Cooper Security EXP-PSU Installation Manual

Page 1
Page 2
Page ii
© Cooper Security Ltd. 2011
IN NO EVENT WILL COOPER BE LIABLE FOR ANY SPECIAL, CONSEQUENTIAL , OR INDIRECT LOSS OR DAMAGE, INCIDENTAL DAMAGES, STATUTORY DAMAGES, EXEMPLARY DAMAGES, LOSS OF PROFITS, LOSS OF REVENUE, LOSS OF ANTICIPATED SAVINGS, LOSS OF BUSINESS OR OPPORTUNTIY, LOSS OF GOODWILL OR INJURY TO REPUTATION,
LIQUIDATED DAMAGES OR LOSS OF USE, EVEN IF INFORMED OF THE POSSIBILITY OF SUCH DAMAGES. COOPERS
LIABILITY FOR DAMAGES ARISING OUT OF OR RELATED TO A PRODUCT SHALL IN NO CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT FROM WHICH THE CLAIM ARISES. TO THE EXTENT PERMITTED BY APPLICABLE LAW, THESE
LIMITATIONS AND EXCLUSIONS WILL APPLY WHETHER COOPER‟S LIABILITY ARISES FROM BREACH OF CONTRACT,
BREACH OF WARRANTY, TORT (INCLUDING BUT NOT LIMITED TO NEGLIGENCE), STRICT LIABILITY, BY OPERATION OF LAW, OR OTHERWISE.
Every effort has been made to ensure that the contents of this book are correct. The contents of this book are subject to change without notice.
Printed and published in the U.K.
This manual applies to the EXP-PSU with version 2 software.
For Your Safety
This book contains several passages alerting you to potential problems or hazards. Each of these are marked by the words Note, Caution or WARNING.:
Note:
Describes conditions that may affect the proper functioning of the equipment (but will not damage the equipment).
Caution:
Describes actions that will physically damage the equipment and prevent its proper function.
WARNING:
Describes actions that are hazardous to health, or cause injury or death.
Please pay particular attention to these marked passages.
www.coopersecurity.co.uk Product Support (UK) Tel: +44 (0) 1594 541978. Available between: 08: 30 and 17:00 Monday to Friday. Product Support Fax: (01594) 545401 email: techsupport@coopersecurity.co.uk Part Number 12071708 7/7/11
Page 3
Page iii
CONTENTS
1. Introduction ..................................... 1
About this Guide ............................... 1
2. Before You Begin .............................. 1
Preparation ......................................... 1
Siting the EXP-PSU ........................... 1
Guided Tour ........................................ 1
Opening the Case ............................. 1
Power Availability ................................. 3
Bus Cabling Requirements ........................... 4
Cable Type ....................................... 4
Cable Segregation............................. 4
Voltage Drop .................................... 4
Connecting A Remote Power Supply .... 4
3. Installation ....................................... 6
Caution: Static Electricity ................... 6
Step 1. Fit the Case .............................. 6
Fitting ............................................. 6
Installing the Lid/Back Tamper ........... 6
Step 2. Run Bus Cable .......................... 6
Step 3. Connect EXP-PSU to the Bus....... 6
Addressing the EXP-PSU .................... 7
Step 4. Connect to Mains ...................... 7
Mains Cabling ................................... 7
Step 5. Connect Wired Zones ................. 7
Four Wire Closed Circuit Connections .. 7
Fully Supervised Loop Connections...... 7
Step 6. Connect Wired Outputs .............. 8
Remote Loudspeaker (Optional).......... 8
Wired Outputs .................................. 8
Step 7. Fit a Plug-By Communicator ....... 9
Step 8. Fit and Connect Battery ............. 9
Step 9. Initial Power-Up .......................... 10
Step 10. Re-fit The Lid ......................... 10
4. Maintenance ................................... 11
5. Technical Specification ................... 11
General .............................................. 11
Capacities .......................................... 11
Power Supply...................................... 11
EN50131-6 ratings ........................... 11
Electromagnetic Compatibility ............... 12
Outputs ............................................. 12
Fuses ................................................. 12
Electrical Safety .................................. 12
Compliance Statements ....................... 12
Compatible Equipment ......................... 12
Page 4
EXP-PSU
Page iv
This page is intentionally blank.
Page 5
EXP-PSU
Page 1
1. Introduction
The EXP-PSU is a remote power supply intended for use in wired/wirefree alarm systems controlled by the i-onEX range of control units.
The power supply comprises a steel case containing a pcb (printed circuit board) and space for backup batteries.
The pcb holds the power supply circuits and provides two sets of terminals for a bus connection.
The pcb also provides a range of connectors for outputs, plug-by communicators, and up to 10 FSL (Fully Supervised Loop) or five CC (Closed Circuit) zones.
The EXP-PSU provides monitoring messages to the control unit over the system bus. These messages include Remote PSU Fault, Remote AC Fail, Remote Battery Fail, and Remote Low Output Voltage.
The EXP-PSU is designed and approved to be used as part of a Security Grade 2 or 3 system.
About this Guide
This guide shows the simple procedure required to physically install the EXP-PSU, connect it to the bus, zones and outputs for an i-onEX alarm system.
When you have completed the physical installation please consult the i-onEX Engineering Guide for details of providing a bus address for the unit.
2. Before You Begin
Preparation
Before installation you should carry out a survey of the site. You need to know how many and what kind of detectors will be connected to the EXP-PSU.
Siting the EXP-PSU
WARNING Ensure that the fixings are
strong enough to support the weight of the EXP-PSU, its lid and two 17Ah lead acid batteries. The total weight of the EXP-PSU plus batteries can be up to 18kg.
Do site the unit:
Close to the equipment it is powering.
Upright, batteries at the bottom. Within a protected area.
Do NOT site the unit:
In the entry or exit zones, or outside
the area covered by the alarm system.
Next to electronic equipment,
particularly computers, photocopiers or other radio equipment, CAT 5 data lines or industrial mains equipment.
Guided Tour
CAUTION: The printed circuit board for the EXP-PSU has been tested for Electromagnetic Compatibility (EMC). However, when handling the pcb you must take the standard precautions for handling static sensitive devices.
Opening the Case
To gain access to the interior of the EXP- PSU undo the screw at the bottom of the lid. Slide the lid vertically up, then swing the bottom of the lid out before moving the lid down and away from the case.
Figure 1 Opening the EXP-PSU.
WARNING: When connected to the mains with power applied mains voltages are present on the shrouded heads of the terminal screws of the mains connector.
Page 6
EXP-PSU
Page 2
1. Case back.
2. Cable entry holes for loudspeakers and communicators.
3. Fixing holes.
4. Plastic PCB tray.
5. Printed circuit board (PCB).
6. Cable entry holes for detector and keypad wiring.
7. Hole for back tamper fitting..
8. Space for batteries (two off).
9.Fused mains terminal block
10. Mains cable anchor point.
11. Cable entry hole for mains.
Figure 2 EXP-PSU
1. Bus connector IN (from control unit).
2. Bus connector OUT (to portion of bus powered by EXP-PSU).
3. Comms fuse fail LED.
4. Plug-by communicator connector (1 of 2).
5. Tamper switch connector.
6. Aux 1 power connector.
7. Aux 1 power fuse.
8. Aux 1 fuse fail LED.
9. Zone connector.
10. Aux 2 connector.
11. Outputs (transistorised).
12. I-RC01 connector.
13.Aux 2 fuse fail LED.
14. Aux 2 fuse.
15. Kick Start pins.
16. Battery 1 connector.
17. Battery 2 connector.
18. AC in connector.
19. Bus address display.
20. Sounder.
21. Loudspeaker connector.
22. Bus Addressing button.
23. Engineering keypad connector.
24. Bus OUT fuse fail LED.
25. RS485 terminator.
26. Status LEDs (from the top): MF = Mains Fail LB = Low Battery 12V = 12V Fault DIAG = See page 10
Figure 3 EXP-PSU Printed Circuit Board
0V
-LS+ AC IN
12V
AUX-2
0V A B
BUS IN
0V 12v A B
BUS OUT
OP3
OP2
OP1
Z6 Z7 Z8 Z9 Z10Z1 Z2 Z3 Z4 Z5
OP4
1
3
5
4
6
7
8
11
3
8
3
10 9
2
0V
-LS+ AC IN
12V
AUX - 2
0V A B
BUS IN
0V 12v A B
BUS OUT
OP3
OP2
OP1
Z6 Z7 Z8 Z9 Z10Z1 Z2 Z3 Z4 Z5
OP4
1 18
17
16 15
14 13
12
9 10 11
2122232425 26 20 19
2
4
3
5
6
7 8
Page 7
EXP-PSU
Page 3
Power Availability
Before connecting any devices to the EXP- PSU, you must make sure that the unit can provide sufficient current to power the portion of the system it is connected to during a mains failure for the time required to meet the appropriate standard.
EN50131-1 Grade 3 requires 30 hours provided that the control unit is fitted with an ATS4 communicator capable of transmitting a mains fail signal.
Note: When calculating the average load during the standby time period you must allow for at least two periods in alarm. To take the worst case these two periods of alarm should each be 15 minutes long, the maximum permitted in EN50131-1 section
8.6.
PD6662 Grade 3, under the same conditions, reduces the standby time requirement to 12 hours.
The amount of current available from the EXP-PSU depends on the size of battery fitted and its health. The current taken by the power supply‟s pcb, is given in
Technical Specifications EN50131-6 Ratings on page 11.
The following calculation shows a simplified example: in an alarm system with an EXP- PSU which is connected to five i-kp01 keypads, and 40 wired PIRs and a wired siren, the portion of the system powered by the EXP-PSU takes the following total quiescent current:
Device
Current
EXP-PSU PCB
50mA
40 x PIRs at 15mA each
600mA
3 x (wired expanders)
60mA
5 x i-kp01 at 30mA each (backlights off)
150mA
Siren (quiescent)
25mA
Total
885mA
During an alarm, these figures become:
Device
Current
EXP-PSU PCB
100mA
40 x PIRs at 15mA each
600mA
3 x (wired expander)
60mA
5 x i-kp01 at 60mA each (backlights off)
300mA
Siren (in alarm)
400mA
Total
1460mA
The total amp hours required = (0.885 A x 29.5h) + (1.46A x 0.5h) =
26.83Ah Note that this example assumes that the
communicator has its own power supply. Two new, fully charged, 17Ah batteries can
provide the charge required by the portion of the system in the example and would meet the EN50131-1 Grade 3 requirements.
A single new, fully charged, charged 17A battery can provide the charge required by the example system for PD6662 Grade 3 requirements.
Note: All current drawn from the 12V Aux terminals must be included in the overall calculation.
CAUTION: Ensure that the system does not demand more than the maximum current available from the EXP-PSU during an alarm, see page 11.
Page 8
EXP-PSU
Page 4
Bus Cabling Requirements
Cable Type
In general, the EXP-PSU requires standard 7/0.2 un-screened four core alarm cable for wiring the bus.
For maximum performance in harsh environments use twisted pair screened cable with a characteristic impedance of 100-120ohms eg: Belden 8132 or other cable designed for RS485.
Use one pair for data lines A and B. Use the other pair for 12V and 0V. For optimum performance the voltage at the keypads and expanders should be greater than 12V.
Screened cable may prove necessary if the installation site has equipment that produces high levels of R.F. (Radio Frequencies). For example, welding equipment is known to produce a large amount of radio interference. If screened cable is required, you should keep to the following guidelines:
1. Avoid earth loops by connecting the screen on the cable to mains earth at the control unit but not at the keypad, expander or EXP-PSU.
2. The continuity of the cable screen is most important and screens MUST be continuous along the full length of the cable.
3. Where the cable enters any metal enclosure, ensure the screen is isolated from the case.
Cable Segregation
Segregate the bus cabling from any other wiring, such as mains supply cables, telephone cables, computer network cables and R.F. cables. Use cable ties to keep cables separated.
Keep the bus cable clear of cables supplying sounders, extension loudspeakers or any other high current devices.
Voltage Drop
In order for the system to work correctly, the voltage at each device must NOT drop below 10.5V even when running on the standby battery. Cooper Security recommend that the voltage at each device should stay above 12V.
Standard 7/0.2 alarm cable has a resistance of 8 Ohms per 100m per core. The voltage drop is calculated using the following formula: V Drop = Current drawn x cable length x 0.08 x 2.
Table 1 on the next page shows the voltage drop against the current drawn and cable length.
The shaded area shows where the voltage drop would cause the bus voltage to fall from 13.8V to below 12.0V when using a single core.
Reducing Voltage Drop - Method 1:
Double up the supply connections (12V and 0V), which will halve the resistance on each core and therefore halve the voltage drop. When using Table 1 to calculate the expected voltage drop, simply divide the voltage drop for a single core by two.
Reducing Voltage Drop - Method 2:
Supply the detection devices from the Aux output on separate cores. This is the preferred method of reducing voltage drop as detectors generally operate at lower voltages (9.5V). When using this method, the network cable must have two spare cores.
Connecting A Remote Power Supply
Figure 4 shows the recommended method of connecting the EXP-PSU power supply. The bus cable from the control unit terminates on the EXP-PSU Bus In connector and a new cable starts from the EXP-PSU Bus Out connector. See page 6 for more details.
Page 9
EXP-PSU
Page 5
Table 1. Voltage Drop
Current Drawn
Cable Length (Standard 7/0.2 alarm cable)
10m
20m
30m
40m
50m
60m
70m
80m
90m
100m
60mA
0.10V
0.19V
0.29V
0.38V
0.48V
0.58V
0.67V
0.77V
0.86V
0.96V
80mA
0.13V
0.26V
0.38V
0.51V
0.64V
0.79V
0.90V
1.02V
1.15V
1.28V
100mA
0.16V
0.32V
0.48V
0.64V
0.80V
0.96V
1.12V
1.28V
1.44V
1.60V
120mA
0.19V
0.38V
0.58V
0.79V
0.96V
1.15V
1.34V
1.54V
1.74V
1.92V
140mA
0.22V
0.45V
0.67V
0.90V
1.12V
1.34V
1.57V
1.79V
2.02V
2.24V
160mA
0.26V
0.51V
0.77V
1.02V
1.28V
1.54V
1.79V
2.05V
2.30V
2.56V
180mA
0.29V
0.58V
0.86V
1.15V
1.44V
1.73V
2.02V
2.30V
2.59V
2.88V
200mA
0.32V
0.64V
0.96V
1.28V
1.60V
1.92V
2.24V
2.56V
2.88V
3.20V
220mA
0.35V
0.70V
1.06V
1.41V
1.76V
2.11V
2.46V
2.82V
3.17V
3.52V
240mA
0.38V
0.79V
1.15V
1.54V
1.92V
2.30V
2.69V
3.07V
3.46V
3.84V
260mA
0.42V
0.83V
1.25V
1.66V
2.08V
2.50V
2.91V
3.33V
3.74V
4.16V
280mA
0.45V
0.90V
1.34V
1.79V
2.24V
2.69V
3.14V
3.58V
4.03V
4.48V
300mA
0.48V
0.96V
1.44V
1.92V
2.40V
2.88V
3.36V
3.84V
4.32V
4.80V
320mA
0.51V
1.02V
1.55V
2.05V
2.56V
3.07V
3.58V
4.10V
4.61V
5.12V
340mA
0.54V
1.09V
1.63V
2.18V
2.72V
3.26V
3.81V
4.35V
4.90V
5.44V
360mA
0.58V
1.15V
1.73V
2.30V
2.88V
3.46V
4.03V
4.61V
5.18V
5.76V
380mA
0.61V
1.22V
1.82V
2.43V
3.04V
3.65V
4.26V
4.86V
5.47V
6.08V
400mA
0.64V
1.28V
1.92V
2.56V
3.20V
3.84V
4.48V
5.12V
5.76V
6.40V
Figure 4. Connecting Remote Power Supply Units
Page 10
EXP-PSU
Page 6
3. Installation
Note: The installation steps listed below assume that you have already decided on the required location for the EXP-PSU.
Caution: Static Electricity
Like many other electronic products, the EXP-PSU contains components that are sensitive to static electricity. Try not handle the PCB directly. If you must handle the PCB, take the standard precautions against damage by static electricity.
Step 1. Fit the Case
Fitting
To prevent access to the inside of the EXP- PSU through the holes in the rear of the case you must mount the unit on a wall or other flat surface.
Locate and mark the position of the case. Mark the position where the lid/back tamper bracket touches the wall.
Fit the tamper shroud at the position where the lid/back tamper touches the wall, see Figure 5.
Figure 5 Fitting Tamper Shroud.
Mount the case vertically, as shown in Figure 2. Use all three fixing holes. Use No14/M6 screws at least 50mm long, inserted into wall anchors appropriate for the type of wall. Figure 2 shows the fixing holes and cable entries.
WARNING Ensure that the fixings are strong enough to support the weight of the EXP-PSU, its lid and two 17Ah lead acid
batteries. The total weight of the EXP-PSU plus batteries can be up to 18kg.
Protect the unit from dust and drilling debris when drilling the fixing holes.
Installing the Lid/Back Tamper
Fit and connect the combined lid/back tamper (provided). Ensure that the switch is oriented as shown in Figure 6.
Figure 6 Lid/Back Tamper
Item 5 in Figure 3 shows the connector for the lid/back tamper.
Note that to be approved at Security Grade 3 you must fit the lid/back tamper.
Step 2. Run Bus Cable
Please read Bus Cabling Requirements on page 4.
Step 3. Connect EXP- PSU to the Bus
The EXP-PSU provides two bus connectors (items 1 and 2 on Figure 3).
Figure 7 Bus Wiring EXP-PSU
Use the BUS IN connector to terminate the bus cable from the part of the system that is being powered by the control unit (or other remote power supplies).
CAUTION DO NOT connect the 12V line of the bus to BUS IN.
Use the BUS OUT connector to terminate the bus cable to the portion of the system being supplied by the EXP-PSU.
0V
+12V
B
0V
From control unit Bus In
Bus Out
To rest of system
A
B
A
Page 11
EXP-PSU
Page 7
Addressing the EXP-PSU
The control unit assigns addresses to all devices connected to the bus. You must start this process off once the EXP-PSU is connected, during the system power up. See i-on160EX Engineering Guide for instructions.
Step 4. Connect to Mains
WARNING: ENSURE THAT THE MAINS SUPPLY IS DISCONNECTED AND ISOLATED BEFORE MAKING ANY MAINS CONNECTIONS. All mains electrical connections must be carried out by a qualified electrician and must comply with the current local regulations (e.g. IEE).
Mains Cabling
Note: To avoid mains interference, the mains cable must enter the EXP-PSU through its own cable entry hole ( 9 in Fig
2) and must not be mixed with other
cables.
Mains Connection
Figure 8 shows the mains connection. Connect to a suitable supply using a double pole disconnect device in accordance with EN60950-1.
Caution: Do not apply power at this
point.
Anchor the mains cable with a strain-relief tie. There is a eye located near the mains cable entry hole for this purpose.
Figure 8 Mains Connection
Step 5. Connect Wired Zones
The EXP-PSU can be used for either four wire Closed Circuit (CC) detectors, or two wire Fully Supervised Loop (FSL) detectors.
Four Wire Closed Circuit Connections
Figure 9 shows the wiring for CCL zones on the EXP-PSU.
Figure 9 EXP-PSU CCL Zone Wiring
Fully Supervised Loop Connections
Figure 10 shows the wiring connections for FSL zones on the EXP-PSU. Note that the resistance values shown are examples.
Figure 10 FSL Zone Wiring EXP-PSU
The allowed values for Alarm Contact/End of Line are: 4k7/2k2. 1k0/1k0, 2k2/2k2, or 4k7/4k7.
Note: Use the same pair of values for ALL FSL wired circuits on the EXP-PSU.
When programming select the FSL resistor values for the EXP-PSU in Installer Menu Detectors Devices Wired Expanders - Edit Expander.
If you wish to connect two or more detectors to a FSL zone, Figure 11 shows the connections required.
L N
T500mA 250V
230V ~50Hz 350mA
Page 12
EXP-PSU
Page 8
Figure 11 Wiring Two Detectors per Zone
FSL.
Figure 12 shows an example of wiring double doors with two door contacts to one FSL zone. Each door contact is a reed switch, connected between the outer terminals. The inner (shaded) terminal is not connected, and provides a spare terminal.
Figure 12 Example: Wiring Two Door
Contacts to One FSL Zone.
Figure 13 shows an example of wiring a trouble/masking output using the 3-
resistor method. Note that you must use
2k2 and 4k7 resistors as shown. Other values will not work (See System Options
Masking in the i-on160EX Engineering Guide).
Figure 13 Example: Wiring a
Trouble/Masking Zone, 3 Resistor Method.
Step 6. Connect Wired Outputs
Remote Loudspeaker (Optional)
If you wish to add a 16 Ohm wired Loudspeaker unit, then connect it as shown in Figures 14. Do not connect another loudspeaker in parallel.
Figure 14 Connecting Wired Peripherals
Note: Loudspeakers are not warning devices as described by EN50131-4. Although loudspeakers may mimic alarm tones, they also give alert tones and other progress tones when setting and unsetting the alarm system.
During normal operation any loudspeakers connected to the EXP-PSU repeat setting and entry tones for the partition that the unit is allocated to. During an alarm the loudspeakers repeat alarm tones.
Each 16 Ohm loudspeaker draws up to 280mA in operation. If there is more than one loudspeaker connected to the EXP-PSU then the +12V line on the Bus Out connector may not be able to supply sufficient current during an alarm.
Wired Outputs
The EXP-PSU provides connections for up to four transistor driven outputs. By default the outputs are 0V when active, +12V when inactive. If you wish to reverse the polarity of these outputs see Changing the
Polarity of a Wired Output in the i-onEX Engineering Guide. Figure 15 shows an example of using
an expander output to drive an LED.
Figure 15 Using EXP-PSU Wired Outputs.
If required you can connect an i-rc01 relay card to the pins immediately above the output terminals (see 12 in Figure 3) or directly to the output terminals. The i-rc01 provides four voltage free outputs that mimic OP1 to OP4.
Zone1
2K2 EOL
4K7
Alarmcontacts Alarmcontacts Tamper contacts Tamper contacts
Max 10 devicesper circuit (notrecommended)
2K2 EOL
Spare
ContactsContacts
4K7
Black
Red
Blue Tozone contacts
Yellow
Zone 1
2K2 EOL
4K7
2K2
Alarm contacts
Trouble contacts Tamper contacts
+LS
-LS
-LS +
Page 13
EXP-PSU
Page 9
Step 7. Fit a Plug-By Communicator
The EXP-PSU can be connected to a separate communicator or speech dialler (for example, the Scantronic 8400, 660, RedCare GSM or RedCare Dual Com). Figure 16 shows the connections provided by the communications wiring harness.
Each output pin of the communications connector on the EXP-PSU follows the state of the corresponding pin on the control unit. These EXP-PSU communication outputs cannot be programmed independently of the control unit communication outputs. Note that the output types shown in Figure 16 are the Factory default types. See the i-onEX Security System Engineering Guide for details on how to change the defaults on the control unit (and, in consequence, on the EXP-PSU).
Figure 16 Plug-By Communicator Wiring
Note: Comms O/P4 will be active when the system is unset. This is normal.
To fit a communicator, follow the instructions below.
Caution: Follow the instructions in the order
shown, or you may damage the EXP- PSU and/or communicator.
1. Disconnect mains power from the EXP- PSU, remove the case lid, and disconnect the battery (if the system has already been installed).
2. Make any necessary connections from the communicator to the communication wiring harness. The default is a 12V positive voltage when the output is inactive.
Refer to the next section if you are
using a dual-path communicator.
3. Plug the Communication Wiring Harness onto the communications connector on the main PCB.
If the system has already been installed:
4. Re-connect the battery.
5. Fit the case lid.
6. Apply mains power.
7. Test communicator operation.
Note: You will need to speak to the ARC in order to confirm that the communicator has worked correctly.
Line Monitoring for a Dual-Path Communicator
If a standalone dual-path (landline and mobile) communication device, such as a RedCARE GSM, is connected to the plug-by connector, you need to do the following to obtain correct line fault reporting that complies with BSIA Form No.175, April 2005:
1. Reprogram one of the plug by outputs to type ATS Test” and wire that output to the ATS Test input of the communicator.
2. Wire the Line Fault output of the communicator to the Line Fault input of the plug-by connector. The communicator must provide +12Vdc to indicate a line fault (for example, if the Line Fault output at the communicator uses a relay, connect the common terminal of the relay to +12Vdc and the normally-open terminal to the Line Fault input of the plug-by connector).
The control unit will generate an "ATE L.F. Single" alert if only one of the networks is not available, or "ATE L.F. All" if both networks are not available.
Step 8. Fit and Connect Battery
Fit either one to two 17Ah Lead Acid batteries into the battery compartment in
Page 14
EXP-PSU
Page 10
the bottom of the EXP-PSU. Use batteries whose case material has a minimum rating of UL94V-2 in order to comply with EN60950 (this standard applies because of the energy content of 17Ah batteries).
See Figure 17. See page 3 for example calculations of battery requirements.
WARNING 17Ah lead acid batteries weigh 6kg each. Do NOT drop.
Connect the battery leads, red to the positive, black to the negative terminals of the battery. Connect the other ends of the leads to either BATT1 or BATT2 (16 and 17 on Figure 3).
If you are fitting only one battery then connect it to BATT1 (the lower set of pins) and disable alerts on BATT2 (see the i-onEX Range Engineering Guide).
Figure 17 Fitting the Batteries
Note: Connecting the batteries without mains power will not start the system. (See “Programming Before Installationin the i- on160EX Engineering Guide.)
Step 9. Initial Power-Up
Please see the i-onEX Security System Engineering Guide for an explanation of bus
addressing.
When you apply power to the unit you may notice the DIAG LED flashing (see 26 on Figure 3). The LED gives one, two, three or four flashes a second. Each of these sequences has the following meaning.
No. Flashes
Meaning
One
Communication with control unit over bus is OK
Two
No communication over the bus in the last 10 seconds.
Three
No bus address allocated to EXP-PSU
Four
No poll request received from control unit in the last minute.
The other status LEDs on the pcb (26 in Figure 3) have the following meaning:
MF
Red=No mains AC.
LB
Amber = Absent or faulty battery
12V
Red=12V fault
When glowing the following LEDs indicate possible short circuits in the cabling.
Comms fuse fail (3 in Figure 3)
Red=communication outputs failed. See Note 1
Aux 1 fuse fail (8 in Figure 3)
Red=Aux 1 fuse blown. See Note 2
Aux 2 fuse fail (13 in Figure 3)
Red=Aux 2 fuse blown. See Note 2
Bus OUT fuse fail (24 in Figure 3)
Red=The output power on the bus has failed. See Note 1
Notes:
1. These outputs are protected by
polyswitches, which will reset themselves when the short is removed.
2. These outputs are protected by F-1A
20mm fuses which must be replaced once the short is removed.
Step 10. Re-fit The Lid
Assemble and close the EXP-PSU:
a) Fit the lid of the EXP-PSU into the back of the case (see Fig 18). b) Fit and tighten the lid fixing screw.
Figure 18 Replacing the EXP-PSU lid.
Page 15
EXP-PSU
Page 11
4. Maintenance
The EXP-PSU should be inspected at least once per year. At each inspection:
Check the unit for obvious signs of
damage to the case or its lid. Check the action of the back tamper.
Check the condition of the standby
battery. Check the cabling to EXP-PSU
expander(s) for signs of damage or
wear. Test any sounders. Note that if you wish to find the location of
any keypad or expander you can employ the Test Locate Bus Device option in the Installer Menu. Use this option to make a selected bus device give a continuous tone from its sounder. Once you have found the bus device you can silence the tone by opening the case and so activating the devices tamper.
5. Technical
Specification
General
Product name
EXP-PSU.
Product Description
External PSU with wired zones and plug by communicator connection.
Manufacturer
Cooper Security Ltd.
Environmental
Class II.
Operating temperature
Tested -10 to +55°C.
Humidity
0 to 93% RH, non- condensing.
Case material
Steel.
Dimensions:
Size:
427 x 400 x 101, mm HxWxD.
Weight:
6 kg (without stand-by batteries).
Capacities
Zones
10 max
Outputs
16 plug-by communicator outputs, plus 4 open collector transistor outputs
Loudspeakers
1 output, minimum impedance 16 Ohms
Power Supply
This product complies with the requirements of EN50131-6 Type A power supply at Grade 3 and environmental class 2.
Power supply type
A
Mains power supply requirements
230VAC +10%/-15%, 350mA max, 50Hz.
Total power supply capacity:
3.0A (of which 1.5A is used for battery recharge and 1.5A is available for powering the system).
Aux 1 12V supply*:
1A max
Aux 2 12V supply*:
1A max
Comms power supply*:
400mA max
12V Expander Bus OUT*:
400mA max LS connectors
280mA in alarm.
*Note: The ratings given here represent the maximum current that can be drawn before triggering over-current protection.
EN50131-6 ratings
The EXP-PSU provides space for two 17Ah batteries, giving a total of 34Ah charge.
Under EN50131-1 for Security Grade 3 installations the required battery standby time is 30 hours, provided the system is fitted with an ATS4 communicator capable of transmitting a mains fail signal
This means that all the devices powered by those backup batteries, within the EXP- PSU, including the EXP-PSU itself, should together draw no more in total than an average of 1.1A over a 30 hour standby time. Note that for Security Grade 3 the i- on160EX or EXP-PSU must use a plug-by communicator, which may have its own power supply.
Under PD6662, battery standby time requirements for Security Grade 3 drop to 12 hours, provided the system is fitted with an ATS4 communicator capable of transmitting a mains fail signal.
For Security Grade 2 the required battery standby time is 12 hours. However, the total average current available over 12 hours from the EXP-PSU batteries is limited by the power supply to 1.5A. (The current is limited to 1.5A because when mains is present the 3.0A power supply reserves 2x750mA to recharge batteries, leaving
1.5A available to supply the system.)
Page 16
EXP-PSU
Page 12
To meet Security Grade 2 the control unit can be fitted with a plug-on communicator, for example the i-sd02.
The table below shows the current consumption of the EXP-PSU itself and each device that can be fitted to it.
EXP-PSU power requirement:
50mA quiescent. 100mA max
Keypad power requirement:
30mA (backlight off) 45mA (backlight on) 65mA (backlight on) 60mA in alarm
Wired Expander requirement
20mA max quiescent. 300mA in alarm if sounder connected.
Radio Expander requirement
40mA max quiescent 320mA in alarm if sounder connected.
Battery charging requirement:
750mA per battery (recharge within 24 hrs)
Plug-by Communicator pins require:
5mA each when active. 10 FSL zones
5mA
5 CCL zones
7mA
12V Bus output voltage range :
10±0.5V to 13.8V
Aux 1 & 2 12V output voltage range:
10±0.5V to 13.8V Max p-to-p ripple voltage:
0.5V
Standby Battery:
12V, 17Ah sealed lead acid, 2 off (not supplied).
Low battery‟ fault
at:
< 12V
Aux power output fault at:
< 9V
Deep discharge protection at:
10±0.5V
Standby time:
See Power Availabillity” on page
3.
Electromagnetic Compatibility
Immunity
Conforms to EN50130-4.
Emissions
Conforms to EN61000-6-3.
Outputs
O/P 1 - 4
Open collector transistor, +12VDC when inactive, 0V when active. 500mA max.
Plug-by O/P 1-16
Open collector transistor +12VDC when inactive, 0V when active, 50mA max.
LS (loudspeaker)
Min impedance 16 Ohm per output, current consumption = 280mA in alarm.
Fuses
The EXP-PSU has a replaceable T500mA mains fuse.
The Aux 1 and Aux 2 outputs are protected by separate F-1A 20mm fuse.
Electrical Safety
Conforms to EN60950-1.
Compliance Statements
The EXP-PSU is a type B ACE (as defined in EN50131-3 clause 8.7).
The EXP-PSU is compliant with EN50130-5 environmental class II.
The EXP-PSU is suitable for use in systems designed to comply with PD 6662: 2004 at grade 3.
When installed correctly the EXP-PSU is capable of compliance with EN50131 at Grade 3.
If the installer selects a non-compliant configuration then they must remove or adjust compliance labelling
Compatible Equipment
i-on160EX 160 zone expandable
control panel
i-on30EX (available end of 2011)
30 zone expandable control panel
i-rc01 Relay Card
KEY-ENG Engineering keypad.
xcelw Wired PIR
xcelwpt Pet tolerant wired PIR
Loading...