Cooper Power Systems Kyle Type ME Series Maintenance Instructions Manual

Figure 1. Kyle
®
Type ME electr onic recloser control
These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide direction for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user’s purpose, please contact your Cooper Power Systems sales engineer.
April 2002
Reclosers
Type ME Electronic Recloser Control, Form 3 and 3A Maintenance Instructions - Basic
1
CONTENTS
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Periodic Field Inspection and Maintenance . . . . . . . 6
Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Circuit Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Plug-In Circuit Boards Function . . . . . . . . . . . . . . . .10
Battery Charging Board . . . . . . . . . . . . . . . . . . . .10
Phase Trip No. 1 Board . . . . . . . . . . . . . . . . . . . .11
Phase Trip No. 2 Board . . . . . . . . . . . . . . . . . . . .11
Ground Trip No. 1 and No. 2 Boards . . . . . . . . . .11
Output Board . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Diode Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Recloser-Reset Board . . . . . . . . . . . . . . . . . . . . .12
Closing Coil Control Fuse . . . . . . . . . . . . . . . . . . . . .12
Interchangeability of Boards Between Form 2,
Form 3 and Form 3A Electronic Controls . . . . . . . . .12
Troubleshooting and Testing . . . . . . . . . . . . . . . . . . .13
Detailed Circuit Checks . . . . . . . . . . . . . . . . . . . . . . .14
Input Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Internal dc Load Current Signal . . . . . . . . . . . . . .
18
Internal Minimum Trip Signal .....................................19
Time-Current Characteristic Curves (TCC) ................20
Control-Recloser operation ........................................22
Major Control Damage ...............................................29
Battery Charging ........................................................31
Mechanical and Electrical Hardware ..........................35
Battery Maintenance ...........................................................35
Battery Specifications ......................................................35
Maintaining Battery Charge .............................................35
Field Testing a Battery .....................................................35
Shop Testing a Battery .....................................................36
Appendix I ...........................................................................37
Test Sheet ........................................................................37
Appendix II ..........................................................................38
List of Electronic Recloser Maintenance Manuals ...........38
Appendix III .........................................................................38
List of Electronic Control Accessory Manuals ..................38
Appendix IV .........................................................................38
Service Parts List .............................................................38
Appendix V ..........................................................................41
Form 2 Connection Diagram ............................................42
Form 3 Connection Diagram ............................................44
Form 3A Connection Diagram .........................................48
88936KMA
S280-75-2
Service Information
2
TYPE ME ELECTRONIC RECLOSER CONTROL
The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equip­ment should install, operate, and service it.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions.
• Is trained in industry-accepted high- and low-voltage safe operating practices and procedures.
• Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment.
• Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc.
Following is important safety information. For safe instal­lation and operation of this equipment, be sure to read and understand all cautions and warnings.
Safety Instructions
Following are general caution and warning statements that apply to this equipment. Additional statements, relat­ed to specific tasks and procedures, are located through­out the manual.
SAFETY INFORMATION
SAFETY FOR LIFE
Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, marketing, and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment and support our “Safety For Life” mission.
This manual may contain four types of hazard statements:
DANGER: Indicates an imminently haz-
ardous situation which, if not avoided, will
result in death or serious injury.
WARNING: Indicates a potentially haz-
ardous situation which, if not avoided, could
result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury.
CAUTION: Indicates a potentially hazardous situ­ation which, if not avoided, may result in equip­ment damage only.
Hazard Statement Definitions
WARNING: This equipment is not intended to
protect human life. Follow all locally approved procedures and safety practices when installing or oper­ating this equipment. Failure to comply can result in death, severe personal injury and equipment damage.
G102.1
DANGER: Hazardous voltage. Contact with
hazardous voltage will cause death or severe personal injury. Follow all locally approved safety pro­cedures when working around high and low voltage lines and equipment. G103.3
WARNING: Before installing, operating, main-
taining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage.
G101.0
WARNING: Power distribution equipment must
be selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety proce­dures. These instructions are written for such personnel and are not a substitute for adequate training and expe­rience in safety procedures. Failure to properly select, install, or maintain this equipment can result in death, severe personal injury, and equipment damage. G122.2
!
SAFETY
FOR LIFE
!
SAFETY
FOR LIFE
!
!
!
!
!
!
!
S280-75-2
3
Figure 2. Electronic control panel.
88937KMA
INTRODUCTION
Service Information S28O-75-2 covers basic maintenance instructions for the Type ME electronic control. The manual includes a general description of the control, its operating principles and instructions for periodic inspection and testing. Service parts lists along with ordering information are includ­ed in Appendix IV.
An introduction to the Form 3A, Type ME, electronic control is available on video cassette (KSPV3); in this program the function of all standard operating and programming features is explained.
The factory service department offers maintenance training
courses for Type ME controls. These classes, taught by ex-
perienced service technicians, are held at the factory’s in-house training facility. For additional information, contact your sales engi­neer.
DESCRIPTION
The Kyle Type ME electronic recloser control (Figure 1 ) is com­prised of a number of programmable, solid-state electronic circuits that perform the command functions involved in automatic recloser operation. It is used to operate all Kyle electronically controlled reclosers.
A swing-out front panel contains the programming and operating
elements of the control (Figure 2). The upper, black portion
4
Figure 3. Tie board on back of front panel mounts the individual printed cir cuit boar ds.
Type ME Electronic Recloser Control
88938KMA
of the front panel contains the plug-in components and setting knobs for programming automatic recloser operation. The switches and indicators used for manual operation and service are grouped on the bottom, light portion of the panel.
The front panel is backed by a printed-circuit tie board which supports and interfaces the plug-in circuit boards with other related circuit components (Figure 3). Program-altering, remote control, indicating, and general convenience acces­sories can be added to further expand and enhance the appli­cation capabilities of the control.
Line current flowing through the recloser is sensed by three internally mounted bushing-current transformers, one on each phase. When the phase current, or the zero-sequence (ground)
current, exceeds its programmed minimum-trip value, the electronic control initiates the programmed sequence of recloser tripping and reclosing operations. If the fault is tempo­rary, the control ceases to command recloser operations after successful reclose, and the control resets to the start of its operating sequence after a preset time delay. If the fault is permanent, the control performs its complete programmed sequence of recloser commands and locks out with the reclos­er open. Once locked out, the control must be manually reset to the start of its operating sequence which simultaneously closes the recloser.
Factory-calibrated timing plugs establish the time-current characteristics for both phase and ground tripping. Two sets of individual timing curves provide dual timing for both phase and ground.
S280-75-2
5
Figure 4. Typical operating sequence of an electr onically contr olled rec loser under permanent fault conditions.
Figure 5. Typical operating sequence of an electr onically contr olled rec loser under temporary fault conditions.
OPERATION
Since the understanding of the terminology and the operat­ing sequences of an electronically controlled recloser is important to the rest of this maintenance manual, examples of typical operating sequences of an electronically controlled recloser under permanent fault (Figure 4) and temporary fault (Figure 5) conditions are given. The definition of the terms and callouts used in Figures 4 and 5 are:
Minimum Trip—Minimum trip is usually set at greater
than 2 times (200%) the maximum expected load current to help prevent nuisance tripping on inrush currents, while still being sensitive to low level faults.
Over-Current—Any current that exceeds the minimum-
trip level of the control.
Permanent Fault—Any over-current condition that per-
sists through the operating sequence of the control.
Temporary Fault—Any over-current condition that does
not persist through the operating sequence of the control.
Home Position—Position of sequence relay immediately after a
reset operation of the control. Reset operation can be either manual, by moving the Manual Control Switch to “CLOSE”, or automatic, after a temporary fault.
Lockout—Sequence-relay position when over-current is not
cleared before the operating sequences of the control are exceeded; control and recloser are tripped and held open until manually reset with the Manual Control Switch, or remotely with one of the remote close accessories.
TCC—Time-Current-Characteristic-Curve.
Reclose Interval—Time-delay interval for each reclosing opera-
tion within the operating sequence of the control.
Fault Level Current—Any current that exceeds the minimum-
trip level of the control.
Normal Load—Any current below the minimum-trip level of the
control.
6
Figure 6. Functional block diagram of Type ME control.
Type ME Electronic Recloser Control
A functional block diagram of the control operation is shown in Figure 6. Line current conditions are continuously monitored by the three bushing-type current transformers in the recloser. output from these transformers is fed to the trip network in the control, which includes: the minimum-trip resistors, isolation transformers, and rectifier circuits.
If current remains above the minimum-trip level, the tripping —reclosing sequence of fast and delayed operations is repeat­ed as programmed to lockout.
When current above the selected minimum-trip level is detected in one or more phases, the following chain of events will occur for an operating sequence of two-fast and two­delayed operations:
The overcurrent signal is integrated with time on the charac­teristic curve of the timing plug in Socket 1 to produce the sig­nal which energizes the trip circuit. Energizing the trip circuit connects the battery to the trip solenoid, tripping the recloser. Simultaneously, the sequence relay advances to energize the first reclosing interval-delay plug. Upon expiration of this reclosing interval delay, a closing signal, from the control, clos­es the recloser, and the sequence relay sets up the circuitry for the second fast trip operation.
If the overcurrent is cleared before the operating sequence reaches lockout, the reset-delay circuit starts timing when the recloser closes into the unfaulted line. When the reset-delay plug times out, the sequence relay is reset to the start or “HOME” position and the control is ready for another two-fast, two-delayed trip-operating sequence. However, should the fault restart before the reset plug times out, the control will continue its operating sequence, where it left off last, and the reset-delay timing will be erased.
Ground-fault sensing and tripping operations occur exactly the same as phase-fault sensing and tripping, except that zero-sequence (ground) current is sensed instead of phase current. The ground-fault circuitry includes its own minimum­trip resistor, fast and delayed trip-timing plugs, and number of fast operations setting. Reclose and reset intervals and opera­tions to lockout are common for both phase-trip and ground­trip modes of operation.
PERlODIC FIELD INSPECTlON AND MAINTENANCE
Periodic inspection of the ME control should include these proce­dures:
1. Remove control from service (if connected to an in service recloser): A. Switch Ground Trip Block switch to “BLOCK”. B. Disconnect control cable from control.
2. Check the outer surface of the control cabinet for paint scratches. Touch up any paint scratches to maintain the cabi­net condition.
3. If the second entrance hole in the bottom of the cabinet is not used, be sure that the hole plug is secure in the bottom of the housing to maintain its weatherproof design.
4. Inspect the gasketing. Check the control interior for any mois­ture or foreign matter. Repair or correct if necessary.
5. Check that the timing plugs, reset and reclosing interval delays, and minimum-trip resistors are firmly in their sockets (Figure 2).
6. Swing open the front panel. Check to see that all leads to tie­board terminals are secure (Figure 7).
CAUTION: Shorting battery positive to battery
negative at the battery test terminals will cause per­manent damage to the control. The control will be inoper­ative and possible misoperation (unintentional operation) of the recloser may result.
CAUTION: In order to prevent possible, misoper-
ation (unintentional operation) of the recloser, the control must be removed from service prior to performing any maintenance, testing or programming changes.
WARNING: High voltage. Contact with high volt-
age will cause serious personal injury or death. Follow all locally approved safety procedures when work­ing around high voltage lines and equipment.
!
!
!
S280-75-2
7
Figure 7. View of a Form 3A tie board (back if front panel.Notations in parenthesis after callout refer to the circuit points on the tie board dia­gram illustrated in Figure 57.
88939KMA
7. Check battery voltage. Three battery test terminals in the
lower right corner of the panel (Figure 2) are used to check battery voltage, quiescent drain, and charging rate. Refer to the “Battery Maintenance” instructions in this manual.
The left-hand pair of terminals (V) are connected directly across the battery output to check battery voltage. The red terminal (far left) is positive (+). The output voltage of a fully charged battery will normally be 26-28-volts. If lower, refer
to the “Detailed Circuit check—Battery Charging” and/or “Battery Maintenance” section of this manual.
If necessary, recharge the battery, as detailed in the
“Battery Maintenance” section.
8. Make sure circuit boards are secure in their receptacles. Examine wiring between transformers and tie boards to see if connections are in order. Close front panel and secure firmly with fasteners.
8
Figure 8. Detailed block diagram of Type ME control in lockout position.Letters in circles (A,B,etc.) refer to control cable receptacle connec­tion pins and to test points referred to in the "T r oub leshooting and Testing" section.
Type ME Electronic Recloser Control
9. Check control battery charging rate before returning the control/recloser to service; see the “Battery Maintenance” section for details on charging rate testing.
NOTE: The servicing procedures outlined in this manual are for a standard Type ME Form 3 and Form 3Acontrol and do not include the operational checks of any of the accessories that may be attached. In some cases the accessories may modify the standard operating characteristics of the Type ME control. Refer to catalog bulletin 280-75 for accessories furnished and/or Accessory opera­tion, Testing, and Installation manuals listed in Appendix lll of this manual.
10. Return control to service: A. Check battery to ensure that it is properly connected.
B. Move Manual Control Switch to match position of reclos-
er (open or closed). C. Reconnect control cable to control. D. Switch Ground Trip Block switch to “NORMAL”.
SERVICING Circuit Logic
Line current conditions are monitored continuously by three bushing-current transformers in the recloser, one on each phase. The current transformers are connected to the control­phase matching transformers in a typical “WYE” to “WYE” con­figuration. Zero-sequence current is derived from the vector sum of the phase currents and fed to a fourth ground matching trans­former.
The minimum-trip resistors calibrate the overall recloser trip current by diverting a portion of the recloser current from the control matching transformers.
The four matching transformers isolate the various signals
from each other and deliver an ac voltage proportional to the recloser-line current to the phase-trip No.1 end ground-trip No. 1 boards.
S280-75-2
9
Figure 9. Diagram of Form 3A tie board showing plug-in circuit boar d location.Form 3 tie boards are similar (see Figure 18), except some of the terminals are missing or in a slightly different location.
From this point, phase- and ground-trip signals are very
similar, and only phase signals will be described.
The phase-trip No. 1 board circuitry, consisting of a three­phase full-wave rectifier, which converts the ac input signal from three phase to a single do signal. The do signal is applied to the phase-trip No. 2 board which measures the do level, and determines whether a fault current exists at the recloser.
If the load current conditions are in the fault region, the mini­mum-trip portion of the phase-trip No. 2 board switches on, allow­ing the time-current curve circuits to start their programmed time delay. The time-current curves are driven by the same do voltage output of the phase-trip No. 1 board, and as a result higher fault­current levels will result in a shorter time delay before tripping.
10
Figure 10. Battery-charging board,
Type ME Electronic Recloser Control
82027aKMA 88940KMA
After the timing plugs have completed their cycle, the output board is triggered. The output board applies a 24-Vdc signal to the recloser trip coil, the control counter, and the control sequence relay. The output board is switched off when the recloser “a” contact de-energize the circuitry, including the sequence relay. The sequence-relay rotary contacts then advance to the next position in the tripping and reclosing cycle.
The recloser “b” contacts then close, connecting battery power to the reclose intervals of the control which provides a time delay for reclosing the recloser. The rotary close solenoid is then energized through the recloser “b” contacts, the control fuse, and the reclose portion of the control circuitry. This mechanically closes the closing contactor in the recloser— allowing the closing solenoid to be energized.
After closing the recloser “b” contact opens, this removes do
power from the entire closing circuit.
The automatic reset portion of the Form 3A control is ener­gized by the sequence relay and the recloser “a” contact; if a fault does not exist on either phase or ground trip, reset timing is initiated (unless connected to time after first trip). If a fault exists on either phase or ground, the reset timing is erased and is blocked for the duration of the fault. For Form 3, reset timing begins after the first tripping operation. Should the reset time-delay operate before the recloser has locked open, the sequence relay will return to the starting position and a new sequence of operations will begin.
NOTE: F3 controls can be updated, with the addition of the KA304ME, to duplicate the automatic reset mode of a F3A control.
The Form 3A control battery is charged by the ac input (120-or 240-Vac) to the control. The ac input is applied through a current limiting resistor and isolating transformer to the bat­tery charging board. The battery charging board converts the input to dc and supplies charging current to the control battery. on Form 3 controls, the battery is charged by bushing current transformers on the recloser unless equipped with an ac charging accessory. on motor operated reclosers, the ac sup­ply to the motor also supplies power to the Form 3 battery charger.
Plug-in Circuit Boards - Function
The ME control contains a total of eight plug-in circuit boards on which are assembled the bulk of its operating circuits. The boards and their function will be discussed individually in the order they appear on the tie board, starting with the bottom board.
BATTERY-CHARGING BOARD
The lowest board in the rack is the battery-charging board (Figure 10). Prior to serial number 50070 controls were equipped with a fixed rate potential charging board (MEA 388-1 ) as stan­dard equipment. After serial number 50070 a temperature regu­lated battery-charging board (MEA 1172) has been supplied as standard. !
The fixed rate charging board consists of a full-wave bridge rectifier, a capacitor, a reference zener diode and some resis­tors. The resistors control the charging rate into the battery, from the zener supply voltage.
The temperature regulated battery-charging board also makes use of a full-wave bridge rectifier, a capacitor, and a zener diode (used to regulate voltage). In addition a temperature sensitive thermistor is added to regulate the bias over a pair of transistors. These transistors are used in the circuit output to regulate the charging rate, in response to temperature. Several resistors are used in the transistor bias circuit; and one resistor is used to limit the maximum charging rate. A diode is placed in the output to protect the circuit from reverse bias. ‘
Energy for either battery-charging board comes from the 120­or 240-Vac source,through current limiting resistance and a potential transformer.
CAUTION: Do not replace a MEA 388-1 board
with a MEA 1172, or vice-versa. A MEA 388-1 board will be damaged if replaced ffor a MEA 1172. A MEA 1172 will not provide adequate charging current if replaced for a MEA 388-1
!
S280-75-2
11
Figure 14. Ground-trip No. 2 board.
Figure 20. Capacitor for CT-type battery charger.
86773KMA
Figure 13. Ground-trip No. 1 board.
88943KMA
Figure 11. Phase-trip No. 1 board.
88941KMA
88944KMA
PHASE-TRIP NO.1 BOARD
The second board from the bottom is the phase-trip No. 1 board (Figure 11). It has three full-wave diode sets, one for each phase, along with a loading resistor for each phase. This board also has the beginning circuits for the minimum trip function.
PHASE-TRIP NO. 2 BOARD
The phase-trip No. 2 board (Figure 12) carries the remaining cir­cuits for minimum-trip and the wave-shaping circuits for the timing plugs. There are two tabs on the phase-trip No. 2 board for the Form 3 and 3A control. one tab is labeled minimum-trip (MIN. TRIP)* and is battery plus for normal line currents and switches to battery minus for fault currents; the second tab marked (DIR. BLOCK)* is an inactive tab at this time.
* In early Form 3 boards, these tabs may not be labeled.
GROUND-TRIP NO. 1 AND NO. 2 BOARDS
The next two boards up, ground-trip No. 1 and No. 2 (Figures 13 and 14), are like the corresponding phase-trip boards, except that the ground-trip No. 1 board has only a single input diode bridge for ground current. These boards carry almost the same parts and same configurations as the corresponding phase boards.
12
Figure 15. Output Board.
Type ME Electronic Recloser Control
88945KMA
Figure 17. Reclose-reset board.
88947KMA
Figure 16. Diode Board.
88946KMA
OUTPUT BOARD
The output board (Figure 15) of the control has another do amplifier which senses the charge on the timing plugs and at the proper time gates the tripping SCR. This board also carries the diodes and resistors which make up the various reference voltages for the control. Other circuits on this board are used to inter-tie the tripping circuits and the reclose and reset cir­cuits.
DlODE BOARD
The diode board (Figure16)consists of a group of diodes which are connected to circuits on the other printed circuit boards. These diodes connect to the timing plugs, the reset circuit, the trip circuit, and the reclose circuit. The board also contains the circuit related to the closing circuit fuse.
RECLOSE-RESET BOARD
The reclose-reset board ( Figure 17) carries all circuits neces­sary for reclosing and resetting. The various large capacitors on this board are the C parts of an R-C circuit operating along with unijunctions and SCR’s. The large SCR on this board is the reclose SCR.
Closing Coil Control Fuse
On solenoid-operated reclosers, the fuse will open the closing cir­cuit to protect the potential closing coil in the recloser if closing cannot be accomplished due to low closing voltage. On motor­operated reclosers, the fuse is connected in series with the clos­ing circuit contactor in the recloser.
A Buss Type MDQ-3/8 amp, 250-volt fuse, manufactured by Bussman Manufacturing is used and a box of five spare fuses is supplied with each control. Fuses of similar ratings by other man­ufacturers have slightly different characteristics and should not be used for replacement.
CAUTION: Use only Buss Type MDQ-3/8 amp
fuses. Previously, all Form 3A and most earlier con­trols were supplied with Buss Type MDL-3/8 amp fuses. Buss has redesigned and changed the characteristics of that fuse and it is no longer suitable for use on any Form 3 or Form 3A control. Failure to use proper closing coil control fuse will result in unnecessary fuse operation and prevent the recloser from closing.
NOTE: Buss has redesigned the MDL-2.5 amp fuse that is used on con­trols shipped with reciosers having “quick-close” mechanisms such as Type VSO and VSMT reclosers. The characteristics of the new single ele­ment MDL-2.5 fuse do not affect the application in the control. Buss will also continue to manufacture the original dual element version of the fuse under the new designation of MDQ-2.5. The MDQ-2.5 amp fuse will be supplied with controls for this application. Both the MDL-2.S amp fuse and the MDQ-2.S amp fuse are acceptable for this application.
INTERCHANGEABILITY OF BOARDS BETWEEN FORM 2, FORM 3 AND FORM 3A ELECTRONIC CONTROLS.
The battery-charger, phase-trip #1, phase-trip #2, ground-trip #1 and ground-trip #2 circuit boards can electrically be inter­changed between Form 2, Form 3 and Form 3A controls. However, the Form 2 circuit boards have an offset connector which can result in clearance problems when Form 2 and Form 3/3A boards are mixed in the same control. This procedure is therefore not recommended except in an emergency.
The fixed rate battery charging board (MEA 388-1 ) is electri­cally interchangeable between Form 2, Form 3 and Form 3A controls, when replacing another fixed rate board. The temper­ature regulated charging board (MEA 1172) should only be used to replace another charging board of the same type.
The upper three circuit boards (output, diode, and reclose­reset boards) are not interchangeable between Form 2 and Form 3/3A controls. Interchanging them will cause control misoperation, and may cause circuit board damage.
!
S280-75-2
13
Figure 18. Form 3 electronic control tie board.The test points listed above will be covered in detail in the "Detailed Circuit Check" section of this manual.
TROUBLESHOOTING AND TESTING
A number of relatively simple circuit tests can be made on the ME electronic control. These tests will indicate whether major circuits are operating properly or not, but they will not necessarily isolate the faulty component within the circuit. For easy reference to testing points, refer to Figures 18 and 19 for Form 3 controls and Figures 20 and 21 for Form 3A controls. When appropriate, isolated test points will be shown for individual circuit tests with reference to the prop­ertie board (Figures 18 to 21).
Trouble Check
1. Completely Are boards plugged in correctly? inoperative Is battery connected and fully charged (23-Vdc
minimum)? Is control cable connected? Is control programming correct?
2. Won’t close Is the control fuse good?
RE and WE series reclosers—Is the yellow oper-
ating handle up?
CE, ME and VS series reclosers—Is the manual-
trip/reset knob in the proper position?
RE and WE series reclosers—Can the rotary close
solenoid be heard to operate? If so, test for high voltage to recloser closing coil (refer to specific recloser maintenance manual— Appendix II).
Is there 120- or 240-Vac power to the control?
3. Won’t trip Is battery connected and fully charged (23-Vdc minimum)? Is control cable properly connected?
TABLE 1 Pre-Check
82040KMA
Figure 19. Form 3 electronic control tie board and contr ol bac k panel.The test points listed above will be covered in detail in the "Detailed Circuit Check" section of this manual.
Type ME Electronic Recloser Control
14
CAUTION: Be sure that test equipment leads
have insulated clips to prevent short circuiting adja­cent ME control terminals during testing. Shorting termi­nals may cause permanent damage to circuit compo­nents. The control may be inoperative and possible misoperation (unintentional operation) of the recloser may result.
82047KMA
Pre-Check
When troubleshooting a control reported to have failed or to have not worked properly, always check for simple problems first.
Detailed Circuit Checks
The following test procedures require only the following two test devices.
A volt-ohm meter will be required (minimum meter input
impedance 20,000 ohms per volt) to perform tests.
The Kyle Type METtest set, or an actual recloser with a source of primary or secondary test currents can also be used to perform tests.
!
S280-75-2
15
Figure 20. Form 3A electronic control tie board.The test points listed above will be covered in detail in the "Detailed Circuit Check" section of this manual.
88948KMA
If a circuit board failure is suspected, always check or
change the diode board first because:
The diode board circuits operate in conjunction with the tim-
ing plugs, the output circuit, reset circuit, and reclosing cir­cuit.
A primary diode failure on the diode board can cause sec-
ondary failures on the output board or reclose set board.
NOTE Diode board short circuits are very rare in controls manufactured
after 1970.
If this does not isolate the problem, continue with the circuit
test.
Figure 21. Form 3A electronic control back panel.The test points listed above will be covered in detail in the "Detailed Circuit Check" section of this manual.
Type ME Electronic Recloser Control
16
88939KMA
S280-75-2
17
INPUT CIRCUITS
WARNING: High voltage. Contact with high volt-
age will cause serious personal injury or death. Follow all locally approved safety procedures when working around high voltage lines and equipment.
CAUTION: When measuring voltage between
the violet and gray leads be careful not to short between the gray wire and the B+ terminal. If the gray wire is shorted to the B+ terminal the Phase Trip #1 board will be permanently damaged.
Figure 22. Measured voltage across minimum-trip resistor s.
TABLE 2 Terminal Strip T1 T est P oints f or Matching Transf ormers (100% Minimum-T rip) (Figures 23 and 24)
82040KMA
Figure 23. Block diagram of matching transformers (Table 2). See Figure 8 for complete block diagram.
To check input signals to the control, measure the voltage across the minimum-trip resistors and matching transformer secondaries as follows:
1. Measure voltage across minimum-trip resistors (Figure 22) with 100% of minimum-trip current applied to control. The voltage should be approximately:
Phase Resistors—0.17-Vac (170 millivolts)
Ground Resistors—0.26-Vac (260 millivolts)
NOTE: The above voltages are proportional to the recloser line current and can be used to calculate the actual load current on the different phases, using a digital AC voltmeter such as a Fluke 77 series. The fol­lowing formula can be used.
(Volts on (Resistor
Line Amps = resistor x value amp)
0.17 Example: 0.023-volts (23-millivolts) measured across a 560-amp phase resistor is equivalent to 75.7-amps recloser-load current.Total accuracy is approximately +
5%.
2. Measure voltage across matching transformer secondaries (Figures 23 and 24) with 100% of minimum-trip current ap­plied to control. The test terminals on “T1 “ are shown in Table
2. The voltages should be:
Phase Transformers—6.5-Vac
Ground Transformers—1.2-Vac
Failure to get these voltage readings can be a result of:
A. Opens in current source, control cable, matching trans-
former windings, or wiring to the transformers and asso­ciated components.
B. Shorts in the control’s male input-cable receptacle.
NOTE: Matching transformers are interchangeable between Form 2, 3, and 3A controls.
Transformer Terminal Position Voltage Reading (Vac)
GND BRO—RED 1.2
Aφ ORG—YEL 6.5 Bφ GRN—BLU 6.5 Cφ VI—GRY 6.5
!
!
Type ME Electronic Recloser Control
18
Figure 24. Measuring voltage across matching transf ormers (Table 2) (control panel open, middle left hand side of control).
Figure 25. Block diagram of secondary side of matching transformers and input bridge (Tab le 3).See Figure 8 for complete block diagram.
Figure 26. Form 3 tie board test points for internal dc-load-current signal (T ab le
3.For relationship of terminal location on the tie board, see figures 18 and 19.
88950KMA
82040KMA
INTERNAL dc-LOAD-CURRENT SIGNAL
To check the dc-load-current output signal, measure the volt­age at tie board test points listed in Table 3 at 100% minimum­trip current.
Failure to get these signals can be due to trouble in the matching transformers, or open/or shorted diodes in phase-trip No. 1 or ground-trip No. 1 circuit boards.
TABLE 3 Tie Board Test Points f or dc-Load-Current Signal (100% Minimum-T rip) (Figures 25,26 and 27)
Terminal Position Voltage
Load Current Form 3 Form 3A Readings
+Lead -Lead +Lead -Lead Vdc*
Seq. Seq.
Phase Relay M-ph Relay Phase Minus 6.1
7A 7A
Seq. Seq.
Ground Relay M-gnd Relay Gnd Minus 0.78
7A 7A
*These are full-wave rectified signals.
S280-75-2
19
Figure 28.
Form 3 tie board test points for internal minimum-trip signal (Table 4). For relationship of terminal location on the tie board, see
Figures 18 and 19.
Figure 27.
Form 3A tie board test points for internal dc-load-current signal
(T able 3).For relationship of terminal location on the tie board,see
figures 20 and 21.
88948KMA
TABLE 4 Tie Board Test Points f or Minimum-Trip Signal Figures 28,29,and 30)
INTERNAL MINIMUM TRIP SIGNAL
To check the minimum-trip signal, measure the voltage at tie board test points listed in Table 4.
Failures to get these signals are most likely due to troubles on the phase-trip No. 2 or ground-trip No. 2 circuit boards or possi­bly with the phase-trip No.1 or ground-trip No.1 boards. Battery voltage below 21-Vdc will cause control misoperation of the min­imum-trip, timing and trip signals of the control. Battery voltage above 23 volts will operate the circuits correctly. Refer to “Battery Maintenance,” page 35, for battery charging and testing information.
Minimum Terminal Position Voltage Reading Vdc
Trip Form 3 Form 3A 120%
Signal Minimum-
+Lead -Lead +Lead -Lead No Fault Trip*
Ph Seq. Ph Seq.
Phase Min. Relay Min. Relay 25 or 0 . 3 0 Max.
Trip 7A T rip 7A Battery
Gnd. Seq. Gnd. Seq.
Ground Min. Relay Min. Relay 25 or 0.30 Max.
Trip 7A Trip 7A Battery
*Voltage reading will last only for the duration of the clearing time of the control and recloser/simulator.
Figure 29. Form 3A tie board test points for internal minimum-trip signal (T able 4).For relationship of terminal location on the tie board, see Figures 20 and 21.
Figure 30. Block diagram of internal minimum-trip signal circuit (Table
4). See Figure 8 for complete block diagram.
Figure 31. Block diagram of time-current circuit (Table 5). See Figure 8 for complete block diagram.
Type ME Electronic Recloser Control
20
88948KMA
TIME CURRENT CHARACTERISTIC CURVES (TCC)
NOTE: Since some volt meter burdens will change control calibration, this test will only verify TCC plug operation.
To check the charging of the phase-or-ground-TCC plug, measure the voltage drop at the tie board and the TCC socket pin test points listed in Table 5. Make connections and raise current to120% minimum-trip level.
Failure to get a sudden voltage change for a fast TCC plug or a gradual change for a slow TCC plug can be caused by trouble on the phase-trip No. 2 or ground-trip No. 2 board, trouble on the var­ious timing plugs, open diodes on the diode board, or open con­tacts on the phase- or ground-trip socket No. 1 selector switches.*
* Problems on selector switches are rare on ME controls above S/N 6000.
TABLE 5 Tie Board/TCC Socket Pin Test P oints for TCC Charging (120% Minimum-T rip) (Figures 31,32 and 33)
* On a fast TCC curve the voltage will drop from 24-Vdc to less than 7-Vdc the
instant the fault current increases above minimum-trip.
* * On a delayed TCC plug an obvious time delay can be observed as the meter volt-
age slowly drops from 24-Vdc to 7-Vdc at which time the unit trips
Test Points TCC Form 3 and 3A Voltage Curve +Lead (Phase or -Lead Drop Vdc
Ground TCC Plug)
Fast No. 1 pin, No. 2 TCC Sequence Relay 7A 24 - 7* Slow No. 1 pin, No. 2 TCC Sequence Relay 7A 24 - 7*
S280-75-2
21
Figure 32. Form 3 test points for TCC operation (Table 5).For relationships of terminal/pin location on the tie board and rear of front panel, see Figures 18 and 19.
82040KMA
Figure 33. Form 3 test points for TCC operation (Table 5).For relationships of terminal/pin location on the tie board and rear of front panel, see Figures 20 and 21.
88948KMA
Figure 35. Typical motor operated rec loser (VSAT shown) and electronic control connection.
Figure 34. Typical RXE and WE series reclosers with electronic control cable connection.
Type ME Electronic Recloser Control
22
CONTROL-RECLOSER OPERATION
To provide a better understanding of the control operational cir­cuit checks and the relationship between the recloser circuits and the control output, typical recloser connections to the ME
electronic control are shown in Figures 34 and 35. For detailed information on electronic recloser/control operational circuits, con­sult the maintenance manual for your recloser (see Appendix 11).
S280-75-2
23
To check voltage changes during typical recloser-trip
operations, measure voltage at test points listed in Table 6.
Failure to get voltage readings indicated usually indicates problems in the recloser. Consult the recloser maintenance manual for testing and service information (see Appendix 11).
Figure 36. Block diagram of trip-operating (Table 6). See Figure 8 for com­plete block diagram.Letters in circles (A,B, etc.) are test points and correspond to control cable receptacle pin connection points.
Figure 37. Form 3 test points of recloser-trip operations (Table 6). For rela­tionship of terminal test points, see Figures 2, 18 and 19.
82040KMA
TABLE 6 Test P oints f or Trip Operating Circuit (Figures 36,37,and 38)
* Trip signals have a time duration of only 0.04- to 0.5-seconds, depending on recloser type. If voltage on tie board B drops to 2.2-volts for longer than 5-seconds, the recloser failed to trip. Unplug the control
battery.
Test Points
Voltage Vdc
Voltage Vdc Control Recloser Closed Voltage Vdc Voltage Vdc Recloser open,
+Lead -Lead Control in Lockout No Fault Trip Signal* But Not Locked out
Form 3 and 3A Form 3 and 3A
Tie Board A Middle Battery Test Terminal 24 24 24 24 Seq. Relay 7A Middle Battery Test Terminal 24 0 0 0 Tie Board B Middle Battery Test Terminal 24 24 2.2 24
Figure 38. Form 3A test points for recloser-trip operation (Table 6). For relationship of terminal tet points, see Figures 2, 20, and 21.
Figure 39. Block diagram of closing,tripping and reclosing circuit (Tab le 7). See Figure 8 for complete block diagram.Letters in circles (A, B, etc.) are test points and correspond to control cable receptacle pin connection points.
Type ME Electronic Recloser Control
24
88948KMA
To check voltage changes during closing from lockout,
tripping and reclosing, measure voltages at test points listed in
Table 7.
Failure to get voltage readings indicated usually indicates prob­lems in the recloser. Consult the recloser maintenance manual for testing and service information (see Appendix 11).
TABLE7 Test P oints f or Closing,Tripping and Reclosing Circuit (Figures 39,40,41)
* Closing signal is about 0.5-seconds, depending on recloser type.
* * Value may vary depending on recloser type
***Recloser will close when approximately 15-Vdc is reached and will drop to zero after reclose operation. This voltage measurement tests the circuitry of the Recloser-
Reset board (MEA381)
Test Points
+Lead -Lead Voltage Vdc Voltage Vdc Voltage Vdc Voltage Vdc Voltage Vdc
Form 3 and 3A Form 3 and 3A Control in Lockout Control Reset Closing* Coil Energized Control Closed Reclosed Timing
Seq. Relay Middle Battery
T est T erminal 25 0 0 0 0
F-1 Middle Battery
T est T erminal 25 25 1 0 25
F-2 Middle Battery
T est T erminal 25 25 1.5** 0 25
E Middle Battery
T est T erminal 25 25 1.5** 0 25
F Middle Battery
T est T erminal 25 25 25 0 25
A Middle Battery
T est T erminal 25 25 25 25 25
8 Middle Battery
T est T erminal 1 0 0 0 0 to15***
S280-75-2
25
Figure 40. Form 3 test points for closing,tripping and reclosing operation (Table 7).For relationship of terminal test points, see Figures 2, 18 and 19.
82040KMA
Figure 41. Form 3 test points for closing,tripping and reclosing opeation (Table 7).For relationship of terminal test points, see Figures 2,18 and 19.
88948KMA
Figure 42. Block diagram of trip-reset circuit (Table 8). See figure 8 for complete block diagram. Letters in circle (A,B,etc.) are test points and correspond to control cable receptacle pin connection points.
Type ME Electronic Recloser Control
26
To check voltage changes during trip and reset opera-
tions, measure voltage at test points listed in Table 8.
Failure to get voltage readings indicated usually indicates problems in the reset-reclose circuit board. Repair involves replacement of the circuit board. Unstable minimum-trip volt­age levels will upset or prevent automatic reset operation.
TABLE 8 Test P oints f or Trip and Reset Circuit (Figures 42,43 and 44).
* At 15-Vdc automatic reset occurs returning voltage levels to "control in home"
condition. Voltage returns to zero after rest operation.
Test Points Voltage Vdc
Voltage Reclose Into V oltage Vdc +Lead -Lead Vdc Low Level Reclose Into Form 3 Form 3 Tripped Fault (120% No Fault and 3A and 3A Minimum-Trip)
Middle
Battery
Reset #2 Test 0 0.7 0.7 to 15*
Terminal
Middle Phase Trip Battery #2 Board, Test 25/0 0 25 Minimum-Trip Terminal
S280-75-2
27
Figure 43. Form 3 test points for trip-reset operation (Table 8). For relationship of terminal test points,see Figures 2, 18 and 19.
Figure 44. Form 3A test points for trip-reset operation (Table 8). For relationship of terminal test points,see Figures 2, 20, and 21.
Type ME Electronic Recloser Control
28
Figure 45. Form 3 continuity checks (Table 9). For relationship of terminal test points, see Figures 2, 18, and 19.
82040KMA
S280-75-2
29
MAJOR CONTROL DAMAGE To verify the condition of the Form 3 and 3A tie board in the event of major control damage, check the continuity of common tie board terminals listed in Table 9 (Form 3) and Table 10 (Form 3A).
Failure to get continuity for any of the test points indicates tie
board failure. Failure in other circuitry is extremely rare.
TABLE 9 Form 3 Tie Boar d Continuity Checks (Figure 45)
Continuity from
Terminals "B+" To
LampL
A
5A
Counter C-1
Continuity from
Terminals "B-" To
N
4B
Figure 46. Form 3A continuity checks (Table 10). For relationship of terminal test points, see Figures 20 and 21.
Type ME Electronic Recloser Control
30
88948KMA
TABLE 10 Form 3A Tie Boar d Continuity Checks (Figure 46)
Continuity from
Terminals "A+" To
Lamp
5A
Counter 1
Continuity from
Terminals "N-1" To*
L-2
4B
* For controls with capacitor backup trip accessory (KA1119ME or KA1122ME,
check continuity from diode point shown on Figure 47.
S280-75-2
31
Figure 47. Battery test terminals.
Figure 48. Comparison of charging rates.
BATTERY CHARGING
To check the battery charging operation:
1. Make sure control is in home (reset) position by moving manual operator to “CLOSE.”
2. Connect a dc milliammeter into right hand pair of battery-test
terminals(←l→ ),see Figure 47. Loosen both terminals slightly and disconnect shorting link from between terminals.
3. With battery charger deenergized, current will flow opposite
to the direction shown by CHG. Under normal conditions, quiescent drain will be 1-1/2-to 2-mA. However, shorter time reset plugs and certain accessories can, as shown in Table 11, increase quiescent drain above nominal value.
NOTE: To verify the charge/discharge polarity of the test meter, momentarily actuate the LAMP/LOCKOUT TEST toggle switch to "LAMP TEST." The current measured is a discharge current.
TABLE 11 Quiescent-Battery Drain Above Normal*
Description Drain (mA)
3-second reset plug 2.3 10-second reset plug 0.8 Sequence coordination accessory (if blocked in
home) 0.8
Remote minimum-trip double-supervisory contacts
closed) 6
Targets 1.9
* For complete list of accessory quiescent drain, see the Service Information
manual on the MET Tester, S28O-76-1.
4. With the battery charger energized, current will flow in the direction shown by CHG. The charging rate should be approximately 17-mA minus the discharge rate measured in Step 3, if the control is equipped with the fixed rate battery charging board ( MEA 388-1). The charging rate wilI vary with internal control cabinet temperature if equipped with the
temperature regulated charging board (MEA 1172), See Figure
48). Atypical charging rate will be about 27 mA, at normal room temperature.
NOTE: The 17-mA charging rate is a nominal value based on a 27-volt battery and rated input parameters (e.g. 120-Vac). Even under these standard conditions. a variation of +
2-mA may be observed in the
charging rate.
Prior to 1978 many recloser-control combinations (control serial numbers below 26000) had the battery-charging circuitry in the recloser. Refer to ME control installation manual S280­75-1 for exact Control-Recloser interchangeability.
In the RE & WE family (Form 3 ME Control era), where the
charging supply is taken from the line on B phase, at least
40-amps must flow in B phase for a minimum of 12 hours per
24-hour day to maintain an adequate battery charge.
In the motor operated equipment (VS, ME and CE family)
manufactured between 1969 and 1978 the charging supply is
taken from the 240-Vac motor supply that is required to oper-
ate the recloser. To maintain battery charge on these units,
the 240-Vac supply must be connected to the recloser, and
the recloser and control must be connected via the control
cable. After 1978 (above serial number 26000) most controls
were provided with battery-charging circuitry within the con-
trol itself. These require 120-Vac (or 240-Vac) to be connect-
ed to the control’s power-supply-input terminals.
Failure to get the proper charging rate can be caused by either a high control quiescent-battery discharge rate or by a malfunction in the battery-charger circuitry. To help isolate prob­lems in the battery-charging circuitry, see Figures 49, 50 and 51 and Table 12.
NOTE: A totally discharged battery may indicate an excessive quies­cent-battery discharge rate due to a problem in the ME control. Test quiescent-battery discharge rate with a fully charged battery.
Figure 49. Block diagram of test points for battery-charging cir cuitry. See Figures 50 and 51 and Tale 12 for specific testing points and values.
Type ME Electronic Recloser Control
32
S280-75-2
33
Figure 50. Form 3 test points for battery-charging acessory circuitry (Table 12).
TABLE 12 Battery-Charging Circuitry Checks (Figures 49,50 and 51)
* The actual voltage reading will depend on the type of voltmeter used. This voltage will be lower if the control battery is totally discharged. Repeat test
with a fully charged battery.
Voltage Reading (V ac)
Test Points Location Form 3 Form 3A Form 3A If Voltage Reading Is
Fixed Rate Temperature Not Obtained, Check:
Charger Regulated Charger
A Incoming - Fused switch 120/240 - - Low voltage supply A Incoming - Potential battery charging - 120/240 120/240 Connections and wire from terminal strip
board Fused switch
B Outgoing - Fused switch 120/240 - - Fuses
B1 & B2 Outgoing - Potential battery charging - 35-38* 52-55* Shorted battery
board Defective ballast board
Open circuit
C Outgoing - Surge protection module 120/240 Defective surge module
Input receptacle connections
C1 & C2 T ie board terminals (L&K) and (3 & 4) - 35-38* 52-55* Wiring
Open transformer
D Outgoing - Battery charging acessory Accessory board connections
35-38* - - Wiring
Defective potential battery charger accessory
Open transformer
Battery transformer connections
D Tie board terminals 1 and 2 - 32-35* 34-36* Wiring
Open transformer winding
Battery transformer connections
E Tie board terminals BRD and RED 32-35* - - Wiring
Open transformer winding
Figure 51. Form 3A test points for battery-charging circuitry (Table 12).
Type ME Electronic Recloser Control
34
S280-75-2
35
Figure 52. Field testing a battery.
MECHANICAL AND ELECTRICAL HARDWARE
All mechanical and electrical hardware components (selector switches, toggle switches, manual switch, operations counter, trip sockets, phase sockets, resistor brackets, fuse receptacle, etc.) can be visually or electrically checked. If replacement is needed, remove wires, noting their exact placement, remove all connecting hardware and then remove the existing component. Install the new component by reversing procedure. See Appendix V for connection diagrams for ME controls Form 2, 3, and 3A.
BATTERY MAINTENANCE
Battery Specifications
Nickel-cadmium.
24-volts (20 cells in series).
1.0 Ampere hour capacity (10 hour rate).
Charging rate: 50-mA maximum.
Weight: 41.5 oz.
Length: 10”.
Width: 2”.
Height: 2”.
Maintaining Battery Charge
The battery is fully charged and ready to use just prior to ship­ment. For storage at temperatures under 70-degrees, the bat­tery will maintain adequate charge for operation up to 1-month without trickle charging. However, extremely high ambient stor­age temperatures can result in a battery shelf-life of as little as one month. Thus we recommend that a control battery in stor­age not be left off charge for a period of more than 1-month.
Two convenient methods exist for applying a trickle charge
to the control battery.
1. Connect the battery to the ME control and energize the potential charger.
CAUTION: Shorting battery positive to battery
negative at the battery test terminals will cause permanent damage to the control. The control will be inoperative and possible misoperation (unintentional operation) of the recloser may result.
CAUTION: Shorting the battery positive to
ground will damage a resistor on the control input board, this will result in the battery negative floating, with respect to ground.
CAUTION: Do not short battery positive to the
control cabinet (or other ground). If shorted on a Form 3 control the control will be permanently damaged, the control will be left inoperative and possible misoper­ation (unintentional operation) of the recloser may result. If shorted on a Form 3A control a resistor on the input board will be destroyed; however, the control will remain operative.
WARNING: High voltage. The COMMON AC
GND terminal is connected to the control cabinet. If the incoming 120-Vac supply is inadvertently connect­ed to the common terminal the control cabinet will be at 120-Vac potential. Contact with high voltage will cause severe personal injury or death.
2. A KA1142ME3 120-Vac battery charger is available for main­taining one ME control battery.
The KA1142ME3 battery charger provides two charging rates, 15-mA and 50-mA. The 15-mA charging rate is used to maintain a battery at full charge. The 50-mA rate is used to charge a discharged battery. A battery must be charged at the 50-mA rate for 48 hours.
NOTE: A fully discharged battery can be brought to full charge in about 7-days with the control’s potential charger, if the battery is good. The KA1142ME3 battery charger, at the 50-mA charge level, will recharge battery in about 48 hours.
Field Testing a Battery
NOTE: The battery in the Form 3 and 3A control has a steady drain of approximately 1.5- to 2.5-milliamperes (may be as high as 4.5-mil­liamperes with certain accessories).
To check the condition of a battery, a field test can easily be made. To positively insure proper control operation, this test is conservative; failure to pass does not necessarily mean the bat­tery needs replacement. But a more thorough test can then be performed—normally in a repair or maintenance shop.
To field test:
1. From the battery test terminals on the control front panel measure the battery voltage (see Figure 52). If battery volt­age is below 24-volts, the battery is either low on charge or is faulty. The battery should be removed for recharging and retested before returning to service.
2. If battery voltage is above 24-volts, a power delivery check should be made. To load the battery, a 10-ohm resistor (mini­mum of 10-watt size) is required. To test the battery—while measuring battery voltage connect a 10-ohm resistor across the battery test terminals, for approximately 2-3 seconds. The battery voltage should drop by no more than 3-volts from the open circuit voltage, for ambient temperatures above 20 degrees F.
NOTE: Either a KA638ME voltmeter accessory or a KMET test set can be used for the load test. Both devices have an internal 10-ohm load resistor.
3. If the temperature is below 20-degrees F. the voltage should be approximately that shown by the lower curve in Figure
53. If the voltage is lower than this, the battery should be removed for shop testing.
!
!
!
!
Figure 53. Typical v olta ge versus temperature characteristics of nic kel-cadmium battery.
Type ME Electronic Recloser Control
36
Shop Testing a Battery
Before testing, the top and bottom covers of the battery should be removed. Then the following tests can be made.
1. Check for leaking cells. These are detectable by the pres­ence of a white powdery deposit of electrolyte.
2. Measure voltage across each cell. Any cell measuring 0.0
volts is cause for immediate rejection of the entire battery.
3. If all cells have at least 0.1-volts or more, charge the battery
using the KA1142ME battery charger. All cells should have et least 1.0-Vdc within 5 minutes. Any battery failing this test should be rejected.
4. Charge the battery for 48 hours with the KA1142ME battery
charger.
5. Place a 10-ohm load (a KA638ME voltmeter or MET Tester
has this built in) across the battery for approximately 2-3 sec­onds. The voltage must not drop more than 3-volts below the open circuit voltage for temperatures above 20-degrees F.
6. Make a capacity check. Discharge the battery through a 100­ohm, 12-watt resistor for 3-hours. At the end of this period and while under load, check the individual cell voltages. No cell should read less than 1.1-volts.
7. Remove the 100-ohm resistor. Recheck the open-circuit volt­age on each cell after 7-days. All cells should measure very close to the same voltage level. Do not recharge the battery prior to this test.
If the battery passes the above test, it is in satisfactory condi-
tion; replace the battery covers, recharge (48-hours using the
KA1142ME battery charger) and return to service.
S280-75-2
37
APPENDIX I Test Sheet
NOTE: The following sample test sheet is a convenient method to systematically test the ME electronic control and then return it to its original pro­gramming condition
TEST RECORD SHEET FOR TYPE ME ELECTRONIC CONTROL
DATE CIRCUIT NO.
LOCATION
TESTER CONTROL S/N
RECLOSER S/N
CONTROL PROGRAMMING AS FOUND
MINIMUM TRIP GND Aφ DIAL SETTING GND: LOCKOUT PHASE:
TOGGLE SWITCH POSITION:
TCC PLUGS GND 1st 2nd GND SWITCH BLOCK ( )
PHASE 1st 2nd GND SWITCH NORMAL ( ) COUNTER READING AS FOUND NORMAL RECLOSE ( ) BA TTERY VOLT AGE AS FOUND NON-RECLOSE ( ) RECLOSING PLUGS 1st 2nd 3rd RESET
TESTS
MINIMUM TRIP GND Aφ DIAL SETTING GND: FAST DELAY LOCKOUT SHOTS
PHASE: FAST DELAY TIMING % AMP FIRST SHOT SECOND SHOT THIRD SHOT FOURTH SHOT GND PHASE A PHASE B PHASE C RECLOSING 1st 2nd 3rd RESET NON-RECLOSE TEST ( ) BA TTER YDISCHARGE RATE GND BLOCK TEST ( ) BATTERY CHARGE RATE BA TTERY VOLT AGE AS LEFT COUNTER READING AS LEFT
Type ME Electronic Recloser Control
38
TABLE 13 Electronic Recloser Maintenance Manuals
APPENDIX II Maintenance Manuals
TABLE 14 Form 3 and 3A T ype ME Electr onic Control Acessory Operation,Circuitry ,Testing and Field Installation Manuals
APPENDIX III Accessory Manuals
TABLE 15 Type ME Contr ol Plug-In Panel Components Form 2 (Abo ve S/N 1900),Form 3 (Above S/N 4000),Form 3A (Above S/N
26000)
APPENDIX IV ME Contol Parts
NOTE: For reference to Control parts and components, refer to Figures 2, 7, 55, 56 and 57. For current prices, see the latest edition of the Parts Price List.
Service Information Number Product Type
S280-40-4 WE S280-40-6 VWE and VWVE S280-40-7 RXE (S/N 517 and above)
WE (S/N 6316 and above)
S280-40-8 RVE (S/N 2200 and above)
WVE (S/N 1000 and above)
S280-45-3 VSML
Service
Information Form Accessory Accessory
Number 2,3,3A Catalog No. Description
S280-75-4 3, 3A KA316ME4 Remote-Close S280-75-5 2, 3 KA304M E Reset-After-Reclose S280-75-14 2, 3, 3A KA333ME Reclose-Blocking S280-75-15 2, 3 KA1009, Low Ground Fault Tripping
KA1010 KA1011,
KA1012 S280-75-17 2 KA418ME Sequence Coordination S280-75-19 2, 3, 3A KA287ME Surge Protection S280-75-20 2 3 KA542ME ThermostaticalIy Controlled,
Heater S280-75-21 3, 3A KA1002ME Minimum-Trip Doubler S280-75-22 2, 3 KA531ME Fuse-Elimination S280-75-23 2, 3 KA472ME Lockout Indicating S280-75-25 3, 3A KA1037ME Instantaneous Trip S280-75-26 2, 3 KA458M E Battery-Charging S280-75-31 3, 3A KA1004ME Remote Trip S280-75-32 2, 3 KA880ME DC Voltage Supply S280-75-33 3, 3A KA1036ME Instantaneous Lockout S280-75-34 3 KA418ME3 Sequence Coordination S280-75-36 3, 3A KA333M E Reclose-Blocking S280-75-37 3A KA418ME7 Sequence Coordination S280-75-38 3, 3A KA639ME3 Remote Lockout S280-75-39 3A KA542ME ThermostaticalIy Controlled
Heater S280-75-40 3A KA880ME DC Voltage Supply S280-75-41 3, 3A KA1137ME Target Annunciator S280-75-42 3, 3A KA1163ME Minimum Response Time S280-75-43 3, 3A KA1009ME, Low Ground Fault Tripping
KA1010ME, KA1011 ME,
KA1012ME S280-75-44 3, 3A KA531ME Fuse Elimination S280-75-45 3A KA1174ME Temperature Regulated Battery
Charger
S280-75-47 3A KA1021ME Phase and Ground Protective
Accessory
S280-75-48 3A KA1119ME, Capacitor Backup Trip
KA1122ME S280-75-49 3, 3A KA2003ME Remote Close With Cold Load
Pickup S280-75-50 3, 3A KA545ME3 Load Current Indicator S280-75-51 3, 3A KA2039ME Recloser Status S280-75-52 3, 3A KA2035ME2 Remote Non-Reclose and
Remote Ground Trip Block,
Maintained Contact S280-75-53 3 3A KA2071 ME1 Remote Non-Reclose and,
Remote Ground Trip Block,
Pulsed Contact S280-75-55 3, 3A KA2070ME Remote Close With Cold Load
Pick Up, Remote Lockout
and Recloser Status S280-75-56 3 3A KA2072ME Remote Battery Test and,
Battery Voltage Monitor
Analog output S280-75-57 3, 3A KA2047ME Remote Battery Test and
Voltage Monitor S280-75-61 2, 3, 3A KA1142ME3 Portable Dual Rate Battery
Charger
Catalog No. Description
KA216ME1S Ground Trip Timing Plug Curve 1 KA216ME2S Ground Trip Timing Plug Curve 2 KA216ME3S Ground Trip Timing Plug Curve 3 KA216ME4S Ground Trip Timing Plug Curve 4 KA216MESS Ground Trip Timing Plug Curve 5 KA216ME6S Ground Trip Timing Plug Curve 6 KA216ME7S Ground Trip Timing Plug Curve 7 KA216ME8S Ground Trip Timing Plug Curve 8 KA216ME9S Ground Trip Timing Plug Curve 9 KA216M E11S Ground Trip Timing Plug Curve 11 KA216ME13S Ground Trip Timing Plug Curve 13 KA216ME14S Ground Trip Timing Plug Curve 14 KA216ME15S Ground Trip Timing Plug Curve 1S KA216ME16S Ground Trip Timing Plug Curve 16 KA216ME17S Ground Trip Timing Plug Curve 17 KA216ME18S Ground Trip Timing Plug Curve 18 KA216MEKS Ground Trip Timing Plug Curve K KA217MEAS Phase Trip Timing Plug Curve A KA217MEBS Phase Trip Timing Plug Curve B KA217MECS Phase Trip Timing Plug Curve C KA217MEDS Phase Trip Timing Plug Curve D KA217MEES Phase Trip Timing Plug Curve E KA217MEFS Phase Trip Timing Plug Curve F KA217MEGS Phase Trip Timing Plug Curve G KA217MEHS Phase Trip Timing Plug Curve H KA217MEJS Phase Trip Timing Plug Curve J KA217MEKS Phase Trip Timing Plug Curve K KA217MELS Phase Trip Timing Plug Curve L KA217MEMS Phase Trip Timing Plug Curve M KA217MENS Phase Trip Timing Plug Curve N KA217MEPS Phase Trip Timing Plug Curve P KA217MERS Phase Trip Timing Plug Curve R KA217METS Phase Trip Timing Plug Curve T KA217MEVS Phase Trip Timing Plug Curve V KA217MEWS Phase Trip Timing Plug Curve W KA217MEXS Phase Trip Timing Plug Curve X KA217MEZS Phase Trip Timing Plug Curve Z KA243MEXXXS Phase Min Trip Resistor 100,120,140,170,
200, 240, 280, 300, 340, 400, 480, 560, 600, 680, 800, 960, or 1120 Amp Yellow Label for all Reclosers Except ME and VSMT. Change XXX in Catalog No. to Amps. Ex: KA243ME280S
KA244ME10SS Low Ground Min Trip Resistor 10 Amp Yellow
Label for all Reclosers Except ME and VSMT
KA244MEXXXS Ground Min Trip Resistor 25, 35, 50, 70,100,
120,140,170, 200, 240, 280, 340, 400, 480, or 560 Amp Yellow Label for all Reclosers Except ME and VSMT. Change XXX in Catalog No. to Amps. Ex: KA244ME140S
KA244ME5.8S Low Ground Min Trip Resistor 5.8 Amp
Yellow Label for all Reclosers Except ME and VSMT
KA275MEXXS Reclosing Delay Single Value, INST. or 60
Sec. Change XX in Catalog No. to INST. Ex: KA275MEINST
KKA301MEXXXS Phase Min Trip Resistor 200, 240, 280, 340,
400, 480, 560, 600, 680, 800, 960,1120 1200,1360 1600 1920 or 2240 Amp Blue Label for ME and VSMT Reclosers only. Change XXX in Catalog No. to Amps. Ex: KA301ME800S
KA302MEXXXS Ground Min Trip Resistor 100,140, 200, 240,
280, 340, 400, 480, 560, 680, 800, 960, or 1120 Amp Blue Label for ME and VSMT Reclosers only. Change XXX in Catalog No. to Amps. Ex: KA3O2MES60S
KA101SMES Reset Delay Multiple Value Plug Including
Settings for 1015, 30, 45, 60, 90,120 and 180 Seconds
KA1016MES Reclosing Delay Multiple Value Plug Including
Settings for 1,2,5,7,10,15,30 and 45 Seconds
S280-75-2
39
TABLE 16 Type ME Contr ol Circuit Boar ds and Control Cables Form 2 (Above S/N 1900),Form 3 (Above S/N 4000, Form 3A (Above S/N 26000)
TABLE 17 Type ME Contr ol Replacement Parts and Accessories Form 2 (Above S/N 1900),Form 3 (Above S/N 4000), Form 3A (Above S/N 26000)
Catalog No. Description
KA1ME7 Control Cable, 7 Ft. All Reclosers KA1MEXX Longer Control Cable: 8 Thru 80 Ft. for RVE RXE
VWE, VWVE, WE, WVE Reclosers. 8 Thru 19 Ft. for CXE, ME, VSA, VSAT, VSML, VSMT Reclosers. Replace XX With Length.
KA18ME20 Control Cable, 20 Ft. for CXE, ME, VSA, VSAT,
VSML, VSMT Reclosers
KA18MEXX Extra Long Control Cable: 81 Thru 125 Ft. for
RVE, RXE, VWE, VWVE, WE, WVE Reclosers. 20 Thru 35 Ft. for CXE, ME, VSA, VSAT, VSML,
VSMT Reclosers. Replace XX With Length. KA251 ME Phase Trip No. 1 Circuit Board for Form 2 KA252ME Phase Trip No. 2 Circuit Board for Form 2 KA253ME Ground Trip No. 1 Circuit Board for Form 2 KA254ME Ground Trip No. 2 Circuit Board for Form 2 KA255ME Output Circuit Board KA256ME Diode Circuit Board for Form 2 KA257ME Battery Charging Circuit Board for Form 2 KA267ME Reclose and Reset Circuit Board for Form 2
Catalog No. Description
KA381MES Reclose and Reset Circuit Board for Form 3
and 3A KA382MES Diode Circuit Board for Form 3 and 3A KA383MES Output Circuit Board for Form 3 and 3A KA384MES Ground Trip No. 2 Circuit Board for Form 3 and 3A KA385MES Ground Trip No. 1 Circuit Board for Form 3 and 3A KA386MES Phase Trip No. 2 Circuit Board for Form 3 and 3A KA387MES Phase Trip No. 1 Circuit Board for Form 3 and 3A KA388ME1S Battery Charging Circuit Board for Standard
Charger on Form 3 and 3A Below 53381 KA388ME2S Battery Charging Circuit Board for Dual Rate
Charger on Form 3 Above 5500 and Form 3A KA1103ME Tie Board for Form 3A KA1109ME8 120-Vac Ballast and Surge Card for Fixed or
Temperature Regulated Battery Charger KA1L00ME9 240-Vac Ballast and Surge Card for Fixed or
Temperature Regulated Battery Charger KA1172ME Temperature Regulated Battery Charging Board
for Form 3A
Catalog No. Description
KA107LS1 Relay Assembly KA107LS2 Relay Assembly KA234ME1 Ground Matching Transformer (1 Per Control) KA250ME Tie Board for Form 2 KA279ME Phase Matching Transformer (3 Per Control)
Form 2 and 3
KA287ME5S 24-Vdc Supply Adapter Accessory for Form 3,
from 5501 Thru 25999
KA287ME6S 24-Vdc Supply Adapter Accessory for Form 3A
Above 26000
KA290ME1 Selector Switch and Wire Pistol Grip Form
2 and 3
KA293ME2 Load Current Indicator Accessory Form 3,
Above 5500
KA304ME1 Reset After Successful Reclose Accessory for
Form 2, Below 1900
KA304ME4 Reset After Successful Reclose Accessory for All
Form 3 Controls
KA316ME2S Remote Closing Accessory for Form 2, 1900
and Above
KA316ME4S Remote Closing Accessory for Form 3,
Above 5500
KA325ME2 Adapter Accessory for Form 3 Control to Form 1
Recloser
KA333ME7 Blocking of Reclosing Accy. When Deenergized
for 120-Vac for Form 3 Above 5500 to 26000
KA333ME8 Blocking of Reclosing Accessory When
Energized for 12O-Vac for Form 3, Above 5500 to 26000
KA333ME9 Blocking of Reclosing Accessory When
Deenergized for 240-Vac for Form 3, Above 5500 to 26000
KA333ME10 Blocking of Reclosing Accessory When
Energized for 240-Vac for Form 3, Above 5500 to 26000
KA333ME11 Block of Reclosing Accy.—120-Vac While
Deenergized, for F3A 26000 and Above
KA333ME12 Block of Reclosing Accy.—120-Vac While
Energized, for F3A 26000 and Above KA406ME Input Plug and Wire Harness for Form 2 KA410ME Tie Board for Form 3 KA418ME3 Sequence Coordination Accessory for Form 3,
Below 5500 KA418ME7S Sequence Coordination Accessory—for Form 3
5501-25999 and Form 3A, Above 26000 KA423MES Circuit Board—for Remote Closing Accessory KA450ME2S Battery—24V, for Form 3 and 3A KA452ME Control Counter Assembly Form 1 2, 3 and 3A KA458ME3 Battery Charging Accessory 115-Vac for Form 3,
from 5501 Thru 25999 KA458ME4 Battery Charging Accessory 230-Vac for Form 3
from 5501 Thru 25999
Catalog No. Description
KA472ME3S Lockout Indicating Contact Accy.—for Form 3
Above 5500 and Form 3A
KA514ME1 Phase Trip Protection Accessory—1 Required
Per Control for Form 2, 1615 and Above; for Form 3 Below 4100; Obsolete
KA531ME3S Fuse Elimination Accessory for Form 2, 1900 and
Above, Form 3 and Form 3A KA544ME1S Heater Element Oniy 120-Vac 100-85F KA544ME2S Heater Element Only 240-Vac 100-85F KA544ME3S Heater Element only 120-Vac 60-15F KA544ME4S Heater Element Only 240-Vac 60-15F KA578MES Potential Battery Charger—for Form 3 only KA609ME1 Target Accessory—With Indicating Buttons,
Phase Trip only for Double Size Cabinet, for
Form 3 Below 5500; obsolete KA614ME1 Control Cable Locking Sleeve KA638ME1S Battery Test V oltmeter Portable Type KA639ME3S Remote Lockout Accessory for Form 3 Above
5500 and Form 3A KA641 ME500 Single Cabinet KA642ME500 Double Cabinet KA682ME1 Standard Input Plug Board and Harness Form 3 KA684ME Battery Connector KA689ME920 Ground Trip Sequence Selector Switch Form 2
and 3 KA703ME Battery (Gould) for Form 1—Obsolete KA710ME2 Battery Adapter Kit for Connection of Form 2
Battery to Form 3 Control, Male Receptacle KA710ME3 Battery Adapter Kit for Connection of Form 3
Battery to Form 2 Control, Female Receptacle KA712ME3 24-Vdc Supply Adapter Accy . for Field
Installation for Form 3, Below 5500 KA712ME4 24-Vdc Supply Adapter Accessory for Field
Installation for Form 3, 5500 and Above KA713ME1 Field Kit for Thermostatic Heater With Surge
Protection 115-Vac, for 1900 to 12250 KA713ME2 Field Kit for Thermostatic Heater with Surge
Protection 23O-Vac, for 1900 to 12250 KA713ME3 Field Kit for Thermostatic Heater with Surge
Protection and Fuse Disconnect 115-Vac, from
S/N 12250 to 26000 KA713ME4 Field Kit for Thermostatic Heater With Surge
Protection and Fuse Disconnect 230-Vac, from
S/N 12250 to 26000 KA713ME5 Field Kit for Thermostatic Heater 120-Vac, 85/100
Degree F. Above 26000 KA713ME6 Field Kit for Thermostatic Heater 120-Vac,
15/60 Degree F; Above 26000 KA713ME7 Field Kit for Thermostatic Heater 240-Vac,
85/100 Degree F; Above 26000 KA713ME8 Field Kit for Thermostatic Heater 240-Vac,
15/60 Degree F; Above 26000
Catalog No. Description
KA1037ME6S Instantaneous Trip—Phase and Ground. Phase
Multiple of 1.4, 2.0, 2.8, 4.0 or 5.6; Ground
Multiple of S.6, 8.0, 11.2, 16.0, or 22.4
KA1037ME7S Instantaneous Trip—Phase and Ground, Phase
Multiple of 5.6, 8.0, 11.2, 16.0, or 22.4: Ground
Multiple of 1.4, 2.0, 2.8, 4.0, or 5.6
KA1037ME8S Instantaneous Trip—Phase and Ground, Both
With Multiples of 5.6, 8.0, 11.2, 16.0, or 22.4
KA1102ME1 Standard Input Plug Board and Harness for
Form 3A
KA1103ME Tie Board, Form 3A KA1109ME8 Standard Charger Board—120-Vac, F3AOnly KA1109ME9 Standard Charger Board—240-Vac, F3AOnly KA1134ME1S Automatic Resetting Fault Indicator Circuit Board KA1137ME1S Annunciator—Type Target Accessory—Auto
Reset, Phase only; Above 14450
KA1137ME2S Annunciator—Type Target Accessory—Auto
Reset, Phase and Ground; Above 14450
KA1141ME1 Selector Switch and Wire Pistol Grip, Form 3A
only
KA1142ME3 Shelf Battery Charger, Portable KA1159ME Ground Trip Sequence Selector Switch—Form
3A only
KA1160ME Operations to Lockout Sequence Switch—Al1
Controls
KA1163MES Minimum Response Time KA1174ME1S Temperature Regulated Battery Charger Accy.—
120-Vac, for F3A26000 and Above
KA1174ME2S Temperature Regulated Battery Charger Accy.—
240-Vac, for F3A26000 and Above
KA1193ME Harness only for Standard Input Plug Board
for F3A
KA1194ME1 Standard Input Plug Board only for Form 3A KA2003MES Remote Close With Cold-Load Pickup KA2035ME2S Remote Non-Reclose and Ground Trip Block—
Maintained Contact, 24V
KA2039ME1S Recloser Status—Without Indicator Lamps KA2039ME2S Recloser Status—With Indicator Lamps KA2047MES Battery Monitor—over 30-Vdc/Under 22-Vdc
Indication
KA2070ME1S Remote Close With Cold Load Pickup Remote
Lockout and Status—Without Indicator Lamps
KA2070ME2S Remote Close With Cold Load Pickup Remote
Lockout and Status—With Indicator Lamps
KA2071ME1S Remote Non-Reclose and Ground Trip Block—
Pulse Contact, 24V
KA2072MES Battery Monitor—Analog KA2189MES Remote Indication of Fault Target Accessory KP457ME Mounting Strip (Conducting) KP483ME1 Trip Resistor Clamps KP509ME Mounting Strip Insulating KP674ME1 Sequence Relay—for Form 3 and 3A KP884ME Circuit Board Shield KP894ME1 Battery Mounting Bracket, Form 3 and 3A KP953ME Panel Locking Spring KP1077ME1S Cover KP1100ME Fuse Block Single Section KP1110ME Fuse Block End Closure Unit KP1139ME1 Flip Disc Target—Complete KP2069A4 Knob for Number of operations Selector
Switches (Ground, Phase or Lockout)
KP2069A8 Manual Control Switch Handle KP2075A2 2 Amp Fuse—Type AGC, Glass Tube; Min.
Qty. 5
KP2075A4 3/4 Amp Fuse, Type AGX KP2075A13 15 Amp Fuse—Type BAN, Fibre Tube; Min.
Qty. 5
KP2075A18 3/8 Amp Fuse, Slow Blow Type MDQ, Min. Qty. 5 KP2075A19 6 Amp Fuse, Type BAN KP2080A1S Plastic Battery Connector—Male, Battery
Connechon
KP2080A2S Plastic Battery Connector—Female, Control
Connection
KP4060A12 120 Volt Relay, 2 to 60 Sec. KP4060A22 28 Volt Relay, 2 to 60 Sec. KP4061A3 28 Volt Relay, 0.15 to 1.0 Sec. K721525105018A Screw—for Trip Resistors Clamps K999904310283A Bulb—24V, for Lockout Indicator
Type ME Electronic Recloser Control
40
TABLE 17 Type ME Contr ol Replacement Parts Acessories Form 2 (Above S/N 1900),Form 3 (Above S/N 4000), Form 3A (Above S/N 26000) (continued)
Catalog No. Description
KA716ME Reclosing Fuse Replacement Kit KA719ME 120-Vac Surge Protection Field Kit KA720ME 240-Vac Surge Protection Field Kit KA721ME Battery Post Installation Kit, 4000 and Above KA734ME1 48-Vdc Supply Adapter (AEP only 15 Amp) KA734ME2 125-Vdc Supply Adapter (AEP only 5 Amp) KA734ME3 125-Vdc Supply Adapter (AEP only 5 Amp) KA734ME4 48-Vdc Supply Adapter (15 Amp) from 5501 Thru
25999
KA734ME5 125-Vdc Supply Adapter (15 Amp) from 5501
Thru 25999
KA734ME6 125-Vdc Supply Adapter (15 Amp) from 5501
Thru 25999
KA734ME10 48-Vdc Supply Adapter (15 Amp) 26000 and
Above
KA734ME11 125-Vdc Supply Adapter (5 Amp) 26000 and
Above
KA734ME12 125-Vdc Supply Adapter (15 Amp) 26000 and
Above
KA734ME13 48-Vdc Field Kit for DC Supply—15A 240-Vac
F3A
KA734ME14 125-Vdc Field Kit for DC Supply—5A 240-Vac
F3A
KA734ME15 125-Vdc Field Kit for DC Supply—15A 240-Vac
F3A
KA735ME Battery Bracket Mounting Kit for GE Batteries in
Controls Below 15000
KA736ME Conversion Kit to Cold Load Pickup from Form 3
to Form 3A
KA741 ME4 Retrofit Kit for Replacing Demand Meters—With
Instantaneous Indicating Elements Below 35909
KA741 ME5 Retrofit Kit for Replacing Demand Meters—
Without Instantaneous Indicating Elements,
Below 35909 KA746ME Battery—24V, for Form 2 KA835ME901 Phase Trip Sequence Selector Switch KA835ME902 Phase Trip Sequence Selector Switch—for Use
With Sequence Coodination Accessory KA852ME2S Standard Heater—240V KA871ME2 Battery Charging Isolation Transformer KA1000ME1S Minimum Trip Doubler—Local Operation—
Phase only KA1000ME2S Minimum Trip Doubler—Local Operation—
Phase and Ground KA1002ME4S Minimum Trip Doubler—Remotely operated KA1002ME5S Minimum Trip Doubler—Three Wire Control to
Double Return KA1004MES Remote Trip Accessory Kit KA1021 ME4 Protective Accessory Field Kit for Ground Trip—
4000 to 50071, Supersedes KA921 ME4 KA1021 ME5 Protective Accessory Field Kit for Phase Trip—
4000 to 50071, Supersedes KA921 ME5 KA1021 ME6 Protective Accessory Field Kit for Phase and
Ground Trip—4000 to 50071, Supersedes
KA921 ME6 KA1030ME2S Fault Indicator—Counter Type Phase and
Ground, Above 14450 KA1036ME1S Instantaneous Lockout—Phase only, Multiple
of 1.4, 2.0, 2.8, 4.0, or 5.6 KA1036ME2S Instantaneous Lockout—Phase Only, Multiple
of 5.6, 8.0 11.2 16.0 or 22.4 KA1036ME5S Instantaneous Lockout—Phase and Ground,
Both With Multiples of 1.4, 2.0, 2.8, 4.0, or 5.6 KA1036ME6S Instantaneous Lockout—Phase and Ground,
Phase Multiple of 1.4, 2.0, 2.8, 4.0 or 5.6;
Ground Multiple of 5.6, 8.0, 11.2, 16.0, or 22.4 KA1036ME7S Instantaneous Lockout—Phase and Ground
Phase Multiple of 5.6, 8.0, 11.2 1 6.0 or 22.4
Ground Multiple of 1.4, 2 0, 2.8, 4.0 or 5.6 KA1036ME8S Instantaneous Lockout—Phase and Ground,
Both With Multiples of 5.6, 8.0, 11.2, 16.0, or
22.4
KA1037ME1S Instantaneous Trip—Phase only, Multiples
of 1.4, 2.0, 2.8, 4.0 or 5.6 KA1037ME2S Instantaneous Trip—Phase only, Multiples
of 5.6, 8.0, 11.2 16.0, or 22.4 KA1037ME5S Instantaneous Tr;p—Phase and Ground, Both
With Multiples of 1.4, 2.0, 2.8, 4.0 or 5.6
S280-75-2
41
APPENDIX V
Schematic diagrams
Form 2 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pages 42-43
Form 3 Connections (below S/N 5500) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pages 44-45
Form 3 Connections (S/N 5500-25999) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pages 46-47
Form 3A Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pages 48-49
Figure 54. Form 2 connection diagram (below S/N 1900).Since late Form 2 and early Form 3 controls share common circuits and design, this connection diagram is given for reference.
Form 2 Connections
42
Type ME Electronic Recloser Control
Figure 54 - continued.
Form 2 Connections - continued
43
S280-75-2
Figure 55. Form 3 connection diagram (below S/N 5500).
Form 3 Connections
44
Type ME Electronic Recloser Control
Figure 55 - continued.
Form 3 Connections - continued
45
S280-75-2
Figure 56. Form 3 connection diagram (S/N 5500 to 25999).
46
Type ME Electronic Recloser Control
Form 3 Connections
Figure 56 - continued.
47
S280-75-2
Form 3 Connections - continued
Figure 57. Form 3A connection diagram.
48
Type ME Electronic Recloser Control
Form 3A Connections
Figure 57 - continued.
Form 3A Connections - continued
S280-75-2
49
KRP
1/01
P.O. Box 1640 Waukesha, WI 53187 www.cooperpower.com
©2002 Cooper Power Systems, Inc. Kyle®is a registered trademark of Cooper Industries, Inc.
Printed on Recycled Paper
Type ME Electronic Recloser Control
Loading...