sensor of Combi-boiler above setpoint, burner off
d.
DHW heat demand, temperature return sensor of Combi-boiler below setpoint, burner on
b
HWS heat demand, temperature external cylinder above setpoint, burner off
b.
HWS heat demand, temperature external cylinder below setpoint, burner on
o
Frost protection 8°C; burner off, pump on
o.
Frost protection 3°C; burner on, pump on
C
flashing
Chimney sweeper function (ionisation current on the right hand segments)
Status Reading
1.3.2. Blocking state (continuous code)
2
Return sensor temperature 5°C above flow sensor temperature, pump on, burner off
6
Combi boiler internal tank sensor not connected or open (parameter H=01)
6.
Combi boiler internal tank sensor shortcut fault (parameter H=01)
9
Flow or return sensor temperature > 95°C
A
Flue gas sensor temperature > 100°C
b/r
Hot water on right unit of TWIN boiler
E
No SLAVE connected / PCB is set as MASTER, (parameter A=0)
SLA/01
No MASTER connected / PCB is set as SLAVE, (parameter A=1)
P
Water pressure low or high, display shows ‘P’+ pressure
t
Outdoor sensor summer switch on, burner off, (parameter O/t)
Status Reading
1.3.3. Lock-out state (flashing code)
1
Max delta temperature, differential temperature between flow and return sensor limits 50°C
1
Boiler does not pass temperature test. After burner start the flow sensor must rise 3°C more in temperature than return sensor within 20 seconds (after 3 start attempts follows lock-out)
2
Flame signal lost 3 times during operation
5
Fan speed error (fan speed deviates > 30% from the speed setpoint)
8
Flame signal detected with closed gas valve
9
Eeprom programmed (to reset press the Set/Reset button)
A
Flue gas temperature > 100°C for more then 3 times within 30 minutes
E
Internal regulation fault / A/D conversion fault (depending type of error display shows ‘E’ or “EEE”)
E t1
Flow sensor open or shortcut fault
E t2
Return sensor open or shortcut fault
E t3
Flue gas sensor open or shortcut fault
F
Too many (4 times) consecutive start attempts
H
Flow or return sensor temperature > 105°C
O
Safety limiter contact is open (no limiter on this boiler, contacts bridged)
Coopra Advanced Heating Technologies Installation manual E40C
6
1.4. Menu structure
To enter the menu structure press and hold the Set/Reset button for longer than 10 seconds. The menu mode opens with the password mode h=10. To unlock menu structure make h=18, use the (+) and (-) buttons. To go to the first parameter press the Set/Reset button.
To change the parameter value, use the (+) and (-) buttons. To go to the next parameter press the Set/Reset button. To save altered parameter settings, walk through the complete menu with the Set/Reset button until normal status indication appears.
Timeout: When inside the menu structure the keys are untouched for 3 minutes, the system will switch back to the normal status indication. Settings are not saved.
Menu structure
Status
parameter
Description Range
Factory
setting
h
Password protected To unlock menu structure make h=18
10 - 99 h=10
C Heating max. flow temperature 25 - 90°C 82°C
C/r Modulation option
0 = Regulation on flow sensor (default) 1 = Regulation on return sensor or regulation on system sensor
0
O Heating pump after run 1 - 25 min; CO=24uur 5 min P Heating max input 45 - 100 % (fan 1800 – 5400 rpm) 100 %
A Boiler application
2=Standalone (for single boiler) 1=Slave (for TWIN right hand PCB) 0=Master (for TWIN left hand PCB)
2
H Type of application
00 = Adjustment for heating only 01 = Combi-boiler (with internal DHW tank) 02 = HWS storage cylinder 12kOhm (use for large volume cylinders) 03 = HWS storage cylinder 10kOhm (use for large volume cylinders) 04 = HWS storage cylinder 12kOhm (use for small volume cylinders)
01
d (1) Setpoint temperature (Combi boiler) 40°C - 65°C 60°C
t (1) Hold temperature internal tank 40°C - 65°C 40°C
b (2) Setpoint temperature storage cylinder 25°C - 70°C 60°C
O/b (3) Basic temperature 10 - 90°C 40°C O/S (3) Slope 01 - 99 20 O/d (3) Day reference temperature 10 - 90°C 40°C
O/t (3) Outdoor summer switch temperature 1 - 50°C 40°C
r
Return to “Factory setting” Press (+) button for at least 5 seconds Note: some settings do not return
= factory setting
= customised setting
u Configuration 0÷10V input
0 = Regulation on temperature 1 = Regulation on boiler output
0
o (4) Configuration of TWIN
01 = power mode (input 14,6 kW – 74,0 kW) 00 = comfort mode (input 7,3 kW – 74,0 kW)
01
F (2) Storage cylinder max flow temperature 65 - 90°C 85°C
S
Configuration pump (2-stage pump regulation)
00 = automatic
= pump always high
= pump always low
00
Notes: (1) Active when H=1; (2) Active when H=2 or H=3 or H=4; (3) Active with outdoor sensor; (4) TWIN only
Coopra Advanced Heating Technologies Installation manual E40C
7
1.4.1. View mode At the end of the menu structure, the view mode is shown. The view mode is a reading only entry; no parameters can be changed in here.
The view mode is to enter directly. Press the (+) button for at least 10 seconds. First upcoming is the water pressure P / u; in the Reading display on the right hand segments is the actual water pressure in bar. Press the Set/Reset button to next parameter.
To switch out of the view mode press the (-) button shortly or after timeout. When the keys are untouched for 3 minutes, the system will switch out of the view mode automatically.
View mode
Single boiler
Status Description
P / u Actual water pressure left hand unit (in bar)
/ u
Setpoint temperature on flow sensor (in °C) (parameter C/r = 0)
Setpoint temperature on return or system sensor (in °C) (parameter C/r = 1) 1 / u Actual flow sensor temperature (in °C) 2 / u Actual return sensor temperature (in °C) 3 / u 0÷10V control (in Volt) 4 / u Outdoor sensor temperature (in °C) 5 / u Combi-boiler internal tank or external storage cylinder temperature (in °C) 6 / u Flue gas sensor temperature (in °C) 7 / u Flame signal (in µA DC) 9 / u Last lock-out A / u Last blocking d / u Actual system sensor temperature (in °C) (parameter C/r=1)
Coopra Advanced Heating Technologies Installation manual E40C
8
1.5. Dimensional sketch
Dimensions in mm
Free Space
There must be sufficient space at the top and bottom to be able to suspend the unit and to be able to connect all feed and drain pipes. Normally, roughly 300 mm is required. It is recommended to leave a free space of 150 mm on the left (for servicing reasons) and 50 mm on the right of the unit. The front of the unit must be easily accessible for servicing at all times.
Coopra Advanced Heating Technologies Installation manual E40C
9
1.5.1. Technical data
Boiler type
35C
power reduced boiler to meet Italian market
Gas type
natural gas G20 natural gas G25 LPG G30/G31
Nominal gas pressure 20 mbar 25 mbar 37/50 mbar
Heat input CH (gross) 8.1 – 38.5 kW
Heat input CH (net) 7.3 – 34.7 kW
Nominal output CH at 80/60ºC 7.2 – 33.7 kW
Nominal output CH at 50/30ºC 7.9 – 36.1 kW
Efficiency at 80/60ºC (net) Low load = 98.7 %; High load = 97.2 %
Gas technical data
Efficiency at 50/30ºC (net) Low load = 108.3 %; High load = 104.1 %
Boiler type 40C
Gas type
natural gas G20 natural gas G25 LPG G30/G31
Mains voltage / Frequency 230 V / 50 Hz
Power consumption (max.) 144 W
Electrical data
Automatic recognition of thermostat connection
(potential free contact)
on/off thermostat or OpenTherm control
Height 700 mm
Width 360 mm
Depth 300 mm
Dimensions and weight
Weight 35 kg
Heat input CH (gross) 8.1 – 41.1 kW
Heat input CH (net) 7.3 – 37.0 kW
Nominal output CH at 80/60ºC 7.2 – 36.0 kW
Nominal output CH at 50/30ºC 7.9 – 37.9 kW
Efficiency at 80/60ºC (net) Low load = 98.7 %; High load = 97.2 %
Gas technical data
Efficiency at 50/30ºC (net) Low load = 108.4 %; High load = 104.2 %
CO2 on low-high fire 8.2% - 8.8% 8.2% - 8.8% 9.2% - 9.8%
CO (0% 02) on low-high fire 12 – 100 ppm
Emission value
NOX (0% O2) on low-high fire 10 – 30 ppm
at 80/60ºC < 70ºC
Flue gas­temperature
at 50/30ºC < 35ºC
Maximum chimney resistance
Air feed and flue tube together
85 Pa
Gas Ø 15 mm
CH (flow and return) Ø 20 mm
Connections
Overflow Ø 15 mm
2-pipe system Ø 60 – Ø 60 mm or Ø 80 – Ø 80 mm
Air feed and flue tube system
Concentric system Ø 60 / 100 mm or Ø 80 / 125 mm
Water contents 0,8 L Max. temperature 90°C
Boiler primary heat exchanger
Max. Water pressure 3 bar
Pump high 40 dB(A)
Sound level
Pump low 30 dB(A)
Certification
CE Identification number CE0063-AT3070
Coopra Advanced Heating Technologies Installation manual E40C
10
1.5.2. Boiler components
No Description
1 Primary heat exchanger 3 Pump 6 Glow plug 7 Ionisation probe 8 Burner type 30/40 9 Vapour tray 10 Gas valve 11 Fan 12 Venturi type 40 13 Water pressure sensor 14 Return sensor 15 Flow sensor 16 Safety device 18 Flue gas sensor 20 Type plate 21 Condensation water overflow 22 Gas connection 23 Central heating return connection 24 Central heating flow connection
Loading...
+ 22 hidden pages